Kidde 1235E User Manual

AC Wire-In Smoke Alarm
• 1235E
Description
The Kidde 1235E is an AC powered, ionization smoke alarm that operates on a 120V power source. The 1235E offers a quick connect power harness making installation fast and easy. This smoke alarm includes an ionization sensor that detects best against fast flaming and other types of fires. The 1235E smoke alarm is easy to install and is suitable for all living areas and has a 5-year limited warranty.
Consumer Benefits
The Kidde 1235E AC powered, wire-in smoke alarm gives you and your family an early warning of smoke and fire in your home. The 1235E can be used as a single station unit or it can be interconnected to up to 24 Kidde devices in a multiple station arrangement. The interconnect system should not exceed the NFPA interconnect limit of 12 smoke alarms and/or 18 initiation alarms. With 18 alarms interconnected, it is still possible to interconnect up to a total of 6 strobe and/or relay devices.
Features and Benefits
• Interconnectable – Interconnect up to 24 Kidde
devices.
•Test Button – Tests unit’s electronic circuitry and horn.
• Red LED – Alarm mode.
•Green LED – Steady on presence of AC power.
• Quick Connect Power Harness – Makes installation
fast and easy.
Test/Reset Button
Tests smoke alarm circuitry and horn
Red LED
Alarm mode
Green LED
Presence of AC power
1394 South Third Street, Mebane NC 27302 1-800-880-6788 • www.kiddeus.com
Architectural and Engineering Specifications
The smoke alarm shall be Kidde Unit 1235 or approved equal.It shall be powered by a 120VAC, 60Hz source. The unit shall incorporate an ionization sensor with nominal sensitivity of 0.64%/ft. The temperature operation range shall be between 40˚F (4˚C) to 100˚F (38˚C) and the humidity operating range shall be 5% - 95% relative humidity.
The smoke alarm can be installed on any standard single gang electrical box, up to a 4” octagon junction box. The electrical connection (to the alarm) shall be made with a plug-in connector. A maximum of 24 Kidde devices can be interconnected in a multiple station arrangement. The inter­connect system must not exceed the NFPA (National Fire Protection Association) limit of 18 initiating devices, of which 12 can be smoke alarms. With 18 initiating devices (Smoke, heat, CO, etc.), interconnected, it is still possible to interconnect 6 strobe lights and or relay modules. The alarm shall provide optional tamper resistance that deters removal of the unit from the wall or ceiling.
The alarm shall include a piezoelectric horn that is rated at 85 decibels at 10 feet. The unit shall incorporate 2 LED’s. A green LED will be constant­ly “ON” when AC power is present and will flash until reset (alarm memory) to indicate which alarm was the originating alarm at the last incident. Pressing the test button will reset the alarm memory condition. A red LED will flash once every 30-40 seconds to indicate the alarm is operating proper­ly and will flash once per every 1.5 seconds when the unit is alarming and will remain so until the air is cleared.
The unit shall at a minimum meet the requirements of UL217, NFPA72, (chapter 11 2002 edition) The State of California Fire Marshall, NFPA101 (One and two family dwellings), Federal Housing Authority (FHA, Housing and Urban Development (HUD).
AC Wire-In Smoke Alarm Unit Number 1235E
Technical Specifications
Unit Number: 1235E UPC: 0-25417-12351-7 Power Source: 120VAC Sensor: Ionization Audio Alarm: 85dB at 10ft Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C) Humidity Range: 5%-95% relative humidity (RH) Size: 5.6” in diameter x 1.55” depth Weight: .6lbs Interconnects: Up to 24 Kidde devices LED: Green, receiving ac power
Red, alarm mode
Warranty: 5 year limited
Ordering Information
Gift Box UPC: 0-25417-12351-7
Part Dimensions Case/ Layers/ Skid Number I 2 of 5 Pack Quantity (w x d x h inches) Weight Skid Skid Weight
1235** N/A Individual 5.75 x 1.75 x 5.75 .6lbs N/A N/A N/A 1235E 200 25417 12351 1 Master Pack (12 units) 5.25 x 10.5 x 10.75 7.2lbs 128 16 921.6lbs
**Not for sale by individual unit
Installation of Smoke Alarm
The smoke alarm should be installed to comply with all local codes having jurisdic­tion in your area, Article 760 of the National Electric Code, and NFPA 72. Make certain all alarms are wired to a single, continuous (non-switched) power line, which is not protected by a ground fault interrupter. A maximum of 1000 ft. of wire can be used in the interconnect system. Use standard UL listed household wire (18 gauge or larger as required by local codes).
FUSE OR CIRCUIT BREAKER
BLACK
WHITE
RED
L N
First Alarm
Additional Alarms
MASTER PACK
12
1
UNIT
5.6" 1.55"
Distributed by: