Keystone Manual: Pneumatic Actuators PremiAir IOM, Keystone-EN Manuals & Guides

KEYSTONE PREMIAIR PNEUMATIC ACTUATOR
InstallatIon and maIntenance InstructIons
Before installation these instructions must be fully read and understood
DOUBLE ACTING AND SPRING RETURN ACTUATORS ARE THE SAME SIZE
INTRODUCTION
The Keystone PremiAir Pneumatic Actuator is a compact, rack and pinion design, conforming to European and International standard EN ISO5211 (preferred dimensions).
GENERAL PNEUMATIC SYSTEMS RECOMMENDATIONS
All Keystone PremiAir Actuators are factory lubricated with Molyrace LT2, which is a molybdenum disulphide (MoS2) grease and, unless the operating environment is extremely harsh, do not require re-lubrication. For applications where the environmental temperature is between -40°C to -30°C, AeroShell Grease 7 is specified. To maintain maximum efficiency with this, or other pneumatic actuators, we advise that the following basic system recommendations are followed:
1. Where air pipelines are subjected to extremes of temperature, the system should be fitted with suitable air drying equipment.
2. When working at low temperatures, it is important that the compressed air has been dried to a dew point of less than the ambient temperature. If this is not the case, water will be condensed from the compressed air and freeze causing damage to the seals inside the actuator, which could result in actuator failure.
3. Air control lines should be fitted in accordance with a ‘Recommended Piping Practice’ and should not have loops, which may trap condensate.
4. All air connection pipe ends should be thoroughly cleaned and deburred after cutting, to ensure that the pipeline is clear of debris.
5. If pipelines are hydraulically tested, then the lines should be 'blown down' with pressurized air to clear all traces of water, prior to connecting lines to the actuator.
6. Where pipe fitting sealants are used, they should be applied to the male threads only, to avoid excess compound being forced into the actuator control lines.
7. Where Air Filter Equipment is used, the air filters should be situated in positions that allow easy access to maintain and/or drain.
8. Where pneumatic valve positioners, or pneumatic controllers are fitted to valve actuator assemblies, oil mist lubricated air should not be used unless the manufacturer states specifically that the controllers are compatible with lubricated air.
Note: PremiAir actuators are rated for air
pressure in the range 2.75 barg (40 psig) to 8.3 barg (120 psig) and will withstand a maximum of 10.3 barg (150 psig).
CONSTRUCTION
PremiAir actuators are designed to be mounted to quarter turn valves either directly or using the correct mounting brackets/adaptors and sizing procedures. All models are of the opposed piston type. Each piston incorporates an integral rack which engages with a one piece drive pinion shaft. The drive shaft is Nitrotech™ treated for maximum protection and fitted with 'engineered polymer' bearings. The actuator body is of extruded aluminium, hard anodized and electrostatic powder coated. The design features bolt on mounting plate and air connection plate for maximum adaptability. O-rings are used for piston and shaft seals. For Spring Return actuators, up to four springs per piston can be fitted between the piston head and end cap to suit the available operating air pressure.
Adjustable travel stops are provided for each end of travel to ensure that the actuator will open and close the valve precisely. The output drive is a female double square (star), conforming to EN ISO5211.
NOTE
These instructions refer to all the range, except size 180. For Installation and Maintenance instructions relating to size 180, please refer to document HDLDS-0012.
VCIOM-00036-EN 17/11Emerson.com/FinalControl © 2017 Emerson. All Rights Reserved.
KEYSTONE PREMIAIR PNEUMATIC ACTUATOR
InstallatIon and maIntenance InstructIons
STANDARD INSTALLATION - DOUBLE AND SINGLE ACTING UNITS
These instructions assume that the actuators are installed with the cylinder axis parallel to the axis of the valve bore (In Line) and are fitted to Resilient Seated Butterfly Valves having mounting pads conforming to EN ISO5211. Single acting actuators are supplied as FAIL­CLOSE units as standard. Reverse acting, (FAIL-OPEN), must be specified at the time of order.
1. Ensure that the valve and actuator are in the following corresponding positions:
 •DoubleActingunitsandSpringReturn
units, (Fail-closed):
Valve closed, actuator fully clockwise.
 •DoubleActingunitsandSpringReturn
units, (Fail-open):
Valve open, actuator fully counter-
clockwise
Mounting to ball and high performance butterfly valves (via bracket)
2a. Secure the mounting bracket to the
underside of the actuator, using four bolts and washers, as shown in Figure 1.
