Keysight Technologies E3646A, E3647A, E3648A, E3649A User's And Service Manual

Keysight E364xA Dual Output DC Power Supplies

User’s and Service Guide
Notices
CAUTION
WARNING
© Keysight Technologies, 2000 - 2014
Manual Part Number
E3646-90001
Edition
Edition 11, November 2014
Keysight Technologies 1400 Fountaingrove Parkway Santa Rosa, CA 95403
Warranty
The material contained in this document is provided “as is,” and is subject to change, without notice, in future editions. Further, to the maximum extent permitted by the applicable law, Keysight disclaims all warranties, either express or implied, with regard to this manual and any information contained herein, including but not limited to the implied warranties of merchantabil­ity and fitness for a particular purpose. Keysight shall not be liable for errors or for incidental or consequential damages in connection with the furnishing, use, or performance of this document or of any information contained herein. Should Key­sight and the user have a separate written agreement with warranty terms covering the material in this document that conflict with these terms, the warranty terms in the separate agreement shall control.
Technology Licenses
The hardware and or software described in this document are furnished under a license and may be used or copied only in accor­dance with the terms of such license.
Restricted Rights Legend
U.S. Government Restricted Rights. Soft­ware and technical data rights granted to the federal government include only those rights customarily provided to end user cus­tomers. Keysight provides this customary commercial license in Software and techni­cal data pursuant to FAR 12.211 (Technical Data) and 12.212 (Computer Software) and, for the Department of Defense, DFARS
252.227-7015 (Technical Data - Commercial Items) and DFARS 227.7202-3 (Rights in Commercial Computer Software or Com­puter Software Documentation).
Safety Notices
A CAUTION notice denotes a haz­ard. It calls attention to an operat­ing procedure, practice, or the likes of that, if not correctly performed or adhered to, could result in dam­age to the product or loss of impor­tant data. Do not proceed beyond a CAUTION notice until the indicated conditions are fully understood and met.
A WARNING notice denotes a hazard. It calls attention to an operating procedure, practice, or the likes of that, if not correctly performed or adhered to, could result in personal injury or death. Do not proceed beyond a WARN­ING notice until the indicated conditions are fully understood and met.
II E364xA User’s and Service Guide
Safety Symbols
The following symbols on the instrument and in the documentation indicate precautions which must be taken to maintain safe operation of the instrument.
Caution, risk of danger (refer to this manual for specific Warning or Caution information)
DC (Direct current or voltage)
AC (Alternating current or voltage) Positive binding post
Protective conductor terminal Negative binding post
Out position of a bi-stable push control
In position of a bi-stable push control
Terminal is at earth potential. Used for measurement and control circuits designed to be operated with one terminal at earth potential.
E364xA User’s and Service Guide III
Safety Considerations
CAUTION
Read the information below before using this instrument.
The following general safety precautions must be observed during all phases of operation, service, and repair of this instrument. Failure to comply with these precautions or with specific warnings elsewhere in this manual violates safety standards for design, manufacture, and intended use of the instrument. Keysight Technologies assumes no liability for the customer’s failure to comply with these requirements.
Use the device with the cables provided with the shipment.
If the device is used in a manner not specified by the manufacturer,
the device protection may be impaired.
Always use a dry cloth to clean the device. Do not use ethyl alcohol or any other volatile liquid to clean the device.
Do not permit any blockage of the ventilation holes of the device.
IV E364xA User’s and Service Guide
WARNING
• Do not use MAINS supply cords by inadequately RATED cord. Always use the MAINS supply cord provided by the manufacturer.
• Do not use the device if it appears damaged or defective. REMOVE POWER and do not use the device until safe operation is verified by service-trained personnel. If necessary, return the device to Keysight for service and repair to ensure that the safety features are maintained.
• Do not operate the device around flammable gases or fumes, vapor, or wet environments.
• Observe all markings on the device before connecting any wiring to the device.
• Turn off the output of the power supply before connecting to the output terminals.
• When servicing the device, use only the specified replacement parts.
• Do not install substitute parts or perform any unauthorized modification to the device. Return the device to Keysight for service and repair to ensure that the safety features are maintained.
• Do not operate the device with the cover removed or loosened.
E364xA User’s and Service Guide V
This power supply is a Safety Class I instrument, which means that it has a protective earth terminal. This terminal must be connected to earth ground through a power source with a 3-wire ground receptacle.
Before installation or operation, check the power supply and review this manual for safety markings and instructions. Safety information for specific procedures is located at the appropriate places in this manual.
Safety and EMC Requirements
This power supply is designed to comply with the following safety and Electromagnetic Compatibility (EMC) requirements:
• IEC61326-1:2005/EN61326-1:2006
• Canada: ICES/NMB-001: Issue 4, June 2006
• Australia/New Zealand: AS/NZS CISPR11:2004
• IEC 61010-1:2001/EN 61010-1:2001
• Canada: CAN/CSA-C22.2 No. 61010-1-04
• USA: ANSI/UL 61010-1:2004
Environmental Conditions
This instrument is designed for indoor use. The table below shows the general environmental requirements for this instrument.
Environmental condition Requirements
Te m p e r a t u r e
Operating condition
0 °C to 40 °C (full rated output) Storage condition
–20 °C to 70 °C
Humidity
Altitude Up to 2000 m
Installation category II (for indoor use)
Pollution degree 2
Operating condition
95% RH (maximum)
VI E364xA User’s and Service Guide
Regulatory Markings
The CE mark is a registered trademark of the European Community. This CE mark shows that the product complies with all the relevant European Legal Directives.
The C-tick mark is a registered trademark of the Spectrum Management Agency of Australia. This signifies compliance with the Australia EMC Framework regulations under the terms of the Radio Communication Act of 1992.
ICES/NMB-001 indicates that this ISM device complies with the Canadian ICES-001. Cet appareil ISM est confomre a la norme NMB-001 du Canada.
The CSA mark is a registered trademark of the Canadian Standards Association.
This symbol is a South Korean Class A EMC Declaration. This is a Class A instrument suitable for professional use and in electromagnetic environment outside of the home.
This instrument complies with the WEEE Directive (2002/96/EC) marking requirement. This affixed product label indicates that you must not discard this electrical or electronic product in domestic household waste.
This symbol indicates the time period during which no hazardous or toxic substance elements are expected to leak or deteriorate during normal use. Forty years is the expected useful life of the product.
E364xA User’s and Service Guide VII
Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/EC
This instrument complies with the WEEE Directive (2002/96/EC) marking requirement. This affixed product label indicates that you must not discard this electrical or electronic product in domestic household waste.
Product Category:
With reference to the equipment types in the WEEE directive Annex 1, this instrument is classified as a “Monitoring and Control Instrument” product.
The affixed product label is as shown below.
Do not dispose in domestic household waste.
To return this unwanted instrument, contact your nearest Keysight Service Center, or visit
www.keysight.com/environment/product
for more information.
VIII E364xA User’s and Service Guide
Declaration of Conformity (DoC)
NOTE
The Declaration of Conformity (DoC) for this instrument is available on the Keysight Web site. You can search the DoC by its product model or description at the Web address below.
http://www.keysight.com/go/conformity
If you are unable to search for the respective DoC, contact your local Keysight representative.
E364xA User’s and Service Guide IX
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK.
X E364xA User’s and Service Guide

Table of Contents

1 Getting Started
Introduction 2
Standard Shipped Items 6
Options 6 Accessories 7
Preparing the Power Supply 8
Checking the power supply 8 Connecting power to the power supply 9 Checking the output 10 Converting line voltage 12 Rack-mounting the power supply 14
Product at a Glance 17
Front panel 17 Rear panel 20 Display annunciators 21
Output Connections 23
Current ratings 23 Voltage drops 24 Load consideration 24 Remote voltage sensing connections 26 Multiple loads 29
Operating the Power Supply 30
Cooling 30 Bench operation 30 Cleaning 30
2 Operation and Features
Overview 32
E364xA User’s and Service Guide XI
Constant Voltage Operation 34
Front panel operation 34 Remote interface operation 36
Constant Current Operation 36
Front panel operation 36 Remote interface operation 38
Track Mode Operation 38
Front panel operation 39 Remote interface operation 39
View Menu Operation 40
Changing the display mode 40 Viewing the errors 41 Viewing the firmware revision 41 Viewing the calibration string 42
Configuring the Remote Interface 42
GPIB configuration 43 RS-232 configuration 43
Storing and Recalling Operating States 44
Front panel operation 44 Remote interface operation 46
Programming the Overvoltage Protection 46
Front panel operation 46 Remote interface operation 49
Disabling the Output 50
Front panel operation 50 Remote interface operation 50 Disconnecting the output using an external relay 51
System-Related Operations 52
State storage 52 Self-test 53
XII E364xA User’s and Service Guide
Error conditions 54 Firmware revision query 54 SCPI language version 55
GPIB Interface Reference 56
RS-232 Interface Reference 57
RS-232 configuration overview 57 RS-232 data frame format 58 Connection to a computer or terminal 58 RS-232 troubleshooting 60
Calibration 61
Calibration security 61 To unsecure for calibration 62 To secure against calibration 63 To change the security code 64 Calibration count 65 Calibration message 66
3 Remote Interface Reference
SCPI Command Summary 68
Introduction to the SCPI Language 74
Command format used in this manual 75 Command separators 76 Using the MIN and MAX parameters 77 Querying parameter settings 77 SCPI command terminators 78 IEEE-488.2 common commands 78 SCPI parameter types 78
Simplified Programming Overview 80
Using the APPLy command 80 Using the low-level commands 80 Reading a query response 81
E364xA User’s and Service Guide XIII
Selecting a trigger source 81 Power supply programming ranges 82
Using the APPLy Command 83
APPLy {<voltage>| DEF | MIN | MAX}[,{<current>| DEF | MIN
| MAX}] 83
APPLy? 83
Output Settings and Operation Commands 84
Triggering Commands 92
Trigger source choices 92 Triggering commands 94
System-Related Commands 95
State Storage Commands 99
Calibration Commands 101
Calibration example 104
Interface Configuration Commands 106
SCPI Status Registers 107
What is an event register? 107 What is an enable register? 107 What is a multiple logical output? 108 SCPI status system 109 Questionable Status register 110 Standard Event register 112 Status byte register 114 Using service request (SRQ) and serial poll 115 Using *STB? to read the Status Byte 116 Using the Message Available Bit (MAV) 116 Using SRQ to interrupt the bus controller 117 Determining when a command sequence is completed 117 Using *OPC to signal when data is in the output buffer 118
Status Reporting Commands 119
XIV E364xA User’s and Service Guide
Halting an Output in Progress 124
SCPI Conformance Information 125
SCPI confirmed commands 125 Device-specific commands 127
IEEE-488 Conformance Information 128
Dedicated hardware lines 128 Addressed commands 128 IEEE-488.2 common commands 129
4 Error Messages
Overview 132
Front panel operation 132 Remote interface operation 133
Execution Error Messages 134
Self-Test Error Messages 139
Calibration Error Messages 141
5 Application Programs
Overview 144
Example Program for C and C++ 145
Example Program for Excel 97 149
6 Tutorial
Overview of the Power Supply Operation 156
Output Characteristics 158
Unregulated state 160 Unwanted signals 160
Extending the Voltage Range and Current Range 163
Series connections 163
E364xA User’s and Service Guide XV
Parallel connections 164
Remote Programming 165
7 Characteristics and Specifications
Physical Characteristics 170
Environmental Characteristics 172
Electrical Specifications 172
Supplemental Characteristics 174
8 Service and Maintenance
Overview 178
Operating Checklist 179
Types of Service Available 180
Standard repair service (worldwide) 180
Repacking for Shipment 181
Electrostatic Discharge (ESD) Precautions 182
Surface Mount Repair 183
Replacing the Power-Line Fuse 183
Troubleshooting Hints 184
Unit reports errors 740 to 755 184 Unit fails self-test 184 Bias supplies problems 185
Self-Test Procedures 186
Power-on self-test 186 Complete self-test 186
General Disassembly 188
Recommended Test Equipment 189
XVI E364xA User’s and Service Guide
Test Considerations 191
Operation Verification and Performance Tests 192
Operation verification tests 192 Performance tests 192
Measurement Techniques 193
Common test setup 193 Current-monitoring resistor 194 General measurement techniques 194 Electronic load 195 Programming 195
Constant Voltage (CV) Verifications 196
Constant voltage test setup 196 Voltage programming and readback accuracy 196 CV load effect (load regulation) 198 CV source effect (line regulation) 199 CV PARD (ripple and noise) 200 Load transient response time 202
Constant Current (CC) Verifications 204
Constant current test setup 204 Current programming and readback accuracy 204 CC load effect (load regulation) 206 CC source effect (line regulation) 207 CC PARD (ripple and noise) 208
Common Mode Current Noise 210
Performance Test Record 211
Calibration Reference 214
Keysight calibration services 214 Calibration interval 214 To unsecure the power supply without the security code 214
General Calibration or Adjustment Procedure 216
E364xA User’s and Service Guide XVII
Front panel voltage and current calibration 217
Calibration Record 221
Calibration Error Messages 222
Component Locator Diagram 225
Component locator diagram for the main board assembly —
top 225
Component locator diagram for the main board assembly —
bottom 226
Component locator diagram for the digital board assembly —
top 227
Component locator diagram for the digital board assembly —
bottom 228 Component locator diagram for the front panel — top 229 Component locator diagram for the main board assembly — top
(serial MY53xx6xxx) 230 Component locator diagram for the main board assembly —
bottom (serial MY53xx6xxx) 231 Component locator diagram for the digital board assembly —
top (serial MY53xx6xxx) 232 Component locator diagram for the digital board assembly —
bottom (serial MY53xx6xxx) 233 Component locator diagram for the front panel — top (serial
MY53xx6xxx) 234
XVIII E364xA User’s and Service Guide

