Keysight 11713B Operation Manual

Page 1
Keysight 11713B/C Attenuator/Switch Driver
Operating and Service Manual
Page 2
Notices
CAUTION
WARNING
Copyright Notice
© Keysight Technologies 2007-2020 No part of this manual may be reproduced in
any form or by any means (including electronic storage and retrieval or translation into a for­eign language) without prior agreement and written consent from Keysight Technologies as governed by United States and international copyright laws.
Manual Part Number
11713-90024
Edition
Edition 4, December 4, 2020
Printed in:
Printed in Malaysia
Published by:
Keysight Technologies Bayan Lepas Free Industrial Zone, 11900 Penang, Malaysia
Technology Licenses
The hardware and/or software described in this document are furnished under a license and may be used or copied only in accordance with the terms of such license.
Declaration of Conformity
Declarations of Conformity for this product and for other Keysight products may be down­loaded from the Web. Go to http://www.key-
sight.com/go/conformity. You can then search
by product number to find the latest Declara­tion of Conformity.
U.S. Government Rights
The Software is “commercial computer soft­ware,” as defined by Federal Acquisition Regu­lation (“FAR”) 2.101. Pursuant to FAR 12.212 and 27.405-3 and Department of Defense FAR Supplement (“DFARS”) 227.7202, the U.S. government acquires commercial computer software under the same terms by which the software is customarily provided to the public. Accordingly, Keysight provides the Software to U.S. government customers under its standard commercial license, which is embodied in its End User License Agreement (EULA), a copy of which can be found at http://www.key-
sight.com/find/sweula. The license set forth in
the EULA represents the exclusive authority by which the U.S. government may use, modify, distribute, or disclose the Software. The EULA and the license set forth therein, does not require or permit, among other things, that Keysight: (1) Furnish technical information related to commercial computer software or commercial computer software documenta­tion that is not customarily provided to the public; or (2) Relinquish to, or otherwise pro­vide, the government rights in excess of these rights customarily provided to the public to use, modify, reproduce, release, perform, dis­play, or disclose commercial computer soft­ware or commercial computer software documentation. No additional government requirements beyond those set forth in the EULA shall apply, except to the extent that those terms, rights, or licenses are explicitly required from all providers of commercial computer software pursuant to the FAR and the DFARS and are set forth specifically in writing elsewhere in the EULA. Keysight shall be under no obligation to update, revise or otherwise modify the Software. With respect to any technical data as defined by FAR 2.101, pursuant to FAR 12.211 and 27.404.2 and DFARS 227.7102, the U.S. government acquires no greater than Limited Rights as defined in FAR 27.401 or DFAR 227.7103-5 (c), as applicable in any technical data.
Warranty
THE MATERIAL CONTAINED IN THIS DOCU­MENT IS PROVIDED “AS IS,” AND IS SUBJECT TO BEING CHANGED, WITHOUT NOTICE, IN FUTURE EDITIONS. FURTHER, TO THE MAXI­MUM EXTENT PERMITTED BY APPLICABLE LAW, KEYSIGHT DISCLAIMS ALL WARRAN­TIES, EITHER EXPRESS OR IMPLIED, WITH REGARD TO THIS MANUAL AND ANY INFOR­MATION CONTAINED HEREIN, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRAN­TIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. KEYSIGHT SHALL NOT BE LIABLE FOR ERRORS OR FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES IN CONNECTION WITH THE FURNISHING, USE, OR PERFORMANCE OF THIS DOCU­MENT OR OF ANY INFORMATION CONTAINED HEREIN. SHOULD KEYSIGHT AND THE USER HAVE A SEPARATE WRITTEN AGREEMENT WITH WARRANTY TERMS COVERING THE MATERIAL IN THIS DOCUMENT THAT CON­FLICT WITH THESE TERMS, THE WARRANTY TERMS IN THE SEPARATE AGREEMENT SHALL CONTROL.
Safety Information
A CAUTION notice denotes a hazard. It calls attention to an operating procedure, practice, or the like that, if not correctly performed or adhered to, could result in damage to the product or loss of important data. Do not pro­ceed beyond a CAUTION notice until the indi­cated conditions are fully understood and met.
A WARNING notice denotes a hazard. It calls attention to an operating procedure, practice, or the like that, if not correctly performed or adhered to, could result in personal injury or death. Do not proceed beyond a WARNING notice until the indicated conditions are fully understood and met.
2 Keysight 11713B/C Operating and Service Manual
Page 3

Certification

Keysight Technologies certifies that this product met its published specifications at the time of shipment from the factory. Keysight Technologies further certifies that its calibration measurements are traceable to the United States National Institute of Standards and Technology (NIST, formerly NBS), to the extend allowed by the Institute’s calibration facility, and to the calibration facilities of the other International Standards Organization members.
Keysight 11713B/C Operating and Service Manual 3
Page 4

Safety Considerations

WARNING
WARNING
WARNING
WARNING
WARNING
WARNING
The following general safety precautions must be observed during all phases of operation, service, and repair of this instrument. Failure to comply with these precautions or with specific warnings elsewhere in this manual violates safety standards of design, manufacture, and intended use of the instrument. Keysight Technologies assumes no liability for the customer's failure to comply with these requirements.
BEFORE APPLYING POWER
– Verify that the correct fuse is installed.
– Ensure the mains supply voltage fluctuation do not exceed ±10% of the nominal supply
voltage.
GROUND THE INSTRUMENT
This product is a Safety Class I instrument (provided with a protective earth terminal). To minimize shock hazard, the instrument chassis and cabinet must be connected to an electrical ground. The instrument must be connected to the AC power supply mains through a three-conductor power cable, with the third wire firmly connected to an electrical ground (safety ground) at the power outlet. Any interruption of the protective (grounding) conductor or disconnection of the protective earth terminal will cause a potential shock hazard that could result in personal injury. If the instrument is to be energized via an external autotransformer for voltage reduction, be certain that the autotransformer common terminal is connected to the neutral (earthed pole) of the AC power lines (supply mains).
DO NOT OPERATE IN AN EXPLOSIVE ATMOSPHERE OR WET ENVIRONMENTS
Do not operate the device around flammable gases or fumes, vapor, or wet environments.
DO NOT OPERATE DAMAGED OR DEFECTIVE INSTRUMENTS
Instruments that appear damaged or defective should be made inoperative and secured against unintended operation until they can be repaired by qualified service personnel.
DO NOT SUBSTITUTE PARTS OR MODIFY INSTRUMENT
Because of the danger of introducing additional hazards, do not install substitute parts or perform any unauthorized modification to the instrument. Return the instrument to a Keysight Technologies Sales and Service Office for service and repair to ensure that safety features are maintained.
USE THE POWER CORD PROVIDED
Use the device with the power cord provided with the shipment.
4 Keysight 11713B/C Operating and Service Manual
Page 5
WARNING
USE THE DEVICE AS SPECIFIED
WARNING
CAUTION
CAUTION
If the device is used in a manner not specified by manufacturer, the device protection may be impaired.
Keysight 11713B/C attenuator/switch drivers are designed for indoor use and in an area with low condensation.
CLEAN WITH SLIGHTLY DAMPENED CLOTH
Clean the outside of the instrument with a soft, lint-free, slightly dampened cloth. Do not use detergent, volatile liquids, or chemical solvents.
The instrument is designed for use in Overvoltage Category II and Pollution Degree 2.

Safety Symbols

The following symbols on the instrument and in the documentation indicate precautions which must be taken to maintain safe operation of the instrument.
When you see this symbol on your instrument, you should refer to the instrument’s instruction manual for important information.
This symbol indicates the protective earth (ground) terminal.
This symbol indicates that the instrument requires alternating current (ac) input.
This symbol indicates the Fuse.
Keysight 11713B/C Operating and Service Manual 5
Page 6

Regulatory Markings

KCC-REM-ATi-
WN11713B
The CE mark is a registered trademark of the European Community. If it is accompanied by a year, it indicates the year the design was proven.
This text indicates that the instrument is an Industrial Scientific and Medical Group 1 Class A product (CISPR 11, Clause 4).
The RCM mark is a registered trademark of the Australian Communications and Media Authority.
This symbol is a South Korean Class A EMC Declaration. This equipment is Class A suitable for professional use and is for use in electromagnetic environments outside of the home.

South Korean Class A EMC Declaration

Information to the user:
This instrument has been conformity assessed for use in business environments. In a residential environment, this equipment may cause radio interference.
This EMC statement applies to the equipment only for use in business environment.
The CSA mark is a registered trademark of the Canadian Standards Association.
ICES/NMB-001 indicates that this ISM device complies with the Canadian ICES-001. Cet appareil ISM est conforme a la norme NMB-001 du Canada.
This symbol indicates the time period during which no hazardous or toxic substance elements are expected to leak or deteriorate during normal use. Forty years is the expected useful life of the product.

Safety and EMC Requirements

6 Keysight 11713B/C Operating and Service Manual
This instrument is designed to comply with the following safety and EMC (Electromagnetic Compatibility) requirements:
– Low Voltage Directive 2014/35/EU
– EMC Directive 2014/30/EU
Page 7

Waste Electrical and Electronic Equipment (WEEE) Directive

This instrument complies with the WEEE Directive marking requirement. This affixed product label indicates that you must not discard this electrical or electronic product in domestic household waste.

Product category:

With reference to the equipment types in the WEEE directive Annex 1, this instrument is classified as a “Monitoring and Control Instrument” product.
The affixed product label is as shown below.
Do not dispose in domestic household waste.
To return this unwanted instrument, contact your nearest Keysight Service Center, or visit
http://about.keysight.com/en/companyinfo/environment/takeback.shtml for more information.

