No p art o f this manu al may be re produce d in
any form or by any means (including electronic storage and retrieval or translation
into a foreign language) without prior agreement and written consent from Keysight
Technologies as governed by United States
and international copyright laws.
Manual Part Number
E3632-90001
Edition
Edition 7, November 2014
Keysight Technologies
1400 Fountaingrove Parkway
Santa Rosa, CA 95403
Warranty
The material contained in this document is
provided “as is,” and is subject to change,
without notice, in future editions. Further,
to the maximum extent permitted by the
applicable law, Keysight disclaims all
warranties, either express or implied, with
regard to this manual and any information
contained herein, including but not limited
to the implied warranties of merchantability and fitness for a particular purpose.
Keysight shall not be liable for errors or for
incidental or consequential damages in
connection with the furnishing, use, or
performance of this document or of any
information contained herein. Should Keysight and the user have a separate written
agreement with warranty terms covering
the material in this document that conflict
with these terms, the warranty terms in
the separate agreement shall control.
Technology Licenses
The hardware and or software described in
this document are furnished under a license
and may be used or copied only in accordance with the terms of such license.
Restricted Rights Legend
U.S. Government Restricted Rights. Software and technical data rights granted to
the federal government include only those
rights customarily provided to end user customers. Keysight provides this customary
commercial license in Software and technical data pursuant to FAR 12.211 (Technical
Data) and 12.212 (Computer Software) and,
for the Department of Defense, DFARS
252.227-7015 (Technical Data - Commercial
Items) and DFARS 227.7202-3 (Rights in
Commercial Computer Software or Computer Software Documentation).
Safety Notices
A CAUTION notice denotes a hazard. It calls attention to an operating procedure, practice, or the likes
of that, if not correctly performed
or adhered to, could result in damage to the product or loss of important data. Do not proceed beyond a
CAUTION notice until the indicated
conditions are fully understood and
met.
A WARNING notice denotes a
hazard. It calls attention to an
operating procedure, practice, or
the likes of that, if not correctly
performed or adhered to, could
result in personal injury or death.
Do not proceed beyond a WARNING notice until the indicated
conditions are fully understood
and met.
IIE3632A User’s Guide
Safety Symbols
The following symbols on the instrument and in the documentation
indicate precautions which must be taken to maintain safe operation of
the instrument.
Caution, risk of danger (refer to this manual
for specific Warning or Caution information)
DC (Direct current or voltage)
AC (Alternating current or voltage)Positive binding post
Protective conductor terminalNegative binding post
Out position of a bi-stable push controlEarth (ground) terminal
In position of a bi-stable push control
Terminal is at earth potential. Used for
measurement and control circuits designed to
be operated with one terminal at earth
potential.
E3632A User’s GuideIII
Safety Considerations
CAUTION
Read the information below before using this instrument.
The following general safety precautions must be observed during all
phases of operation, service, and repair of this instrument. Failure to
comply with these precautions or with specific warnings elsewhere in this
manual violates safety standards for design, manufacture, and intended
use of the instrument. Keysight Technologies assumes no liability for the
customer’s failure to comply with these requirements.
• Use the device with the cables provided with the shipment.
• If the device is used in a manner not specified by the manufacturer,
the device protection may be impaired.
• Always use a dry cloth to clean the device. Do not use ethyl alcohol
or any other volatile liquid to clean the device.
• Do not permit any blockage of the ventilation holes of the device.
IVE3632A User’s Guide
WARNING
• Do not use MAINS supply cords by inadequately RATED cord.
Always use the MAINS supply cord provided by the manufacturer.
• Do not use the device if it appears damaged or defective. REMOVE
POWER and do not use the device until safe operation is verified
by service-trained personnel. If necessary, return the device to
Keysight for service and repair to ensure that the safety features
are maintained.
• Do not operate the device around flammable gases or fumes,
vapor, or wet environments.
• Observe all markings on the device before connecting any wiring
to the device.
• Turn off the output of the power supply before connecting to the
output terminals.
• When servicing the device, use only the specified replacement
parts.
• Do not install substitute parts or perform any unauthorized
modification to the device. Return the device to Keysight for
service and repair to ensure that the safety features are
maintained.
• Do not operate the device with the cover removed or loosened.
E3632A User’s GuideV
This power supply is a Safety Class I instrument, which means that it has a
protective earth terminal. This terminal must be connected to earth ground
through a power source with a 3-wire ground receptacle.
Before installation or operation, check the power supply and review this
manual for safety markings and instructions. Safety information for
specific procedures is located at the appropriate places in this manual.
Safety and EMC Requirements
This power supply is designed to comply with the following safety and
Electromagnetic Compatibility (EMC) requirements:
• IEC61326-1:2005/EN61326-1:2006
• Canada: ICES/NMB-001: Issue 4, June 2006
• Australia/New Zealand: AS/NZS CISPR11:2004
• IEC 61010-1:2001/EN 61010-1:2001
• Canada: CAN/CSA-C22.2 No. 61010-1-04
• USA: ANSI/UL 61010-1:2004
Environmental Conditions
This instrument is designed for indoor use and in an area with low
condensation. The table below shows the general environmental
requirements for this instrument.
Environmental conditionRequirements
Te m p e r a t u r e
Operating condition
• 0 °C to 40 °C (full rated output)
Storage condition
• –20 °C to 70 °C
HumidityUp to 80% RH
AltitudeUp to 2000 m
Installation categoryII (for indoor use)
Pollution degree2
VIE3632A User’s Guide
Regulatory Markings
The CE mark is a registered trademark
of the European Community. This CE
mark shows that the product complies
with all the relevant European Legal
Directives.
The C-tick mark is a registered
trademark of the Spectrum
Management Agency of Australia. This
signifies compliance with
the Australia EMC Framework
regulations under the terms of the
Radio Communication Act of 1992.
ICES/NMB-001 indicates that this ISM
device complies with the Canadian
ICES-001.
Cet appareil ISM est confomre a la
norme NMB-001 du Canada.
The CSA mark is a registered
trademark of the Canadian Standards
Association.
This symbol is a South Korean Class A
EMC Declaration. This is a Class A
instrument suitable for professional
use and in electromagnetic
environment outside of the home.
This instrument complies with the
WEEE Directive (2002/96/EC) marking
requirement. This affixed product label
indicates that you must not discard
this electrical or electronic product in
domestic household waste.
This symbol indicates the time period
during which no hazardous or toxic
substance elements are expected to
leak or deteriorate during normal use.
Forty years is the expected useful life
of the product.
E3632A User’s GuideVII
Waste Electrical and Electronic Equipment (WEEE) Directive 2002/96/EC
This instrument complies with the WEEE Directive (2002/96/EC) marking
requirement. This affixed product label indicates that you must not discard
this electrical or electronic product in domestic household waste.
Product Category:
With reference to the equipment types in the WEEE directive Annex 1, this
instrument is classified as a “Monitoring and Control Instrument” product.
The affixed product label is as shown below.
Do not dispose in domestic household waste.
To return this unwanted instrument, contact your nearest Keysight Service
Center, or visit
www.keysight.com/environment/product
for more information.
VIIIE3632A User’s Guide
Declaration of Conformity (DoC)
NOTE
The Declaration of Conformity (DoC) for this instrument is available on the
Keysight Web site. You can search the DoC by its product model or
description at the Web address below.
http://www.keysight.com/go/conformity
If you are unable to search for the respective DoC, contact your local
Keysight representative.
E3632A User’s GuideIX
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK.
XE3632A User’s Guide
Table of Contents
1Getting Started
Introduction 2
Standard Shipped Items 7
Options 7
Accessories 8
Preparing the Power Supply 9
Preliminary checkout 9
Power-on checkout 10
Checking the output 11
Input power requirements 13
Rack-mount the power supply 16
Product at a Glance 18
Front panel 18
Rear panel 21
Display annunciators 22
Operating the Power Supply 24
Cooling 24
Bench operation 24
Cleaning 24
2Operation and Features
Overview 26
Constant Voltage Operation 28
Front panel operation 28
Remote interface operation 30
Constant Current Operation 30
Front panel operation 30
Remote interface operation 32
E3632A User’s GuideXI
Storing and Recalling Operating States 33
Front panel operation 33
Remote interface operation 35
Programming the Overvoltage Protection 35
Front panel operation 35
Remote interface operation 37
Programming the Overcurrent Protection 38
Front panel operation 38
Remote interface operation 40
Parity selection (RS-232) 53
To set the GPIB address 53
To set the baud rate and parity (RS-232) 54
GPIB Interface Configuration 56
RS-232 Interface Configuration 57
RS-232 configuration overview 57
RS-232 data frame format 58
Connection to a computer or terminal 58
DTR/DSR handshake protocol 60
RS-232 troubleshooting 62
Calibration 63
Calibration security 63
To unsecure for calibration 64
To secure against calibration 65
To change the security code 66
Calibration count 67
Calibration message 68
3Remote Interface Reference
SCPI Command Summary 70
Introduction to the SCPI Language 74
Command format used in this manual 75
Command separators 76
Using the MIN and MAX parameters 77
Querying parameter settings 77
SCPI command terminators 78
IEEE-488.2 common commands 78
SCPI parameter types 78
Simplified Programming Overview 80
Using the APPLy command 80
Using the low-level commands 80
E3632A User’s GuideXIII
Reading a query response 81
Selecting a trigger source 81
Power supply programming ranges 82
Using the APPLy Command 83
APPLy {<voltage>| DEF | MIN | MAX}[,{<current>| DEF | MIN
| MAX}] 83
APPLy? 84
Output Settings and Operation Commands 85
Triggering Commands 93
Trigger source choices 93
Triggering commands 95
System-Related Commands 96
Calibration Commands 102
RS-232 Interface Commands 106
SCPI Status Registers 107
What is an event register? 107
What is an enable register? 107
SCPI status system 108
The Questionable Status register 109
The Standard Event register 110
The Status Byte register 112
Using Service Request (SRQ) and Serial POLL 113
Using *STB? to read the Status Byte 114
Using the Message Available Bit (MAV) 114
To interrupt your bus controller using SRQ 115
To determine when a command sequence is completed 115
Using *OPC to signal when data is in the output buffer 116
Front panel operation 128
Remote interface operation 129
Execution Error Messages 130
Self-Test Error Messages 135
Calibration Error Messages 137
5Application Programs
Overview 140
Example Program for C++ (GPIB IEEE 488) 141
Example Program for Excel 5.0 (Windows 3.1 and GPIB) 144
6Tutorial
Overview of the Power Supply Operation 150
Output Characteristics 152
Unregulated state 154
Unwanted signals 154
Connecting the Load 157
Output isolation 157
Multiple loads 157
E3632A User’s GuideXV
Remote voltage sensing 158
Load consideration 159
Extending the Voltage Range and Current Range 162
Series connections 162
Parallel connections 163
Remote Programming 164
Reliability 166
7Characteristics and Specifications
Physical Characteristics 168
Environmental Characteristics 169
Electrical Specifications 169
Supplemental Characteristics 171
XVIE3632A User’s Guide
List of Figures
Figure 1-1 Shorting conductors without insulation 5
Figure 1-2 Front panel 18
Figure 1-3 Voltage and current limit settings 20
Figure 1-4 Rear panel 21
Figure 1-5 Display annunciators 22
Figure 2-1 Recommended protection circuit for battery
charging 38
Figure 2-2 Remote voltage sensing connections 43
Figure 2-3 RS-232 data frame format 58
Figure 2-4 DB-9 serial connection 59
Figure 2-5 DB-25 serial connection 60
Figure 3-1 SCPI status system 108
Figure 6-1 Diagram of a simple series power supply with tap
selection 150
Figure 6-2 Block diagram of the power supply showing the remote
interface isolation 151
Figure 6-3 Ideal constant voltage power supply 152
Figure 6-4 Ideal constant current power supply 152
Figure 6-5 Output characteristics 153
Figure 6-6 Simplified diagram of the common mode and normal
mode sources of noise 156
Figure 6-7 Regulated power supply with remote sensing 159
Figure 6-8 Speed of response — programming up (full load) 164
Figure 6-9 Speed of response — programming down 165
Figure 7-1 E3632A dimensions 168
Introduction 2
Standard Shipped Items 7
Preparing the Power Supply 9
Product at a Glance 18
Operating the Power Supply 24
This chapter guides you to set up your power supply for the
first time. An introduction to all the features of the power
supply is also given.