List of Figures

Figure 1-1 Rear output terminals 5 Figure 1-2 Line voltage selector (set for 115 Vac) 12 Figure 1-3 Front panel 17 Figure 1-4 Voltage and current limit settings 19 Figure 1-5 Rear panel 20 Figure 1-6 Display annunciators 21 Figure 1-7 Remote voltage sensing connections 26 Figure 2-1 Recommended protection circuit for battery
charging 49 Figure 2-2 DB-9 serial connection 59 Figure 2-3 DB-25 serial connection 60 Figure 3-1 Multiple logical output 108 Figure 3-2 SCPI status system 109 Figure 5-1 Example program result 149 Figure 6-1 Diagram of a simple series power supply 156 Figure 6-2 Block diagram of the power supply showing the remote
interface isolation 157 Figure 6-3 Ideal constant voltage power supply 158 Figure 6-4 Ideal constant current power supply 158 Figure 6-5 Output characteristics 159 Figure 6-6 Simplified diagram of the common mode and normal
mode sources of noise 162 Figure 6-7 Speed of response — programming up (full load) 165 Figure 6-8 Speed of response — programming down 166 Figure 7-1 E364xA dimensions 170 Figure 7-2 E364xA dimensions for rack-mounting 171 Figure 8-1 General disassembly 188 Figure 8-2 Performance verification test setup 193 Figure 8-3 Front or rear panel terminal connections 194 Figure 8-4 CV PARD (ripple and noise) 201 Figure 8-5 Transient response time 203 Figure 8-6 CC PARD connections (ripple and noise) 209
E364xA User’s and Service Guide XIX
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK.
XX E364xA User’s and Service Guide

List of Tables

Table 1-1 E364xA options 6 Table 1-2 E364xA accessories 7 Table 1-3 E364xA power-line fuse 9 Table 1-4 Front panel overview 17 Table 1-5 Rear panel overview 20 Table 1-6 Display annunciators overview 21 Table 1-7 Wire rating 23 Table 2-1 Factory-setting security codes 62 Table 3-1 SCPI command summary 69 Table 3-2 Keysight E364xA programming ranges 82 Table 3-3 Power supply state 98 Table 3-4 Bit definitions — Questionable Status register 110 Table 3-5 Bit definitions — Standard Event register 112 Table 3-6 Bit definitions — Status Byte summary register 114 Table 3-7 SCPI confirmed commands 125 Table 3-8 Non-SCPI commands 127 Table 4-1 Execution error messages 134 Table 4-2 Self-test error messages 139 Table 4-3 Calibration error messages 141 Table 7-1 Physical characteristics 170 Table 7-2 Electrical specifications 172 Table 7-3 Supplemental characteristics 174 Table 8-1 Bias supplies voltages 185 Table 8-2 Bias supplies voltages (serial MY53xx6xxx) 185 Table 8-3 Self-test error messages 186 Table 8-4 Recommended test equipment 189 Table 8-5 Verification programming values 196 Table 8-6 CV performance test record 211 Table 8-7 CC performance test record 212 Table 8-8 Parameters for calibration 216 Table 8-9 Calibration record 221 Table 8-10 Calibration error messages 222
E364xA User’s and Service Guide XXI
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK.
XXII E364xA User’s and Service Guide
E364xA Dual Output DC Power Supplies User’s and Service Guide

1 Getting Started

Introduction 2 Standard Shipped Items 6 Preparing the Power Supply 8 Product at a Glance 17 Output Connections 23 Operating the Power Supply 30
This chapter guides you to set up your power supply for the first time. An introduction to all the features of the power supply is also given.
1Getting Started

Introduction

Introduction
The Keysight E3646A/E3647A (30 W) and E3648A/E3649A (50 W) are high performance dual output dual range programmable DC power supplies with GPIB and RS-232 interfaces. The combination of bench- top and system features in these power supplies provides versatile solutions for your design and test requirements.
Convenient bench-top features
Dual output dual range
Output on/off
High accuracy and high resolution
Excellent load and line regulation
Low ripple and noise
Overvoltage protection
Five operating states storage
Tracking operation
Easy- to- use controls
Remote voltage sensing
Front and rear output terminals
Portable, ruggedized case with non- skid feet
Error messages available on the display
Flexible system features
Standard GPIB (IEEE- 488) and RS- 232 interfaces
Standard Commands for Programmable Instruments
(SCPI) compatibility
Easy I/O setup from the front panel
Software calibration, no internal physical adjustments
2 E364xA User’s and Service Guide
Getting Started 1
Introduction
The E364xA power supplies feature a combination of programming capabilities and linear power supply performance that makes them ideal for power systems applications. The E364xA power supplies may be programmed locally from the front panel or remotely over the GPIB and RS- 232 interfaces.
The E364xA power supplies have two ranges, allowing more voltage at a lower current or more current at a lower voltage. The output range is selected from the front panel or over the remote interfaces.
Operational features
Dual output dual range
Constant voltage (CV) or constant current (CC) operation
Overvoltage protection (OVP)
Five storage locations (1 to 5) for user- defined
operating states
Automatic turn- on self- test
Remote sense at rear panel terminals
User calibration from the front panel or over the remote
interfaces
Front panel operations
Easy- to- use control features
Output (1 or 2) and output voltage range selection
Enabling or disabling OVP
OVP trip level setting and condition clearing
Setting and displaying the voltage and current limit values
Storing or recalling the operating state
Resetting the power supply to the power- on state
Returning the power supply to the local mode from the
remote mode
Retrieving or scrolling error messages on the display
Changing the display mode (V- V, I- I, or V- I display)
E364xA User’s and Service Guide 3
1Getting Started
Introduction
Viewing the errors, calibration string, or system firmware
revision
Enabling or disabling the Tracking mode
Calibrating the power supply, including changing the
calibration secure code
Configuring the remote interface
Enabling or disabling the output
When operated over the remote interface, the E364xA power supplies can be both a listener and a talker. Using an external controller, you can instruct the power supply to set the output and to send the status data back over the GPIB or RS- 232 interface. Capabilities include the following features:
Voltage and current programming
Voltage and current readback
Present and stored status readback
Programming syntax error detection
Complete self- test
The front panel Vacuum- Fluorescent Display (VFD) includes:
Displaying the actual values of the output voltage and
current (meter mode)
Displaying the limit values of the voltage and current
(limit mode)
Checking the operating status from the annunciators
Checking the type of error from the error codes
(messages)
Front panel binding posts are available to connect load wires for bench operation. Connections to the power supply’s output and to chassis ground are made to the rear output terminals.
4 E364xA User’s and Service Guide
Getting Started 1
WARNING
Introduction
Floating the power supply output at more than ±60 Vdc from the chassis presents an electric shock hazard to the user.
Do not float the outputs at more than ±60 Vdc when uninsulated sense wires are used to connect the (+) output to the (+) sense and the (–) output to the (–) sense terminals on the back of the unit.
E364xA User’s and Service Guide 5
Figure 1-1 Rear output terminals
1 Float voltage ±60 Vdc Max to (shorting conductors
without insulation).
2 Float voltage ±240 Vdc Max to (insulated shorting
conductors).
1Getting Started

Standard Shipped Items

Standard Shipped Items
Verify that you have received the following items in the shipment of your power supply. If anything is missing or damaged, contact your nearest Keysight Sales Office.
Power cord
Certificate of Calibration
E364xA User’s and Service Guide (this manual)
E364xA Quick Reference Card

Options

Options 0EM, 0E3, and 0E9 determine which power-line voltage is selected at the factory. The standard unit is configured for 115 Vac ±10%, 47 Hz to 63 Hz input voltage.
For more information about changing the power- line voltage setting, refer to
Tab l e 1 - 1 E364xA options
Option Description
OEM 115 Vac ±10%, 47 Hz to 63 Hz input voltage
OE3 230 Vac ±10%, 47 Hz to 63 Hz input voltage
OE9 100 Vac ±10%, 47 Hz to 63 Hz input voltage
1CM Rack-mount kit (Keysight part number 5063-9243)
OL2 Extra English manual set (local language manual files are included in the
CD-ROM, Keysight part number 5964-8251)
6 E364xA User’s and Service Guide
“Converting line voltage” on page 12.