Sales and Technical Support

To contact Keysight for sales and technical support, refer to the support links on the following Keysight websites:
www.keysight.com/find/11713
(product-specific information and support, software and documentation updates)
www.keysight.com/find/assist
(worldwide contact information for repair and service)
Keysight 11713B/C Operating and Service Manual 7
Page 8
8 Keysight 11713B/C Operating and Service Manual
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK
Page 9

Table of Contents

Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Safety Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Safety Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Regulatory Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
South Korean Class A EMC Declaration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Safety and EMC Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Waste Electrical and Electronic Equipment (WEEE) Directive . . . . . . . . . . . . . . . . . . . . 7
Sales and Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1Introduction
Key Features of Keysight 11713B/C Attenuator/Switch Drivers . . . . . . . . . . . . . . . . . . 16
Compatible Keysight Attenuators and Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Connecting Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
11713B Front and Rear Panels at a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
11713C Front and Rear Panels at a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
2Installation
Initial Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Preparing for Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Connecting to Keysight Attenuators and Switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3 Specifications
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4 Verification
Operator’s Check for Local Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Operator’s Check for Remote Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
5 Local Operations
Getting Started with the 11713B/C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Main Menu of the 11713B/C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Save/Recall State Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
6 Remote Operations
Configuring Remote Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Programming Guide (SCPI) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Programming Guide (Legacy) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
SCPI and Legacy Commands Compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
7 Remote Interface Configurations
Keysight 11713B/C Operating and Service Manual 9
Page 10
Connecting the 11713B/C to your Computer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Exploring the 11713B/C Web Interface over LAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
8 Servicing the Attenuator/Switch Driver
Preparing a Static-Safe Workstation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Maintenance and Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
10 Keysight 11713B/C Operating and Service Manual
Page 11

List of Figures

Figure 1-1 11713B front panel features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Figure 1-2 11713B rear panel features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Figure 1-3 11713C front panel features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Figure 1-4 11713C rear panel features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Figure 2-1 Handle positioning for bench operation . . . . . . . . . . . . . . . . . . . . . . . 27
Figure 2-2 Illustrations of steps 2 and 3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Figure 2-3 Illustration of completed setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Figure 2-4 Typical connection for a programmable four-section attenuator . . . . 33
Figure 2-5 Typical connection for 8762 and 8765 series coaxial switches . . . . . 34
Figure 2-6 Typical connection for 8761 series coaxial switches . . . . . . . . . . . . . . 35
Figure 2-7 Typical connection for relay driving circuit . . . . . . . . . . . . . . . . . . . . . 36
Figure 4-1 Switching system for verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Figure 6-1 Example of control using Keysight IO Libraries Suite . . . . . . . . . . . . . 64
Figure 7-1 11713B/C Web Interface’s Welcome Window . . . . . . . . . . . . . . . . . . 79
Figure 7-2 11713B/C Browser Web Control Interface . . . . . . . . . . . . . . . . . . . . . 81
Keysight 11713B/C Operating and Service Manual 11
Page 12
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK.
12 Keysight 11713B/C Operating and Service Manual
Page 13

List of Tables

Table 1-1 Key features of 11713B/11713C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Table 1-2 Compatible Keysight switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 1-3 Compatible Keysight attenuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 1-4 Connecting accessories for Keysight 11713B/11713C . . . . . . . . . . . . 18
Table 2-1 Summary of switches and attenuators connections to 11713B/C . . . 30
Table 2-2 11713B/C front panel and back panel properties . . . . . . . . . . . . . . . . 32
Table 3-1 11713B/C supplemental characteristics . . . . . . . . . . . . . . . . . . . . . . . 38
Table 3-2 11713B/C environmental specifications . . . . . . . . . . . . . . . . . . . . . . . 39
Table 4-1 Recommended test equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Table 5-1 Connection between the 11713B/C and programmable attenuators 51
Table 5-2 Connection between the 11713B/C and switches . . . . . . . . . . . . . . . 51
Keysight 11713B/C Operating and Service Manual 13
Page 14
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK.
14 Keysight 11713B/C Operating and Service Manual
Page 15
Keysight 11713B/C Attenuator/Switch Drivers Operating and Service Manual

1 Introduction

Key Features of Keysight 11713B/C Attenuator/Switch Drivers 16 Compatible Keysight Attenuators and Switches 17 Connecting Accessories 18 11713B Front and Rear Panels at a Glance 18 11713C Front and Rear Panels at a Glance 21
This chapter provides an overview of the Keysight 11713B/C attenuator/switch drivers which includes the instruments’ functions and capabilities, compatibility with Keysight switching components, and physical appearances.
15
Page 16
1Introduction
NOTE

Key Features of Keysight 11713B/C Attenuator/Switch Drivers

The 11713B attenuator/switch driver is a GPIB compatible instrument that concurrently drives up to two four-section programmable step attenuators and two microwave coaxial switches, or up to 10 SPDT switches. The 11713B is fully backward compatible with 11713A in terms of functionality and fit. Connectivity using USB and LAN are optional.
The 11713C attenuator/switch driver is a GPIB/USB/LAN compatible instrument that concurrently drives up to four four-section programmable step attenuators and four microwave coaxial switches, or up to 20 SPDT switches. The 11713C comes with tri-voltage selection of +5 V, +15 V and +24 V and also permits user-defined voltage supply capability.
The 11713B/C attenuator/switch drivers output continuous current and do not support pulse drive. Please ensure your switching devices can withstand continuous current or have a built-in current interrupt feature.
Tab le 1 -1 Key features of 11713B/11713C
Key features 11713B 11713C
Manually-controlled using front panel push buttons Yes Yes
Automatically-control through: –GPIB –USB –LAN
Integrated LCD display Yes Yes
Self-contained power supply with current limiting Yes Yes
Common terminal supplies of: – +5 Vdc –+15 Vdc – +24 Vdc
– User-defined
TTL control
[a] For 11713C, maximum user-defined voltage supply is 30 Vdc.
[b] This TTL specification is 2.4 V at 1 mA.
[a]
[b]
Yes Optional Optional
No No Yes No
No Yes
Yes Yes Yes
Yes Yes Yes Yes
16 Keysight 11713B/C Operating and Service Manual
Page 17

Compatible Keysight Attenuators and Switches

The 11713B/C attenuator/switch drivers are designed to drive the following Keysight attenuators and switches. If you are using attenuators and switches made by another supplier, check the switching characteristics against those specified in Chapter 3, "Specifications". Refer to Keysight 11713B/C Configuration Guide, literature number 5989-7277EN, for the most updated list.
Table 1-2 Compatible Keysight switches
Introduction 1
Keysight model number
8761A/B, 8765A/B/C/D/F (33314A/B/D), N1810UL SPDT, unterminated
8762A/B/C/F (33311A/B/C), N1810TL SPDT, terminated
8763A/B/C (33312A/B/C), N1811TL Bypass, 4-port, terminated
8764A/B/C (33313A/B/C), N1812UL Bypass, 5-port, unterminated
8766K (33366K) SP3T, unterminated
8767K (33367K), 8767M, L7204A/B/C SP4T, unterminated
87104A/B/C/D/E, 87204A/B/C/D/E, L7104A/B/C SP4T, terminated
8768K (33368K), 8768M SP5T, unterminated
8769K (33369K), 8769M, L7206A/B/C SP6T, unterminated
87106A/B/C/D/E, 87206A/B/C/D/E, L7106A/B/C SP6T, terminated
87222C/D/E, L7222C DPDT (transfer), unterminated
87406B Matrix, 4-port, terminated
87606B Matrix, 6-port, terminated
U9397A/C SPDT, terminated, solid state
[a] * Electromechanical switches unless specified
Description
[a]
Table 1-3 Compatible Keysight attenuators
Keysight model number Description
8494G/H (33320G/H), 84904K/L/M (33324K/L) 11 dB, 1 dB steps
8495G/H/K (33321 G/H/K), 84907K/L (33327K/L) 70 dB, 10 dB steps
8496G/H (33322G/H) 110 dB, 10 dB steps
8497K (33323K), 84906K/L (33326K/L) 90 dB, 10 dB steps
84905M 60 dB, 10 dB steps
84908M 65 dB, 5 dB steps
Keysight 11713B/C Operating and Service Manual 17
Page 18
1Introduction

Connecting Accessories

Various types of connecting accessories are available to drive Keysight attenuators and switches using the 11713B/C attenuator/switch drivers. Tab le 1-4 lists available accessories.
Tab le 1 -4 Connecting accessories for Keysight 11713B/11713C
Connecting accessories Description
11716A
11716C
11713B-001 11713C-001
11713B-101 11713C-101
11713B-201 11713C-201
11713B-301 11713C-301
11713B-401 11713C-401
11713B-501 11713C-501
11713B-601 11713C-601
11713B-701 11713C-701
11713B-801 11713C-801
11713B-908 11713C-908
11713B-909 11713C-909
Interconnect kit (Type-N connectors)
Interconnect kit (SMA connectors)
11764-60004, Viking connector to 10-pin DIP connector, 60 inches long
8120-2703, Viking connector to Viking connector, 60 inches long
5061-0969, Viking connector to 12-pin conductor cable, bare wire (for five switches), 60 inches long
11761-60001, Viking connector to (4) ribbon cables, connect up to four switches, 60 inches long
11713-60042, dual Viking connector to 16-pin DIP connector, 60 inches long
11713-60043, Viking connector to (4) 9-pin Dsub connectors, connect up to four switches, 60 inches long
11713-60044, Viking connector to 16-pin DIP connector, 60 inches long
5064-7848, Viking connector to 14-pin DIP connector, 60 inches long
11713-60047, Viking connector to (4) 10-pin DIP connectors, connect up to 4 switches, 50 inches long
5063-9240, rack mount kit for one instrument
5061-9694 & 5063-9212, rack mount kit for two instruments
[a]
[a]
[a] Order this kit to connect two programmable step attenuators in series
Refer to Keysight 11713A/B/C Attenuator/Switch Driver Configuration Guide, literature number 5989-3703EN, for configuration details.

