Kewtech EZYPATPLUS, EZYPAT, SMARTPAT User Manual

EZYPAT / EZYPAT+ / SMARTPAT PORTABLE APPLIANCE TESTER
INSTRUCTION MANUAL
1
CONTENTS
2.1 Product summary .......................................................................................... 5
2.2 Test Function ................................................................................................. 5
2.3 Features ........................................................................................................ 5
2.4 Testers layout ................................................................................................ 6
2.4.1 Function Switches ...................................................................................... 6
2.4.2 LCD indications .......................................................................................... 8
2.4.3 Connector ................................................................................................. 10
2.5 Accessories ................................................................................................. 11
3.1 General specification, measuring range and accuracy ............................... 12
3.3 Threshold and display ................................................................................. 15
4.1 Visual inspection ......................................................................................... 17
4.2 Battery Voltage Check ................................................................................. 17
4.3 Setting ......................................................................................................... 17
4.3.1 Null setting ............................................................................................... 17
4.3.2 Voltage setting for insulation resistance measurement............................ 18
(How to change between 250V and 500V) ....................................................... 18
4.3.3 Criteria setting for CL I leakage current test ............................................ 18
5.1 Class I Test .................................................................................................. 20
5.3 Class ll Test ................................................................................................. 25
5.3 Extension Leads Test .................................................................................. 30
5.4 RCD TEST .................................................................................................. 33
8.1 Battery Replacement ................................................................................... 38
8.2 Fuse Replacement ...................................................................................... 39
2
1. Safe testing
Electricity is dangerous and can cause injury and death. Always treat it with the greatest of respect and care. If you are not quite sure how to proceed, then stop, take advice from a qualified person. This instruction manual contains warning and safety rules which must be observed by the user to ensure safe operation of the Tester and retain it in safe condition. Therefore, read through these operating instructions before using the Tester.
IMPORTANT:
The Tester must only be used by a competent and trained person and operated in strict accordance with these instructions.
KEWTECH will not accept liability for any damage or injury caused by misuse or
non-compliance with the instructions or with the safety procedures. It is essential to read and to understand the safety rules contained in these instructions and with the safety procedures. The symbol indicated on the Tester means that the user must refer to the related sections in the manual for safe operation of the Tester. Be sure to carefully read instructions following each symbol in this manual.
DANGER
● The Tester can be connected only to the commercial power of 100V – 253V, 50Hz.
For safety reasons, only use the Test Leads designed to be used with this Tester and recommended by KEWTECH.
Use only grounded mains outlets to supply the Tester.
Do not touch the device under test whilst testing is in progress.
DANGER : is reserved for conditions and actions that are likely to cause
serious or fatal injury.
WARNING: is reserved for conditions and actions that can cause serious or
fatal injury.
CAUTION : is reserved for conditions and actions that can cause injury or
instrument damage.
3
DANGER
Since a high voltage of 500V is being output continuously, when measuring insulation resistance, the user may get an electrical shock. Any capacitors in the appliance under test may become charged during testing and may contain hazardous voltages do not touch them.
When testing, always be sure to keep your fingers behind the safety protective finger guard on the test leads.
Disconnect the Tester from the power supply when measurement is finished.
Do not leave the Tester with connected to the power supply.
WARNING
Never open the instrument case – because dangerous voltages are present. Only fully trained and competent electrical engineers should open the case.
If abnormal conditions of any sort are noted (such as a faulty display, un­ expected readings, broken case, cracked test leads, etc.) do not use the Tester and return it to your distributor for inspection and repair.
Never attempt to use the Tester if the Tester or your hands are wet.
CAUTION
When using Test Leads with the crocodile clip, be sure to check the crocodile clip is firmly connected to the metal part of the device under test. Otherwise, inaccurate measurements or arcing at the contacts may occur.
The rated measuring voltage for the insulation test is 500V. DC. If this voltage seems too high for the appliance under test contact the appliance manufacturer for advice. The IEE Code of Practice allows for a touch current test where an insulation test cannot be carried out.