Accessories

The accessories listed below may be ordered from your local Keysight Sales Office either with the power supply or separately.
Tab l e 1 - 2 E364xA accessories
Part number Description
10833A GPIB cable, 1 m (3.3 ft.)
10833B GPIB cable, 2 m (6.6 ft.)
34398A RS-232, 9 pin (f) to 9 pin (f), 2.5 m (8.2 ft.) cable
9 pin (f) to 25 pin (m) adapter
Getting Started 1
Standard Shipped Items
E364xA User’s and Service Guide 7
1Getting Started
Display
Limit
Display
Limit
NOTE

Preparing the Power Supply

Preparing the Power Supply

Checking the power supply

1 Check the shipped items.
Verify that you have received the items listed in “Standard
Shipped Items” on page 6. If anything is missing or
damaged, contact your nearest Keysight Sales Office.
2 Connect the power cord and turn on the power supply.
The front panel display will light up briefly while the power supply performs its power-on self- test. The GPIB address is also displayed. To review the power- on display with all annunciators turned on, hold down turn on the power supply. If the power supply does not turn on properly, refer to
“Connecting power to the power
supply” on page 9.
3 Perform a complete self- test.
The complete self- test performs a more extensive set of tests than those performed at power-on. Hold down as you turn on the power supply and hold down the key until you hear a long beep. The self- test will begin when you release the key following the beep.
If the self- test fails, refer to Chapter 8, “Service and
Maintenance” for instructions on returning the power
supply to Keysight for service.
as you
The power supply is shipped from the factory with a power-line cord that has a plug appropriate for your location. Your power supply is equipped with a 3-wire grounding type power cord; the third conductor being the ground. The power supply is grounded only when the power-line cord is plugged into an appropriate receptacle. Do not operate your power supply without adequate cabinet ground connection.
8 E364xA User’s and Service Guide

Connecting power to the power supply

If the power supply does not turn on
Use the following steps to help solve problems you might encounter when turning on the instrument. If you need more help, refer to instructions on returning the instrument to Keysight for service.
1 Verify that there is AC power to the power supply.
First, verify that the power cord is firmly plugged into the power receptacle on the rear panel of the power supply. You should also make sure that the power source you plugged the power supply into is energized. Then, verify that the power supply is turned on.
2 Verify the power- line voltage setting.
The line voltage is set to the proper value for your country when the power supply is shipped from the factory. Change the voltage setting if it is not correct. The settings are 100 Vac, 115 Vac, or 230 Vac.
3 Verify that the correct power- line fuse is installed.
The correct fuse is installed for your country when the power supply is shipped from the factory. Refer to
Table 1- 3 to replace the fuse for your power supply.
Chapter 8, “Service and Maintenance” for
Getting Started 1
Preparing the Power Supply
Tab l e 1 - 3 E364xA power-line fuse
Model Keysight part number Part description
E3646A
E3647A
E3648A
E3649A
2110-1550 Fuse 2.5 A T 125 V for 100 Vac and 115 Vac
2110-1346 Fuse 1 A T 250 V for 230 Vac
2110-0996 Fuse 4 A T 250 V for 100 Vac and 115 Vac
2110-1548 Fuse 2 A T 250 V for 230 Vac
E364xA User’s and Service Guide 9
1Getting Started
NOTE
Power
On/Off
Output
1
Preparing the Power Supply

Checking the output

The following procedures ensure that the power supply develops its rated outputs and properly responds to operation from the front panel. For complete performance and verification tests, refer to
Maintenance”.
If an error is detected during the output checkout procedures, the ERROR annunciator will turn on. Refer to Chapter 4, “Error Messages” for more information.
Voltage output check
The following steps verify the basic voltage functions with no load.
1 Turn on the power supply.
The power supply will go into the power- on/reset state, the outputs are disabled (the OFF annunciator turns on), and its output1 and low voltage range are selected. The OVP1, OVP2, OUT1, and low voltage range indication annunciators turn on (for example, the 8 V annunciator turns on for the E3646A model), and the knob is selected for the voltage control.
2 Enable the outputs.
The OFF annunciator turns off and the CV annunciator turns on. Notice that the display is in the meter mode. Meter mode means that the display shows the actual output voltage and current.
3 Check that the front panel voltmeter properly responds to
the knob control for both the low and high voltage ranges.
Turn the knob clockwise or counter- clockwise to check that the voltmeter responds to the knob control and the ammeter indicates nearly zero. The flashing digit can be adjusted by turning the knob.
4 Ensure that the voltage can be adjusted from zero to the full
rated value by adjusting the knob.
Chapter 8, “Service and
[1]
[1] You can use the resolution selection keys to move the flashing digit to the right
or left when setting the voltage.
10 E364xA User’s and Service Guide
Getting Started 1
Power
On/Off
Output
Display
Limit
Display
Limit
Current
Vol tag e
1
Preparing the Power Supply
Current output check
The following steps check the basic current functions with a short across the power supply’s output.
1 Turn on the power supply.
Make sure that the output is disabled. The OFF annunciator is turned on.
2 Connect a short across the (+) and (–) output terminals with
an insulated test lead.
Use a wire size sufficient to handle the maximum current. Refer to
3 Enable the output.
The CV or CC annunciator turns on depending on the resistance of the test lead. Notice that the display is in the meter mode.
4 Adjust the voltage limit value to 1.0 V.
Set the display to the limit mode (the Limit annunciator will be flashing). Adjust the voltage limit to 1.0 V to assure the CC operation. The CC annunciator will turn on. To return to the normal mode, press the or let the display time- out after several seconds.
5 Set the knob to the current control to check that the front
panel ammeter properly responds to the knob control.
Turn the knob clockwise or counter- clockwise when the display is in the meter mode (the Limit annunciator is turned off). Check that the ammeter responds to the knob control and the voltmeter indicates nearly zero (the voltmeter will show the voltage drop caused by the test lead). The flashing digit can be adjusted by turning the knob.
6 Ensure that the current can be adjusted from zero to the full
rated value.
7 Turn off the power supply and remove the short from the
output terminals.
Table 1- 7 for more information.
key again
[1]
[1] You can use the resolution selection keys to move the flashing digit to the right
or left when setting the current.
E364xA User’s and Service Guide 11
1Getting Started
WARNING

230 V
100 V
115 V
Top v ie w
Preparing the Power Supply

Converting line voltage

Shock Hazard Operating personnel must not remove the power supply covers. Component replacement and internal adjustments must be made only by qualified service personnel.
Line voltage conversion is accomplished by adjusting two components: the line voltage selection switch and the power-line fuse on the rear panel.
1 Remove the AC line power.
2 Remove the cover. Refer to “Gen
page 188.
3 Set the two sections of the line voltage selector switch on
th
e PC board for the desired line voltage. Refer to
Figure 1- 2.
4 Refer to “Repl
ace the power- line fuse” on page 13 to
check the rating of the power-line fuse and replace with
e correct one if necessary.
th
5 Replace th
e cover and mark the power supply clearly with a tag or label indicating the correct line voltage and fuse that is in use.
eral Disassembly” on
12 E364xA User’s and Service Guide
Figure 1-2 Line voltage selector (set for 115 Vac)
Getting Started 1
Preparing the Power Supply
Replace the power-line fuse
1 Remove the power cord, and remove the fuse- holder
assembly from the rear panel with a flat- blade screwdriver.
2 Remove the fuse- holder from the assembly.
3 Replace with the correct fuse.
E364xA User’s and Service Guide 13
1Getting Started
NOTE
NOTE
Preparing the Power Supply
4 Replace the fuse- holder assembly in the rear panel.
Verify that the correct line voltage is selected and the power-line fuse is good.

Rack-mounting the power supply

You can mount the power supply in a standard 19- inch rack cabinet using one of three optional kits available. Instructions and mounting hardware are included with each rack- mounting kit. Any Keysight System II instrument of the same size can be rack- mounted beside the Keysight E3646A, E3647A, E3648A, or E3649A.
Remove the front and rear rubber bumpers before rack-mounting the instrument.
14 E364xA User’s and Service Guide
Getting Started 1
Front Rear (bottom view)
Preparing the Power Supply
1 To remove the front bumper, stretch a corner and then
slide it off.
2 To remove the rear bumper, pull the bumper off from the
top as there are potrusions on the sides and bottom of the cover.
3 To rack-mount a single instrument, order the adapter kit
(5063- 9243).
4 To rack-mount two instruments of the same depth
side- by- side, order the lock- link kit (5061- 9694) and rack- mount kit (5063- 9214).
E364xA User’s and Service Guide 15
1Getting Started
Preparing the Power Supply
5 To install two instruments in a sliding support shelf,
order the support shelf (5063- 9256) and the slide kit (1494- 0015).
16 E364xA User’s and Service Guide

Product at a Glance

Front panel

Getting Started 1
Product at a Glance
Figure 1-3 Front panel
Tab l e 1 - 4 Front panel overview
No Item Description
1 Output 1 selection key Select the output 1 voltage and current to be controlled and
monitored on the display.
2 Output 2 selection key Select the output 2 voltage and current to be controlled and
monitored on the display.
E364xA User’s and Service Guide 17
1Getting Started
Product at a Glance
Tab l e 1 - 4 Front panel overview (continued)
No Item Description
3 Low voltage range selection key Select the low voltage range and allow its full rated output to the
output terminals.
4 High voltage range selection key Select the high voltage range and allow its full rated output to the
output terminals.
5 Overvoltage protection key Enable or disable the overvoltage protection function, set the trip
voltage level, and clear the overvoltage condition.
6 Display limit key Display the voltage and current limit values on the display and allow
the knob adjustment for setting the limit values.
7 Resolution selection keys Move the flashing digit to the right or left, and adjust the scrolling
speed of the text being displayed in the View menu.
8 Voltage/Current adjust selection key Select the knob control function for voltage or current adjustment.
9 Knob Increase or decrease the value of the flashing digit by turning
clockwise or counter-clockwise.
10 Output On/Off key Enable or disable the power supply output. This key toggles between
on and off.
[1]
11 I/O configuration menu/Secure key
12 View menu/Calibrate key
13 State storage menu/Local key
[2]
[3]
Configure the power supply for remote interfaces, or secure or unsecure the power supply for calibration.
View the error codes and the text of the error message, calibration string, and system firmware revision, or enable the calibration mode.
Store up to five power supply states and assign a name to each of the storage locations, or return the power supply to the local mode from the remote interface mode.
14 Stored state Recall/Reset key Recall a stored operating state from location 1 through 5 and reset
the power supply to the power-on state (*RST command).
15 Tracking enabling/disabling key Enable or disable the track mode of the outputs.
[1] You can use it as the Secure or Unsecure key when the power supply is in the calibration mode.
[2] You can enable the calibration mode by holding down this key when you turn on the power supply.
[3] The key can be used as the Local key when the power supply is in the remote interface mode.
18 E364xA User’s and Service Guide
Getting Started 1
+
+
Low
High
Or
1
2
Or
Display
Limit
Display
Limit
Current
Vol tag e
On/Off
Output
NOTE
Product at a Glance
Voltage and current limit settings
You can set the voltage and current limit values from the front panel using the following method.
Figure 1-4 Voltage and current limit settings
1 Select the desired output and voltage range using the
output selection keys and the voltage range selection keys after turning on the power supply.
2 Press to show the limit values on the display.
3 Move the blinking digit to the appropriate position using
the resolution selection keys and change the blinking digit value to the desired voltage limit by turning the control knob. If the display limit times out, press
4 Set the knob to the current control mode by pressing
.
5 Move the blinking digit to the appropriate position using
the resolution selection keys and change the blinking digit value to the desired current limit by turning the control knob.
6 Press to enable the output. After about 5 seconds,
the display will go to the output monitoring mode automatically to display the voltage and current at the output.
again.
All the front panel keys and controls can be disabled with the remote interface commands. The power supply must be in the Local mode for the front panel keys and controls to function.
E364xA User’s and Service Guide 19
1Getting Started
Product at a Glance

Rear panel

Figure 1-5 Rear panel
Tab l e 1 - 5 Rear panel overview
No Description
1 AC inlet
2 Power-line fuse-holder assembly
3 Power-line module
4 Output 1 rear output terminals
5 Output 2 rear output terminals
20 E364xA User’s and Service Guide
Tab l e 1 - 5 Rear panel overview (continued)
No Description
6 GPIB (IEEE-488) interface connector
7 RS-232 interface connector