11713B Front and Rear Panels at a Glance

This section briefly describes the function of the front panel keys of 11713B.
18 Keysight 11713B/C Operating and Service Manual
Page 19
Figure 1-1 11713B front panel features
1 2
3
4
5
6
7
89
10
11
12
1 LCD screen.
Introduction 1
2Softkeys. These unmarked keys are referred to by the text on display next to them.
3Menu/Enter. Press this key to select the highlighted parameter On/Off or select the highlighted
field or go back to the main menu.
4Preset. Press this key to preset the driver.
5Config. Press this key to access the configuration menu. You can set the attenuator type, supply
voltage, and TTL condition through this menu.
6Save/Recall. Press this key to save current settings or recall saved settings.
7Navigation buttons. The arrow keys are used to navigate parameters displayed on the LCD
screen or change parameters such as GPIB address.
8Switches. In the local mode, pushbutton switches 9 and 0 change the position of a coaxial
switch connected to rear panel banana jacks S9 A/B and S0 A/B respectively.
9Attenuator Y. In the local mode, pushbuttons 5, 6, 7, and 8 change the attenuation setting of an
attenuator or change the position of coaxial switch(es) connected to the ATTEN Y connector on the rear panel.
10 Attenuator X. In the local mode, pushbuttons 1, 2, 3, and 4 change the attenuation setting of
an attenuator or change the position of coaxial switch(es) connected to the ATTEN X connector on the rear panel.
11 On/Standby. Press this key to switch between on and standby. When power is supplied, the
background LED is red. Pressing the key once switches the driver on and the background LED turns to green.
12 Local. Press this key to control the driver from the front panel when it is operating via the
remote interfaces.
Keysight 11713B/C Operating and Service Manual 19
Page 20
1Introduction
1 2
3
4
7
8
9
10
11
5
6
This section briefly describes the function of the rear panel connectors of 11713B.
Figure 1-2 11713B rear panel features
1ATTEN X. Viking connector for connection to attenuator or switch(es).
2ATTEN Y. Viking connector for connection to attenuator or switch(es).
3S9 A/B. Banana jack connectors for connection to coaxial switch.
4 24 VDC COM. Banana jack connector to provide common +24 Vdc in driving the coaxial
switches connected to S9 and/or S0.
5S0 A/B. Banana jack connectors for connection to coaxial switch.
6 Receptacle. Matches transformer primary to line voltage via power cable.
7Alert symbol. This symbol is used to point out a necessary reference for the user.
8GPIB connector. The interface connector from a source device to a listening device for the
remote mode of operation.
9 LAN connector. The interface connector for LAN cable (option LXI only).
10 USB connector. The interface connector for Type mini B 5-pin USB cable (option LXI only).
11 Instrument markings.
20 Keysight 11713B/C Operating and Service Manual
Page 21

11713C Front and Rear Panels at a Glance

1 2
3
4
5
6
7
8
9
10
11
12131415
16
17
This section briefly describes the function of the front panel keys of 11713C.
Introduction 1
Figure 1-3 11713C front panel features
1 LCD screen.
2Softkeys. These unmarked keys are referred to by the text on display next to them.
3Navigation buttons. The arrow keys are used to navigate parameters displayed on the LCD
screen or change parameters such as GPIB address.
4Menu/Enter. Press this key to select the highlighted parameter On/Off or select the highlighted
field or go back to the main menu.
5Preset. Press this key to preset the driver.
6Config. Press this key to access the configuration menu. You can set the attenuator type, supply
voltage, and TTL condition through this menu.
7Save/Recall. Press this key to save current settings or recall saved settings.
8 Supply Voltage for Bank 1. Indicates supply voltage setting (background LED in red) for bank
1.
9 Supply Voltage for Bank 2. Indicates supply voltage setting (background LED in red) for bank
2.
10 Switches for Bank 1. In the local mode, pushbutton switches 9 and 0 change the position of a
coaxial switch connected to rear panel banana jacks S9 A/B and S0 A/B respectively, for bank
1.
11 Switches for Bank 2. In the local mode, pushbutton switches 9 and 0 change the position of a
coaxial switch connected to rear panel banana jacks S9 A/B and S0 A/B respectively for, bank
2.
12 Attenuator Y for Bank 1. In the local mode, pushbuttons 5, 6, 7, and 8 change the attenuation
setting of an attenuator or change the position of coaxial switch(es) connected to the ATTEN Y connector on the rear panel, for bank 1.
Keysight 11713B/C Operating and Service Manual 21
Page 22
1Introduction
13 Attenuator Y for Bank 2. In the local mode, pushbuttons 5, 6, 7, and 8 change the attenuation
setting of an attenuator or change the position of coaxial switch(es) connected to the ATTEN Y connector on the rear panel, for bank 2.
14 Attenuator X for Bank 1. In the local mode, pushbuttons 1, 2, 3, and 4 change the attenuation
setting of an attenuator or change the position of coaxial switch(es) connected to the ATTEN X connector on the rear panel, for bank 1.
15 Attenuator X for Bank 2. In the local mode, pushbuttons 1, 2, 3, and 4 change the attenuation
setting of an attenuator or change the position of coaxial switch(es) connected to the ATTEN X connector on the rear panel, for bank 2.
16 On/Standby. Press this key to switch between on and standby. When power is supplied, the
background LED is red. Pressing the key once switches the driver on and the background LED turns to green.
17 Local. Press this key to control the driver from the front panel when it is operating via the
remote interfaces.
22 Keysight 11713B/C Operating and Service Manual
Page 23
Introduction 1
1
2
3
4
7
8
9
10
11
5
6 12
13
14
15161718
This section briefly describes the function of the rear panel connectors of 11713C.
Figure 1-4 11713C rear panel features
1 ATTEN X Bank 1. Viking connector for connection to attenuator or switch(es), for bank 1.
2 ATTEN X Bank 2. Viking connector for connection to attenuator or switch(es), for bank 2.
3 ATTEN Y Bank 1. Viking connector for connection to attenuator or switch(es), for bank 1.
4 ATTEN Y Bank 2. Viking connector for connection to attenuator or switch(es), for bank 2.
5 S9 A/B Bank 1. Banana jack connectors for connection to coaxial switch, for bank 1.
6 S9 A/B Bank 2. Banana jack connectors for connection to coaxial switch, for bank 2.
7VDC COM Bank 1. Banana jack connector to provide common Vdc in driving the coaxial
switches connected to S9 and/or S0, for bank 1.
8VDC COM Bank 2. Banana jack connector to provide common Vdc in driving the coaxial
switches connected to S9 and/or S0, for bank 2.
9 S0 A/B Bank 1. Banana jack connectors for connection to coaxial switch, for bank 1.
10 S0 A/B Bank 2. Banana jack connectors for connection to coaxial switch, for bank 2.
11 External VDC. Banana jack connector to provide user-defined Vdc, for both banks.
12 Ground. Banana jack connector to provide grounding, for both banks.
13 Receptacle. Matches transformer primary to line voltage via power cable.
14 Alert symbol. This symbol is used to point out a necessary reference for the user.
15 GPIB connector. The interface connector from a source device to a listening device for the
remote mode of operation.
16 LAN connector. The interface connector for LAN cable.
17 USB connector. The interface connector for Type mini B 5-pin USB cable.
18 Instrument markings.
Keysight 11713B/C Operating and Service Manual 23
Page 24
1Introduction
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK.
24 Keysight 11713B/C Operating and Service Manual
Page 25
Keysight 11713B/C Attenuator/Switch Drivers Operating and Service Manual

2 Installation

Initial Inspection 26 Preparing for Use 27 Connecting to Keysight Attenuators and Switches 30
This chapter provides you important information on how to unpack and check your instrument, how to prepare your instrument for bench operation, and tips on configuring the 11713B/C with Keysight attenuators and switches.
25
Page 26
2Installation

Initial Inspection

1 Unpack and inspect the shipping container and its contents thoroughly to ensure that nothing
was damaged during shipment. If the shipping container or cushioning material is damaged, the contents should be checked both mechanically and electrically.
2 If the contents are damaged or defective, contact your nearest Keysight Technologies Service
and Support Office. Refer to “Sales and Technical Support” on page 7. Keysight Technologies will arrange for repair or replacement of the damaged or defective equipment. Keep the shipping materials for the carrier's inspection.
3 If you are returning your instrument for service, repackaging the attenuator/switch driver
requires original shipping containers and materials or their equivalents. Keysight Technologies can provide packaging materials identical to the original materials. Refer to Sales and Technical
Support for the Keysight Technologies nearest to you.
26 Keysight 11713B/C Operating and Service Manual
Page 27

Preparing for Use

Bench operation

Pull the handle outwards, and adjust it into one of the two positions illustrated in Figure 2-1.
– (Top) Handle placed underneath the instrument to assure self- alignment of the instruments
when stacked.
– (Bottom) Handle tilted to raise the front of the instrument for easier viewing of the front panel.
Installation 2
Figure 2-1 Handle positioning for bench operation
Keysight 11713B/C Operating and Service Manual 27
Page 28
2Installation
CAUTION

Rack mounting one instrument (Option 908)

1 Remove the handle and front/rear bumpers.
2 Fit the rack mount flanges (part number 5063-9240).
3 Ready for installation.
Figure 2-2 Illustrations of steps 2 and 3
When installing the product in a cabinet, the convection into and out of the product must not be restricted. The ambient temperature (outside the cabinet) must be less than the maximum operating temperature of the product by 4 °C for every 100 watts dissipated in the cabinet. If the total power dissipated in the cabinet is greater than 800 watts, forced convection must be used.
28 Keysight 11713B/C Operating and Service Manual
Page 29

Rack mounting two instruments (Option 909)

CAUTION
1 Remove the handle and front/rear bumpers.
2 Fit one small mounting flange to opposite sides of each instrument (part numbers 5061-9694
and 5063-9212).
3 Fit two front linking plates to each instrument.
4 Engage the linking plates at the front of the instruments.
5 Attach the rear linking brackets.
6 Ready for installation.
Installation 2
Figure 2-3 Illustration of completed setup
When installing the product in a cabinet, the convection into and out of the product must not be restricted. The ambient temperature (outside the cabinet) must be less than the maximum operating temperature of the product by 4 °C for every 100 watts dissipated in the cabinet. If the total power dissipated in the cabinet is greater than 800 watts, forced convection must be used.
Keysight 11713B/C Operating and Service Manual 29
Page 30
2Installation