1Getting Started
Introduction
Introduction
The Keysight E3632A is a high performance 120 W dual
range DC power supply with GPIB and RS- 232 interfaces.
The combination of bench- top and system features in this
power supply provides versatile solutions for your design
and test requirements.
Convenient bench-top features
• Dual range
• Easy- to- use knob control settings
• Highly visible vacuum- f luorescent display meters
• High accuracy and high resolution
• Remote voltage sensing
• Overvoltage and overcurrent protection
• Output on/off
• Excellent load and line regulation and low ripple and
noise
• Operating states storage
• Portable, ruggedized case with non- skid feet
Flexible system features
• GPIB (IEEE- 488) and RS- 232 interfaces are standard
• SCPI (Standard Commands for Programmable
Instruments) compatibility
• I/O setup easily done from front- panel
• Software calibration, no internal adjustments required
2E3632A User’s Guide
Getting Started1
Introduction
The E3632A DC power supply features a combination of
programming capabilities and linear power supply
performance that makes it ideal for power systems
applications. The power supply is programmable locally from
the front panel or remotely over the GPIB and RS- 232
interfaces. This power supply has two ranges, allowing more
voltage at a lower current. The desired output range is
selected from the front panel or over the remote interfaces.
Operational features
• Dual range of 15 V/7 A or 30 V/4 A
• Constant voltage (CV) or constant current (CC) operation
• Overvoltage protection (OVP) and overcurrent protection
(OCP)
• Three storage locations (1 to 3) for user- defined operating
states
• Automatic power- on self- test
• Remote sensing for load voltage
• User calibration from the front panel or via the remote
interfaces
Front panel operations
• Easy- to- use knob control
• Output range selection
• Enabling or disabling OVP and OCP features
• Setting the OVP and OCP trip levels
• Clearing OVP and OCP conditions
• Setting and displaying the voltage and current limit values
• Saving and recalling operating states
• Returning the power supply to local mode from remote
interface mode
• Displaying remote interface error message
• Calibrating the power supply, including changing the
calibration security code
E3632A User’s Guide3
1Getting Started
WARNING
Introduction
• Configuring the power supply for remote interfaces
• Enabling or disabling the output
When operated over the remote interface, the power supply
can be both a listener and a talker. Using an external
controller, you can instruct the power supply to set the
output and to send the status data back over the GPIB or
RS- 232 interfaces. Capabilities include the following features:
• Voltage and current programming
• Voltage and current readback
• Present and stored status readback
• Programming syntax error detection
• Complete self- test
The front- panel Vacuum- Fluorescent Display (VFD) includes:
• Displaying actual values of output voltage and current
(meter mode)
• Or displaying the limit values of voltage and current (limit
mode)
• Checking the operating status from the annunciators
• Checking the type of error from the error codes
(messages)
4E3632A User’s Guide
Connections to the power supply’s output and to chassis
ground are made to binding posts on the front panel.
Floating the power supply output more than ±60 Vdc from the
chassis presents an electric shock hazard to the operator. Do not
float the outputs more than ±60 Vdc when metal shorting bars
without insulation are used to connect the (+) output to the (+)
sense and the (–) output to the (–) sense terminals.
Getting Started1
WARNING
Introduction
Figure 1-1 Shorting conductors without insulation
Outputs can be floated to maximum of ±240 Vdc provided that the
metal shorting bars without insulation are either replaced with
insulated conductors or they are removed from the terminals so
there is no operator access to the output conductors without
insulation. All field wiring insulation must be adequate for the
voltage present.
E3632A User’s Guide5
1Getting Started
Introduction
The power supply is shipped with a detachable, 3- wire
grounding type power cord. The AC line fuse is an extractor
type on the rear panel. The power supply can be calibrated
from the front panel directly or with a controller over the
GPIB or RS- 232 interface using calibration commands.
Correction factors are stored in non- volatile memory and
are used during output programming. Calibration from the
front panel or a controller eliminates the need to remove the
top cover or even the need to remove the power supply from
your system cabinet. You can guard against unauthorized
calibration by using the “Secured” calibration protection
function.
6E3632A User’s Guide
Standard Shipped Items
Verify that you have received the following items in the
shipment of your power supply. If anything is missing or
damaged, contact your nearest Keysight Sales Office.
✔ Power cord
✔ Certificate of Calibration
✔ E3632A User’s Guide (this manual)
✔ E3632A Service Guide (E3632- 90010)
Options
Options 0EM, 0E3, and 0E9 determine which power-line
voltage is selected at the factory. The standard unit is
configured for 115 Vac ±10%, 47 Hz to 63 Hz input voltage.
Getting Started1
Standard Shipped Items
For more information about changing the power- line voltage
setting, refer to
Tab l e 1 - 1 E3632A options
OptionDescription
OEM115 Vac 10%, 47 Hz to 63 Hz input voltage
OE3230 Vac 10%, 47 Hz to 63 Hz input voltage
OE9100 Vac 10%, 47 Hz to 63 Hz input voltage
1CMRack-mount kit (Keysight part number 5063-9243)
OL2Extra English manual set (local language manual files are included in the
CD-ROM, Keysight part number 5964-8251)
E3632A User’s Guide7
“Power- line voltage selection” on page 14.
1Getting Started
Standard Shipped Items
Accessories
The accessories listed below may be ordered from your local
Keysight Sales Office either with the power supply or
separately.
Tab l e 1 - 2 E3632A accessories
Part numberDescription
10833AGPIB cable, 1 m (3.3 ft.)
10833BGPIB cable, 2 m (6.6 ft.)
34398A• RS-232, 9 pin (f) to 9 pin (f), 2.5 m (8.2 ft.) cable
• 9 pin (f) to 25 pin (m) adapter
8E3632A User’s Guide
Preparing the Power Supply
NOTE
Preliminary checkout
1 Verify the power- line voltage setting on the rear panel.
The power- line voltage is set to the proper value for your
country when the power supply is shipped from the
factory. Change the voltage setting if it is not correct. The
settings are 100 Vac, 115 Vac, or 230 Vac.
2 Verify that the correct power- line fuse is installed.
The correct fuse is installed for your country when the
power supply is shipped from the factory. For 100 Vac or
115 Vac operation, you must use a 4 AT fuse. For 230 Vac
operation, you must use a 2.5 AT fuse.
3 Connect the power- line cord and turn on your power
supply.
The front- panel display will light up and a power- on
self- test occurs automatically when you turn on the power
supply.
Getting Started1
Preparing the Power Supply
• Refer to “Power-line voltage selection” on page 14 if you need to
change the power-line voltage or the power-line fuse.
• To replace the 4 AT fuse, order Keysight part number 2110-0996.
• To replace the 2.5 AT fuse, order Keysight part number 2110-0999.
E3632A User’s Guide9
1Getting Started
Display Limit
NOTE
Output On/Off
Output On/Off
Preparing the Power Supply
Power-on checkout
The power- on test includes an automatic self- test that
checks the internal microprocessors and allows the user
visually check the display. You will observe the following
sequence on the display after pressing the front panel power
switch to on.
1 All segments of the display including all annunciators will
turn on for about one second.
To review the annunciators, hold down as
you turn on the power supply.
2 The GPIB address or RS- 232 message will then be displayed
for about one second.
ADDR 5 (or RS-232)
The GPIB address is set to “5” when the power supply is
shipped from the factory for remote interface
configuration. If this is not the first time the power
supply is turned on, a different interface (RS- 232) or a
different GPIB address may appear.
10E3632A User’s Guide
Refer to Chapter 3, “Remote Interface Reference” if you need to change
the remote interface configuration.
3 The 15V, OVP, OCP, and OFF annunciators are on. All others
are off.
The power supply will go into the power- on/reset state,
the output is disabled (the OFF annunciator turns on),
the 15 V/7 A range is selected (the 15V annunciator turns
on), and the knob is selected for voltage control. Notice
that the OVP and OCP annunciator also turn on.
4 Enable the outputs.
Press to enable the output. The OFF
annunciator turns off and the 15V, OVP, OCP, and CV
annunciators are lit. The blinking digit can be adjusted by
turning the knob. Notice that the display is in the meter
mode. Meter mode means that the display shows the
actual output voltage and current.
NOTE
If the power supply detects an error during power-on self-test, the ERROR
NOTE
Power
Output On/Off
annunciator will turn on. Refer to Chapter 4, “Error Messages”.
Checking the output
The following procedures check to ensure that the power
supply develops its rated outputs and properly responds to
operation from the front panel. For complete performance
and verification tests, refer to the Service Guide(E3632- 90010).
For each step, use the keys shown on the left margins.
Voltage output check
The following steps verify the basic voltage functions with
no load.
1 Turn on the power supply.
The power supply will go into the power- on/reset state,
the output is disabled (the OFF annunciator turns on),
the 15 V/7 A range is selected (the 15V annunciator turns
on), and the knob is selected for voltage control.
2 Enable the outputs.
The OFF annunciator turns off and the 15V, OVP, OCP, and CV annunciators are lit. The blinking digit can be adjusted
by turning the knob. Notice that the display is in the
meter mode. Meter mode means that the display shows
the actual output voltage and current.
Getting Started1
Preparing the Power Supply
E3632A User’s Guide11
1Getting Started
Power
Output On/Off
Display Limit
Preparing the Power Supply
3 Check that the front- panel voltmeter properly responds to
knob control for the 15 V/7 A range.