When testing a faulty appliance, it may trip the circuit breaker of main power supply during test and may cause interruption of service. Be careful when the same main power supply is used for PCs.
We are not liable for loss of data on PC during testing with The Tester. The appliance under test is powered on during most tests, but please turn it to the OFF position after testing.
Use a very slightly damp cloth for cleaning the Tester. Do not use abrasives or solvents.
4
Measurement Category
To ensure safe operation of measuring instruments, IEC 61010 establishes safety standards for various electrical environments, categorized as O to CAT IV, and called measurement categories. Higher-numbered categories correspond to electrical environments with greater momentary energy, so a measuring instrument designed for CAT III environments can endure greater momentary energy than one designed for CAT II.
O : Circuits which are not directly connected to the mains power supply. CAT II : Electrical circuits of equipment connected to an AC electrical outlet by a power cord. CAT III : Primary electrical circuits of the equipment connected directly to the distribution panel, and feeders from the distribution panel to outlets. CAT IV : The circuit from the service drop to the service entrance, and to the power meter and primary over-current protection device (distribution panel).
5
2. Product summary and explanation
2.1 Product summary
EZYPAT / EZYPAT+ / SMARTPAT (Tester) is a hand-held portable appliance tester and can test electrical safety of Class I and Class II appliances. The
Tester performs test and indicates PASS/ FAIL result complying with the criteria of judgement defined in The IEE Code of Practice for In-service
Inspection and Testing of Electrical Equipment: 2003. As a guide, the IEC standard defines these two categories as follows:
Class I : Appliances which have a functional insulation throughout and an earth connected case. These are often described as earthed appliances. Class II : Appliances which have both functional and additional insulation where any metal parts cannot become Live under fault conditions.
2.2 Test Function
Available functions vary depending on models.
Function
EZYPAT
EZYPAT+
SMARTPAT
C L 1
Protective conductor resistance test (Test current 200mA DC nominal)
C L 2
Insulation test (250V or 500V)
Substitute leakage current test
Run leakage current test
レ レ
Load current
レ レ
Extension Lead test
RCD Test
Remote function
2.3 Features
Check for whether the appliance is switched ON.  Selection for 250V or 500V on the insulation resistance test.  Null function for the protective conductor resistance test.  Auto-testing & PASS/ FAIL indication with backlight  Auto-power-off  Remote testing (SMARTPAT only)
6
2.4 Tester layout
2.4.1 Function Switches
Switch
Details
CLI switch
Short press: Starts CLI test. (Continuity test: 1 sec.) Long press: Starts CLI test. (Continuity test: 5 sec.)
CLII switch
Starts CLII test.
Extension switch
Short press: Starts Extension lead test. (Cont. test: 1 sec.) Long press: Starts Extension lead test. (Cont. test: 5 sec.)
NULL switch
Long press (at least 2 sec.): Performs NULL.
Connector
Display(LCD)
Keys
Connector
7
Switch
Details
Power switch
Short press: Works as ESC switch. Returns to the stand-by screen when a test is halted by “FAIL” result. Long press: Turns on/ off the Tester.
250V /500V
Short press: Switches output voltage for insulation resistance test between 250 V and 500 V. (Default setting: 250 V) Long press: Switches threshold current for CL I leakage current test between 0.75 mA and 3.5 mA. (Default setting: 0.75 mA)
Light switch
Short press: Turns on/ off LCD backlight. Long press: Enters into remote mode.
SMART PAT only
RCD switch
Switches to RCD stand-by screen. Another press on the stand-by screen starts RCD test. Long press on the screen switches test current between 10 mA and 30 mA. (Default setting: 30 mA)
8
2.4.2 LCD indications
<All symbols to be displayed on the LCD>
Display symbols
NULL value has been set.
Rated voltage for insulation resistance test
SUB: Substitute leakage current RUN: Leakage current test under actual working condition
Rated current for RCD test
Measurement in process
Switches are locked and Tester is in remote test mode. (The Tester is being controlled via a tablet device.)