Connecting to Keysight Attenuators and Switches

The 11713B/C attenuator/switch drivers can be used to drive various switches and attenuators.
Table 2-1 shows the summary of switches and attenuators connections to the 11713B/C, with
various interface cables for point-to-point connection. Tab le 2-2 shows the properties of 11713B/ C’s front panel and rear panel.
For configuration details, please refer to Keysight 11713B/C Configuration Guide, literature number 5989-7277EN.
Tab le 2-1 Summary of switches and attenuators connections to 11713B/C
Switches/attenuators
Switches – 8761A/B
Switches – 8762A/B/C/F – 8763A/B/C – 8764A/B/C
Switches – 8765A/B/C/D/F
Switches – 8766K
Switches
– N1810UL/TL
– N1811TL
– N1812UL
Switches – 87222C/D/E – L7222C
[c]
[c]
[c]
11713B/C cable
[a]
option
201 1 No Yes
201 2 Yes Yes
201, 301 2 Yes Yes
001, 101 2 Yes Yes
201, 501 2 Yes Yes
201, 801 2 Yes No
# of channels
[b]
required
Controlled by ATTEN X (1-4) ATTEN Y (5-8)
Controlled by SWITCHES (9/0)
Switches – 8767K Attenuators – 8495G/H
Switches – 8767M Attenuators – 84905M – 84907K/L
001, 101 3 Yes Yes
001 3 Yes Yes
30 Keysight 11713B/C Operating and Service Manual
Page 31
Installation 2
Tab le 2-1 Summary of switches and attenuators connections to 11713B/C (continued)
Switches/attenuators
Switches – 8768K Attenuators – 8494G/H – 8496G/H – 8495K, 8497K
Switches – 8768M Attenuators – 84904K/L/M – 84906K/L – 84908M
[d]
Switches – 87104A/B/C/D – 87204A/B/C – L7104A/B/C – L7204A/B/C
Switches – 8769K
11713B/C cable
[a]
option
# of channels
[b]
required
Controlled by ATTEN X (1-4) ATTEN Y (5-8)
Controlled by SWITCHES (9/0)
001, 101 4 Yes Yes
001 4 Yes Yes
201, 601
[e]
4
Yes Yes
101 5 Yes Yes
Switches – 8769M
701 5 Yes Yes
Switches – 87106A/B/C/D – 87206A/B/C – L7106A/B/C
201, 401
[f]
6
Yes Yes
– L7206A/B/C – 87406B, 87606B
[a] Type of interface cable required depends on the DC connector on the switching device
[b] One channel represent control with one pushbutton
[c] Ensure switch is equipped with current interrupt (option 403) to protect switch from overheating and destruction as this switch cannot
withstand continuous current
[d] For switches with option 161, ground pin 16 opens all path. Use S9 for Attenuator X or S0 for Attenuator Y. Do not close any path and
ground pin 16 simultaneously as this makes the switch buzz.
[e] If option 601 is used, number of channels required is 5, to cater for open all path function controlled via S9/S0
[f] If option 401 is used, number of channels required is 7, to cater for open all path function controlled via S9/S0
Keysight 11713B/C Operating and Service Manual 31
Page 32
2Installation
Tab le 2 -2 11713B/C front panel and back panel properties
Front panel pushbuttons
Pushbutton number
[a]
Pushbutton
SWITCHES
9
0
ATTENUATOR S
XY
15
26
37
48
Rear panel connectors
LEDs
Pin numbers
Wire color code
1Red (Vcc)
2 White/Brown (Gnd)
ON ATTEN X-3 (S9-A) Gray
OFF ATTEN X-4 (S9-B) White/Red
ON ATTEN Y-3 (S0-A) Gray
OFF ATTEN Y-4 (S0-B) White/Red
OFF 5 Violet
ON 6 Yellow
OFF 7 Black
ON 8 Green
OFF 9 Orange
ON 10 Blue
OFF 11 Brown
ON 12 White
[b]
[a] The ON/OFF status of the pushbutton LEDs indicates which cable wire or pin on the rear panel connector is grounded. As an example, if
ATT ENUATOR X pus hbutton 3 is illuminated, pin 10 of the ATTEN X connector (blue wire from cable) is grounded and pin 9 floats at a high impedance. For SWITCHES, if pin 3 is grounded (LED on), pin 4 is connected to +Vcc.
[b] With reference to interface cable option 201 (Viking connector to 12-pin bare), consists of 12 color-coded wires
32 Keysight 11713B/C Operating and Service Manual
Page 33

Driving four-section attenuators and switches

– To use one four-section attenuator assembly, connect an attenuator interface cable either to
the ATTEN X output (A6J1) or ATTEN Y output (A6J2). Connect all outputs (two for 11713B and four for 11713C) to have more than four attenuator segments.
– A typical connection for a programmable four-section attenuator to 11713B is illustrated in
Figure 2-4, together with pin number for each connector.
– Using these same connections to Keysight 8762 or 8765 series coaxial switches, control can be
extended to number of switches in multiple of four. If S9 and S0 outputs are utilized, 11713B and 11713C can drive up to 10 switches and 20 switches respectively.
Installation 2
Figure 2-4 Typical connection for a programmable four-section attenuator

Driving additional coaxial switches

– Make switch connections to S0 outputs, S9 outputs, or to rear panel ATTEN X output or ATTEN
Y output.
Figure 2-5 below shows the rear panel connections to S0 outputs and the corresponding switch
positions reflected by pushbutton indicators.
– Connections to Keysight 8762 or 8765 series coaxial switches can also be made to the ATTEN X
output or ATTEN Y output as illustrated in Figure 2-4.
Keysight 11713B/C Operating and Service Manual 33
Page 34
2Installation
Figure 2-5 Typical connection for 8762 and 8765 series coaxial switches
– Connections to Keysight 8761 series coaxial switches can only be made to S0 outputs and S9
outputs.
Figure 2-6 illustrates the rear panel connections to S9 outputs and the corresponding switch
positions reflected by pushbutton indicators.
34 Keysight 11713B/C Operating and Service Manual
Page 35
Installation 2
Figure 2-6 Typical connection for 8761 series coaxial switches
Keysight 11713B/C Operating and Service Manual 35
Page 36
2Installation
NOTE
CAUTION
NOTE

Driving relays

– To drive ten devices for 11713B, connect attenuator cables at ATTEN X and Y and switch cables
– A total of 10 relays may be on at one time if the total current is less than 1.7 A. However, since
Figure 2-7 below shows the connections for a simplified relay driving circuit. The circuit is
to S9 and S0.
there are dual transistor and relay drivers, where one driver is on while the other is off, a total of 20 relays may be controlled.
11713C is capable of driving double the amount of devices that 11713B can. However, the total load current that can be consumed is still 1.7 A.
If the total load current of 1.7 A is exceeded, damage may result.
adaptable for simple non-latching relays.
Figure 2-7 Typical connection for relay driving circuit
It is also recommended that two 28.7 V zener diodes be connected back-to-back across the relay coils to reduce voltage transients.
36 Keysight 11713B/C Operating and Service Manual
Page 37
Keysight 11713B/C Attenuator/Switch Drivers Operating and Service Manual

3 Specifications

General Specifications 38 Environmental Specifications 39
This chapter provides you the specifications of Keysight 11713B/C attenuator/switch drivers.
37
Page 38
3 Specifications

General Specifications

Supplemental characteristics

Supplemental characteristics are intended to provide useful information and are typical but non-warranted performance parameters.
Tab le 3 -1 11713B/C supplemental characteristics
Line power
Current
Response time
Driver life >2,000,000 switchings at 0.7 A for contact pairs 9 and 0
Maximum load inductance
Maximum load capacitance

Physical specifications

Net weight 3.2 kg (7.1 lbs)
Dimensions (H x W x D) with handle and rubber bumper
Dimensions (H x W x D) without handle and rubber bumper
100 to 240 Vac, automatic selection, 50/60 Hz 100 VA maximum
1.7 A maximum continuous current Contact pairs 1 through 8, 9, and 0, maximum current of 1.7 A continuous through all contacts (<
0.7 A per contact)
100 μs maximum for contact pairs 1 through 8 20 ms maximum for contact pairs 9 and 0
500 mH
< 0.01 μF for contact pairs 9 and 0
103.8 mm x 261. (4.1 inches x 10.2 inches x 14.9 inches)
88.3 mm x 212.7 mm x 364.0 mm (3.5 inches x 8.4 inches x 14.3 inches)
3 mm x 378.7 mm

Remote programming characteristics

GPIB interface operates to IEEE 488.2 and IEC 65
Interface
Command language SCPI standard interface commands (Keysight 11713A backward compatible)
GPIB compatibility SH0, AH1, T0, TE0, L2, LE0, SR0, RL1, PP0, DC0, DT0, C0
38 Keysight 11713B/C Operating and Service Manual
10/100 BaseT LAN interface USB 2.0 interface
Page 39

Environmental Specifications

Keysight 11713B/C attenuator/switch drivers are designed to fully comply with Keysight Technologies’ product operating environmental specifications as shown in the table below.
Table 3-2 11713B/C environmental specifications
Temperature
–Operating –Storage
Humidity
–Operating –Storage – Condensing
Shock
– End-user handling – Bench handling – Functional – Transportation
Vibration
– Operating (Random) – Survival (Random) – Swept-sine
Specifications 3
0 °C to +50 °C –40 °C to +70 °C
95% RH up to 40 °C, decreases linearly to 45% RH at 50 °C, non-condensing, 95% RH at 40 °C, 5 days cyclic 90% RH at 65 °C, 24 hours 95% RH at 40 °C, 5 hours (condensation 15 minutes)
Half-sine: 2 to 3 ms duration, 60 in/s (1.6 ms) delta-V Half-sine: 11 ms duration, 30 grms Trapezoidal: 18-22 ms duration, 337 in/s (8.56 ms) delta-V Per MIL-PRF-28800F
0.21 Grms, 5 to 500 Hz, 10 min/axis
2.09 Grms, 5 to 500 Hz, 10 min/axis
0.5 Grms, 5 to 500 Hz, 10 min/axis
Altitude
–Operating – Non-operating
< 4,000 meters (13,080 feet) < 15,300 meters (50,000 feet)
Keysight 11713B/C Operating and Service Manual 39
Page 40
3 Specifications
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK.
40 Keysight 11713B/C Operating and Service Manual
Page 41
Keysight 11713B/C Attenuator/Switch Drivers Operating and Service Manual

4 Verification

Operator’s Check for Local Operation 42 Operator’s Check for Remote Operation 43
This chapter provides you simple instructions to verify Keysight 11713B/C attenuator/switch drivers’ functionality in both local operation and remote (GPIB/USB/LAN) operation.
41
Page 42
4 Verification

Operator’s Check for Local Operation

Recommended test equipment

Table 4-1 lists the test equipment required for performance test verification and equipment
troubleshooting. Equipment other than the recommended models can be used, provided minimum specifications are satisfied.
Tab le 4 -1 Recommended test equipment
Instrument type Critical specifications
Digital voltmeter 0 to +30 Vdc T
Attenuators (2 required) Programmable, 4 sections P, T
Switches (2 required) +5 Vdc, +15 Vdc, or +24 Vdc drive source P, T
[a] P = Performance, T = Troubleshooting

Procedure

1 Configure the switching system as illustrated in Figure 4-1 by following all steps described in
Chapter 5, "Local Operations".
Use
[a]
Figure 4-1 Switching system for verification
2 Once configuration is completed, press and depress the 10 numbered pushbuttons on the
driver front panel. Each LED should alternate between off and on as each key is pressed.
3 In addition, if any switching devices is connected (attenuators, relays, or switches), an audible
click should be heard from the unit actuated. Pressing any numbered pushbutton should not cause any other pushbutton to change state.
42 Keysight 11713B/C Operating and Service Manual
Page 43

Operator’s Check for Remote Operation

These procedure verify that the driver can be controlled remotely using GPIB, USB, and/or LAN.
1 Refer to Chapter 7, "Remote Interface Configurations", to connect the 11713B/C to your
computer through GPIB, USB, and/or LAN.
2 Once remote connection is available, send the following SCPI commands to the driver and note
the changes on front panel LEDs.
Description Command Observation
Verification 4
Close switching paths from channel 1 to channel 4 (bank1)
Open switching paths from channel 5 to channel 8 (bank 1)
Query status on channel 2 (bank 1) ROUTe:CLOSe? (@102)
Query status on channel 7 (bank 1) ROUTe:CLOSe? (@107)
ROUTe:CLOSe (@101:104)
ROUTe:OPEn (@105:108)
LEDs for
pushbuttons
ON
pushbuttons
LEDs for
OFF
Return value “1” (LED for pushbutton 2 light ON)
Return value “0” (LED for pushbutton 7 light OFF)
1 to 4 light
5 to 8 light
If the above checks are successful, the driver’s remote operation is working correctly. These procedures do not check all of the driver’s program codes that can be executed. However, if the driver work correctly from the front panel, there is a high probability that the driver will respond to all the program codes.
Keysight 11713B/C Operating and Service Manual 43
Page 44
4 Verification
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK.
44 Keysight 11713B/C Operating and Service Manual
Page 45
Keysight 11713B/C Attenuator/Switch Drivers Operating and Service Manual

5 Local Operations

Getting Started with the 11713B/C 46 Main Menu of the 11713B/C 52 Save/Recall State Menu 59
This chapter outlines some simple steps to start using the 11713B/C in local operations. Also, functionality of all menus are described to assist operations using the 11713B/C.
45
Page 46
5 Local Operations
NOTE
NOTE

Getting Started with the 11713B/C

The Keysight 11713B/C attenuator/switch driver can be easily configured to drive programmable attenuators and/or switches through the front panel operations. The following three simple steps will guide you through the configuration of the 11713B/C.