3a. Install the appropriate coupling onto the
valve stem. The coupling should be lightly tapped or pressed onto the valve stem. The use of a lubricant is recommended.
4a. Mount the actuator and bracket onto the
valve top flange using the appropriate bolts.
Mounting to resilient seated butterfly valves (with EN ISO5211 mounting)
2b. Screw the actuator mounting studs tightly
into the actuator base plate.
3b. Mount the actuator onto the valve top flange
and secure using a lockwasher and nut on each mounting stud.
All ¼ turn valve types
5. Before installing the valve/actuator assembly in a piping system, the valve operation should be verified and adjusted, if necessary, using the travel stop screws (see detailed instructions for travel setting)
6. When installing the valve/actuator assembly into pipeline, ensure that the specific instructions relating to the valve installation are followed.
Note: some valves may require to be fitted
into the pipeline prior to mounting the actuator.
Fail Safe butterfly valves are an example
of this.
NON STANDARD INSTALLATION - DOUBLE AND SINGLE ACTING UNITS
All ¼ turn valve types
In circumstances where the actuator is required to be installed in the transverse position i.e. at right angles to the valve bore (Across Line), the actuator must be rotated through 90°. This is achieved in the following manner:
1. Remove the actuator from the valve or the bracket by removing the 4 fixing bolts/nuts and withdraw it vertically from the valve.
2. Rotate the actuator through 90°.
3. Refit actuator to the top of the valve or to the bracket. The output drive of the actuator is a double square (star) design, with the squares being at 90° to each other.
FIGURE 1 Typical installation on ball or high performance butterfly valves, using bracket mounting
Actuator
Lockwasher
Bolt
Bolt
Coupling if required
Bracket if required
FIGURE 2 Typical installation on resilient seated butterfly valves, with direct EN ISO5211 mounting
Lockwasher
Actuator
Stud
Nut
2
KEYSTONE PREMIAIR PNEUMATIC ACTUATOR
InstallatIon and maIntenance InstructIons - parts IdentIfIcatIon
23
1
8
9
11
24
25
2
17
16
12
10
26
29
15
14
21
20
6
4
27
28
5
19
18
3
7
22
13
MATERIALS OF CONSTRUCTION
Subject Item Material Finish
1 Body Extruded aluminium BS 1474 (6000 series) Hard Anodize + ESPC* or SNP** 2 End cap Die cast aluminium DIN1725 Alloy 231 Chromate + ESPC* or SNP** 3 Piston Die cast aluminium DIN1725 Alloy 231 Anodize or SNP** 4 Pinion shaft Carbon steel BS 1490:1983 212 A42 Nitrotech™*** or SNP** 5 Base plate Die cast aluminium DIN1725 Alloy 231 Chromate + ESPC* or SNP** 6 Air connection plate Aluminium DIN1725 Alloy 231 Chromate + ESPC* or SNP** 7 Piston backing pad Devlon-V™ Natural 8 Piston support ring Devlon-V™ Natural 9 Top bearing Devlon-V™ Natural 10 Bottom bearing Devlon-V™ Natural 11 Top spacer Devlon-V™ Natural 12 Bottom spacer Devlon-V™ Natural 13 Stop bolt Stainless steel A2 / 70 Natural 14 Lock nut Stainless steel A2 / 70 Natural 15 Sealing washer Stainless steel A2 / 70 Natural 16 End cap bolt Stainless steel A2 / 70 Natural 17 End cap washer Stainless steel A2 / 70 Natural 18 Base plate bolt Stainless steel A2 / 70 Natural 19 Base plate washer Stainless steel A2 / 70 Natural 20 Air connection plate bolt Stainless steel A2 / 70 Natural 21 Air connection plate washer Stainless steel A2 / 70 Natural 22 Spring Chrome silicon spring steel
BS 2806 685 A55 HD R2 Oil dip 23 Indicator ABS Natural 24 Piston O-ring Rubber-NBR or FPM Natural 25 End cap O-ring Rubber-NBR or FPM Natural 26 Shaft top O-ring Rubber-NBR or FPM Natural 27 Shaft bottom O-ring Rubber-NBR or FPM Natural 28 Base plate O-ring Rubber-NBR or FPM Natural 29 Air connection plate O-ring Rubber-NBR or FPM Natural
NOTES
* ESPC = Electrostatic powder coating ** SNP = Special nickel protection finish *** Nitrotech™ = Roprietary corrosion resistant finish
3
Loading...
+ 4 hidden pages