Protective conductor resistance
Insulation resistance
Insulation resistance between L-N (Extension Lead Test)
Leakage current
Load current
Mains voltage
Polarity test result
Indicates items failed the test.
9
RCD test range
Prompts to check and turn on a DUT.
Incorrect connection
Indicates the resistance between L-L (N-N) is less than 10 Ω and polarity is correct.
Open circuit warning –resistance between L-L (N-N) is 10 Ω or higher at polarity test.
Crossed L-N polarity warning - resistance between L-N (N-L) is 10 Ω or lower at polarity test.
Short-circuited L-N warning – resistance between L-N
is 100 kΩ or lower at insulation test. (Extension Lead
Test)
Fault voltage of 50 V or higher is detected at RCD test.
Test result is “PASS”.
Test result is “FAIL”.
RCD tripped at fault current detection.
Indicates the measured protective conductor resistance is between 0.11 and 0.88 Ω.
10
2.4.3 Connector
(1)
Test socket
Insert the mains plug of DUT to this socket for the polarity test of protective conductor resistance, insulation resistance and leakage current test.
(2)
Terminal for mains lead
This terminal is connected to a mains supply via EZYMAIN.
(3)
PE-probe terminal
Connect the Test Lead with alligator clip to this terminal for the measurement of protective conductor resistance, and clip the metal parts of DUT with the alligator clip.
(4)
Terminal for Extension leads adaptor
It corresponds to L, N, E of test socket, and the extension leads adaptor connected with the cord reel to be plugged to it.
(1)
(3)
(4)
(2)
(3)
(4)
EZYPAT
EZYPAT+/SMARTPAT
11
2.5 Accessories
(1) Mains lead EZYMAIN (EZYPAT+/SMARTPAT) This mains lead can be connected to the mains supply so that the Tester supply power to the DUT.
(2) Test Lead with safety crocodile clip (MODEL7208) and Probe with Blade type Prod(MODEL7168). The probe and crocodile clip are interchangeable. Please use it according to a measurement use.
*1
Protective finger guard is a part providing protection against electrical shock and
ensuring the minimum required air and creepage distances.
(3) Extension leads adaptor EZYEXT This is for connecting the Tester and an extension lead (cord reel).
(4) Soft case EZYBAG (5) Six AA alkaline batteries (LR6) (6) Instruction manual
Crocodile Clip
Probe with Blade Type Prod
IEC Connector
Protective finger guard*1
Protective finger guard*1
12
3. Specification
3.1 General specification, measuring range and accuracy
Mains voltage indication: available on EZYPAT+ and SMARTPAT only
Display range
30 - 270 V
Hi/ Lo indication
< 30 V: No voltage indication > 270 V: 270 V
Resolution
1 V
Accuracy
±5 V
* Voltage between L-N of mains lead terminal is measured and displayed at voltage test.
Protective conductor resistance test
Measuring range
0.00 - 20.00 Ω (NULL value included.)*
Over-range indication
> 20.00 Ω
Resolution
0.01Ω
Open-circuit voltage
5 V ±0.4 V DC
Measuring current
200 mA DC (nominal value)
Accuracy
±3%rdg ±5dgt
* Resistances exceeding 3 Ω cannot be canceled by NULL function.
Insulation resistance test
Rated voltage
250V
500V
Measuring range
0.00 - 20.00
Over-range indication
> 20.00 MΩ Resolution
0.01
No-load voltage
250 V DC +20%, -0%
500 V DC +20,-0
Short-circuit current
1.5 mA DC or less
Rated current
1 -1.2 mA with a load of
0.25 MΩ
1 to 1.2 mA with a load
of 0.5 MΩ
Accuracy
±2%rdg±3dgt
13
Leakage current test under actual working condition: EZYPAT+ and SMARTPAT (Load current is also measured.)