Step 1: Turn on the 11713B/C

For Step 1, all details on the 11713C are applicable to the 11713B.
1 Connect the AC power supply to the 11713B/C. You should see:
– the background LED of the power button is red which indicates that the 11713B/C is in the
standby mode.
2 Press the power button once to turn on the 11713B/C. You should see:
– the background LED turns green.
– six menus are displayed on the LCD screen.
– all numbered buttons are lighted up
[1]
.
3 Ensure the Local button is lighted up to enable operation through the front panel. If not, press
the button once.
4 Now, you are ready to configure the 11713B/C.

Step 2: Configure the 11713B/C settings to drive attenuators and switches

To drive programmable attenuators
Step 2 — To drive programmable attenuators, only item 2 is applicable to the 11713B. When the Config button is pressed, the next screen is CONFIGURATION MENU.
[1] At factory default setting. Last state is followed if instrument was configured before shutdown.
46 Keysight 11713B/C Operating and Service Manual
Page 47
Item Action Illustration
a Press Config button. b At SELECT BANK screen, you can
1 Select bank
(only for 11713C)
2 Select
attenuator type
see two softkey selections: BANK1 and BANK2.
c Press BANK1 softkey to select
bank 1.
d Press BANK2 softkey to select
bank 2.
a At CONFIGURATION MENU screen,
press ATTEN TYPE softkey.
b At ATTENUATOR MODEL screen,
scroll to highlight the desired attenuator model number using the navigation keys.
c Once the attenuator model is
determined, press ATTEN X or ATTEN Y softkey to assign the selected attenuator model.
d Repeat steps b and c if needed. e Model assigned to ATTEN X and
ATTEN Y is marked <X> (e.g.
8494G/H) and <Y> (e.g. 8496G/H) respectively.
f To return to the previous screen,
press BACK softkey.
Local Operations 5
Keysight 11713B/C Operating and Service Manual 47
Page 48
5 Local Operations
NOTE
Item Action Illustration
3 Select voltage
type (only for 11713C)
a At CONFIGURATION MENU screen,
press Voltage LEVEL softkey.
b At OUTPUT VOLTAGE screen, scroll
to highlight the desired voltage (e.g. +5V).
c Press SET softkey to assign
highlighted voltage.
d At the next screen, press OK
softkey to confirm decision or press Cancel softkey to cancel.
e Output voltage assigned is marked
<*>.
f To exit this screen, press BACK
softkey.
To drive switches
Step 2 — To drive switches, only applicable to the 11713C as the 11713B is predefined with +24 Vdc supply and no TTL drive.
48 Keysight 11713B/C Operating and Service Manual
Page 49
Item Action Illustration
a Press Config button. b At SELECT BANK screen, you can
1 Select bank
(only for 11713C)
see two softkey selections: BANK1 and BANK2.
c Press BANK1 softkey to select
bank 1.
d Press BANK2 softkey to select
bank 2.
Local Operations 5
2 Select voltage
type (only for 11713C)
a At CONFIGURATION MENU screen,
press TTL ON/OFF softkey.
b At TTL MODE ON/OFF screen,
scroll to highlight the TTL OPTION or Non TTL (e.g. TTL OPTION).
c Press SET softkey to assign
highlighted voltage.
d At the next screen, press OK
softkey to confirm decision or press Cancel softkey to cancel.
e Selection is marked <*>. f To exit this screen, press BACK
softkey.
Keysight 11713B/C Operating and Service Manual 49
Page 50
5 Local Operations
Item Action Illustration
3 Select voltage
type (only for 11713C)
a At CONFIGURATION MENU screen,
press Voltage LEVEL softkey.
b At OUTPUT VOLTAGE screen, scroll
to highlight the desired voltage (e.g. +5V).
c Press SET softkey to assign
highlighted voltage.
d At the next screen, press OK
softkey to confirm decision or press Cancel softkey to cancel.
e Output voltage assigned is marked
<*>.
f To exit this screen, press BACK
softkey.
50 Keysight 11713B/C Operating and Service Manual
Page 51
Local Operations 5

Step 3: Configure the 11713B/C connections to attenuators and switches

1 Determine the interface cable option of the 11713B/C.
2 Determine the DC connector option of the attenuator(s) or switch(es).
3 Check for compatibility using Table 11 for programmable attenuators and Table 12 for switches:
Table 5-1 Connection between the 11713B/C and programmable attenuators
11713B/C Attenuators (Option)
Option 001
Option 101 8494G/H, 8495G/H, 8496G/H, 8495K, 8497K (Option 060)
Table 5-2 Connection between the 11713B/C and switches
11713B/C Switches (Option)
Option 001 8766K, 8767K/M, 8768K/M (Option 016)
Option 101 8766K, 8767K/M, 8768K/M, 8769K/M (Option 060)
8494G/H, 8495G/H, 8496G/H, 8495K, 8497K (Option 016) 84904K/L/M, 84905M, 84906K/L, 84907K/L, 84908M (No option)
8763A/B/C, 8764A/B/C, 8761A/B, 8762A/B/C/F (No option) 8765A/B/C/D/F (Option 305/310/315/324)
N1810UL/TL, N1811TL, N1812UL (Option
Option 201
Option 301 8765A/B/C/D/F (Option 005/010/015/024)
Option 401
Option 501
Option 601
Option 701 8769K/M (Option 016)
Option 801 87222C/D/E, L7222C (Option 161)
[a] If TTL is required, include Option 401. Must order switch with Option 403 (current interrupt) as switch cannot withstand continuous current
supplied by 11713B/C.
87104A/B/C/D, 87204A/B/C, 87106A/B/C/D, 87206A/B/C (Option 100) L7104A/B/C, L7204A/B/C, L7106A/B/C, L7206A/B/C (Option 100) 87406B, 87606B (Option 100) 87222C/D/E, L7222C (Option 100)
87106A/B/C/D, 87206A/B/C (Option 161) L7106A/B/C, L7206A/B/C (Option 161) 87406B, 87606B (Option 161)
N1810UL/TL, N1811TL, N1812UL (Option
87104A/B/C/D, 87204A/B/C (Option 161) L7104A/B/C, L7204A/B/C (Option 161)
[a]
[a]
202)
201)
4 For more details, refer to the 11713B/C Configuration Guide, literature number 5989-7277EN.
Keysight 11713B/C Operating and Service Manual 51
Page 52
5 Local Operations

Main Menu of the 11713B/C

The main menu can be displayed on the LCD screen by pressing the Menu/Enter button. The six submenus, each with their own functionality, are described in the subsequent sections.

SYSTEM menu

Function Action Illustration
a Navigate to the SYSTEM icon using
the navigation keys.
b Press Menu/Enter button when
Display attenuator type(s) configured for
11713B/C
SYSTEM icon is highlighted.
c On display are attenuator models
assigned to ATTEN X and ATTEN Y for each bank (e.g. 8494G/H, 8496G/H, N/A, N/A).
d Press Menu/Enter button again to
return to main menu.
52 Keysight 11713B/C Operating and Service Manual
Page 53

ATTEN menu

Function Action Illustration
Display attenuation levels of each bank
Attenuation value on display changes according to the input from the front panel pushbuttons or through the virtual web interface:
– Pushbutton LED ON — attenuation card selected (attenuation applied) on corresponding
attenuator section
– Pushbutton LED OFF — thru path selected (attenuation lifted) on corresponding attenuator
section
Local Operations 5
a Navigate to the ATTEN icon using
the navigation keys.
b Press Menu/Enter button when
ATTEN icon is highlighted.
c On display are attenuation levels for
ATTEN X and AT TEN Y (e.g. 11 dB, 110 dB, 0, 0).
d Press Menu/Enter button again to
return to main menu.
Keysight 11713B/C Operating and Service Manual 53
Page 54
5 Local Operations

CYCLE menu

Function Action Illustration
Display number of cycles of switching path for each channel
– 10 channels for
11713B (CH1 to
CH9, CH0)
– 20 channels for
11713C (B1-1 to
B1-10, B2-1 to B2-10)
a Navigate to the CYCLE icon using
the navigation keys.
b Press Menu/Enter button when
CYCLE icon is highlighted.
c On display are number of relay
cycles for each channel.
d Press Menu/Enter button again to
return to main menu.
Clear cycle for selected channel(s)
a Scroll to the desired bank-channel
(e.g. B1-1) using the navigation keys.
b Press CLEAR CYCLE. c At the next screen, press OK
softkey to confirm decision or press Cancel softkey to cancel.
d.Note that relay cycle for B1-1 is 0
and below screen indicates CLEARED.
54 Keysight 11713B/C Operating and Service Manual
Page 55
Function Action Illustration
a Press Clear All. b At the next screen, press OK
Clear cycle for all channels
softkey to confirm decision or press Cancel softkey to cancel.
c.Note that relay cycle for all
channels is 0.
Local Operations 5
Save cycle for all channels
a Press Save All. b At the next screen, Cycles saved.
appears and this confirms all channels’ cycles are saved.
Keysight 11713B/C Operating and Service Manual 55
Page 56
5 Local Operations

IO menu

Refer to Chapter 7, "Remote Interface Configurations".