Display annunciators

Getting Started 1
Product at a Glance
Figure 1-6 Display annunciators
Tab l e 1 - 6 Display annunciators overview
Item Description
Adrs The power supply is addressed to listen or talk over a remote interface.
Rmt The power supply is in the remote interface mode.
[1]
/35V
[1]
/60V
[2]
[2]
Indicate that the low voltage range is selected.
Indicate that the high voltage range is selected.
overvoltage protection circuit has caused the power supply to shut down when the annunciator blinks.
8V
20V
OUT1 The output1 is selected for the front panel or remote operation.
OUT2 The output2 is selected for the front panel or remote operation.
OVP1 The output1 overvoltage protection function is enabled when the OVP1 annunciator turns on or the
E364xA User’s and Service Guide 21
1Getting Started
NOTE
Display
Limit
Product at a Glance
Tab l e 1 - 6 Display annunciators overview (continued)
Item Description
OVP2 The output2 overvoltage protection function is enabled when the OVP2 annunciator turns on or the
overvoltage protection circuit has caused the power supply to shut down when the annunciator blinks.
CAL The power supply is in the calibration mode.
Limit The display shows the limit values of the voltage and current.
ERROR Hardware or remote interface command errors are detected and the error bit has not been cleared.
OFF The output of the power supply is disabled. Refer to “Disabling the Output” on page 50 for
more information.
Unreg The output of the power supply is unregulated (output is neither CV nor CC).
CV The power supply is in the constant voltage mode.
CC The power supply is in the constant current mode.
TRACK The output1 and output2 are in the track mode.
[1] For E3646A and E3648A power supplies.
[2] For E3647A and E3649A power supplies.
To review the display annunciators, hold down as you turn on the power supply.
22 E364xA User’s and Service Guide

Output Connections

CAUTION
NOTE
Getting Started 1
Output Connections
Before attempting to connect wires to the rear output terminals, make sure to turn off the power supply first to avoid damage to the circuits being connected.
Front panel binding posts are available to connect load wires for bench operation and are paralleled with the rear panel (+) and (–) connections. Both the front and rear panel terminals are optimized for noise, regulation, and transient response as documented in
Available connections on the rear output terminals include the (+) and (–) outputs, the (+) and (–) sense terminals, and an earth ground terminal. The rear output terminals accept wire sizes from American Wire Gauge (AWG) 24 to AWG 14.
When making load connections from the rear output terminals, four load wire connection is recommended to keep good CV load regulation if carrying the full-rated current of the power supply.
Chapter 7.
Tab l e 1 - 7 Wire rating
AWG 10121416182022242628
Suggested maximum current (amperes)
mΩ/ft 1.001.592.534.026.3910.216.125.740.864.9
mΩ/m 3.3 5.2 8.3 13.2 21.0 33.5 52.8 84.3 133.9 212.9
[1] Single conductor in free air at 30 °C with insulation.
E364xA User’s and Service Guide 23

Current ratings

[1]
40 25 20 13 10 7 5 3.5 2.5 1.7
Table 1- 7 lists the characteristics of the AWG copper wire.
1Getting Started
NOTE
Output Connections
To satisfy safety requirements, load wires must be heavy enough not to overheat when carrying the maximum short-circuit output current of the power supply. If there is more than one load, then any pair of load wires must be capable of safely carrying the full-rated current of the power supply.

Voltage drops

The load wires must also be large enough to avoid excessive voltage drops due to the impedance of the wires. In general, if the wires are heavy enough to carry the maximum short circuit current without overheating, excessive voltage drops will not be a problem. The voltage drops across the load wires should be limited to less than two volts. Refer to
Table 1- 7 to calculate the voltage drop for some commonly
used AWG copper wires.

Load consideration

Capacitive loading
The power supply will be stable for almost any size load capacitance. However, large load capacitors may cause transient response ringing. Certain combinations of load capacitance, equivalent series resistance, and load lead inductance may result in instability (oscillation). If this occurs, the problem may often be solved by either increasing or decreasing the size of the capacitive load.
A large load capacitor may cause the power supply to cross into CC or unregulated mode momentarily when the output voltage is reprogrammed. The slew rate of the output voltage will be limited to the current setting divided by the total load capacitance (internal and external).
24 E364xA User’s and Service Guide
Getting Started 1
Output Connections
Inductive loading
Inductive loads present no loop stability problems in the constant voltage mode. In the constant current mode, inductive loads form a parallel resonance with the power supply’s output capacitor. Generally this will not affect the stability of the power supply, but it may cause ringing of the current in the load.
Pulse loading
In some applications, the load current varies periodically from a minimum to a maximum value. The constant current circuit limits the output current. Some peak loading exceeding the current limit can be obtained due to the output capacitor. To stay within the specifications for the output, the current limit should be set greater than the peak current expected or the supply may go into the CC mode or unregulated mode for brief periods.
Reverse current loading
An active load connected to the power supply may actually deliver a reverse current to the supply during a portion of its operating cycle. An external source can not be allowed to pump current into the supply without risking loss of regulation and possible damage.
These effects can be avoided by pre- loading the output with a dummy load resistor. The dummy load resistor should draw at least the same amount of current from the supply as the active load may deliver to the supply. The value of the current for the dummy load plus the value of the current the load draws from the supply must be less than the maximum current of the supply.
E364xA User’s and Service Guide 25
1Getting Started
NOTE
Output Connections

Remote voltage sensing connections

Remote voltage sensing is used to maintain regulation at the load and reduce the degradation of regulation that would occur due to the voltage drop in the leads between the power supply and the load.
When the power supply is connected for remote sensing, the OVP circuit senses the voltage at the sensing points (load) and not the output terminals.
Connections between the power supply sensing and output terminals should be removed, and using a shielded two- wire cable, the power supply sensing terminals should be connected to the load as shown in
Do not use the shield as one of the sensing conductors and the other end should be left unconnected.
Connect one end of the sensing lead shield to the chassis ground ( supply’s output voltage to decrease at the load leads. Observe the polarity when connecting the sensing leads to the load.
) only. Opening a sensing lead causes the power
Figure 1- 7.
Figure 1-7 Remote voltage sensing connections
26 E364xA User’s and Service Guide
Getting Started 1
NOTE
Output Connections
Stability
Using remote sensing under certain combinations of load lead lengths and large load capacitances may cause your application to form a filter, which becomes part of the voltage feedback loop. The extra phase shift created by this filter can degrade the power supply’s stability, resulting in poor transient response or loop instability.
In severe cases, it may cause oscillations. To minimize this possibility, keep the load leads as short as possible and twist them together. As the sense leads are part of the power supply’s programming feedback loop, accidental open- connections of sense or load leads during remote sensing operation have various unwanted effects. Provide secure and permanent connections.
During remote sensing setup, it is strongly recommended to power off (by pressing the power ON/OFF button) the power supply to avoid undesirable damage to the load or the power supply.
CV regulation
The voltage load regulation specification in Chapter 7 applies at the output terminals of the power supply. When remote sensing, add 5 mV to this specification for each 1 V drop between the positive sensing point and (+) output terminal due to the change in load current. Because the sense leads are part of the power supply’s feedback path, keep the resistance of the sense leads at or below 0.5 Ω per lead to maintain the above specified performance.
E364xA User’s and Service Guide 27
1Getting Started
Output Connections
Output rating
The rated output voltage and current specifications in
Chapter 7 apply at the output terminals of the power
supply. With remote sensing, any voltage dropped in the load leads must be added to the load voltage to calculate the maximum output voltage. The performance specifications are not guaranteed when the maximum output voltage is exceeded. If the excessive demand on the power supply forces the power supply to lose regulation, the Unreg annunciator will turn on to indicate that the output is unregulated.
Output noise
Any noise picked up on the sense leads also appears at the output of the power supply and may adversely affect the voltage load regulation. Twist the sense leads to minimize external noise pickup and run them parallel and close to the load leads. In noisy environments, it may be necessary to shield the sense leads. Ground the shield at the power supply end only. Do not use the shield as one of the sense conductors.
28 E364xA User’s and Service Guide

Multiple loads

Getting Started 1
Output Connections
When connecting multiple loads to the power supply, each load should be connected to the output terminals using separate connecting wires. This minimizes mutual coupling effects between loads and takes full advantage of the low output impedance of the power supply. Each pair of wires should be as short as possible and twisted or bundled to reduce lead inductance and noise pick- up. If a shield is used, connect one end to the power supply ground terminal and leave the other end disconnected.
If cabling considerations require the use of distribution terminals that are located remotely from the power supply, connect output terminals to the distribution terminals by a pair of twisted or shielded wires. Connect each load to the distribution terminals separately.
E364xA User’s and Service Guide 29
1Getting Started

Operating the Power Supply

Operating the Power Supply

Cooling

The power supply can operate at the rated specifications within the temperature range of 0 °C to 40 °C. A fan cools the power supply by drawing air through the sides and exhaust it out the back. Using a Keysight rack-mount will not impede the flow of air.

Bench operation

Your power supply must be installed in a location that allows sufficient space at the sides and rear of the power supply for adequate air circulation. The rubber bumpers must be removed for rack- mounting.

Cleaning

No cleaning is required for this product. If you wish to remove dust from the enclosure, use a dry cloth.
30 E364xA User’s and Service Guide
E364xA Dual Output DC Power Supplies User’s and Service Guide

2 Operation and Features

Overview 32 Constant Voltage Operation 34 Constant Current Operation 36 Track Mode Operation 38 View Menu Operation 40 Configuring the Remote Interface 42 Storing and Recalling Operating States 44 Programming the Overvoltage Protection 46 Disabling the Output 50 System-Related Operations 52 GPIB Interface Reference 56 RS-232 Interface Reference 57 Calibration 61
This chapter describes the operations and features for the E364xA dual output DC power supplies.
2 Operation and Features
2
Local
Store
Display
Limit
Display
Limit
On/Off
Output

Overview

Overview
The following section describes an overview of the front panel keys before operating your power supply.
The power supply is shipped from the factory configured in the front panel operation mode. When in this mode, the front panel keys can be used. At power- on, the power supply is automatically set to operate in the front panel operation mode and the output1 is selected for front panel operation. Press panel operation.
When the power supply is in the remote operation mode, you can return to the front panel operation mode at any time by pressing the previously send the front panel lockout command. A change between the front panel and remote operation modes will not result in a change in the output parameters.
When you press (the Limit annunciator flashes), the display of the power supply goes to the limit mode and the present limit values will be displayed. In this mode, you can also observe the change of the limit values when adjusting the knob. If you press display time- out after several seconds, the power supply will return the display to the meter mode (the Limit annunciator turns off). In this mode, the actual output voltage and current will be displayed.
The output of the power supply can be enabled or disabled from the front panel by pressing output is off, the OFF annunciator turns on and the output is disabled.
for the output2 front
(Local) key if you did not
again or let the
. When the
32 E364xA User’s and Service Guide
Operation and Features 2
Overview
The display provides the present operating status of the power supply with annunciators and also informs you of error codes. For example, the power supply is operating in the CV mode in the 8 V/3 A range and controlled from the front panel, then the CV and 8 V annunciators will turn on. IF, however the power supply is remotely controlled, the Rmt annunciator will also turn on, and when the power supply is being addressed over the GPIB interface, the Adrs annunciator will turn on. Refer to
“Display annunciators” on page 21 for more information.
The display provides the present operating status of the power supply with annunciators and also informs you of the error codes.
E364xA User’s and Service Guide 33
2 Operation and Features
Power
High
Display
Limit
NOTE

Constant Voltage Operation

Constant Voltage Operation
To set up the power supply for constant voltage (CV) operation, proceed as follows.