Turn the knob clockwise or counter- clockwise to check
that the voltmeter responds to knob control and the
ammeter indicates nearly zero.
4 Ensure that the voltage can be adjusted from zero to the full
rated value .
[1]
Adjust the knob until the voltmeter indicates 0 V, and
then adjust the knob until the voltmeter indicates 15.0 V.
Current output check
The following steps check the basic current functions with a
short across the power supply’s output.
1 Turn on the power supply.
The power supply will go into the power- on/reset state,
the output is disabled (the OFF annunciator turns on), the
15 V/7 A range is selected (the 15V annunciator turns on),
and the knob is selected for voltage control.
2 Connect a short across the (+) and (–) output terminals with
an insulated test lead.
3 Enable the output.
The OFF annunciator turns off and the 15V, OVP, and OCP
annunciators are lit. The CV or CC annunciator turns on
depending on the resistance of the test lead. The blinking
digit can be adjusted by turning the knob. Notice that the
display is in the meter mode. Meter mode means that the
display shows the actual output voltage and current.
4 Adjust the voltage limit value to 1.0 V.
Set the display to the limit mode (the Limit annunciator
will be flashing). Adjust the voltage limit to 1.0 V to
assure CC operation. The CC annunciator will turn on.
12E3632A User’s Guide
[1] You can use the resolution selection keys to move the flashing digit to the right
or left when setting the voltage.
5 Check that the front- panel ammeter properly responds to
Volt/Curr
NOTE
knob control for the 15 V/7 A range.
Set the knob to the current control, and turn the knob
clockwise or counter- clockwise when the display is in the
meter mode (the Limit annunciator is off). Check that the
ammeter responds to knob control and the voltmeter
indicates nearly zero (the voltmeter will show the voltage
drop caused by the test lead).
6 Ensure that the current can be adjusted from zero to the full
rated value.
If an error has been detected during the output checkout procedures, the
If an error has been detected during the output checkout procedures, the ERROR annunciator will turn
on. See "Error Messages" for more information starting on page 121 in ch apter 5.
ERROR annunciator will turn on. Refer to Chapter 4, “Error Messages”.
Input power requirements
You can operate your power supply from a nominal 100 V,
115 V, or 230 V single phase AC power source at 47 Hz to
63 Hz. An indication on the rear panel shows the nominal
input voltage set for the power supply at the factory. If
necessary, you can change the power- line voltage setting
according to the instructions as shown in
selection” on page 14.
Getting Started1
Preparing the Power Supply
[1]
“Power-line voltage
Power-line cord
The power supply is shipped from the factory with a
power- line cord that has a plug appropriate for your
location. Contact the nearest Keysight Sales and Service
Office if the wrong power- line cord is included with your
power supply. Your power supply is equipped with a 3- wire
grounding type power cord where the third conductor is the
ground. The power supply is grounded only when the
power- line cord is plugged into an appropriate receptacle.
Do not operate your power supply without adequate cabinet
ground connection.
[1] You can use the resolution selection keys to move the flashing digit to the right
or left when setting the current.
E3632A User’s Guide13
1Getting Started
100 Vac or 115 Vac, 4 AT fuse
230 Vac, 2.5 AT fuse
Power-line voltage selector
Preparing the Power Supply
Power-line voltage selection
Power- line voltage selection is accomplished by adjusting two
components — power- line voltage selector and power- line
fuse on the power-line module of the rear panel. To change
the power- line voltage, proceed as follows:
1 Remove the power cord.
Remove the fuse- holder assembly with a flat- blade
screwdriver from the rear panel.
14E3632A User’s Guide
2 Install the correct line fuse.
Remove the power- line voltage selector from the
power- line module.
Getting Started1
100 Vac, 115 Vac, or 230 Vac
NOTE
Preparing the Power Supply
3 Rotate the power-line voltage selector until the correct
voltage appears.
4 Replace the power- line voltage selector and the
fuse- holder assembly in the rear panel.
E3632A User’s Guide15
Verify that the correct line voltage is selected and the power-line fuse
is good.
1Getting Started
FrontRear (bottom view)
Preparing the Power Supply
Rack-mount the power supply
The power supply can be mounted in a standard 19- inch
rack cabinet using one of three optional kits available. A
rack- mounting kit for a single instrument is available as
Option 1CM (5063- 9243). Installation instructions and
hardware are included with each rack- mounting kit. Any
Keysight System II instrument of the same size can be
rack- mounted beside the Keysight E3632A power supply.
1 Remove the front and rear bumpers before rack- mounting
the power supply.
2 To rack-mount a single instrument, order the adapter kit
(5063- 9243).
16E3632A User’s Guide
Getting Started1
Preparing the Power Supply
3 To rack-mount two instruments of the same depth
side- by- side, order the lock- link kit (5061- 9694) and
rack- mount kit (5063- 9212).
4 To install two instruments in a sliding support shelf,
order the support shelf (5063- 9256) and the slide kit
(1494- 0015).
E3632A User’s Guide17
1Getting Started
Product at a Glance
Product at a Glance
Front panel
Figure 1-2 Front panel
Tab l e 1 - 3 Front panel overview
NoItemDescription
115 V/7 A range selection keySelect the 15 V/7 A range and allow the full rated output to 15 V/7 A.
230 V/4 A range selection key Select the 30 V/4 A range and allow the full rated output to 30 V/4 A.
18E3632A User’s Guide
Getting Started1
Product at a Glance
Tab l e 1 - 3 Front panel overview (continued)
NoItemDescription
3Overvoltage protection key Enable or disable the overvoltage protection function, set the trip
voltage level, and clear the overvoltage condition.
4Overcurrent protection keyEnable or disable the overcurrent protection function, set the trip
current level, and clear the overcurrent condition.
5Display limit keyDisplay the voltage and current limit values on the display and allow
the knob adjustment for setting the limit values.
6Recall operating state keyRecall a previously stored operating state from location 1, 2, or 3.
7Store operating state/Local key
8Error/Calibrate key
[2]
9I/O Configuration/Secure key
[1]
[3]
Store an operating state in location 1, 2, or 3 or return the power
supply to the local mode from the remote interface mode.
Display the error codes generated during operation, self-test, and
calibration or enable the calibration mode (the power supply must be
unsecured before performing calibration). Refer to the Service Guide (E3632-90010) for more details on calibration.
Configure the power supply for remote interfaces, or secure or
unsecure the power supply for calibration. Refer to the Service Guide (E3632-90010) for more details on how to secure or unsecure the
power supply.
10Output On/Off keyEnable or disable the power supply output. This key toggles between
on and off.
11Control knobIncrease or decrease the value of the flashing digit by turning
clockwise or counter-clockwise.
12Resolution selection keysMove the flashing digit to the right or left.
13Voltage/Current adjust selection key Select the knob control function for voltage or current adjustment.
[1] The key can be used as the Local key when the power supply is in the remote interface mode.
[2] You can enable the calibration mode by holding down this key when you turn on the power supply.
[3] You can use it as the Secure or Unsecure key when the power supply is in the calibration mode.
E3632A User’s Guide19
1Getting Started
Display Limit
Display Limit
Output On/Off
Display Limit
NOTE
Product at a Glance
Voltage and current limit settings
You can set the voltage and current limit values from the
front panel using the following method.
Figure 1-3 Voltage and current limit settings
1 Select the desired range using the range selection keys
after turning on the power supply.
2 Press to show the limit values on the
display.
3 Move the blinking digit to the appropriate position using
the resolution selection keys and change the blinking digit
value to the desired voltage limit by turning the control
knob. If the display limit times out, press
again.
4 Set the knob to current control mode using the
voltage/current adjust selection key.
5 Move the blinking digit to the appropriate position using
the resolution selection keys and change the blinking digit
value to the desired current limit by turning the control
knob.
6 Press to enable the output. After about
five seconds, the display will go to output monitoring
mode automatically to display the voltage and current at
the output or the display will go to output monitoring
mode immediately by pressing
again.
20E3632A User’s Guide
All the front panel keys and controls can be disabled with the remote
interface commands. The power supply must be in the Local mode for the
front panel keys and controls to function.
Rear panel
Getting Started1
Product at a Glance
Figure 1-4 Rear panel
Tab l e 1 - 4 Rear panel overview
NoDescription
1Power-line voltage setting
2Power-line fuse-holder assembly
3AC inlet
4Power-line module
5GPIB (IEEE-488) interface connector
6RS-232 interface connector
E3632A User’s Guide21
1Getting Started
NOTE
I/O Config
Product at a Glance
Use the front-panel key to:
• Select the GPIB or RS-232 interface (see Chapter 2).
• Set the GPIB bus address (see Chapter 2).
• Set the RS-232 baud rate and parity (see Chapter 2).
Display annunciators
Figure 1-5 Display annunciators
Tab l e 1 - 5 Display annunciators overview
ItemDescription
AdrsThe power supply is addressed to listen or talk over a remote interface.
RmtThe power supply is in the remote interface mode.
15 VShows the 15 V/7 A range is selected.
30 VShows the 30 V/4 A range is selected.
OVPThe overvoltage protection function is enabled when the annunciator turns on or the overvoltage
protection circuit has caused the power supply to shut down when the annunciator flashes.
OCPThe overcurrent protection function is enabled when the annunciator turns on or the overcurrent
protection circuit has caused the power supply to shut down when the annunciator flashes.
CALThe power supply is in the calibration mode.
LimitThe display shows the limit values of the voltage and current.
22E3632A User’s Guide
Getting Started1
NOTE
Display Limit
Product at a Glance
Tab l e 1 - 5 Display annunciators overview (continued)
ItemDescription
ERRORHardware or remote interface command errors are detected and the error bit has not been cleared.
OFFThe output of the power supply is disabled. Refer to “System-Related Operations” on page 46 for more
information.
UnregThe output of the power supply is unregulated (output is neither CV nor CC).
CVThe power supply is in the constant voltage mode.
CCThe power supply is in the constant current mode.
To review the display annunciators, hold down as you
turn on the power supply.
E3632A User’s Guide23
1Getting Started
Operating the Power Supply
Operating the Power Supply
Cooling
The power supply can operate at the rated specifications
within the temperature range of 0 C to 40 C. A fan cools
the power supply by drawing air through the sides and
exhausting it out the back. Using a Keysight rack- mount will
not impede the flow of air.
Bench operation
Your power supply must be installed in a location that
allows sufficient space at the sides and rear of the power
supply for adequate air circulation. The rubber bumpers
must be removed for rack- mounting.
Cleaning
No cleaning is required for this product. If you wish to
remove dust from the enclosure, use a dry cloth.