INFO menu

Function Action Illustration
Display system info for
11713B/C –Model – Serial number – Firmware
revision – GPIB address –LAN IP – USB address –MAC address
a Navigate to the INFO icon using the
navigation keys.
b Press Menu/Enter button when
INFO icon is highlighted.
c Press Menu/Enter button again to
return to main menu.
56 Keysight 11713B/C Operating and Service Manual
Page 57

UTILITY menu

Function Action Illustration
Display system utility settings for 11713B/C and adjust beep volume.
Beep volume range from 0 (mute) to 8 (loudest).
To e nab le Auto-Power on
Local Operations 5
a Navigate to the UTILITY icon using
the navigation keys.
b Press Menu/Enter button when
UTILITY icon is highlighted.
c Scroll to highlight Beep volume
using the navigation keys.
d Adjust beep volume using Volume
up and Volume down softkeys.
e Press Menu/Enter button again to
return to main menu.
a Scroll to highlight Auto-Power on
using the navigation keys, then press Enable softkey.
b Factory default is set as Disable
for this feature.
c The status shows Enable. d There are three possible outcome
for standby mode as follows:
– Select unit on standby, the unit
will remain on standby.
– When unit is on standby,
unplugging the unit within 5 s and then replugging it will cause the unit remain on standby mode.
– When unit is on standby,
unplugging the unit after 5 s and then replugging it will cause the unit to auto power on.
e Recommendation: To enable the
auto power on, it is recommended to use “Save Cycles” (via LCD display or SCPI remote command) to save the cycle count before powering the unit off.
Keysight 11713B/C Operating and Service Manual 57
Page 58
5 Local Operations
Function Action Illustration
Set factory default – For more
information: “List
of default
values” on
page 60
Reset LAN
a Scroll to highlight Factory default
using the navigation keys, then press Yes softkey.
b At the next screen, press OK
softkey to confirm decision or press Cancel softkey to cancel.
a Scroll to highlight LAN RESET
using the navigation keys, then press Yes softkey.
b At the next screen, press OK
softkey to confirm decision or press Cancel softkey to cancel.

Preset menu

The preset function is used to apply full attenuation or open all switching paths (all LEDs light ON). For more information: “List of default values” on page 60.
58 Keysight 11713B/C Operating and Service Manual
Page 59

Save/Recall State Menu

The save state function is important to enable you to store up to four different configurations and the recall state function allows you to re-instate one of the four saved states for use. This greatly helps to minimize the amount of work required to make “standard” configuration changes.
Function Action Illustration
a Press Save/Recall button. b Scroll to the desired state to store
To save state
To recall state
c Press Save State softkey to store
d Press Menu/Enter button again to
a Press Save/Recall button. b Scroll to the desired state to recall
c Press Recall State softkey to
d Press Menu/Enter button again to
Local Operations 5
configuration (e.g. STATE 0) using the navigation keys.
configuration.
return to main menu.
configuration (e.g. STATE 2) using the navigation keys.
reinstate configuration.
return to main menu.
Keysight 11713B/C Operating and Service Manual 59
Page 60
5 Local Operations

List of default values

Factory
Key operation Factory-shipped setting
Channel
Attenuator Type N/A << * * K/C
Supply Voltage +24V << * * K/C
TTL OFF << **K/C
Beep Volume 8 << * K
GPIB Address 28 << * K
IP Config AUTO << * K
Manual IP Addr “192.168.1.101” << * K
Manual Gateway “0.0.0.0” << * K
Manual Subnet Mask “255.255.255.0” << * K
[a] When channel light is ON, it means attenuation is being applied (when attenuator is connected) or switch path is open (when switch is
connected).
[b] “<<“ symbol shows that the setup is the same as that in the box to the left.
[c] K = Using front panel. C = Using SCPI command.
All Lights ON
[a]
default key
[b]
<<
Preset (*RST)
<< * *
Backup
Save/ Recall
Available means of defining a setting
[c]
K/C
Definition
Factory Default All data that the user can set are cleared. The relay cycle count is not cleared.
Preset
*RST
Backup
Save/Recall
Status when you press Preset key.
Status when you execute *RST in your program.
Settings that are backed up (set state not affected by turning power ON/OFF). In the table, a setting that is automatically backed up is denoted in the following manner: *: Backup operation performed. Blank: Backup operation not performed.
Settings that permit Save/Recall of a setup state. In the table, states that can be saved/recalled are denoted in the following manner: *: Save/Recall can be performed. Blank: Save/Recall cannot be performed.
60 Keysight 11713B/C Operating and Service Manual
Page 61
Keysight 11713B/C Attenuator/Switch Drivers Operating and Service Manual

6 Remote Operations

Configuring Remote Interface 62 Programming Guide (SCPI) 65 Programming Guide (Legacy) 69 SCPI and Legacy Commands Compatibility 70
This chapter provides the programming guide for the 11713B/C in SCPI commands and legacy commands.
61
Page 62
6 Remote Operations
NOTE
NOTE
NOTE
NOTE

Configuring Remote Interface

This section briefly describes how to configure the GPIB, USB, and LAN remote interfaces.
For more detailed information on remote interface connectivity configuration, refer to the Keysight Technologies USB/LAN/GPIB Interfaces Connectivity Guide. If you have installed the IO Libraries Suite, you can access the Connectivity Guide via the Keysight IO Libraries Control icon. Alternatively, you can access the Connectivity Guide via the Web at
www.keysight.com/find/connectivity.
The latest version of Keysight IO Libraries Suite can be downloaded from
www.keysight.com/find/iosuitedownload. The Keysight Instrument Control
DVD, with the above software, is no longer shipped with Keysight instruments. If you require a Keysight Instrument Control DVD, it can be ordered by contacting your local Keysight Customer Contact Center.

Interface selection

You can choose to control the 11713B/C remotely using the GPIB, USB, or LAN interfaces.
For information on selecting and configuring the remote interface manually from the driver front panel or remotely via virtual front panel, refer to Chapter 5, "Local Operations".

GPIB configuration

Each device on the GPIB (IEEE-488) interface must have a unique address. You can set the 11713B/C’s address to any value between 0 and 30. The attenuator/switch driver is shipped with a default address set to 28. The GPIB address is stored in non-volatile memory and does not change when the driver is switched off or after a remote interface reset.
For information on setting the GPIB address manually from the front panel, refer to “Connecting
over GPIB” on page 72.

USB configuration

The USB interface requires no front panel or remote configuration. The USB cannot be changed — it is set at the factory and is unique for each 11713B/C.
It is expected that most users will use the front panel keys to set up the remote interfaces. The remote interface commands are provided for completeness (for front panel operation).
For further information on USB configuration, refer to “Connecting over USB” on page 73.
62 Keysight 11713B/C Operating and Service Manual
Page 63

LAN configuration

NOTE
NOTE
The 11713B/C has three LAN operating modes:
– Dynamic mode (Dynamic Host Configuration Protocol or DHCP)
– Auto IP mode (Local PC Control or isolated LAN)
– Static mode (Manual mode)
Refer to “Connecting over LAN” on page 75 to configure the above LAN operating modes.
Remote Operations 6
Before connecting the USB cable, make sure that I/O software is installed on your computer.
For more information about Keysight IO Libraries software, refer to the Connectivity Guide. If you have installed other I/O software, refer to the documentation that accompanies the software.
Keysight 11713B/C Operating and Service Manual 63
Page 64
6 Remote Operations

Control using Keysight IO Libraries Suite

The Keysight IO Libraries Suite is a collection of libraries that provides you the ability to use your instruments from a test and measurement program. Figure 6-1 shows an example of controlling via Keysight IO Libraries Suite (when the I/P address of the 11713C is 10.74.73.33). Please ensure the remote instrument name is selected.
Figure 6-1 Example of control using Keysight IO Libraries Suite
64 Keysight 11713B/C Operating and Service Manual
Page 65

Programming Guide (SCPI)

NOTE

SCPI command syntax

The following conventions are used for SCPI command syntax for remote interface programming.
– Square brackets ([]) indicate optional keywords or parameters
– Braces ({}) enclose paramter choices within a command string
–Angle brackets (<>) enclose parameters for which you must specify a value
–A vertical bar (|) separates multiple parameters

Rules for using a channel or scan list

Many of the SCPI commands include a channel list or scan list parameter which allows you to specify one or more channels. The channel number has the form (@bnn), where b is the bank number and nn is the channel number.
Channel list is from 101 to 110 for bank 1 and 201 to 210 for bank 2.
Remote Operations 6
The 11713B has only one bank. Therefore, by default, b = 1.
You can specify a bank, a single channel, multiple channels, or a range of channels as described below.
– The following command closes a single channel (channel 4) on bank 1:
ROUTe:CLOSe (@104)
– The following command closes multiple channels on modules in banks 1 and 2:
ROUTe:CLOSe (@104,107, 201, 206)
– The following command closes a range of channels. When you specify a range of channels, the
range may contain invalid channels (they are ignored), but the first and last channel in the list must be valid:
ROUTe:CLOSe (@101:109)

Commands relevant to attenuators

To configure attenuator type
The commands below set the attenuator type (model number) for corresponding attenuators.
– :CONFigure:[BANK1]:X
{NA|AG8494g|AG8495g|AG8495k|AG8496g|AG8497k|AG84904k|AG84905m|AG84906k|AG8 4907k|AG84908m}
– :CONFigure:[BANK1]:Y
{NA|AG8494g|AG8495g|AG8495k|AG8496g|AG8497k|AG84904k|A G84905m|AG84906k|AG84907k|AG84908m}
Keysight 11713B/C Operating and Service Manual 65
Page 66
6 Remote Operations
NOTE
– :CONFigure:BANK2:X
{NA|AG8494g|AG8495g|AG8495k|AG8496g|AG8497k|AG84904k|AG84905m|AG84906k|AG8 4907k|AG84908m}
– :CONFigure:BANK2:Y
{NA|AG8494g|AG8495g|AG8495k|AG8496g|AG8497k|AG84904k|AG84905m|AG84906k|AG8 4907k|AG84908m}
To set attenuation level
The commands below are used to set the attenuation level of corresponding attenuator(s).
– ATTenuator:[BANK1]:X <attenuation value in dB>
– ATTenuator:[BANK1]:Y <attenuation value in dB>
– ATTenuator:BANK2:X <attenuation value in dB>
– ATTenuator:BANK2:Y <attenuation value in dB>
For AG849xh, use AG849xg. For AG84904l/m, use AG84904k. For 84906l, use AG84906k. For AG84907l, use AG849907k.
To query attenuation level
The commands below return the current attenuation value for corresponding attenuator(s).
– ATTenuator:[BANK1]:X?
– ATTenuator:[BANK1]:Y?
– ATTenuator:BANK2:X?
– ATTenuator:BANK2:Y?
To set supply voltage
The commands below set the supply voltage for each bank.
– CONFigure:BANK1 {OFF|P5v|P15v|P24v|USER}
– CONFigure:BANK2 {OFF|P5v|P15v|P24v|USER}
To query supply voltage
The commands below query the supply voltage set for each bank. Value to be returned: OFF, P5, P15, P24, or USER.
– CONFigure:BANK1?
– CONFigure:BANK2?
To query number of relay cycles
The command below query the number of relay cycles for each channel. Value to be returned: number of cycles.
– DIAGnostic:RELay:CYCles? <channel list>
66 Keysight 11713B/C Operating and Service Manual
Page 67
To clear relay cycles
The commands below clear relay cycle for selected or all channels.
– DIAGnostic:RELay:CLEAr <channel list>
– DIAGnostic:RELay:CLEAr:ALL