Item
Load current
Leakage current
Mains voltage range
100 - 253 V/ 50 Hz
Measuring range
0.10 - 13.00 A rms
0.10 - 20.00 mA rms
Display range
0.00 - 13.00 A
0.00 - 20.00 mA
Over-range indication
> 13.00 A
> 20.00 mA
Resolution
0.01A
0.01mA
Accuracy
±10%rdg ±5dgt
±3%rdg ±5dgt
Max. rating
3 kVA max./ 15 sec. continuous
---
*If 100 V or higher voltage is being applied to, the Tester automatically performs leakage current test under actual working condition.
Substitute leakage current test
Measuring range
0.10 - 12.00 mA rms
Over-range indication
> 12.00 mA
Resolution
0.01mA
Open-circuit voltage/ Freq.
30 V ±5 V rms / 50 Hz ±5% Measuring current
1.2 mA AC ±0.5 mA (when measuring 12.00 mA )
Accuracy
±3%rdg±5dgt
Insulation test between L-N at Extension Lead Test
Open-circuit voltage
4.5 V ±0.5 V DC
Criteria of judgement
100 kΩ ±20 kΩ or less: LCD shows “<0.10 MΩ”
and the measurement is halted.
RCD test: available with SMARTPAT only Four tests with the pre-set rated current are performed in the following sequence: ×1(0°)→×1(180°)→×5(0°)→×5(180°).
Rated voltage
230 V - 15% to +10%/ 50Hz
Rated current
10 mA/ 30 mA
Function
×1
×5
Test duration
0.0 ms - 500.0 ms
0.0 ms - 40.0 ms
Energization
FS ±3%
Test current accuracy
2% - 8%
Operating time accuracy
±2 ms (40 ms) ±8 ms (>40 ms)
14
3.2 General specification
Reference conditions
Specifications are based on the following conditions, except where otherwise stated:­(1) Ambient temperature: 23±5˚C (2) Relative humidity: 45 - 75% (3) Attitude: Horizontal (4) AC power supply: 230 V, 50Hz
(EZYPAT+,SMARTPAT)
(5) Altitude: 2000m or less
Battery type
Six size AA alkaline batteries (LR6)
Operating temperature and humidity range
0ºC to +40ºC, relative humidity: 85% or less (no condensation)
Storage temperature and humidity range
-20ºC to +60ºC, relative humidity: 85% or less (no condensation)
Rate voltage and frequency (EZYPAT+, SMARTPAT)
Rated voltage: 230 V +10%, -15% Rated frequency: 50 Hz
Maximum load current at test socket (EZYPAT+, SMARTPAT)
3 kVA (15sec.)
Outer dimension and weight
Outer dimension: 261(L) × 104 (W) × 57(D)mm Weight (Tester body only):
EZYPAT: Approx. 860g EZYPAT+: Approx. 950g SMARTPAT:Approx. 970g
Auto power off
The Tester turns off automatically after 5 minutes.
Applicable standards:
Instrument operation
The IEE Code of Practice for In-service Inspection and Testing of Electrical Equipment
Safety
IEC/EN61010-1 CAT II 300V-instrument IEC/EN61010-2-030 IEC/EN61010-031 CAT III 600V (MODEL7208 / MODEL7168 )
EMC
EN61326-1, 2-2
Possible number of measure­ments where battery voltage is
Approx. 1400 times (CLI Rpe: 0 Ω, Rins: 1.1 MΩ)
15
within the effective range (measuring every 30 sec.)
Symbols used on the Tester:
CAT II
Electrical circuits of equipment connected to an AC electrical outlet by a power cord.
Double or reinforced insulation User must refer to the explanations in the instruction manual.
Earth
Crossed-out wheel bin symbol (according to WEEE Directive: 2002/96/EC) indicating that this electrical product may not be treated as household waste, but that it must be collected and treated separately.