24E3632A User’s Guide
E3632A DC Power Supply
User’s Guide
2
Operation and Features
Overview 26
Constant Voltage Operation 28
Constant Current Operation 30
Storing and Recalling Operating States 33
Programming the Overvoltage Protection 35
Programming the Overcurrent Protection 38
Remote Voltage Sensing 41
Disabling the Output 44
System-Related Operations 46
Remote Interface Configuration 51
GPIB Interface Configuration 56
RS-232 Interface Configuration 57
Calibration 63
This chapter describes the operations and features for the
E3632A DC power supply.
2Operation and Features
Local
Display Limit
Display Limit
Output On/Off
Overview
Overview
The following section describes an overview of the front
panel keys before operating your power supply.
• The power supply is shipped from the factory configured
in the front panel operation mode. At power- on, the
power supply is automatically set to operate in the front
panel operation mode. When in this mode, the front panel
keys can be used. When the power supply is in remote
operation mode, you can return to front panel operation
mode at any time by pressing
previously send the front panel lockout command. A
change between front panel and remote operation modes
will not result in a change in the output parameters.
• The power supply has two output ranges of 15 V/7 A or
30 V/4 A. This feature allows more voltage at a lower
current or more current at a lower voltage. The desired
output range is selected from the front panel or over the
remote interfaces. The 15V or 30V annunciator indicates
the presently selected range.
• When you press (the Limit annunciator
flashes), the display of the power supply goes to the limit
mode and the present limit values will be displayed. In
this mode, you can also observe the change of the limit
values when adjusting the knob. If you press
again or let the display time- out after
several seconds, the power supply will return the display
to the meter mode (the Limit annunciator turns off). In
this mode, the actual output voltage and current will be
displayed.
• The output of the power supply can be enabled or
disabled from the front panel using
the output is off, the OFF annunciator turns on and the
output is disabled.
if you did not
. When
26E3632A User’s Guide
Operation and Features2
Overview
• The display provides the present operating status of the
power supply with annunciators and also informs the user
of error codes. For example, the power supply is
operating in CV mode in the 15 V/7 A range and
controlled from the front panel, then the CV and 15V
annunciators will turn on. If, however, the power supply
is remotely controlled, the Rmt annunciator will also turn
on, and when the power supply is being addressed over
GPIB interface, the Adrs annunciator will turn on. Refer to
“Display annunciators” on page 22 for more information.
E3632A User’s Guide27
2Operation and Features
Power
30V,4A
Display Limit
NOTE
Constant Voltage Operation
Constant Voltage Operation
To set up the power supply for constant voltage (CV)
operation, proceed as follows.
Front panel operation
1 Connect a load to the output terminals.
With power- off, connect a load to the (+) and (–) output
terminals.
2 Turn on the power supply.
The power supply will go into the power- on/reset state,
the output is disabled (the OFF annunciator turns on), the
15 V/7 A range is selected (the 15V annunciator turns on),
and the knob is selected for voltage control.
To operate the power supply in the 30 V/4 A range, press
before proceeding to the next step. The 30V
annunciator turns on.
3 Set the display to the limit mode.
Notice that the Limit annunciator flashes, indicating that
the display is in the limit mode. When the display is in
the limit mode, you can see the voltage and current limit
values of the power supply.
28E3632A User’s Guide
In the constant voltage mode, the voltage values between the meter and
limit modes are the same, but the current values are not. Moreover, if the
display is in the meter mode, you cannot see the change of current limit
value when adjusting the knob. We recommend that you should set the
display to the limit mode to see the change of current limit value in the
constant voltage mode whenever adjusting the knob.
Operation and Features2
Volt/Curr
Volt/Curr
Display Limit
Display Limit
Output On/Off
Constant Voltage Operation
4 Adjust the knob for the desired current limit.
[1]
Check that the Limit annunciator still f lashes. Set the knob
for current control. The first digit of the ammeter will be
flashing. The flashing digit can be changed using the
resolution selection keys and the flashing digit can be
adjusted by turning the knob. Adjust the knob to the
desired current limit.
5 Adjust the knob for the desired output voltage.
[2]
Check that the Limit annunciator still f lashes. Set the knob
for voltage control. The second digit of the voltmeter will
be flashing. Change the f lashing digit using the resolution
selection keys and adjust the knob for the desired output
voltage.
6 Return to the meter mode.
Press or let the display time- out after
several seconds to return to the meter mode. Notice that
the Limit annunciator turns off and the display shows the
OUTPUT OFF message.
7 Enable the output.
The OFF annunciator turns off and the 15V or 30V, OVP,
OCP, and CV annunciators are lit. Notice that the display is
in the meter mode. In the meter mode, the display shows
the actual output voltage and current.
Refer to “Programming the Overvoltage Protection” on
page 35 and “Programming the Overcurrent Protection” on
page 38 for more information on the OVP and OCP
annunciators.
8 Verify that the power supply is in the constant
voltage mode.
If you operate the power supply in the constant voltage
(CV) mode, verify that the CV annunciator is lit. If the CC
annunciator is lit, choose a higher current limit.
E3632A User’s Guide29
[1] You can use the resolution selection keys to move the flashing digit to the right
or left when setting current.
[2] You can use the resolution selection keys to move the flashing digit to the right
or left when setting voltage.
2Operation and Features
NOTE
Power
30V,4A
Constant Current Operation
During actual CV operation, if a load change causes the current limit to be
exceeded, the power supply will automatically cross over to the constant
current mode at the preset current limit and the output voltage will drop
proportionately.
Remote interface operation
CURRent {<current>|MIN|MAX}Set the current.
VOLTage {<voltage>|MIN|MAX}Set the voltage.
OUTPut ONEnable the output.
Constant Current Operation
To set up the power supply for constant current (CC)
operation, proceed as follows.
Front panel operation
1 Connect a load to the output terminals.
With power- off, connect a load to the (+) and (–) output
terminals.
2 Turn on the power supply.
The power supply will go into the power- on/reset state,
the output is disabled (the OFF annunciator turns on), the
15 V/7 A range is selected (the 15V annunciator turns on)
and the knob is selected for voltage control.
To operate the power supply in the 30 V/4 A range, press
before proceeding to the next step. The 30V
annunciator turns on.
30E3632A User’s Guide
Operation and Features2
Display Limit
NOTE
Volt/Curr
Display Limit
Display Limit
Constant Current Operation
3 Set the display to the limit mode.
Notice that the Limit annunciator flashes, indicating that
the display is in the limit mode. When the display is in
the limit mode, you can see the voltage and current limit
values of the selected supply.
In constant current mode, the current values between the meter mode and
limit mode are the same, but the voltage values are not. Moreover, if the
display is in the meter mode, you cannot see the change of voltage limit
value when adjusting the knob. We recommend that you should set the
display to the limit mode to see the change of voltage limit value in the
constant current mode whenever adjusting the knob.
4 Adjust the knob for the desired voltage limit.
[1]
Check that the Limit annunciator still flashes and the
second digit of voltmeter flashes to indicate the knob is
selected for voltage control. The flashing digit can be
changed using the resolution keys and the flashing digit
can be adjusted by turning the knob. Adjust the knob for
the desired voltage limit.
5 Adjust the knob for the desired output current
[1]
Check that the Limit annunciator still f lashes. Set the knob
for current control. The first digit of the ammeter will be
flashing. Change the flashing digit using the resolution
selection keys and adjust the knob to the desired output
current.
6 Return to the meter mode.
Press or let the display time- out after
several seconds to return to the meter mode. Notice that
the Limit annunciator turns off and the display shows the
OUTPUT OFF message.
E3632A User’s Guide31
[1] You can use the resolution selection keys to move the flashing digit to the right
or left when setting the voltage.
2Operation and Features
Output On/Off
NOTE
Constant Current Operation
7 Enable the output.
The OFF annunciator turns off and the 15V or 30V, OVP,
OCP, and CC annunciators are lit. Notice that the display is
in the meter mode. In the meter mode, the display shows
the actual output voltage and current.
Refer to “Programming the Overvoltage Protection” on
page 35 and “Programming the Overcurrent Protection” on
page 38 for more information on the OVP and OCP
annunciators.
8 Verify that the power supply is in the constant
current mode.
If you operate the power supply in the constant current
(CC) mode, verify that the CC annunciator is lit. If the CV
annunciator is lit, choose a higher voltage limit.
During actual CC operation, if a load change causes the voltage limit to be
exceeded, the power supply will automatically cross over to constant
voltage mode at the preset voltage limit and the output current will drop
proportionately.
32E3632A User’s Guide
Remote interface operation
VOLTage {<voltage>|MIN|MAX}Set the voltage.
CURRent {<current>|MIN|MAX}Set the current.
OUTPut ONEnable the output.
Storing and Recalling Operating States
Store
You can store up to three different operating states in
non- volatile memory. This also enables you to recall the
entire instrument configuration with just a few key presses
from the front panel.
The memory locations are supplied with the reset states
from the factory for front- panel operation. Refer to the
description of
following steps show you how to store and recall an
operating state.
Front panel operation
Storing the operating state
1 Set up the power supply for the desired operating state.
The storage feature “remembers” output range selection,
the limit value settings of voltage and current, output
on/off state, OVP and OCP on/off state, and OVP and OCP
trip levels.
2 Turn on the storage mode.
Three memory locations (numbered 1, 2, and 3) are
available to store the operating states. The operating
states are stored in non- volatile memory and are
remembered when being recalled.
STORE 1
This message appears on the display for approximately
three seconds.
3 Select the storage location.
Turn the knob to the right to specify the memory
location 3.
STORE 3
“*RST” on page 99 for more information. The
Operation and Features2
Storing and Recalling Operating States
E3632A User’s Guide33
2Operation and Features
Store
Store
Recall
Recall
Recall
Storing and Recalling Operating States
To cancel the store operation, let the display time- out
after about three seconds or press any other function key
except
. The power supply returns to the normal
operating mode and to the function pressed.
4 Save the operating state.
The operating state is now stored.
DONE
This message appears on the display for approximately 1
second.
Recalling a stored state
1 Turn on the recall mode.
Memory location 1 will be displayed in the recall mode.
RECALL 1
This message appears on the display for approximately
three seconds.
2 Recall the stored operating state.
Turn the knob to the right to change the displayed
storage location to 3.
RECALL 3
If this setting is not followed within three seconds with
, the power supply returns to normal operating
mode and will not recall the instrument state 3 from
memory.
3 Restore the operating state.
DONE
This message appears on the display for approximately 1
second.
34E3632A User’s Guide
Programming the Overvoltage Protection
Power
Output On/Off
Remote interface operation
Use the following commands to store and recall the power
supply state.
*SAV {1|2|3}Store an operating state to a
specified location
*RCL {1|2|3} Recall a previously stored state from
a specified location
Programming the Overvoltage Protection
Overvoltage protection guards the load against output
voltages that reach a specified value greater than the
programmed protection level. It is accomplished by shorting
the output via an internal SCR when the trip level is set to
equal or greater than 3 V, or by progamming the output to
1 V when the trip level is set to less than 3 V.
Operation and Features2
E3632A User’s Guide35
The following steps show how to set the OVP trip level, how
to check OVP operation, and how to clear overvoltage
condition.