Commands relevant to switches

To open/close switch
The commands below close/open switching path(s).
– [:ROUTe]:CLOSe <channel list>
– [:ROUTe]:OPEn <channel list>
– [:ROUTe]:CLOSe:ALL
– [:ROUTe]:OPEn:ALL
To query switch status
The commands below query the status of switching path(s). Value to be returned: “1” if true and “0” if false.
– [:ROUTe]:CLOSe? <channel list>
– [:ROUTe]:OPEn? <channel list>
Remote Operations 6
To set supply voltage
The commands below set the supply voltage for each bank.
– CONFigure:BANK1 {OFF|P5v|P15v|P24v|USER}
– CONFigure:BANK2 {OFF|P5v|P15v|P24v|USER}
To query supply voltage
The commands below query the supply voltage set for each bank. Value to be returned: OFF, P5, P15, P24, or USER.
– CONFigure:BANK1?
– CONFigure:BANK2?
To set TTL O N/OFF
The commands below set TTL ON/OFF for each bank.
– CONFigure:BANK1:TTL {OFF|ON}
– CONFigure:BANK2:TTL {OFF|ON}
Keysight 11713B/C Operating and Service Manual 67
Page 68
6 Remote Operations
To query T T L status
The commands below query the supply voltage status for each bank. Value to be returned: “1” if true and “0” if false.
– CONFigure:BANK1:TTL?
– CONFigure:BANK2:TTL?
To query number of relay cycles
The command below query the number of relay cycles for each channel. Value to be returned: number of cycles.
– DIAGnostic:RELay:CYCles? <channel list>
To clear relay cycles
The commands below clear relay cycle for selected or all channels.
– DIAGnostic:RELay:CLEAr <channel list>
– DIAGnostic:RELay:CLEAr:ALL
68 Keysight 11713B/C Operating and Service Manual
Page 69

Programming Guide (Legacy)

NOTE
NOTE
NOTE
NOTE

Data message input format

Legacy commands cannot be utilized to control Bank 2 of the 11713C.
The programming data string for the driver consists of a string of ASCII-coded characters composed of one or both of the following fields:
[Adm] [Bdn]
where: A or a = general ON command; B or b = general OFF command
dm = any digits 0 through 9 (excluding dn)
dn = any digits 0 through 9 (excluding dm)
The driver responds to an alphanumeric data string such as “A12B34” when the driver is in the remote state and addressed to listen.
Remote Operations 6
The alpha characters in the data string can be either upper or lower case.
The maximum number of characters in a data string is 12.
The data string is further defined as follows:
Ax Bx = data string for ATTEN X (x can be none, one or more of digits 1, 2, 3, or 4)
Ay By = data string for ATTEN Y (y can be none, one or more of digits 5, 6, 7, or 8)
If Ax (Ay) uses a digit, then that digit may not be used in Bx (By).
A/B 9 = legacy command for switch S9
A/B 0 = legacy command for switch S0
Keysight 11713B/C Operating and Service Manual 69
Page 70
6 Remote Operations

SCPI and Legacy Commands Compatibility

Front panel
Pushbutton
number
1
2
3
4
5
6
7
8
9
0
Pushbutton
[a]
LED
ON
OFF 6 L H
ON 7 H L
OFF 8 L H
ON 9 H L
OFF 10 L H
ON 11 H L
OFF 12 L H
ON
OFF 6 L H
ON 7 H L
OFF 8 L H
ON 9 H L
OFF 10 L H
ON 11 H L
OFF 12 L H
ON
OFF G
ON
OFF G
ON
OFF G
ON
OFF G
Rear panel
connector
ATTEN X
ATTEN Y
S9
S0
Connector
pin
number
5H L
5H L
A (3)
B (4)
A (3)
B (4)
(SCPI) [:ROUTe]:CLOSe:
(Legacy) A
<channel list>
+Vcc
+Vcc
Command result
(SCPI) [:ROUTe]:OPEn:
<channel list>
(Legacy) B
+Vcc
+Vcc
[a] Note:
LED lights on = attenuation applied (for attenuators)/switching path opened (for switches). LED lights off = no attenuation (for attenuators)/switching path closed.
Legends
H = Open (Low) L = Closed (High)
G = Connected to ground
70 Keysight 11713B/C Operating and Service Manual
Page 71
Keysight 11713B/C Attenuator/Switch Drivers Operating and Service Manual

7 Remote Interface Configurations

Connecting the 11713B/C to your Computer 72 Exploring the 11713B/C Web Interface over LAN 79
This chapter provides you information and steps to establish remote connections with the Keysight 11713B/C attenuator/switch drivers via GPIB, USB, and LAN. You will also be introduced to the 11713B/C web interface over LAN.
71
Page 72
7 Remote Interface Configurations
NOTE
NOTE
NOTE

Connecting the 11713B/C to your Computer

To easily connect the 11713B/C to your PC, configure and verify your connection, you can use the Keysight IO Libraries Suite, the E2094M Keysight IO Libraries for Windows, or and equivalent.
– Keysight IO Libraries Suite for Windows 98/2000/ME/XP.
– E2094M Keysight IO Libraries Suite for Windows 98/NT/2000/ME/ XP. You can find information
and install this application via the Web at www.keysight.com/find/iolib.
– You can also access other information about Keysight IO Libraries at
www.keysight.com/find/iolib.
The procedures in this section refer to the Keysight Technologies USB/LAN/ GPIB Interfaces Connectivity Guide. If you have installed the IO Libraries Suite,
you can access the Connectivity Guide via the Keysight IO Libraries Control icon. Or, you can access the Connectivity Guide via the Web at
www.keysight.com/find/connectivity.

Connecting over GPIB

1 Make sure you have installed the required I/O software on your computer.
2 Follow the instructions included with your GPIB interface card to install the GPIB hardware in
your computer.
3 Connect the GPIB cable (not provided) between the computer and the 11713B/C.
4 Make sure power is applied to your computer and verify that the operating system is fully
booted. Then apply power to 11713B/C.
5 Configure your GPIB hardware as instructed by the documentation provided by the hardware
vendor.
6 Use the Connection Expert utility of the Keysight IO Libraries Suite to add the 11713B/C and
verify a connection.
7 The 11713B/C is shipped from the factory with a default GPIB address of 28. To change the
address, refer to table below:
If you have installed any other I/O software, refer to the documentation included with that software.
72 Keysight 11713B/C Operating and Service Manual
Page 73
Step Action Illustration
NOTE
NOTE
a At IO SETUP screen, press GPIB
ADDR softkey.
b Current GPIB address is
displayed on screen (default
1 Changing GPIB
address (integer between 0 to 30)
address is 28).
c Use navigation keys to change
value.
d Press SAVE ADDR to save and
GPIB ADDR SAVED is displayed at the bottom of LCD.
e Press BACK soffkey to return to
IO SETUP.
Remote Interface Configurations 7
8 Now you can use various programming environments to control the 11713B/C. For an overview
on programming instruments via GPIB, refer to the Connectivity Guide.

Connecting over USB

The USB interface requires no front panel configuration.
1 After the I/O software is installed on your computer, connect a 11713B/C to your computer
using a Type Mini-B 5 pin USB cable.
2 Make sure power is applied to your computer and verify that the operating system is fully
booted. Then apply power to the 11713B/C.
3 The Found New Hardware Wizard will automatically start and guide you through configuring
the 11713B/C as a USB device. To install the software automatically, accept all defaults.
Before connecting the USB cable, make sure that I/O software is installed on your computer. See “Connecting the 11713B/C to your Computer” on page 72 for more information on installing the Keysight IO Libraries software.
If you have installed the Keysight I/O Libraries Software, this also installs the required low-level software drivers. Therefore you do not need to insert the CD when the Found New Hardware Wizard instructs you to do so.
Keysight 11713B/C Operating and Service Manual 73
Page 74
7 Remote Interface Configurations
NOTE
If you have installed any other I/O interface software, refer to the documentation included in that software.
4 Use the Connectivity Expert utility of the Keysight I/O Libraries Suite to verify that the 11713B/
C is displayed under the USB interface.
5 Now you can use various programming environments to control the 11713B/C. For an overview
on programming instructions via USB, refer to the Connectivity Guide.
74 Keysight 11713B/C Operating and Service Manual
Page 75

