Kidde 1296 User Manual

UTHA / UTGT Compliant Smoke Alarm
• Model 1296
Description
The Kidde 1296E is a 120VAC direct wire-in smoke alarm offering a level of protection that you have come to expect in a Kidde product. The Kidde 1296E is designed to alert you and your family from the dangers of smoke and fire. This smoke alarm utilizes an ionization sensor. (For maximum protection Kidde recommends that both photo­electric and ionization smoke alarm be used). The 1296E has interconnect capabilities and can be interconnected up to 24 Kidde devices including smoke alarms, CO alarms and heat alarms. The 1296E includes a 9V battery backup to provide continuous protection, even during a power failure along with a 5 year limited warranty. The Kidde 1296E has been designed manufactured and approved to UTHA/UTGT standards.
Consumer Benefits
The Kidde 1296E 120VAC direct wire-in smoke alarm pro­vides an early warning signal to you and your family in the event of a smoke or fire incident. This smoke alarm is listed as a commercial residential multiple-station smoke alarm and meets the UTHA sensitivity verification criteria. The 1296E may be installed in one and two family dwellings, lodging and rooming houses, apartment build­ings, hotels, dormitories, day care houses, and residential board and care facilities. This smoke alarm is equipped with two test buttons. Test button A is used for testing the unit’s electronic circuitry, horn and battery. Test button B tests the alarms sensor sensitivity
Features and Benefits
• UTHA/UTGT Compliant – Meets the sensitivity
verification criteria outlined in NFPA 72 and may be installed in one and two family dwellings, lodging and rooming houses, apartment buildings, hotels, dormitories, day care homes, and residential board and care facilities.
•Two Test Buttons – Verifies alarm operation and
sensitivity verification.
• Interconnectable System – Interconnects with up to
24 Kidde devices (of which 18 can be initiation) including smoke, co and heat alarms.
• 9V Battery Backup – Provides protection even during
power failures.
• Alarm Memory – Informs you if the alarm has
sounded since the test button was last pressed.
•Tamper Resist – Helps prevent someone from
tampering with or removing smoke alarm from mounting bracket.
• Separate Trim Ring – Fits all standard electrical box
configurations.
Test Button B
Tests the alarms sensor sensitivity
Test Button A
Tests the units electronic circuitry, horn and battery
Separate Trim Ring
Fits all standard electrical box configurations
1394 South Third Street, Mebane NC 27302 1-800-880-6788 • www.kiddeus.com
Architectural and Engineering Specifications
The smoke alarm shall be Kidde Unit 1296E or approved equal. It shall be powered by a 120VAC, 60Hz source along with a 9V battery backup. The unit shall incorporate an ionization sensor with nominal sensitivity of 0.84%/ft. The temperature operation range shall be between 40˚F and 100˚F (4˚C and 38˚C) and the humidity operation range shall be 5% - 95% relative humidity.
The smoke alarm can be installed on any standard single gang electrical box, up to a 4” octagon junction box. The electrical connection (to the alarm) shall be made with a plug-in connector. A maximum of 24 Kidde devices can be interconnected in a multiple station arrangement. The interconnect system must not exceed the NFPA (National Fire Protection Association) limit of 18 initiating devices (Smoke, heat, CO, etc) interconnected, it is still possible to interconnect 6 strobe lights and or relay modules. The alarm shall provide optional tamper resistance that deters removal of the unit from the wall or ceiling.
The unit shall include a piezoelectric horn that is rated at 85dB at 10ft. The unit shall incorporate 2 LED’s. A green LED will be constantly “ON” when AC power is present. A red LED will flash once approximately every 30-40 seconds to indicate that the smoke alarm is operating properly and will flash rapidly when the unit is alarming and will remain so until the air is cleared. The red LED will be on while test B button is being pressed and will illuminate for about 1.5 seconds every 16 seconds to indicate the memory condition until unit is reset.
The unit shall incorporate two test buttons. Test button A shall test all the electronic circuitry, horn, and battery. Test button B shall test the alarms senor sensitivity.
The unit shall at a minimum meet the requirements of UL217, NFPA72, (chapter 10 & 11 2002 edition) The State of California Fire Marshall, NFPA101 (One and two family dwellings, Federal Housing Authority (FHA), Housing and Urban Development (HUD).
UTHA / UTGT Compliant Smoke Alarm
Model 1296
Technical Specifications
Model Number: 1296 UPC: 0-47871-05127-4 Power Source: 120VAC, 60HZ, 9V battery backup Sensor: Ionization Audio Alarm: 85dB at 10ft Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C) Humidity Range: 5%-95% relative humidity (RH) Size: 5.6” in diameter x 1.55” depth Weight: .5lb Interconnects: Up to 24 Kidde devices LED: Green, AC power present
Red, alarm mode
Warranty: 5 year limited
Installation of Smoke Alarm
The smoke alarm should be installed to comply with all local codes having jurisdic­tion in your area, Article 760 of the National Electric Code, and NFPA 72. Make certain all alarms are wired to a single, continuous (non-switched) power line, which is not protected by a ground fault interrupter. A maximum of 1000 ft. of wire can be used in the interconnect system.
FUSE OR CIRCUIT BREAKER
BLACK
WHITE
RED
L N
First Alarm
Additional Alarms
Ordering Information
Gift Box UPC: 0-47871-05127-4
**Not for sale by individual unit
MASTER PACK
6
1
UNIT
Part Dimensions Case/ Layers/ Skid Number I 2 of 5 Pack Quantity (w x d x h inches) Weight Skid Skid Weight
21005186** N/A Individual 5.75 x 1.75 x 5.75 .5lb N/A N/A N/A 21005127 100 47871 05127 1 Master (6 units) 6 x 11.5 x 6 3.5lbs 162 6 567lbs
5.6"
1.55"