Front panel operation
Setting the OVP level and enable the OVP circuit
1 Turn on the power supply.
The power supply will go into the power- on/reset state,
the output is disabled (the OFF annunciator turns on), the
15 V/7 A range is selected (the 15V annunciator turns on);
and the knob is selected for voltage control.
2 Enable the output.
The OFF annunciator turns off and the display will go to
the meter mode.
2Operation and Features
Over Voltage
Over Voltage
Over Voltage
Over Voltage
Programming the Overvoltage Protection
3 Enter the OVP menu and set the desired trip level.
LEVEL 32.0 V
You will see the above message on the display when you
enter the OVP menu. Adjust the control knob for the
desired OVP trip level. Note that you cannot set the trip
levels to lower than 1.0 V.
4 Enable the OVP circuit.
OVP ON
You will see the above message after pressing
.
5 Exit the OVP menu.
CHANGED
The CHANGED message is highlighted for a second to show
that the new OVP trip level is now in effect. If the OVP
settings are not changed, NO CHANGE will be displayed.
The power supply will exit the OVP menu and the display
will return to the meter mode. Check that the OVP
annunciator turns on.
36E3632A User’s Guide
Checking the OVP operation
To check OVP operation, raise the output voltage to near the
trip point. Then very gradually increase the output by
turning the knob until the OVP circuit trips. This will cause
the power supply output to drop to near zero, the OVP
annunciator to flash, and the CC annunciator to turn on. The
OVP TRIPPED message also appears on the display.
Clearing the overvoltage condition
When the OVP condition occurs (the OVP TRIPPED message is
shown on the display), the OVP annunciator flashes. When it
was caused by external voltage source such as a battery,
disconnect it first. The following steps show how to clear the
overvoltage conditions and get back to normal mode
operation. In the following steps, the display will go back to
OVP TRIPPED if you let the display time- out after about
several seconds.
Operation and Features2
or
Over Voltage
Display Limit
Display Limit
Over Voltage
Over Voltage
Over Voltage
Over Voltage
Over Voltage
Over Voltage
NOTE
Programming the Overvoltage Protection
1 Readjust the OVP trip level or the output voltage level.
Lower the output voltage level below the OVP trip point
after pressing
or raise the OVP trip level
by using the knob after pressing .
2 Move to the clear mode.
OVP ON
You will see the above message after pressing
. If you changed the output voltage level,
press the twice. Turn the knob to the right
until the OVP CLEAR message appears on the display.
3 Clear the overvoltage condition and exit this menu.
Now, when you press again, the DONE
message is displayed for a second and the OVP
annunciator will not flash any more. The output will
return to meter mode.
Remote interface operation
VOLT:PROT {<voltage>|MIN|MAX}Set the OVP level.
VOLT:PROT:STAT {OFF|ON)Disable or enable the
OVP ci rcuit.
VOLT:PROT:CLEClear the tripped
OVP ci rcuit.
The power supply’s OVP circuit contains a crowbar SCR, which effectively
shorts the output of the power supply whenever the overvoltage condition
occurs. If external voltage source such as a battery is connected across
the output, and the overvoltage condition inadvertently occurs, the SCR
will continuously sink a large current from the source and possibly damage
the power supply. To avoid this a diode must be connected in series with
the output as shown in Figure 2-1.
E3632A User’s Guide37
2Operation and Features
Power
Programming the Overcurrent Protection
Figure 2-1 Recommended protection circuit for battery charging
Programming the Overcurrent Protection
Overcurrent protection guards the load against output
currents that reach a specified value greater than the
programmed protection level. It is accomplished by
programming the output current to zero.
The following steps show how to set the overcurrent
protection trip level, how to check OCP operation and how
to clear overcurrent condition.
Front panel operation
Setting the OCP level and enable the OCP circuit
1 Turn on the power supply.
The power supply will go into the power- on/reset state,
the output is disabled (the OFF annunciator turns on), the
15 V/7 A range is selected (the 15V annunciator turns on);
and the knob is selected for voltage control.
38E3632A User’s Guide
Operation and Features2
Output On/Off
Over Current
Over Current
Over Current
Over Current
Programming the Overcurrent Protection
2 Enable the output.
The OFF annunciator turns off and the display will go to
the meter mode.
3 Enter the OCP menu and set the desired trip level.
LEVEL 7.5 A
You will see the above message on the display when you
enter the OCP menu. Adjust the knob for the desired OCP
trip level.
4 Enable the OCP circuit.
OCP ON
You will see the above message after pressing
.
5 Exit the OCP menu.
CHANGED
The CHANGED message is displayed for a second to show
that the new OCP trip level is now in effect. If the OCP
settings are not changed, NO CHANGE will be displayed.
The power supply will exit the OCP menu and the display
will return to the meter mode. Check that the OCP
annunciator turns on.
E3632A User’s Guide39
Checking the OCP operation
To check OCP operation, raise the output current to near
the trip point. Then very gradually increase the output by
turning the knob until the OCP circuit trips. This will cause
the power supply’s output current to drop to zero and the
OCP annunciator to flash. The OCP TRIPPED message also
appears on the display.
2Operation and Features
or
Display Limit
Over Current
Display Limit
Over Current
Over Current
Over Current
Over Current
Over Current
Over Current
Programming the Overcurrent Protection
Clearing the overcurrent condition
When the OCP condition occurs (the OCP TRIPPED message is
shown on the display), the OCP annunciator flashes. When it
was caused by external voltage source such as a battery,
disconnect it first. The following steps show how to clear the
overcurrent conditions and get back to normal mode
operation. In the following steps, the display will go back to
OCP TRIPPED if you let the display time- out after about
several seconds.
1 Readjust the OCP trip level or the output current level.
Lower the output current level below the OCP trip point
after pressing
by using the knob after pressing .
2 Move to the clear mode.
OCP ON
You will see the above message after pressing
. If you changed the output voltage level,
press the twice. Turn the knob to the right
until the OCP CLEAR message appears on the display.
3 Clear the overcoltage condition and exit this menu.
Now, when you press again, the DONE
message is displayed for a second and the OCP
annunciator will not flash any more. The output will
return to meter mode.
or raise the OCP trip level
40E3632A User’s Guide
Remote interface operation
CURR:PROT {<current>|MIN|MAX}Set the OCP level.
CURR:PROT:STAT {OFF|ON)Disable or enable the
OCP circuit.
CURR:PROT:CLEClear the tripped
OCP circuit.
Remote Voltage Sensing
Remote voltage sensing is used to maintain regulation at the
load and reduce the degradation of regulation that would
occur due to the voltage drop in the leads between the
power supply and the load.
By connecting the power supply for remote voltage sensing,
voltage is sensed at the load rather than at the power
supply’s output terminals. This will allow the power supply
to automatically compensate for the voltage drop in
applications with long lead lengths as well as to accurately
read back the voltage directly across the load.
When the power supply is connected for remote sensing, the
OVP circuit senses the voltage at the sensing points (load)
and not the output terminals.
CV regulation
Operation and Features2
Remote Voltage Sensing
The voltage load regulation specification in Chapter 7
applies at the output terminals of the power supply. When
remote sensing, add 5 mV to this specification for each 1 V
drop between the positive sensing point and (+) output
terminal due to the change in load current. Because the
sense leads are part of the power supply’s feedback path,
keep the resistance of the sense leads at or below 0.5 per
lead to maintain the above specified performance.
E3632A User’s Guide41
2Operation and Features
Remote Voltage Sensing
Output rating
The rated output voltage and current specifications in
Chapter 7 apply at the output terminals of the power
supply. With remote sensing, any voltage dropped in the
load leads must be added to the load voltage to calculate
maximum output voltage. The performance specifications are
not guaranteed when the maximum output voltage is
exceeded. If the excessive demand on the power supply
forces the power supply to lose regulation, the Unreg
annunciator will turn on to indicate that the output is
unregulated.
Output noise
Any noise picked up on the sense leads also appears at the
output of the power supply and may adversely affect the
voltage load regulation. Twist the sense leads to minimize
external noise pickup and run them parallel and close to the
load leads. In noisy environments it may be necessary to
shield the sense leads. Ground the shield at the power
supply end only. Do not use the shield as one of the sense
conductors.
Stability
Using remote sensing under certain combinations of load
lead lengths and large load capacitances may cause your
application to form a filter, which becomes part of the
voltage feedback loop. The extra phase shift created by this
filter can degrade the power supply’s stability, resulting in
poor transient response or loop instability. In severe cases,
it may cause oscillations. To minimize this possibility, keep
the load leads as short as possible and twist them together.
As the sense leads are part of the power supply’s
programming feedback loop, accidental open- connections of
42E3632A User’s Guide
sense or load leads during remote sensing operation have
NOTE
various unwanted effects. Provide secure and permanent
connections.
Remote voltage sensing connections
Remote voltage sensing requires connecting the load leads
from output terminals to the load and connecting the sense
leads from sense terminals to the load as shown in
Figure 2- 2. Observe polarity when connecting the sensing
leads to the load.
Notice that the metal shorting bars should be removed from
the output and sense terminals for remote voltage sensing
connections.
• For local voltage sensing connections, the sense leads must be
connected to the output terminals.
• During remote sensing setup, it is strongly recommended to power off
(by presssing the power ON/OFF button) the power supply to avoid
undesirable damage to the load or the power supply.
Operation and Features2
Remote Voltage Sensing
Figure 2-2 Remote voltage sensing connections
E3632A User’s Guide43
2Operation and Features
NOTE
Output On/Off
Disabling the Output
Disabling the Output
The output of the power supply can be disabled or enabled
from the front panel.
• When the power supply is in the Off state, the OFF
annunciator turns on and the output is disabled. The OFF
annunciator turns off when the power supply returns to
the On state. When the output is disabled, the voltage
value is 0 V and the current value is 0.02 A.
• The output state is stored in volatile memory; the output
is always disabled when power has been off or after a
remote interface reset.
While the output is disabled, the range selection keys, the control knob,
resolution selection keys, and adjust selection key are still working. If the
display is in the meter mode, you cannot see the changes of output voltage
and current settings on the display when turning the knob. To see or check
the changes when the outputs are disabled, the display should be in the
limit mode.
44E3632A User’s Guide
Front panel operation
You can disable the output by pressing . This
key toggles between output Off and On states.
Remote interface operation
OUTP {OFF|ON}Disable or enable the output.
Operation and Features2
NOTE
Disabling the Output
Disconnecting the output using an external relay
When the output of the E3632A is turned off, it is
implemented by setting the output to 0 V and 0.02 A. This
gives a zero output voltage without actually disconnecting
the output. To disconnect the output an external relay must
be connected between the output and the load. A TTL signal
of either low true or high true is provided to control an
external relay. This signal can only be controlled with the
remote command OUTPut:RELay {OFF|ON}. The TTL
output is available on the RS- 232 connection pin 1 and
pin 9.