Front panel operation

1 Connect a load to the output terminals.
With power- off, connect a load to the (+) and (–) output terminals.
2 Turn on the power supply.
The power supply will go into the power- on/reset state and the output is disabled (the OFF annunciator turns on). The low voltage range is selected and the annunciator for the range presently selected turns on, for example, the 8V annunciator turns on for the E3646A model. The knob is selected for voltage control. At power- on, the output1 is selected and the OUT1 annunciator turns on.
Press to operate the power supply in the high voltage range before proceeding to the next step. The 20V or 60V annunciator turns on depending on which power supply you are using.
3 Set the display to the limit mode.
Notice that the Limit annunciator flashes, indicating that the display is in the limit mode. When the display is in the limit mode, you can see the voltage and current limit values of the power supply.
In the constant voltage mode, the voltage values between the meter and limit modes are the same, but the current values are not. Moreover, if the display is in the meter mode, you cannot see the change of current limit value when adjusting the knob. We recommend that you should set the display to the limit mode to see the change of current limit value in the constant voltage mode whenever adjusting the knob.
34 E364xA User’s and Service Guide
Operation and Features 2
1
Current
Vol tag e
1
Current
Vol tag e
Display
Limit
Display
Limit
On/Off
Output
NOTE
Constant Voltage Operation
4 Adjust the knob for the desired current limit.
[1]
Check that the Limit annunciator still f lashes. Set the knob for current control. The flashing digit can be changed using the resolution selection keys and the flashing digit can be adjusted by turning the knob. Adjust the knob to the desired current limit.
5 Adjust the knob for the desired output voltage.
[2]
Check that the Limit annunciator still f lashes. Set the knob for voltage control. Change the flashing digit using the resolution selection keys and adjust the knob for the desired output voltage.
6 Return to the meter mode.
Press or let the display time- out after several seconds to return to the meter mode. Notice that the Limit annunciator turns off and the display shows the OUTPUT
OFF message.
7 Enable the output.
The OFF annunciator turns off and the CV annunciator turns on. Notice that the display is in the meter mode.
8 Verify that the power supply is in the constant
voltage mode.
If you operate the power supply in the constant voltage (CV) mode, verify that the CV annunciator is lit. If the CC annunciator is lit, choose a higher current limit.
During actual CV operation, if a load change causes the current limit to be exceeded, the power supply will automatically crossover to the constant current mode at the preset current limit and the output voltage will drop proportionately.
[1] You can use the resolution selection keys to move the flashing digit to the right
or left when setting current.
[2] You can use the resolution selection keys to move the flashing digit to the right
or left when setting voltage.
E364xA User’s and Service Guide 35
2 Operation and Features
Power
High
Display
Limit

Constant Current Operation

Remote interface operation

CURRent {<current>|MIN|MAX} Set the current.
VOLTage {<voltage>|MIN|MAX} Set the voltage.
OUTPut ON Enable the output.
Constant Current Operation
To set up the power supply for constant current (CC) operation, proceed as follows.

Front panel operation

1 Connect a load to the output terminals.
With power- off, connect a load to the (+) and (–) output terminals.
2 Turn on the power supply.
The power supply will go into the power- on/reset state and the output is disabled (the OFF annunciator turns on). Its low voltage range is selected and the annunciator for the range presently selected turns on. For example, the 8V annunciator turns on for the E3646A model. The knob is selected for voltage control. At power- on, the output1 is selected and the OUT1 annunciator turns on.
Press to operate the power supply in the high voltage range before proceeding to the next step. The 20V or 60V annunciator turns on depending on which power supply you are using.
3 Set the display to the limit mode.
Notice that the Limit annunciator flashes, indicating that the display is in the limit mode. When the display is in the limit mode, you can see the voltage and current limit values of the selected supply.
36 E364xA User’s and Service Guide
Operation and Features 2
NOTE
1
1
Current
Vol tag e
Display
Limit
Display
Limit
On/Off
Output
Constant Current Operation
In constant current mode, the current values between the meter mode and limit mode are the same, but the voltage values are not. Moreover, if the display is in the meter mode, you cannot see the change of voltage limit value when adjusting the knob. We recommend that you should set the display to the limit mode to see the change of voltage limit value in the constant current mode whenever adjusting the knob.
4 Adjust the knob for the desired voltage limit.
[1]
Check that the Limit annunciator still flashes and the knob is selected for voltage control. The flashing digit can be changed using the resolution keys and the flashing digit can be adjusted by turning the knob. Adjust the knob for the desired voltage limit.
5 Adjust the knob for the desired output current.
[2]
Check that the Limit annunciator still flashes. Set the knob for current control. Change the flashing digit using the resolution selection keys and adjust the knob to the desired output current.
6 Return to the meter mode.
Press or let the display time- out after several seconds to return to the meter mode. Notice that the Limit annunciator turns off and the display shows the OUTPUT
OFF message.
7 Enable the output.
The OFF annunciator turns off and the CC annunciator turns on. Notice that the display is in the meter mode.
8 Verify that the power supply is in the constant
current mode.
If you operate the power supply in the constant current (CC) mode, verify that the CC annunciator is lit. If the CV annunciator is lit, choose a higher voltage limit.
[1] You can use the resolution selection keys to move the flashing digit to the right
or left when setting the voltage.
[2] You can use the resolution selection keys to move the flashing digit to the right
or left when setting the current.
E364xA User’s and Service Guide 37
2 Operation and Features
NOTE

Track Mode Operation

During actual CC operation, if a load change causes the voltage limit to be exceeded, the power supply will automatically crossover to constant voltage mode at the preset voltage limit and the output current will drop proportionately.

Remote interface operation

VOLTage {<voltage>|MIN|MAX} Set the voltage.
CURRent {<current>|MIN|MAX} Set the current.
OUTPut ON Enable the output.
Track Mode Operation
This power supply provides tracking outputs. In the track mode, two voltages of the output1 and the output2 supplies track each other within the voltage programming accuracy as described on convenience in varying the symmetrical voltages needed by operational amplifiers and other circuits using two balanced outputs. The track mode is always in the off state when power has been turned off or after a remote interface reset.
“Supplemental Characteristics” on page 174 for
38 E364xA User’s and Service Guide

Front panel operation

Track
Track
Track
NOTE
1 Set either the output1 or the output2 supply to the desired
voltage.
2 Enable the track mode.
HOLD_KEY
Hold down until the Tr ac k annunciator turns on. For example, when the track mode is first enabled with the output1 selected, the output2 supply will be set to the same voltage level as the output1 supply. Once enabled, any change of the voltage level in either the output1 or the output2 supply will be reflected in other supply. The current limit is independently set for each of the output1 or the output2 supply and is not affected by the track mode.
3 Exit the track mode.
The Tr ac k annunciator turns off.
The tracking accuracy is dependent upon the voltage programming accuracy of each output. Refer to “Electrical Specifications” on page 172 for more information.
Operation and Features 2
Track Mode Operation

Remote interface operation

OUTPut:TRACk[:STATe] {OFF|ON}
OUTPut:TRACk[:STATe]? Queries the track
E364xA User’s and Service Guide 39
Disable/enable the track mode.
mode status.
2 Operation and Features
<
Current
Vol tag e
>
Low
High
View
View
View
View
View

View Menu Operation

View Menu Operation
From the View menu, you can read the errors, firmware revision, and calibration string. In addition, you can change the front panel display mode to V-V display, I- I display, or V- I display as desired. With this V-V or I- I display mode setting, you can see voltages or currents on the output1 and the output2, simultaneously.
After the display mode is set to V- V or I- I, you cannot change the limit values. If you attempt to change the limit values by turning the knob or pressing one of the following keys — front panel display will automatically return to the normal display to allow you to change the limit values.
After the display mode is set to V-V or I- I, all the annunciators remain unchanged.
To exit the view menu without any changes, press until NO CHANGE is displayed, or select EXIT by turning the knob and press
, , , , or , the
.

Changing the display mode

1 Enter the View menu.
DISPLAY
If ERRORS appears when you enter the view menu, one or more command syntax or hardware errors have been detected. Then turn the knob until “DISPLAY” is displayed.
2 Select the display mode you want to display.
V-I DISPLAY
Select one of the following display modes by turning the knob — V-V D I SPLAY, I-I DISPLAY, or V-I DISPLAY.
3 Save the change and exit the menu.
40 E364xA User’s and Service Guide

Viewing the errors

View
View
>>>
View
View
View
View
1 Press twice to view the errors.
1: ERR -103
The total number of the errors detected will be displayed shortly before the above message is displayed. The above number 1 stands for the first error in queue and the -103 is the error code.
2 Scroll through the error numbers and view the text of the
error message by using the knob and key.
Press to increase the scrolling speed of the text on the display.
3 Clear the errors and exit the menu.
All the errors are cleared when you exit the menu by pressing 30 seconds.
Refer to Chapter 4, “Error Messages” for more information.
Operation and Features 2
View Menu Operation
or let the display time- out for about

Viewing the firmware revision

1 Enter the View menu and select FW REVISION.
FW REVISION
2 View the firmware revision of your power supply.
REV X.X-Y.Y-Z.Z
The first number is the firmware revision number for the main processor; the second is for the input/output processor; and the third is for the front panel processor. Refer to information.
E364xA User’s and Service Guide 41
“Firmware revision query” on page 54 for more
2 Operation and Features
View
View
>
I/O
Config

Configuring the Remote Interface

Viewing the calibration string

1 Enter the View menu and select CAL STRING.
CAL STRING
2 Scroll through the text of the message.
FACTORY CAL 26/11/12
NO STRING is displayed if no calibration message is stored.
Press
to increase the scrolling speed. The Cal String cannot be changed from the front panel. Refer to
“Calibration message” on page 66 for more information.
Configuring the Remote Interface
This power supply is shipped with both a GPIB (IEEE- 488) interface and an RS- 232 interface. The GPIB interface is selected when the power supply is shipped from the factory. Only one interface can be enabled at a time. To exit the I/O configuration mode without any changes, press the NO CHANGE message is displayed.
You can set the GPIB address, parity, and baud rate from the front panel only.
The current selection is highlighted for emphasis. All other choices are dimmed.
The interface selection is stored in the non- volatile memory, and does not change when power has been turned off or after a power- on reset (*RST command).
until
42 E364xA User’s and Service Guide

GPIB configuration

I/O
Config
I/O
Config
I/O
Config
NOTE
I/O
Config
I/O
Config
1 Turn on the remote configuration mode.
GPIB / 488
If RS-232 appears, select GPIB / 488 by turning the knob.
2 Select the GPIB address.
ADDR 05
You can set the power supply’s address to any value between 0 and 30. The factory setting is address 5.
3 Save the change and exit the menu.
SAVED
Your computer's GPIB interface card has its own address. Be sure to avoid using the computer's address for any instrument on the interface bus. Keysight GPIB interface cards generally use address 21.
Operation and Features 2
Configuring the Remote Interface

RS-232 configuration

1 Turn on the remote configuration mode.
GPIB / 488
Notice that if you changed the remote interface selection to RS- 232 before, the RS-232 message is displayed.
2 Choose the RS- 232 interface.
RS-232
You can choose the RS- 232 interface by turning the knob.
3 Select the baud rate.
Select one of the following: 300, 600, 1200, 2400, 4800, or 9600 (factory setting) baud.
9600 BAUD
E364xA User’s and Service Guide 43
2 Operation and Features
I/O
Config
I/O
Config
Store

Storing and Recalling Operating States

4 Select the parity and number of stop bits.
Select one of the following: None (8 data bits, factory setting), Odd (7 data bits), or Even (7 data bits). When you set the parity, you are also indirectly setting the number of the data bits.
NONE 8 BITS
5 Save the change and exit the menu.
SAVED
Storing and Recalling Operating States
You can store up to five different operating states in non- volatile storage locations. When shipped from the factory, storage locations 1 through 5 are empty. You can name a location from the front panel or over the remote interface but you can only recall a named state from the front panel.
The following steps show you how to store and recall an operating state.
To cancel the store/recall operation, select the EXIT menu by turning the knob and then pressing
or letting the
display time- out.