3.3 Threshold and display
Function
Protective conductor resistance
Insulation resistance
Leakage current
Class l
RPE <
0.1Ω
(*1)
RINS > 1MΩ
ILEAK < 0.75mA or ILEAK < 3.75mA
Class ll
RINS > 2MΩ
ILEAK < 0.25mA
Extension Lead
RPE <
0.1Ω
(*1)
RINS > 1MΩ RCD
(*2)
RCD Type
×1
×5
Plug Top
200 ms or less
40 ms or less
Installation
300 ms or less
40 ms or less
(*1)
: Extension leads and appliances with long mains leads have a greater
resistance allowance for earth continuity. Please refer to the Table 1 on next page.
(*2)
: Plug Top type RCD-based judgement.
16
Table 1:
Summary of flexible table resistance rounded to two decimal places* *For flexible cables to BS 6500 or BS 6360
Nominal Conductor csa – should be marked on flexible cable (mm2)
Length (m)
Resistance (at 20°) (Ω)
Max. carrying current (A)
0.5 1
0.04
3 2
0.08
3
0.12
4
0.16
0.75
1
0.025
6
2
0.05
3
0.08
4
0.10
5
0.13
1.0
1
0.02
10
2
0.04
3
0.06
4
0.08
5
0.10
1.25
1
0.015
13
2
0.03
3
0.05
4
0.06
5
0.08
1.5
1
0.01
15
2
0.03
3
0.04
4
0.05
5
0.06
2.5
1
0.01
20
2
0.01
3
0.02
4
0.03
5
0.04
4
1
0.00
25
2
0.01
3
0.01
4
0.01
5
0.02
17
Note: Further information on protective conductor resistance and testing of portable appliances can be found in the Code of Practice for In-service Inspection and Testing of Electrical Equipment published by the IEE.
4. Preparation before a measurement
4.1 Visual inspection
Before starting a measurement, the user should undertake visual checks on the mains lead, case and that the correct type and rated fuse is fitted to the appliance under test. There should also be no evidence of damage of a nature that may impair the electrical safety of the appliance.
4.2 Battery Voltage Check
(1) Insert batteries with reference to 7. Battery/ Fuse Replacement in this manual. (2) Hold down Power switch 2 sec. to turn on the Tester. (3) Check the battery indicator displayed in the upper left corner of the LCD.
If just the last one segment of the indicator remains, the battery voltage is extremely low. Refer to 7. Battery/ Fuse Replacement and replace batteries to
perform further measurements. If an empty battery indicator is displayed, the battery voltage is lower than the working voltage limit. Replace batteries immediately to keep accurate measurement.
Battery recommendation: Use of alkaline battery is recommended. Use of other type of batteries may cause
improper indication of battery level.
4.3 Setting
4.3.1 Null setting
The IEE Code of Practice pass level for Protective conductor resistance is 0.1 Ω, which is a low value. So even the resistance of Test Leads will affect the measurement result.
The Tester can cancel the resistance of test lead by pressing NULL. The
procedure of Null setting is shown below. The Null function is held in memory even when the Tester is turned off, so theres no need to Null the lead resistance every time. However, when replacing fuses or test leads, it is recommended to do a Null setting again.
Note: Null setting is possible at both Class l Test and Extension Lead Test. However, only one Null value can be held in memory. For example, when the Null setting is carried out at Class l Test, the set value will also be used for Extension Lead Test (unless it is reset).
18
(1) Insert Test Lead with probe (MODEL7208) into the Earth terminal of the
Tester, and contact the tip of the Test Lead with the earth contacts of the
socket on the Tester. (2) Hold down NULL switch at least 2 sec. on any screen. (3) The screen switches to NULL screen, and NULL measurement starts. The
LCD shows blinking “MEAS” mark and measured value during a
measurement. The measured value is saved and subtracted from the
further measured values.
(4) If the measured value is less than 3 Ω, previous NULL value is cleared and
a new value is saved. When 3 Ω or higher is measured, previous NULL
value is just cleared (NULL mark disappears).