Connecting over LAN

The 11713B/C has two LAN operating modes:
–Auto mode
–Manual mode
Selecting the LAN network type
You can connect and configure your 11713B/C for site LAN or isolated (non-site) LAN operation.
–A Site LAN network is defined as a local area network (LAN) in which computers and
LAN-enabled instruments are connected to a site LAN (workgroup LAN, Intranet, or enterprise LAN) via optional routers, hubs, and/or switches.
–An Isolated LAN network is defined as a local area network (LAN) in which computers and
LAN-enabled instruments are not
Auto mode
This mode is used when you are connecting 11713B/C via site LAN. In auto mode, the IP Address, Subnet Mask, and Default Gateway values are obtained from the DHCP server or automatically assigned and the values cannot be configured from the front panel.
To prepare the 11713B/C for auto mode,
Remote Interface Configurations 7
connected to a site LAN.
Step Action Illustration
1 Ensure your
computer and 11713B/C are turned on and connected to LAN
2 Verify 11713B/
C LAN configuration is ready for auto mode
a Connect your computer and 11713B/C to LAN outlets using standard LAN cable. b Make sure power is applied to your computer and verify that the operating system is fully booted. c Apply power to 11713B/C and background LED color turns red, indicating standby mode. d Allow 11713B/C to warm up for 15 seconds, then press the ON button (LED turns from red to green).
a Press Menu/Enter button on the
front panel of 11713B/C.
b Select IO using navigation keys
and press Menu/Enter.
c At IO SETUP screen, press LAN
CONFIG softkey.
d At LAN CONFIGURATION screen,
ensure IP Configuration is AUTO.
e If needed, press Auto/Manual
softkey until AUTO is displayed and SAVE.
f Press BACK softkey to go back to
IO SETUP screen.
Keysight 11713B/C Operating and Service Manual 75
Page 76
7 Remote Interface Configurations
NOTE
Step Action Illustration
a At IO SETUP screen, press IP
ADDR softkey.
b At IP ADDRESS screen, select LAN
STAT softkey.
c Verify values CURRENT IP
3 Verify LAN
status on 11713B/C
ADDRESS, CURRENT SUBNET, and CURRENT GATEWAY are valid.
d Ensure LAN STATUS is NORMAL. e If LAN STATUS is FAULT, check
your LAN connection and then press Restart Netw softkey and wait.
f Press BACK softkey to go back to
IP ADDRESS screen.
Now you can use the 11713B/C Web Browser Interface to access and control the instrument. See
“Exploring the 11713B/C Web Interface over LAN” on page 79.
If you plan to program the instrument over LAN or use such programs, make sure you have installed the required I/O software on your computer.
Use the Connectivity Expert utility of the Keysight IO Libraries Suite to add the 11713B/C and verify a connection. When identifying the instrument, it is easiest if you use the IP address noted in step 3 above.
If you have installed any other I/O software, refer to the documentation included with that software.
Now you can use various programming environments to control the 11713B/C. For an overview on programming instructions via USB, refer to the Connectivity Guide.
Manual mode
In a manual mode, you must set up the IP Address, Subnet Mask, and Default Gateway that are compatible with your network infrastructure. If it is not correctly set up, the 11713B/C will not be visible on your network.
To prepare the 11713B/C for manual mode,
76 Keysight 11713B/C Operating and Service Manual
Page 77
Step Action Illustration
1 Ensure your
computer is connected to 11713B/C are turned on
2 Verify 11713B/
C LAN configuration is ready for manual mode
a Connect your computer to 11713B/C using CAT5 crossover cable. b Make sure power is applied to your computer and verify that the operating system is fully booted. c Apply power to 11713B/C and background LED color turns red, indicating standby mode. d Allow 11713B/C to warm up for 15 seconds, then press the ON button (LED turns from red to green).
a Press Menu/Enter button on the
front panel of 11713B/C.
b Select IO using navigation keys
and press Menu/Enter.
c At IO SETUP screen, press LAN
CONFIG softkey.
d At LAN CONFIGURATION screen,
ensure IP Configuration is Manual.
e If needed, press Auto/Manual
softkey until Manual is displayed and SAVE.
f Press BACK softkey to go back to
IO SETUP screen.
Remote Interface Configurations 7
3 Manually enter
IP ADDRESS, SUBNET, and GATEWAY
a At IO SETUP screen, press IP
ADDR softkey.
b At IP ADDRESS screen, select
MANUAL IP softkey.
c At MANUAL IP ADDRESS screen,
enter IP ADDRESS, SUBNET, and GATEWAY (scroll using NEXT ITEM
softkey).
d Then SAVE. e Press BACK softkey to go back to
IP ADDRESS screen.
Keysight 11713B/C Operating and Service Manual 77
Page 78
7 Remote Interface Configurations
NOTE
Step Action Illustration
a At IO SETUP screen, press IP
ADDR softkey.
b At IP ADDRESS screen, select LAN
STAT softkey.
c Verify values CURRENT IP
4 Verify LAN
status on 11713B/C
ADDRESS, CURRENT SUBNET, and CURRENT GATEWAY are valid.
d Ensure LAN STATUS is NORMAL. e If LAN STATUS is FAULT, check
your LAN connection and then press Restart Netw softkey and wait.
f Press BACK softkey to go back to
IP ADDRESS screen.
Now you can use the 11713B/C Web Browser Interface to access and control the instrument. See
“Exploring the 11713B/C Web Interface over LAN” on page 79.
If you plan to program the instrument over LAN or use such programs, make sure you have installed the required I/O software on your computer.
Use the Connectivity Expert utility of the Keysight IO Libraries Suite to add the 11713B/C and verify a connection. When identifying the instrument, it is easiest if you use the IP address noted in step 3 above.
If you have installed any other I/O software, refer to the documentation included with that software.
Now you can use various programming environments to control the 11713B/C. For an overview on programming instructions via USB, refer to the Connectivity Guide.
78 Keysight 11713B/C Operating and Service Manual
Page 79

Exploring the 11713B/C Web Interface over LAN

NOTE
NOTE
You can use the 11713B/C’s Web Browser Interface for remote access and control of the instrument via a Java™-enabled Web browser, such as Microsoft Internet Explorer. Using the Web Interface, you can configure, troubleshoot, and monitor your system remotely. This section provides an overview of the 11713B/C Web Interface.
The following tasks assume you have configured the 11713B/C for LAN communication and have verified connection to a LAN network. See
“Connecting over LAN” on page 75 for more information.

Launching the web interface

1 Open your Internet browser from your computer.
2 From the Tools > Internet Options menu, navigate to Connections (exact navigation depends
on your browser), and then select LAN Settings.
3 From the LAN Settings dialog, select/activate bypass proxy server for local addresses (exact
terminology depends on your browser).
4 Exit the Options window.
5 Enter the IP address of the 11713B/C in the Address field and press return. Use the 11713B/C’s
front panel utility menu to read the IP address.
Remote Interface Configurations 7
6 After entering the appropriate IP address, the 11713B/C Web Interface’s Welcome Window
should appear.
The procedure in this section will help you understand tasks commonly performed using the 11713B/C Web Interface. For additional help on using the interface, click the ? Help with the Page tab on the lower-left corner of the Web Interface window.
Figure 7-1 11713B/C Web Interface’s Welcome Window
Keysight 11713B/C Operating and Service Manual 79
Page 80
7 Remote Interface Configurations

Navigation bar

Displaying the browser web control page

1 From the Welcome Window, click the Browser Web Control tab on the left side of the window.
2 You will notice a pop-up window, requesting for password.
3 Enter password (default password is “keysight”) and click submit.
Welcome page Display various setting information
Browser Web Control Virtual front panel and sending/reading
SCPI commands
View & Modify Configuration Displays and modifies various setting information
Get Image Receives image
Print Display Calls the printing function of the browser
Help with this Page Displays the Help file
4 You can view the virtual front panel of the 11713B/C.
5 Now, you can control the switching devices remotely, similar to the front panel of the actual
instrument.
80 Keysight 11713B/C Operating and Service Manual
Page 81
Remote Interface Configurations 7
Figure 7-2 11713B/C Browser Web Control Interface
Keysight 11713B/C Operating and Service Manual 81
Page 82
7 Remote Interface Configurations
THIS PAGE HAS BEEN INTENTIONALLY LEFT BLANK.
82 Keysight 11713B/C Operating and Service Manual
Page 83
Keysight 11713B/C Attenuator/Switch Drivers Operating and Service Manual
8 Servicing the Attenuator/Switch
Driver
Preparing a Static-Safe Workstation 84 Maintenance and Adjustments 86
This chapter provides the procedures for removal and replacement of major assemblies in the 11713B/C and the list of replaceable parts.
83
Page 84
8 Servicing the Attenuator/Switch Driver

Preparing a Static-Safe Workstation

Electrostatic discharge (ESD) can damage or destroy electronic components. All works performed on assemblies consisting of electronic components should be done at a static-safe workstation.
An example of a static-safe workstation is shown below using two types of ESD protection:
– conductive table mat and wrist strap combination, and
– conductive floor mat and heel strap combination
The methods may be used together or separately. A list of static-safe accessories and their part numbers is given in the table below.
Keysight part number Description
Set includes:
9300-0797
9300-0865 Ground-wire, 4.6 m (15 ft)
9300-0980 Wrist-strap cord, 1.5 m (5 ft)
9300-1367
9300-1308 ESD heel-strap (reusable 6 to 12 months)
– 3M static control mat 0.6 m x 1.2 m (2 ft x 4 ft) – 4.6 m x (115 ft) ground wire The wrist-strap and wrist-strap cord are not included. They must be ordered separately.
Wrist-strap, color black, stainless steel, without cord, has four adjustable links, and a 7 mm post-type connection
The above can be ordered by contacting any Keysight Sales Office.
84 Keysight 11713B/C Operating and Service Manual
Page 85

Reducing ESD damage

To help reduce the amount of ESD damage that occurs during installation, testing, or servicing instruments, use the following guidelines:
– Be sure that all instruments are properly earth-grounded to prevent buildup of static charge.
– Personnel should be grounded with a resistor-isolated wrist-strap before touching the center
pin of any connector and before removing any assembly from the instrument.
– Before connecting any coaxial cable to an instrument connector for the first time each day,
momentarily ground the center and outer conductor of the table.
– Handle all PC board assemblies and electronic components only at static-safe workstations.
– Store or transport PC board assemblies and electronics components only in static-shielding
containers.
– PC board assembly edge-connector contacts may be cleaned by using a lint-free cloth with a
solution of 80% electronics-grade isopropyl alcohol and 20% deionized water. This should be performed at a static-safe workstation.
Servicing the Attenuator/Switch Driver 8
Keysight 11713B/C Operating and Service Manual 85
Page 86
8 Servicing the Attenuator/Switch Driver
NOTE

Maintenance and Adjustments

Fuse removal/replacement

User maintenance is limited to replacement of the rear panel fuse. The main ac line fuse is located on the rear panel in the line power module. Please ensure that the fuse is 250 V, T3.15 A.
Use the following procedure to replace fuse.
1 Remove the fuse holder using a tweezer.
2 You will see two fuses — the one on the left is the active fuse and the other is backup.
3 Remove fuse and replace with one of the correct rating and type for your selected input ac line
voltage.

Adjustment

The 11713B/C attenuator/switch driver has no internal electrical or mechanical adjustments.
Be sure to select the correct fuse rating for the selected line voltage. Do not use repaired fuses or short circuited fuse-holders. To do so could cause a shock or fire hazard.
86 Keysight 11713B/C Operating and Service Manual
Page 87
This information is subject to change without notice. Always refer to the Keysight website for the latest revision.
© Keysight Technologies 2007-2020 Edition 4, December 4, 2020
Printed in Malaysia
11713-90024
www.keysight.com
Loading...