When the OUTPut:RELay state is ON, the TTL output of pin
1 is high (4.5 V) and pin 9 is low (0.5 V). The levels are
reversed when the OUTPut:RELay state is OFF.
• TTL output of pin 1 or pin 9 of the RS-232 connector is available only
after installing two jumpers inside the power supply. Refer to the
Service Guide (E3632-90010) for more information.
• Do not use the RS-232 interface if you have configured the power
supply to output relay control signals. Internal components on the
RS-232 circuitry may be damaged.
Knob locking
The knob locking function can be used to disable the knob,
thereby preventing any unwanted changes during an
experiment, or when you leave the power supply unattended.
To disable the knob, press the resolution selection key until
the blinking digit disappears.
Notice that the knob and front panel keys are disabled when
in the remote interface mode.
E3632A User’s Guide45
2Operation and Features
Recall
Error
Recall
System-Related Operations
System-Related Operations
This section gives information on topics such as self- test,
error conditions, and front- panel display control. This
information is not directly related to setting up the power
supply but is an important part of operating the power
supply.
Self-test
A power- on self- test occurs automatically when you turn on
the power supply. This test assures you that the power
supply is operational. This test does not perform the
extensive set of tests that are included as part of the
complete self- test described below. If the power- on self- test
fails, the ERROR annunciator turns on.
A complete self- test performs a series of tests and takes
approximately two seconds to execute. If all tests pass, you
can have a high confidence that the power supply is
operational.
If the complete self- test is successful, PASS is displayed on
the front panel. If the self- test fails, FAIL is displayed and
the ERROR annunciator turns on. See the Service Guide (E3632- 90010) for instructions on returning the power
supply to Keysight for service.
Front panel operation
The complete self- test is enabled by pressing
(actually any front panel keys except ) and the
power- line switch simultaneously and then continuing to
press
finished in two seconds.
for five seconds. The complete self- test will be
Remote interface operation
“*TST?”
Returns 0 if the complete self- test passes or 1 if it fails.
46E3632A User’s Guide
Error conditions
Error
When the front- panel ERROR annunciator turns on, one or
more command syntax or hardware errors have been
detected. A record of up to 20 errors can be stored in the
power supply’s error queue. Refer to
Messages” for more information.
• Errors are retrieved in first- in- first- out (FIFO) order. The
• If more than 20 errors have occurred when you operate
• The error queue is cleared when power has been off or
Operation and Features2
System-Related Operations
Chapter 4, “Error
first error returned is the first error that was stored.
When you have read all errors from the queue, the
ERROR annunciator turns off. The power supply beeps
once each time an error is generated.
the power supply over the remote interface, the last error
stored in the queue (the most recent error) is replaced
with - 350, “Queue overflow”. No additional errors are
stored until you remove errors from the queue. If no
errors have occurred when you read the error queue, the
power supply responds with +0, “No error” over the
remote interface or NO ERRORS from the front panel.
after a *CLS (clear status) command has been executed.
The *RST (reset) command does not clear the error
queue.
Front panel operation
If the ERROR annunciator is on, press repeatedly to
read the errors stored in the queue. All errors are cleared
when you read all errors.
ERROR -113
Remote interface operation
SYST:ERR?Reads an error from the error queue
Errors have the following format (the error string may
contain up to 80 characters).
- 113, “Undefined header”
E3632A User’s Guide47
2Operation and Features
Local
System-Related Operations
Display control
For security reasons, you may want to turn off the
front- panel display. From the remote interface, you can
display a 12- character message on the front panel.
The display can be enabled/disabled from the remote
interface only.
• When the display is turned off, outputs are not sent to
the display and all annunciators are disabled except the
ERROR annunciator. Front-panel operation is otherwise
unaffected by turning off the display.
• The display state is stored in volatile memory; the display
is always enabled when power has been off, after a
remote interface reset, or after returning to local from
remote.
• You can display a message on the front panel by sending
a command from the remote interface. The power supply
can display up to 12 characters of the message on the
front panel; any additional characters are truncated.
Commas, periods, and semicolons share a display space
with the preceding character, and are not considered
individual characters. When a message is displayed,
outputs are not sent to the display.
• Sending a message to the display from the remote
interface overrides the display state; this means that you
can display a message even if the display is turned off.
The display state is automatically turned on when you
return to the local (front panel) operation. Press
to return to the local state from the remote interface.
Remote interface operation:
DISP {OFF|ON}Disable/enable the display.
DISP:TEXT <quoted string>Display the string enclosed in quotes
DISP:TEXT:CLEClear the displayed message
48E3632A User’s Guide
The following statement shows how to display a message on
the front panel from a Keysight controller.
DISP:TEXT ‘HELLO’
Firmware revision query
The power supply has three microprocessors for control of
various internal systems. You can query the power supply to
determine which revision of firmware is installed for each
microprocessor.
You can query the firmware revision from the remote
interface only.
The power supply returns four fields separated by commas
and the fourth field is a revision code which contains three
numbers. The first number is the firmware revision number
for the main processor, the second is for the input/output
processor, and the third is for the front- panel processor.
Operation and Features2
System-Related Operations
Remote interface operation
*IDN?
The above command returns a string in the form:
HEWLETT-PACKARD,E3632A,0,X.X-X.X-X.X
Be sure to dimension a string variable with at least
40 characters.
SCPI language version
The power supply complies with the rules and regulations of
the present version of Standard Commands for
Programmable Instruments (SCPI). You can determine the
SCPI version with which the power supply is in compliance
by sending a command from the remote interface.
E3632A User’s Guide49
2Operation and Features
System-Related Operations
You can query the SCPI version from the remote interface
only.
Remote interface operation
SYST:VERS?Query the SCPI version
Returns a string in the form of YYYY.V where the Y
represents the year of the version, and the V represents the
version number for that year (for example, 1995.0).
50E3632A User’s Guide
Remote Interface Configuration
Before you can operate the power supply over the remote
interface, you must configure the power supply for the
remote interface. This section gives information on
configuring the remote interface. For additional information
on programming the power supply over the remote interface,
Refer to
Remote interface selection
The power supply is shipped with both a GPIB (IEEE- 488)
interface and an RS- 232 interface on the rear panel. Only
one interface can be enabled at a time. The GPIB interface
is selected when the power supply is shipped from the
factory.
The remote interface can be selected from the front- panel
only.
• The interface selection is stored in non- volatile memory,
• If you select the GPIB interface, you must select a unique
• Your GPIB bus controller has its own address. Be sure to
• If you enable the RS- 232 interface, you must select the
Chapter 3, “Remote Interface Reference”.
and does not change when power has been off or after a
remote interface reset.
address for the power supply. The current address is
displayed momentarily on the front panel when you turn
on the power supply.
avoid using the bus controller’s address for any
instrument on the interface bus. Keysight controllers
generally use address 21.
baud rate and parity to be used. RS-232 is displayed
momentarily on the front panel when you turn on the
power supply if you have selected this interface.
Operation and Features2
Remote Interface Configuration
[1]
[2]
[1] Refer to “GPIB Interface Configuration” on page 56 for more information on
connecting the power supply to a computer over the GPIB interface.
E3632A User’s Guide51
2Operation and Features
Remote Interface Configuration
GPIB address
Each device on the GPIB (IEEE- 488) interface must have a
unique address. You can set the power supply’s address to
any value between 0 and 30. The current address is
displayed momentarily on the front panel when you turn on
the power supply. The address is set to 05 when the power
supply is shipped from the factory.
The GPIB address can be set from the front- panel only.
• The address is stored in non- volatile memory, and does
not change when power has been off or after a remote
interface reset.
• Your GPIB bus controller has its own address. Be sure to
avoid the bus controller’s address for any instrument on
the interface bus. Keysight controllers generally use
address 21.
Baud rate selection (RS-232)
You can select one of six baud rates for RS- 232 operation.
The rate is set to 9600 baud when the power supply is
shipped from the factory.
The baud rate can be set from the front- panel only.
• Select one of the following: 300, 600, 1200, 2400, 4800,
9600 baud. The factory- setting is 9600 baud.
• The baud rate selection is stored in non- volatile memory,
and does not change when power has been off or after a
remote interface reset.
[2] Refer to“RS-232 Interface Configuration” on page 57for more information on
connecting the power supply to a computer over the RS-232 interface.
52E3632A User’s Guide
Parity selection (RS-232)
I/O Config
I/O Config
You can select the parity for RS- 232 operation. The power
supply is configured for no parity and 8 data bits when
shipped from the factory.
The parity can be set from the front- panel only.
• Select one of the following: None (8 data bits), Even (7
data bits), or Odd (7 data bits). When you set the parity,
you are indirectly setting the number of data bits.
• The parity selection is stored in non- volatile memory, and
does not change when power has been off or after a
remote interface reset.
To set the GPIB address
To configure the power supply for the GPIB interface,
proceed as follows:
1 Turn on the remote configuration mode.
HPIB/488
You will see the above message on the front-panel display
if the power supply has not been changed from the
factory- setting. If RS-232 appears, choose HPIB/488 by
turning the knob to the right.
2 Move to the GPIB address setting mode.
ADDR 05
The address is set to 05 when the power supply is
shipped from the factory. Notice that a different GPIB
address may appear if the power supply has been changed
from the factory- setting.
3 Turn the knob to change the GPIB address.
The displayed address is changed when turning the knob
to the right or left.
Operation and Features2
Remote Interface Configuration
E3632A User’s Guide53
2Operation and Features
I/O Config
NOTE
I/O Config
I/O Config
I/O Config
Remote Interface Configuration
4 Save the change and turn off the I/O configuration mode.
CHANGE SAVED
The address is stored in non- volatile memory, and does
not change when power has been off or after a remote
interface reset. The power supply displays a message to
show that the change is now in effect. If the GPIB address
is not changed, NO CHANGE will be displayed for one
second.
To exit the I/O configuration mode without any further changes, press
until the NO CHANGE message is displayed.
To set the baud rate and parity (RS-232)
To configure the power supply for the RS- 232 interface,
proceed as follows:
1 Turn on the remote configuration mode.
HPIB/488
You will see the above message on the display if the
power supply has not been changed from the
factory- setting.
Notice that if you changed the remote interface selection
to RS- 232 before, RS-232 message will be displayed.
2 Choose the RS- 232 interface.
RS-232
You can choose the RS- 232 interface by turning the knob
to the left.
3 Move to the RS- 232 interface setting mode and select the
baud rate.
9600 BAUD
The rate is set to 9600 baud when the power supply is
shipped from the factory. Choose from one of the
following by turning the knob to the right or left: 300,
600, 1200, 2400, 4800, or 9600 baud.