Front panel operation

Storing the operating state
1 Set up the power supply for the desired operating state.
The storage feature “remembers” the output voltage range selection, the limit value settings of voltage and current, output on/off state, OVP on/off state, and OVP trip levels.
44 E364xA User’s and Service Guide
Operation and Features 2
Store
Store
Store
Store
Store
NOTE
Recall
Recall
Storing and Recalling Operating States
2 Turn on the storage mode.
STORE STATE
From the front panel, you can assign names (up to nine characters) to each of the five stored states. Turn the knob until NAME STATE appears and press
to select
the locations. Then press to name the locations.
NAME STATE
1:P15V_TEST
3 Select the storage location.
Turn the knob to the right to specify the memory location 2.
2: STATE2
4 Save the operating state.
DONE
Recalling a stored state
Before proceeding with the steps listed below, ensure that the outputs are disabled throughout the recall procedure (the CV or CC annunciator turns off and the OFF annunciator turns on).
1 Turn on the recall mode.
Memory location 1 will be displayed in the recall mode.
1: P15V_TEST
2 Select the stored operating state.
2: STATE2
RESET
You can select the above RESET mode to reset the power supply to the power- on state without turning power off/on or without using the *RST command over the remote interface. Refer to
*RST” on page 98 for more
details on the *RST command.
3 Recall the stored operating state.
DONE
E364xA User’s and Service Guide 45
2 Operation and Features
Power
2or1

Programming the Overvoltage Protection

Remote interface operation

Use the following commands to store and recall the power supply state.
*SAV {1|2|3|4|5} Store an operating state to
a specified location.
*RCL {1|2|3|4|5} Recall a previously stored
state from a specified location.
MEM:STAT:NAME 1, P15V_TEST’” Name the storage location 1
as “P15V_TEST”.
Programming the Overvoltage Protection
Overvoltage protection guards the load against output voltages reaching values greater than the programmed protection level. It is accomplished by shorting the output via an internal SCR when the trip level is set to equal or greater than 3 V, or by programming the output to 1 V when the trip level is set to less than 3 V.
The following steps show how to set the OVP trip level, how to check the OVP operation, and how to clear the overvoltage condition.

Front panel operation

Setting the OVP level and enabling the OVP circuit
1 Turn on the power supply.
2 Select the output to be programmed.
46 E364xA User’s and Service Guide
Operation and Features 2
Over
Vol tag e
<
>
Over
Vol tag e
Over
Vol tag e
Programming the Overvoltage Protection
3 Enter the OVP menu and set the desired trip level.
LEVEL 22.0 V (E3646A)
Use the knob and the resolution selection key or
to set the desired trip level. Note that you cannot set
the trip levels to lower than 1.0 V.
4 Enable the OVP circuit.
OVP ON
5 Exit the OVP menu.
CHANGED
If the OVP settings are not changed, NO CHANGE will be displayed. The power supply will exit the OVP menu and the display will return to the meter mode. Check that the OVP1 and OVP2 annunciators turn on if the OVP circuit is enabled.
Checking the OVP operation
To check the OVP operation, raise the output voltage to near the trip point. Then very gradually increase the output by turning the knob until the OVP circuit trips. This will cause the power supply output to drop to near zero, the OVP1 or OVP2 annunciator to flash depending on the output operated, and the CC annunciator to turn on. The OVP1 (or OVP2) TRIP message also appears on the display.
Clearing the overvoltage condition
When the OVP condition occurs, the OVP1 or OVP2 annunciator flashes. When it was caused by an external voltage source such as a battery, disconnect it first. Clear the overvoltage condition by adjusting the output voltage level or by adjusting the OVP trip level.
The following steps show you how to clear the overvoltage condition and return to the normal mode operation. In the following steps, the display will return to OVP1 (or OVP2) TRIP if you allow the display to time- out after about several seconds.
E364xA User’s and Service Guide 47
2 Operation and Features
Display
Limit
Display
Limit
Over
Vol tag e
Over
Vol tag e
Over
Vol tag e
Over
Vol tag e
Over
Vol tag e
Over
Vol tag e
Programming the Overvoltage Protection
• By adjusting the output voltage level
i Lower the output voltage level below the OVP trip point.
The OVP1 or OVP2, and Limit annunciators are flashing after
is pressed.
ii Check that you lowered the voltage level below the OVP
trip point.
The OVP trip point is displayed. Do not adjust the trip point at this step.
iii Select the OVP CLEAR mode by turning the knob.
OVP ON
OVP CLEAR
iv Clear the overvoltage condition and exit this menu.
DONE
The annunciator for the OVP operation will not flash any more. The output will return to the meter mode.
• By adjusting the OVP trip level
i Raise the OVP trip level higher than the level tripped.
ii Select the OVP CLEAR mode by turning the knob.
OVP ON
OVP CLEAR
iii Clear the overvoltage condition and exit this menu.
DONE
The annunciator for the OVP operation will not flash any more. The output will return to the meter mode.
48 E364xA User’s and Service Guide

Remote interface operation

NOTE
VOLT:PROT {<voltage>|MIN|MAX} Set the OVP level.
VOLT:PROT:STAT {OFF|ON) Disable or enable the
VOLT:PROT:CLE Clear the tripped
The power supply’s OVP circuit contains a crowbar SCR, which effectively shorts the output of the power supply whenever the overvoltage condition occurs. If an external voltage source such as a battery is connected across the output, and the overvoltage condition inadvertently occurs, the SCR will continuously sink a large current from the source and possibly damaging the power supply. To avoid this, a diode must be connected in series with the output as shown in Figure 2-1.
Operation and Features 2
Programming the Overvoltage Protection
OVP ci rcuit.
OVP ci rcuit.
Figure 2-1 Recommended protection circuit for battery charging
E364xA User’s and Service Guide 49
2 Operation and Features
<
>
Display
Limit
On/Off
Output

Disabling the Output

Disabling the Output
The output of the power supply can be disabled or enabled from the front panel.
When the power supply is in the Off state, the OFF annunciator turns on and the output is disabled. The OFF annunciator turns off when the power supply returns to the On state. When the output is disabled, the voltage value is 0 V and the current value is 0.02 A. This gives a zero output voltage without actually disconnecting the output.
The output state is stored in the volatile memory. The output is always disabled when power has been turned off or after a remote interface reset.
While the output is disabled, the control knob is locked to prevent any unwanted changes from occurring. The other front panel keys are still working.
To lock the control knob, move the flashing digit to the right or left using the keys until the flashing digit disappears.
To see or check the changes while the output is disabled, press
before returning to the meter mode.
or resolution selection

Front panel operation

OUTPUT OFF

Remote interface operation

OUTP {OFF|ON}
50 E364xA User’s and Service Guide
Operation and Features 2
NOTE
Disabling the Output

Disconnecting the output using an external relay

To disconnect the output, an external relay must be connected between the output and the load. A TTL signal of either low true or high true is provided to control an external relay. This signal can only be controlled with the remote command OUTPut:RELay {OFF|ON}. The TTL output is available on the RS- 232 connection pin 1 and pin 9.
When the OUTPut:RELay state is “ON”, the TTL output of pin 1 is high (4.5 V) and pin 9 is low (0.5 V). The levels are reversed when the OUTPut:RELay state is OFF. The TTL output of pin 1 or pin 9 of the RS- 232 connector is available only after installing two jumpers (JP1 and JP2) power supply. Refer to “Component Locator Diagram” on
page 225 to locate them.
Do not use the RS-232 interface if you have configured the power supply to output relay control signals. Internal components on the RS-232 circuitry may be damaged.
[1]
inside the
[1] For serial MY53xx6xxx, the two jumpers are JP752 and JP751.
E364xA User’s and Service Guide 51
2 Operation and Features

System-Related Operations

System-Related Operations
This section gives information on system- related topics such as storing power supply states, reading errors, running a self- test, displaying messages on the front panel, and reading firmware revisions.

State storage

The power supply has five storage locations in non-volatile memory to store power supply states. The locations are numbered 1 through 5. You can assign a name to each of the locations for use from the front panel.
You can store the power supply state in any of the five locations. However, you can only recall a state from a location that contains a previously stored state.
The power supply stores the following: the state of output range selection, flashing digit position on the display, the limit value settings of voltage and current, output on/off state, OVP on/off state, and trip levels.
When shipped from the factory, storage locations 1 through 5 are empty.
You can assign a name to the storage locations. You can name a location from the front panel or over the remote interface but you can only recall a named state from the front panel. From the remote interface, you can only recall a stored state using a number (1 through 5).
The name can contain up to nine characters. A letter (A- Z) or number (0- 9) can be used for the first character to name a state. The underscore character (“_”) can be used for the remaining eight characters. Blank spaces are not allowed. An error is generated if you specify a name with more than nine characters.
A power- on reset (*RST command) does not affect the configurations stored in memory. Once a state is stored, it remains until it is overwritten.
52 E364xA User’s and Service Guide
Operation and Features 2
Store
Recall
System-Related Operations
Front panel operation
STORE STATE, NAME STATE, EXIT
To reset the power supply to the power- on reset state without using the *RST command or turning power off/on, select RESET from the following.
5 states, RESET, EXIT
Remote interface operation
Use the following commands to store and recall power supply states.
*SAV {1|2|3|4|5}
*RCL {1|2|3|4|5}
To assign a name to a stored state to be recalled from the front panel, send the following command. From the remote interface, you can only recall a stored state using a number (1 through 5).
MEM:STAT:NAME 1, P15V_TEST

Self-test

A power- on self- test occurs automatically when you turn on the power supply. This test assures you that the power supply is operational. This test does not perform the extensive set of tests that are included as part of the complete self- test described below. If the power-on self- test fails, the ERROR annunciator turns on.
A complete self- test performs a series of tests and takes approximately 2 seconds to execute. If all tests pass, you can have a high confidence that the power supply is operational.
E364xA User’s and Service Guide 53
2 Operation and Features
Display
Limit
System-Related Operations
If the complete self- test is successful, PASS is displayed on the front panel. If the self- test fails, FAIL is displayed and the ERROR annunciator turns on. Refer to
and Maintenance” for instructions on returning the power
supply to Keysight for service.
Chapter 8, “Service
Front panel operation
To perform the complete front panel self- test, hold down
as you turn on the power supply and hold down the
key until you hear a long beep. The self- test will begin when you release the key following the beep.
Remote interface operation
*TST?
Returns 0 if the complete self- test passes or 1 if it fails.

Error conditions

When the front panel ERROR annunciator turns on, one or more command syntax or hardware errors have been detected. A record of up to 20 errors can be stored in the power supply’s error queue. Refer to
Messages” for more information.
Chapter 4, “Error

Firmware revision query

The power supply has three microprocessors for control of various internal systems. You can query the power supply to determine which revision of firmware is installed for each microprocessor.
The power supply returns three revision numbers. The first number is the firmware revision number for the main processor; the second is for the input/output processor; and the third is for the front panel processor.
54 E364xA User’s and Service Guide
Front panel operation
View
View
View
View
REV X.X-Y.Y-Z.Z
Press and turn the knob until FW REVISION appears and then press to read the system firmware revision numbers.
Remote interface operation
*IDN?
The above command returns a string in the form:
Keysight Technologies,E3646A,0,X.X-Y.Y-Z.Z (E3646A)
Be sure to dimension a string variable with at least 40 characters.