54E3632A User’s Guide
Operation and Features2
I/O Config
I/O Config
NOTE
I/O Config
Remote Interface Configuration
4 Save the change and choose the parity.
NONE 8 BITS
The power supply is configured for 8 data bits with no
parity when shipped from the factory. Choose from one of
the following by turning the knob to the right or left:
None 8 Bits, Odd 7 Bits, or Even 7 Bits. When you set
parity, you are indirectly setting the number of the data
bits.
5 Save the change and turn off the I/O configuration mode.
CHANGE SAVED
The RS- 232 baud rate and parity selections are stored in
non- volatile memory, and does not change when power
has been off or after a remote interface reset. The power
supply displays a message to show that the change is now
in effect. If the baud rate and the parity are not changed,
NO CHANGE will be displayed for one second.
To exit the I/O configuration mode without any further changes, press
until the NO CHANGE message is displayed.
E3632A User’s Guide55
2Operation and Features
NOTE
GPIB Interface Configuration
GPIB Interface Configuration
The GPIB connector on the rear panel connects your power
supply to the computer and other GPIB devices.
“Getting Started” lists the cables that are available from
Keysight Technologies. A GPIB system can be connected
together in any configuration (star, linear, or both) as long
as the following rules are observed:
• The total number of devices including the computer is not
more than 15.
• The total length of all the cables used is not more than
2 m times the number of devices connected together, up
to a maximum of 20 m.
IEEE-488 states that you should exercise caution if your individual cable
lengths exceed 4 m.
Do not stack more than three connector blocks together on
any GPIB connector. Make sure that all connectors are fully
seated and that the lock screws are firmly finger tightened.
Chapter 1,
56E3632A User’s Guide
RS-232 Interface Configuration
I/O Config
You connect the power supply to the RS- 232 interface using
the 9- pin (DB- 9) serial connector on the rear panel. The
power supply is configured as a DTE (Data Terminal
Equipment) device. For all communications over the RS- 232
interface, the power supply uses two handshake lines: DTR
(Data Terminal Ready, on pin 4) and DSR (Data Set Ready,
on pin 6).
The following sections contain information to help you use
the power supply over the RS- 232 interface. The
programming commands for RS- 232 are explained in
“RS- 232 Interface Commands” on page 106.
RS-232 configuration overview
Configure the RS- 232 interface using the parameters shown
below. Use
rate, parity, and number of data bits (refer to “To set the
baud rate and parity (RS- 232)” on page 54 for more
• None/8 data bits (factory- setting), even/7 data bits, or
odd/7 data bits
Number of start bits:
• 1 bit (fixed)
Number of stop bits:
• 2 bits (fixed)
E3632A User’s Guide57
2Operation and Features
RS-232 Interface Configuration
RS-232 data frame format
A character frame consists of all the transmitted bits that
make up a single character. The frame is defined as the
characters from the start bit to the last stop bit, inclusively.
Within the frame, you can select the baud rate, number of
data bits, and parity type. The power supply uses the
following frame formats for seven and eight data bits.
Figure 2-3 RS-232 data frame format
Connection to a computer or terminal
To connect the power supply to a computer or terminal, you
must have the proper interface cable. Most computers and
terminals are DTE (Data Terminal Equipment) devices. Since
the power supply is also a DTE device, you must use a
DTE- to- DTE interface cable. These cables are also called
null- modem, modem- eliminator, or crossover cables.
The interface cable must also have the proper connector on
each end and the internal wiring must be correct.
Connectors typically have nine pins (DB- 9 connector) or 25
pins (DB- 25 connector) with a “male” or “female” pin
configuration. A male connector has pins inside the
connector shell and a female connector has holes inside the
connector shell.
If you cannot find the correct cable for your configuration,
you may have to use a wiring adapter. If you are using a
DTE- to- DTE cable, make sure the adapter is a
“straight- through” type. Typical adapters include gender
changers, null- modem adapters, and DB- 9 to DB- 25
adapters.
58E3632A User’s Guide
Operation and Features2
Instrument
PC
DB9
Male
DB9
Female
DB9
Female
DB9
Male
DCD
RX
TX
DTR
1
2
3
4
5
6
7
8
9
GND
DSR
RTS
CTS
RI
1
2
3
4
5
6
7
8
9
DCD
RX
TX
DTR
GND
DSR
RTS
CTS
RI
5182-4794
Cable
RS-232 Interface Configuration
The cable and adapter diagrams shown below can be used to
connect the power supply to most computers or terminals.
DB-9 serial connection
If your computer or terminal has a 9- pin serial port with a
male connector, use the null- modem cable included with the
Keysight 34398A Cable Kit. This cable has a 9- pin female
connector on each end. The cable pin diagram is shown in
Figure 2- 4.
Figure 2-4 DB-9 serial connection
DB-25 serial connection
If your computer or terminal has a 25- pin serial port with a
male connector, use the null- modem cable and 25- pin
adapter included with the Keysight 34398A Cable Kit. The
cable and adapter pin diagram are shown in
E3632A User’s Guide59
Figure 2- 5.
2Operation and Features
Instrument
PC
DB9
Male
DB9
Female
DB9
Female
DB9
Male
DCD
RX
TX
DTR
1
2
3
4
5
6
7
8
9
GND
DSR
RTS
CTS
RI
TX
RX
RTS
CTS
DSR
GND
DCD
DTR
5182-4794
Cable
5181-6641
Adapter
1
2
3
4
5
6
7
8
9
1
2
3
4
5
6
7
8
9
2
3
4
5
6
7
8
20
DB25
Female
DB25
Male
RS-232 Interface Configuration
Figure 2-5 DB-25 serial connection
DTR/DSR handshake protocol
The power supply is configured as a DTE (Data Terminal
Equipment) device and uses the DTR (Data Terminal Ready)
and DSR (Data Set Ready) lines of the RS- 232 interface to
handshake. The power supply uses the DTR line to send a
hold- off signal. The DTR line must be TRUE before the
power supply will accept data from the interface. When the
power supply sets the DTR line FALSE, the data must cease
within 10 characters.
To disable the DTR/DSR handshake, do not connect the DTR
line and tie the DSR line to logic TRUE. If you disable the
DTR/DSR handshake, also select a slower baud rate to
ensure that the data is transmitted correctly.
60E3632A User’s Guide
Operation and Features2
NOTE
RS-232 Interface Configuration
The power supply sets the DTR line FALSE in the following
cases:
1 When the power supply’s input buffer is full (when
approximately 100 characters have been received), it sets
the DTR line FALSE (pin 4 on the RS- 232 connector).
When enough characters have been removed to make
space in the input buffer, the power supply sets the DTR
line TRUE, unless the second case (see next) prevents
this.
2 When the power supply wants to “talk” over the interface
(which means that it has processed a query) and has
received a <new line> message terminator, it will set the
DTR line FALSE. This implies that once a query has been
sent to the power supply, the bus controller should read
the response before attempting to send more data. It also
means that a <new line> must terminate the command
string. After the response has been output, the power
supply sets the DTR line TRUE again, unless the first case
(see above) prevents this.
The power supply monitors the DSR line to determine when
the bus controller is ready to accept data over the interface.
The power supply monitors the DSR line (pin 6 on the
RS- 232 connector) before each character is sent. The output
is suspended if the DSR line is FALSE. When the DSR line
goes TRUE, transmission will resume.
The power supply holds the DTR line FALSE while output is
suspended. A form of interface deadlock exists until the bus
controller asserts the DSR line TRUE to allow the power
supply to complete the transmission. You can break the
interface deadlock by sending the <Ctrl- C> character, which
clears the operation in progress and discards pending output
(this is equivalent to the IEEE- 488 device clear action).
For the <Ctrl-C> character to be recognized reliably by the power supply
while it holds DTR FALSE, the bus controller must first set DSR FALSE.
E3632A User’s Guide61
2Operation and Features
RS-232 Interface Configuration
RS-232 troubleshooting
Here are a few things to check if you are having problems
communicating over the RS-232 interface. If you need
additional help, refer to the documentation that came with
your computer.
• Verify that the power supply and your computer are
configured for the same baud rate, parity, and number of
data bits. Make sure that your computer is set up for one
start bit and two stop bits (these values are fixed on the
power supply).
• Make sure to execute the SYSTem:REMote command to
place the power supply in the remote mode.
• Verify that you have connected the correct interface cable
and adapters. Even if the cable has the proper connectors
for your system, the internal wiring may be incorrect. The
Keysight 34398A Cable Kit can be used to connect the
power supply to most computers or terminals.
• Verify that you have connected the interface cable to the
correct serial port on your computer (COM1, COM2, etc).
62E3632A User’s Guide
Calibration
Operation and Features2
Calibration
This section gives an overview of the calibration features of
the power supply. For more detailed discussion of the
calibration procedures, refer to the Service Guide (E3632- 90010).
Calibration security
This feature allows you to enter a security code to prevent
accidental or unauthorized calibrations of the power supply.
When you first receive your power supply, it is secured.
Before you can calibrate the power supply, you must
unsecure it by entering the correct security code.
• The security code is set to “HP003632” when the power
supply is shipped from the factory. The security code is
stored in non- volatile memory, and does not change when
power has been off or after a remote interface reset.
• To secure the power supply from the remote interface, the
security code may contain up to 12 alphanumeric
characters as shown below. The first character must be a
letter, but the remaining characters can be letters or
numbers. You do not have to use all 12 characters but the
first character must always be a letter.
A _ _ _ _ _ _ _ _ _ _ _ (12 characters)
• To secure the power supply from the remote interface so
that it can be unsecured from the front panel, use the
eight- character format shown below. The first two
characters must be “H P” and the remaining characters
must be numbers. Only the last six characters are
recognized from the front panel, but all eight characters
are required. To unsecure the power supply from the front
panel, omit the “H P” and enter the remaining numbers as
shown on the following pages.
H P _ _ _ _ _ _ (8 characters)
E3632A User’s Guide63
2Operation and Features
NOTE
Calibrate
Secure
Secure
Secure
Calibration
If you forget your security code, you can disable the security feature by
adding a jumper inside the power supply, and then entering a new code.
Refer to the Service Guide (E3632-90010) for more information.
To unsecure for calibration
You can unsecure the power supply either from the front
panel or over the remote interface. The power supply is
secured when shipped from the factory, and the security
code is set to “HP003632”.
Front panel operation
1 Select the calibration mode.
SECURED
If the power supply is secured, you will see the above
message for one second by holding
seconds when you turn on the power supply.
2 Enter the security code.
000000 CODE
To unsecure the power supply, press after the
CAL MODE message is displayed in the calibration mode,
enter the security code using the knob and resolution
selection keys, and then press
3 Save the change and exit the menu.
UNSECURED
When you press to save the change, you will see
the message above for one second if the security code is
correct. The unsecured setting is stored in non- volatile
memory, and does not change when power has been off or
after a remote interface reset. To exit the calibration
mode, turn the power off and on.
Notice that if you enter the wrong security code, INVALID
is displayed and the code entering mode is displayed for
you to enter the correct code.
.
for five
64E3632A User’s Guide
Remote interface operation
Calibrate
Secure
Secure
CAL:SEC:STAT {OFF|ON},<code>Secure or unsecure
To unsecure the power supply, send the above command
with the same code used to secure. For example:
CAL:SEC:STAT OFF, HP003632
To secure against calibration
You can secure the power supply against calibration either
from the front panel or over the remote interface. The power
supply is secured when shipped from the factory, and the
security code is set to “HP003632”.
Read the security code rules at “Calibration security” on
page 63 before attempting to secure the power supply.
Operation and Features2
Calibration
the power supply.
Front panel operation
1 Select the calibration mode.
UNSECURED
If the power supply is unsecured, you will see the above
message for one second by holding
seconds when you turn on the power supply.
2 Enter the security code.
000000 CODE
To secure the power supply, press after the CAL
MODE message is displayed in the calibration mode, enter
the security code using the knob and resolution selection
keys, and then press
E3632A User’s Guide65
.
for five
2Operation and Features
Secure
Secure
Secure
Calibration
3 Save the change and exit the menu.
SECURED
When you press to save the change, you will see
the message below. The secured setting is stored in
non- volatile memory, and does not change when power
has been off or after a remote interface reset. To exit the
calibration mode, turn the power off and on.
Remote interface operation
CAL:SEC:STAT {OFF|ON},<code>Secure or unsecure
the power supply.
To secure the power supply, send the above command with
the same code as used to unsecure. For example,
CAL:SEC:STAT ON, HP003632
To change the security code
To change the security code, you must first unsecure the
power supply, and then enter a new code. Read the security
code rules at
attempting to secure the power supply.
Front panel operation
To change the security code, first make sure that the power
supply is unsecured. Press
message is displayed in the calibration mode, enter the new
security code using the knob and resolution selection keys,
then press
Changing the code from the front panel also changes the
code as seen from the remote interface.
66E3632A User’s Guide
“Calibration security” on page 63 before
after the CAL MODE
.
Operation and Features2
Calibration
Remote interface operation
CAL:SEC:CODE <new code>Change the security
code.
To change the security code, first unsecure the power supply
using the old security code. Then, enter the new code as
shown below.
CAL:SEC:STAT OFF, HP003632Unsecure with the
old code.
CAL:SEC:CODE ZZ001443Enter the new code.
CAL:SEC:STAT ON, ZZ001443Secure with the new
code.
Calibration count
You can determine the number of times that your power
supply has been calibrated. Your power supply was
calibrated before it left the factory. When you receive your
power supply, read the count to determine its initial value.
The calibration count feature can be performed from the
remote interface only.
• The calibration count is stored in non- volatile memory,
and does not change when power has been turned off or
after a remote interface reset.
• The calibration count increments up to a maximum of
32767 after which it wraps- around to 0. Since the value
increments by one for each calibration point, a complete
calibration will increase the value by five counts.
E3632A User’s Guide67
2Operation and Features
Calibration
Remote interface operation
CAL:COUN?Query the number of times of calibration
Calibration message
You can use the calibration message feature to record
calibration information about your power supply. For
example, you can store such information as the last
calibration date, the next calibration due date, the power
supply’s serial number, or even the name and phone number
of the person to contact for a new calibration.
You can record and read information in the calibration
message from the remote interface only.
• The power supply should be unsecured before sending a
calibration message.
• The calibration message may contain up to 40 characters.
• The calibration message is stored in non- volatile memory,
and does not change when power has been off or after a
remote interface reset.
Remote interface operation
CAL:STR <quoted string>Store the cal message.
To store the calibration message, send the following
command.
CAL:STR ‘CAL 12-05-99’
68E3632A User’s Guide
E3632A DC Power Supply
User’s Guide
3
Remote Interface Reference
SCPI Command Summary 70
Introduction to the SCPI Language 74
Simplified Programming Overview 80
Using the APPLy Command 83
Output Settings and Operation Commands 85
Triggering Commands 93
System-Related Commands 96
Calibration Commands 102
RS-232 Interface Commands 106
SCPI Status Registers 107
Status Reporting Commands 117
Halting an Output in Progress 121
SCPI Conformance Information 122
IEEE-488 Conformance Information 125
This chapter lists the SCPI commands.
3Remote Interface Reference
NOTE
SCPI Command Summary
SCPI Command Summary
If you are a first-time user of the SCPI language, refer to “Introduction to
the SCPI Language” and “Simplified Programming Overview” to familiarize
with the SCPI language before attempting to program the power supply.
This section summarizes the Standard Commands for
Programmable Instruments (SCPI) available to program the
power supply over the remote interface. Refer to the
respective sections in this chapter for more details on each
command.
Throughout this manual, the following conventions are used
for the SCPI command syntax.
• Square brackets ([]) indicate optional keywords or
parameters.
• Braces ({}) enclose parameters within a command string.
• Triangle brackets (<>) indicate that you must substitute a
value or a code for the enclosed parameter.
• A vertical bar (|) separates one of two or more
alternative parameters.
Standard Commands for Programmable Instruments (SCPI)
is an ASCII- based instrument command language designed
for test and measurement instruments. Refer to
Programming Overview” for an introduction to the basic
techniques used to program the power supply over the
remote interface.
SCPI commands are based on a hierarchical structure, also
known as a tree system. In this system, associated
commands are grouped together under a common node or
root, thus forming subsystems. A portion of the SOURce
subsystem is shown below to illustrate the tree system.
[SOURce:]
CURRent {<current>|MIN|MAX|UP|DOWN}
CURRent? [MIN|MAX]
CURRent:
TRIGgered {<current>|MIN|MAX}
TRIGgered? {MIN|MAX}
VOLTage {<voltage>|MIN|MAX|UP|DOWN}
VOLTage? [MIN|MAX]
VOLTage:
TRIGgered {<voltage>|MIN|MAX}
TRIGgered? {MIN|MAX}
“Simplified
SOURce is the root keyword of the command, CURRent and
VOLTage are second- level keywords, and TRIGgered is the
third- level keyword. A colon (:) separates a command
keyword from a lower- level keyword.
74E3632A User’s Guide
Introduction to the SCPI Language
Command format used in this manual
The format used to show commands in this manual is shown
below:
CURRent {<current>|MINimum|MAXimum|UP|DOWN}
The command syntax shows most commands (and some
parameters) as a mixture of upper- case and lower-case
letters. The upper- case letters indicate the abbreviated
spelling for the command. For shorter program lines, send
the abbreviated form. For better program readability, send
the long form.
For example, in the above syntax statement, CURR and
CURRENT are both acceptable forms. You can use upper-case
or lower- case letters. Therefore, CURRENT, curr, and Curr
are all acceptable. Other forms, such as CUR and CURREN,
will generate an error.
Braces ({}) enclose the parameter choices for a given
command string. The braces are not sent with the command
string.
Remote Interface Reference3
A vertical bar (|) separates multiple parameter choices for a
given command string.
Triangle brackets (<>) indicate that you must specify a value
for the enclosed parameter. For example, the above syntax
statement shows the current parameter enclosed in triangle
brackets. The brackets are not sent with the command
string. You must specify a value for the parameter (such as
CURR 0.1).
Some parameters are enclosed in square brackets ([]). The
brackets indicate that the parameter is optional and can be
omitted. The brackets are not sent with the command string.
If you do not specify a value for an optional parameter, the
power supply chooses a default value.
E3632A User’s Guide75
3Remote Interface Reference
Introduction to the SCPI Language
Some portions of commands are enclosed in square brackets
([]). The brackets indicate that this portion of the command
is optional. Most optional portions of the command are not
shown in the command description. For the full command
showing all the options, refer to
A colon (:) separates a command keyword from a
lower- level keyword. You must insert a blank space to
separate a parameter from a command keyword. If a
command requires more than one parameter, you must
separate adjacent parameters using a comma as shown
below:
SOURce:CURRent:TRIGgered
APPLy 3.5,1.5
Table 3- 1.
Command separators
A colon (:) is used to separate a command keyword from a
lower-level keyword as shown below:
SOURce:CURRent:TRIGgered
A semicolon (;) is used to separate two commands within
the same subsystem, and can also minimize typing. For
example, sending the following command string,
SOUR:VOLT MIN;CURR MAX
is the same as sending the following two commands:
SOUR:VOLT MIN
SOUR:CURR MAX
Use a colon and a semicolon to link commands from
different subsystems. For example, in the following command
string, an error is generated if you do not use the colon and
semicolon:
DISP:TEXT:CLE;:SOUR:CURR MIN
76E3632A User’s Guide
Using the MIN and MAX parameters
CAUTION
You can substitute MINimum or MAXimum in place of a
parameter for many commands. For example, consider the
following command:
CURRent {<current>|MIN|MAX}
Instead of selecting a specific current, you can substitute
MINimum to set the current to its minimum value or
MAXimum to set the current to its maximum value.
Querying parameter settings
You can query the value of most parameters by adding a
question mark (?) to the command. For example, the
following command sets the output current to 5 A:
CURR 5
You can query the value by executing:
Remote Interface Reference3
Introduction to the SCPI Language
E3632A User’s Guide77
CURR?
You can also query the maximum or minimum value allowed
with the present function as follows:
CURR? MAX
CURR? MIN
If you send two query commands without reading the response from
the first, and then attempt to read the second response, you may
receive some data from the first response followed by the complete
second response. To avoid this, do not send a query command without
reading the response. When you cannot avoid this situation, send a
device clear before sending the second query command.
3Remote Interface Reference
Introduction to the SCPI Language
SCPI command terminators
A command string sent to the power supply must terminate
with a <new line> character. The IEEE- 488 EOI
(end- or- identify) message is interpreted as a <new line>
character and can be used to terminate a command string in
place of a <new line> character. A <carriage return>
followed by a <new line> is also accepted. Command string
termination will always reset the current SCPI command
path to the root level. The <new line> character has the
ASCII decimal code of 10.
IEEE-488.2 common commands
The IEEE- 488.2 standard defines a set of common
commands that perform functions like reset, self- test, and
status operations. Common commands always begin with an
asterisk (*), are four to five characters in length, and may
include one or more parameters. The command keyword is
separated from the first parameter by a blank space. Use a
semicolon (;) to separate multiple commands as shown
below:
*RST; *CLS; *ESE 32; *OPC?
SCPI parameter types
The SCPI language defines several different data formats to
be used in program messages and response messages.
Numeric parameters
Commands that require numeric parameters will accept all
commonly used decimal representations of numbers
including optional signs, decimal points, and scientific
notation. Special values for numeric parameters like
MINimum, MAXimum, and DEFault are also accepted.
78E3632A User’s Guide
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.