SCPI language version

Operation and Features 2
System-Related Operations
This power supply complies with the rules and regulations of the present version of Standard Commands for Programmable Instruments (SCPI). You can determine the SCPI version with which the power supply is in compliance by sending a command from the remote interface.
You can query the SCPI version from the remote interface only.
Remote interface operation
SYST:VERS? Query the SCPI version
Returns a string in the form of YYYY.V where the Y represents the year of the version, and the V represents the version number for that year (for example, 1997.0).
E364xA User’s and Service Guide 55
2 Operation and Features
NOTE

GPIB Interface Reference

GPIB Interface Reference
The GPIB connector on the rear panel connects your power supply to the computer and other GPIB devices.
“Accessories” lists the cables that are available from
Keysight. A GPIB system can be connected together in any configuration (star, linear, or both) as long as the following rules are observed:
Each device on the GPIB (IEEE- 488) interface must have a unique address. You can set the power supply’s address to any value between 0 and 30. The address is set to 5 when the power supply is shipped from the factory. The GPIB address is displayed at power- on.
You can set the GPIB address from the front panel only.
The address is stored in the non- volatile memory, and does not change when power has been turned off or after a power- on reset (*RST command).
Your computer's GPIB interface card has its own address. Avoid using the computer's address for any instrument on the interface bus. Keysight GPIB interface cards generally use address 21.
The total number of devices including the computer is not more than 15.
The total length of all the cables used is not more than 2 m times the number of devices connected together, up to a maximum of 20 m.
Do not stack more than three connector blocks together on any GPIB connector. Make sure that all connectors are fully seated and that the lock screws are firmly finger tightened.
Chapter 1,
Refer to “Configuring the Remote Interface” on page 42 for more information on configuring the power supply for remote interface operations from the front panel.
IEEE-488 states that you should exercise caution if your individual cable lengths exceed 4 m.
56 E364xA User’s and Service Guide

RS-232 Interface Reference

I/O
Config
The power supply can be connected to the RS- 232 interface using the 9- pin (DB- 9) serial connector on the rear panel. The power supply is configured as a Data Terminal Equipment (DTE) device. For all communications over the RS- 232 interface, the power supply uses two handshake lines: Data Terminal Ready (DTR, on pin 4) and Data Set Ready (DSR, on pin 6).
The following sections contain information to help you use the power supply over the RS- 232 interface. The programming commands for RS- 232 are explained in
“Interface Configuration Commands” on page 106.

RS-232 configuration overview

Configure the RS- 232 interface using the parameters as shown below. Use the front panel baud rate, parity, and number of data bits (refer to
“Configuring the Remote Interface” on page 42 for more
information).
Operation and Features 2
RS-232 Interface Reference
key to select the
Baud rate: 300, 600, 1200, 2400, 4800, or 9600 (factory setting)
Parity and data bits: None/8 data bits (factory setting) Even/7 data bits, or Odd/7 data bits
Number of start bits: 1 bit (fixed)
Number of stop bits: 2 bits (fixed)
E364xA User’s and Service Guide 57
2 Operation and Features
RS-232 Interface Reference

RS-232 data frame format

A character frame consists of all the transmitted bits that make up a single character. The frame is defined as the characters from the start bit to the last stop bit, inclusively. Within the frame, you can select the baud rate, number of data bits, and parity type. The power supply uses the following frame formats for seven and eight data bits.

Connection to a computer or terminal

To connect the power supply to a computer or terminal, you must have the proper interface cable. Most computers and terminals are Data Terminal Equipment (DTE) devices. Since the power supply is also a DTE device, you must use a DTE- to- DTE interface cable. These cables are also called null- modem, modem- eliminator, or crossover cables.
The interface cable must also have the proper connector on each end and the internal wiring must be correct. Connectors typically have nine pins (DB- 9 connector) or 25 pins (DB- 25 connector) with a male or female pin configuration. A male connector has pins inside the connector shell and a female connector has holes inside the connector shell.
If you cannot find the correct cable for your configuration, you may have to use a wiring adapter. If you are using a DTE- to- DTE cable, make sure the adapter is a “straight- through” type. Typical adapters include gender changers, null- modem adapters, and DB- 9 to DB- 25 adapters.
58 E364xA User’s and Service Guide
Operation and Features 2
Instrument
PC
DB9 Male
DB9 Female
DB9 Female
DB9 Male
DCD RX TX DTR
1 2 3 4
5 6 7 8 9
GND DSR RTS CTS RI
1 2 3 4
5 6 7 8 9
DCD RX TX DTR
GND DSR RTS CTS RI
5182-4794
Cable
RS-232 Interface Reference
The cable and adapter diagrams as shown in Figure 2- 2 and
Figure 2- 3 can be used to connect the power supply to most
computers or terminals.
DB-9 serial connection
If your computer or terminal has a 9- pin serial port with a male connector, use the null- modem cable included with the Keysight 34398A Cable Kit. This cable has a 9- pin female connector on each end. The cable pin diagram is as shown in
Figure 2- 2.
Figure 2-2 DB-9 serial connection
DB-25 serial connection
If your computer or terminal has a 25- pin serial port with a male connector, use the null- modem cable and 25- pin adapter included with the Keysight 34398A Cable Kit. The cable and adapter pin diagrams are as shown in
E364xA User’s and Service Guide 59
Figure 2- 3.
2 Operation and Features
Instrument
PC
DB9 Male
DB9 Female
DB9 Female
DB9 Male
DCD RX TX DTR
1 2 3 4
5 6 7 8 9
GND DSR RTS CTS RI
TX RX RTS CTS
DSR GND DCD DTR
5182-4794
Cable
5181-6641
Adapter
1 2 3 4
5 6 7 8 9
1 2 3 4
5 6 7 8 9
2 3 4 5
6 7 8 20
DB25 Female
DB25 Male
RS-232 Interface Reference
Figure 2-3 DB-25 serial connection

RS-232 troubleshooting

Here are a few things to check if you are having problems communicating over the RS- 232 interface. If you need additional help, refer to the documentation that came with your computer.
Verify that the power supply and your computer are configured for the same baud rate, parity, and number of data bits. Make sure that your computer is set up for one start bit and two stop bits (these values are fixed on the power supply).
Make sure to execute the SYSTem:REMote command to place the power supply in the remote mode.
Verify that you have connected the correct interface cable and adapters. Even if the cable has the proper connectors for your system, the internal wiring may be incorrect. The Keysight 34398A Cable Kit can be used to connect the power supply to most computers or terminals.
Verify that you have connected the interface cable to the correct serial port on your computer (COM1, COM2, etc.).
60 E364xA User’s and Service Guide

Calibration

NOTE
This section gives an overview of the calibration features of the power supply. For more detailed discussion of the calibration procedures, refer to
Maintenance”.

Calibration security

This feature allows you to enter a security code to prevent accidental or unauthorized calibrations of the power supply. When you first receive your power supply, it is secured. Before you can calibrate the power supply, you must unsecure it by entering the correct security code.
Table 2- 1 shows the security code for each model when
the power supply is shipped from the factory. The security code is stored in non- volatile memory, and does not change when power has been turned off or after a power- on reset (*RST command).
The security code may contain up to 11 alphanumeric characters or underscore character (“_”). A letter (A- Z) or number (0- 9) can be used for the first character. You do not have to use all 11 characters.
_ _ _ _ _ _ _ _ _ _ _ (11 characters)
When you secure the power supply from the remote interface, use a maximum of eight alphanumeric characters to unsecure the power supply from the front panel also. For example, the security code for E3646A has less than nine characters.
Operation and Features 2
Calibration
Chapter 8, “Service and
If you forget your security code, you can disable the security feature by adding a jumper inside the power supply and then enter a new code. Refer to Chapter 8, “Service and Maintenance” for more information.
E364xA User’s and Service Guide 61
2 Operation and Features
Calibrate
View
Power
Calibrate
View
Secure
Config
I/O
Power
Secure
Config
I/O
Calibration
Tab l e 2 - 1 Factory-setting security codes
Model Security code
E3646A 003646
E3647A 003647
E3648A 003648
E3649A 003649

To unsecure for calibration

You can unsecure the power supply either from the front panel or over the remote interface. The power supply is secured when shipped from the factory. Refer to for the factory- setting secure code for your power supply.
Front panel operation
Table 2- 1
1 Select the calibration mode.
SECURED
If the power supply is secured, the above message is displayed as you turn on the power supply by holding down the
(Calibrate) key. Hold down the key until
you hear a long beep and the CAL MODE message is displayed.
2 Enter the security code.
000000
Enter the security code using the control knob and resolution selection keys.
3 Save the change and exit the menu.
UNSECURED
You will see the above message if the security code is correct and the CAL MODE message is displayed. To exit the calibration mode, turn the power off and on.
62 E364xA User’s and Service Guide
Notice that if you enter the wrong security code, INVALID
Calibrate
View
Power
Calibrate
View
Secure
Config
I/O
is displayed and the code entering mode is displayed for you to enter the correct code.
Remote interface operation
CAL:SEC:STAT {OFF|ON},<code> Secure or unsecure
To unsecure the power supply, send the above command with the same code used to secure. For example:
CAL:SEC:STAT OFF, 003646’ (E3646A model)

To secure against calibration

You can secure the power supply against calibration either from the front panel or over the remote interface. The power supply is secured when shipped from the factory.
Operation and Features 2
Calibration
the power supply.
Be sure to read the security code rules at “Calibration
security” on page 61 before attempting to secure the power
supply.
Front panel operation
1 Select the calibration mode.
UNSECURED
If the power supply is unsecured, the above message is displayed as you turn on the power supply by holding down the you hear a long beep and the CAL MODE message is displayed.
2 Enter the security code.
000000
Enter the desired security code using the control knob and resolution selection keys.
E364xA User’s and Service Guide 63
(Calibrate) key. Hold down the key until
2 Operation and Features
Power
Secure
Config
I/O
Secure
Config
I/O
Secure
Config
I/O
Calibration
3 Save the change and exit the menu.
SECURED
The secured setting is stored in non- volatile memory, and does not change when power has been turned off or after a power- on reset (*RST command).
Remote interface operation
CAL:SEC:STAT {OFF|ON},<code> Secure or unsecure
the power supply.
To secure the power supply, send the above command with the same code as used to unsecure. For example,
CAL:SEC:STAT ON, 003646’ (E3646A model)

To change the security code

To change the security code, you must first unsecure the power supply, and then enter a new code. Read the security code rules at
“Calibration security” on page 61 before
attempting to secure the power supply.
Front panel operation
To change the security code, first make sure that the power supply is unsecured. Go to the security code entry, press the
(Secure) key after the CAL MODE message is displayed,
enter the new security code using the control knob and resolution selection keys, and then press the key.
Changing the code from the front panel also changes the code as seen from the remote interface.
64 E364xA User’s and Service Guide
(Secure)
Remote interface operation
CAL:SEC:CODE <new code> Change the security
To change the security code, first unsecure the power supply using the old security code. Then, enter the new code as shown below.
CAL:SEC:STAT OFF, ‘003646 Unsecure with the
CAL:SEC:CODE ‘ZZ001443 Enter the new code.
CAL:SEC:STAT ON, ‘ZZ001443 Secure with the new

Calibration count

Operation and Features 2
Calibration
code.
old code.
code.
You can determine the number of times that your power supply has been calibrated. Your power supply was calibrated before it left the factory. When you receive your power supply, read the count to determine its initial value.
The calibration count feature can be performed from the remote interface only.
The calibration count is stored in non- volatile memory, and it does not change when power has been turned off or after a remote interface reset.
The calibration count increments up to a maximum of 32767 after which it wraps- around to 0. Since the value increments by one for each calibration point, a complete calibration will increase the value by six counts.
Remote interface operation
CAL:COUN? Query the number of times of calibration
E364xA User’s and Service Guide 65
2 Operation and Features
View
View>View
View
Calibration

Calibration message

The power supply allows you to store one message in calibration memory in the mainframe. For example, you can store such information as the date when the last calibration was performed, the date when the next calibration is due, the power supply’s serial number, or even the name and phone number of the person to contact for a new calibration.
You can record a calibration message only from the remote interface and only when the power supply is unsecured. You can read the message from either the front panel or over the remote interface. You can read the calibration message whether the power supply is secured or unsecured.
The calibration message may contain up to 40 characters. From the front panel, you can view 11 characters of the message at a time.
Storing a calibration message will overwrite any message previously stored in memory.
The calibration message is stored in non- volatile memory, and does not change when power has been turned off or after a remote interface reset.
Front panel operation
To read the calibration message from the front panel, press
and turn the knob until CAL STRING is displayed. Press to scroll through the text of the message. Press
to increase the scrolling speed.
CAL STRING
Remote interface operation
To store the calibration message, send the following command.
CAL:STR CAL 12-05-99
66 E364xA User’s and Service Guide
E364xA Dual Output DC Power Supplies User’s and Service Guide

3 Remote Interface Reference

SCPI Command Summary 68 Introduction to the SCPI Language 74 Simplified Programming Overview 80 Using the APPLy Command 83 Output Settings and Operation Commands 84 Triggering Commands 92 System-Related Commands 95 State Storage Commands 99 Calibration Commands 101 Interface Configuration Commands 106 SCPI Status Registers 107 Status Reporting Commands 119 Halting an Output in Progress 124 SCPI Conformance Information 125 IEEE-488 Conformance Information 128
This chapter lists the SCPI commands.
3 Remote Interface Reference
NOTE

SCPI Command Summary

SCPI Command Summary
If you are a first-time user of the SCPI language, refer to “Introduction to
the SCPI Language” and “Simplified Programming Overview” to familiarize
with the SCPI language before attempting to program the power supply.
This section summarizes the Standard Commands for Programmable Instruments (SCPI) available to program the power supply over the remote interface. Refer to the respective sections in this chapter for more details on each command.
Throughout this manual, the following conventions are used for the SCPI command syntax.
Square brackets ([]) indicate optional keywords or parameters.
Braces ({}) enclose parameters within a command string.
Triangle brackets (<>) indicate that you must substitute a
value or a code for the enclosed parameter.
A vertical bar (|) separates one of two or more alternative parameters.
68 E364xA User’s and Service Guide
Tab l e 3 - 1 SCPI command summary
Output Settings and Operation Commands
APPLy {<voltage>|DEF|MIN|MAX}[,{<current>|DEF|MIN|MAX}] APPLy? [SOURce:]
CURRent[:LEVel][:IMMediate][:AMPLitude] {<current>|MIN|MAX|UP|DOWN} CURRent[:LEVel][:IMMediate][:AMPLitude]? [MIN|MAX] CURRent[:LEVel][:IMMediate]:STEP[:INCRement] {<numeric value>|DEFault} CURRent[:LEVel][:IMMediate]:STEP[:INCRement]? [DEFault] CURRent[:LEVel]:TRIGgered[:AMPLitude] {<current>|MIN|MAX} CURRent[:LEVel]:TRIGgered[:AMPLitude]? [MIN|MAX] VOLTage[:LEVel][:IMMediate][:AMPLitude] {<voltage>|MIN|MAX|UP|DOWN} VOLTage[:LEVel][:IMMediate][:AMPLitude]? [MIN|MAX] VOLTage[:LEVel][:IMMediate]:STEP[:INCRement] {<numeric value>|DEFault} VOLTage[:LEVel][:IMMediate]:STEP[:INCRement]? [DEFault] VOLTage[:LEVel]:TRIGgered[:AMPLitude] {<voltage>|MIN|MAX} VOLTage[:LEVel]:TRIGgered[:AMPLitude]? [MIN|MAX] VOLTage:PROTection[:LEVel] {<voltage>|MIN|MAX} VOLTage:PROTection[:LEVel]? [MIN|MAX] VOLTage:PROTection:STATe {0|1|OFF|ON} VOLTage:PROTection:STATe? VOLTage:PROTection:TRIPped? VOLTage:PROTection:CLEar VOLTage:RANGe {P8V VOLTage:RANGe?
INSTrument[:SELect] {OUTPut1|OUTPut2|OUT1|OUT2}
[:SELect]? :NSELect {1|2} :NSELect? :COUPle [:TRIGger] {ON|OFF} [:TRIGger]?
MEASure
[:SCALar] :CURRent[:DC]? [:VOLTage][:DC]?
OUTPut
:TRACk[:STATe] {ON|OFF} :TRACk[:STATe]?
[1]
|P20V
[1]
|P35V
[2]
|P60V
[2]
|LOW|HIGH}
Remote Interface Reference 3
SCPI Command Summary
E364xA User’s and Service Guide 69
3 Remote Interface Reference
SCPI Command Summary
Tab l e 3 - 1 SCPI command summary (continued)
Triggering Commands
INITiate[:IMMediate] TRIGger[:SEQuence]
:DELay {<seconds>|MIN|MAX} :DELay? [MIN|MAX] :SOURce {BUS|IMM} :SOURce?
*TRG
System-Related Commands
DISPlay[:WINDow]
[:STATe] {OFF|ON} [:STATe]? :MODE {VV|VI|II} :MODE? :TEXT[:DATA] <quoted string> :TEXT[:DATA]? :TEXT:CLEar
SYSTem
:BEEPer[:IMMediate] :ERRor? :VERSion?
OUTPut
:RELay[:STATe] {OFF|ON} :RELay[:STATe]? [:STATe] {OFF|ON}
[:STATe]? *IDN? *RST *TST?
State Storage Commands
*SAV {1|2|3|4|5} *RCL {1|2|3|4|5} MEMory:STATe
:NAME {1|2|3|4|5}, <quoted name>
:NAME? {1|2|3|4|5}
70 E364xA User’s and Service Guide
Tab l e 3 - 1 SCPI command summary (continued)
Calibration Commands
CALibration
:COUNt?
:CURRent[:DATA] <numeric value>
:CURRent:LEVel {MIN|MID|MAX}
:SECure:CODE <new code>
:SECure:STATe {OFF|ON}, <quoted code>
:SECure:STATe?
:STRing <quoted string>
:STRing?
:VOLTage[:DATA] <numeric value>
:VOLTage:LEVel {MIN|MID|MAX}
:VOLTage:PROTection
Interface Configuration Commands
SYSTem
:INTerface {GPIB|RS232}
:LOCal
:REMote
:RWLock
Remote Interface Reference 3
SCPI Command Summary
E364xA User’s and Service Guide 71
3 Remote Interface Reference
SCPI Command Summary
Tab l e 3 - 1 SCPI command summary (continued)
Status Reporting Commands
STATus:QUEStionable
[:EVENt]?
:ENABle <enable value>
:ENABle?
:INSTrument
[:EVENt]?
:ENABle <enable value>
:ENABle?
:ISUMmary<n>
[:EVENt]?
:CONDition?
:ENABle <enable value>
:ENABle? SYSTem:ERRor? *CLS *ESE <enable value> *ESE? *ESR? *OPC *OPC? *PSC {0|1} *PSC? *SRE <enable value> *SRE? *STB? *WAI
72 E364xA User’s and Service Guide
Tab l e 3 - 1 SCPI command summary (continued)
IEEE-488 Conformance Information
*CLS *ESR? *ESE <enable value> *ESE? *IDN? *OPC *OPC? *PSC {0|1} *PSC? *RST *SAV {1|2|3|4|5} *RCL {1|2|3|4|5} *STB? *SRE <enable value> *SRE? *TRG *TST? *WAI
[1] Applicable for E3646A and E3648A only.
Remote Interface Reference 3
SCPI Command Summary
[2] Applicable for E3647A and E3649A only.
E364xA User’s and Service Guide 73
3 Remote Interface Reference

Introduction to the SCPI Language

Introduction to the SCPI Language
Standard Commands for Programmable Instruments (SCPI) is an ASCII- based instrument command language designed for test and measurement instruments. Refer to
Programming Overview” for an introduction to the basic
techniques used to program the power supply over the remote interface.
SCPI commands are based on a hierarchical structure, also known as a tree system. In this system, associated commands are grouped together under a common node or root, thus forming subsystems. A portion of the SOURce subsystem is shown below to illustrate the tree system.
[SOURce:] CURRent {<current>|MIN|MAX|UP|DOWN} CURRent? [MIN|MAX] CURRent: TRIGgered {<current>|MIN|MAX} TRIGgered? {MIN|MAX} VOLTage {<voltage>|MIN|MAX|UP|DOWN} VOLTage? [MIN|MAX] VOLTage: TRIGgered {<voltage>|MIN|MAX} TRIGgered? {MIN|MAX}
“Simplified
SOURce is the root keyword of the command, CURRent and VOLTage are second- level keywords, and TRIGgered is the
third- level keyword. A colon (:) separates a command keyword from a lower- level keyword.
74 E364xA User’s and Service Guide
Introduction to the SCPI Language

Command format used in this manual

The format used to show commands in this manual is shown below:
CURRent {<current>|MINimum|MAXimum|UP|DOWN}
The command syntax shows most commands (and some parameters) as a mixture of upper- case and lower-case letters. The upper- case letters indicate the abbreviated spelling for the command. For shorter program lines, send the abbreviated form. For better program readability, send the long form.
For example, in the above syntax statement, CURR and CURRENT are both acceptable forms. You can use upper-case or lower- case letters. Therefore, CURRENT, curr, and Curr are all acceptable. Other forms, such as CUR and CURREN, will generate an error.
Braces ({}) enclose the parameter choices for a given command string. The braces are not sent with the command string.
Remote Interface Reference 3
A vertical bar (|) separates multiple parameter choices for a given command string.
Triangle brackets (<>) indicate that you must specify a value for the enclosed parameter. For example, the above syntax statement shows the current parameter enclosed in triangle brackets. The brackets are not sent with the command string. You must specify a value for the parameter (such as CURR 0.1).
Some parameters are enclosed in square brackets ([]). The brackets indicate that the parameter is optional and can be omitted. The brackets are not sent with the command string. If you do not specify a value for an optional parameter, the power supply chooses a default value.
E364xA User’s and Service Guide 75
3 Remote Interface Reference
Introduction to the SCPI Language
Some portions of commands are enclosed in square brackets ([]). The brackets indicate that this portion of the command is optional. Most optional portions of the command are not shown in the command description. For the full command showing all the options, refer to
A colon (:) separates a command keyword from a lower- level keyword. You must insert a blank space to separate a parameter from a command keyword. If a command requires more than one parameter, you must separate adjacent parameters using a comma as shown below:
SOURce:CURRent:TRIGgered APPLy 3.5,1.5
Table 3- 1.

Command separators

A colon (:) is used to separate a command keyword from a lower-level keyword as shown below:
SOURce:CURRent:TRIGgered
A semicolon (;) is used to separate two commands within the same subsystem, and can also minimize typing. For example, sending the following command string,
SOUR:VOLT MIN;CURR MAX
is the same as sending the following two commands:
SOUR:VOLT MIN SOUR:CURR MAX
Use a colon and a semicolon to link commands from different subsystems. For example, in the following command string, an error is generated if you do not use the colon and semicolon:
DISP:TEXT:CLE;:SOUR:CURR MIN
76 E364xA User’s and Service Guide
Loading...