4.3.2 Voltage setting for insulation resistance measurement (How to change between 250V and 500V)
Two difference rated voltages, 250 V and 500 V, are available for insulation resistance test. Press 250V/500V switch on the stand-by screen or while measured result is being displayed at CL I/ CL II/ Extension lead test. Default setting is 250 V.
Sets to 250 V.
Sets to 500 V.
19
4.3.3 Criteria setting for CL I leakage current test
Either 0.75 mA or 3.5 mA can be set as threshold value for CL I leakage current test. Long press of 250V/500V switch on the stand-by screen or while measured result is being displayed at CL I/ CL II/ Extension lead test changes 0.75 mA and
3.5 mA. Default setting is 0.75 mA. The Code of Practice for In-service Inspection and Testing of Electrical Equipment specifies 0.75 mA for portable or hand-held type Class I equipment and Class I heating devices and 3.5 mA for the other Class I equipment.
Threshold setting:
0.75 mA
Blinking 3.50 mA is displayed (2 sec.), and then the screen returns to the stand-by screen. Now current of 3.5 mA is set.
20
5. Measuring method
5.1 Class I Test
The purpose of the test carried out for Class I appliances is to check the resistance of earth continuity from exposed metal parts and the plug is below a certain level and the insulation resistance between live and neutral connected together and earth is 1MΩ or more. The Tester provides two different measurement methods to measure leakage current flowing on the earth terminal or exposed metal parts of Class I appliance. One is “RUN leakage current” test with the Tester connected to an outlet, and another is “SUBSTITUTE leakage current (SUB leak current)” test without connecting the Tester to an outlet.
To perform Class I test, connect the mains plug of the appliance to the test socket (1) described in clause 2.4.3. Connector and the PE probe to terminal (3). To perform RUN leak test, connect Mains lead EZYMAIN to Main cord terminal (2). Use the following setups, depending upon the type of appliance.
While the Tester is supplied power via Mains lead EZYMAIN, RUN leak test is automatically performed. If the EZYMAIN cord is not connected and used, the Tester performs SUB leak test.
21
CL I Test Detail
1. Continuity test
Earth continuity test between the exposed metal parts and plug
2. Insulation test
Between LINE, NEUTRAL and EARTH.
3. Leakage current test
RUN Leak test: Connect Tester to outlet:
(Load current is also measured.)
SUB leak test: Not connect Tester to outlet
RUN leak test: Connect Tester to outlet SUB leak test: No need to connect Tester to outlet.
Power ON the DUT.
Press CLI switch for Class I test.
Connect to exposed metal parts but not rotating parts or heating elements.
22
CL I Test Flow
Press CLI to start a test. Short press: 1 sec of continuity test Long press: 5 sec of continuity test
Continuity test
DUT ON Check
0.11 - 0.88Ω = tAbL
Stand-by
Press to proceed to the next; continuity test is regarded as PASS.
Rpe>0.88Ω = FAIL
Rpe>0.11Ω =PASS
2. Insulation resistance test
1. Continuity test
DUT is ON.
DUT is OFF.
Voltage value is displayed while the Tester is connected to an outlet.
Press to halt a measurement in process.
Tester performs next test when CL I switch is pressed while a test is halted with “FAIL” indication.
DUT is powered on, or CL I is pressed.
Insulation resistance test
23
3. Leakage current test
Rins1MΩ = PASS
Rins1MΩ = FAIL
Mains voltage is 100 V or higher.
Mains voltage is less than 100 V.
SUB leakage test
ILEAK0.75mA (3.5mA) = PASS
ILEAK0.75mA (3.5mA) = FAIL
Check screen for RUN leakage test. Buzzer sounds and blue backlight blinks.
24
Note 1: The IEE Code of Practice states that the maximum resistance should be no greater than 0.1 Ohms + the resistance of the mains cable. Therefore, if the appliance has a long mains lead then the allowable resistance can be higher than the pre-programmed 0.1 Ω.
WARNING
When conducting a leakage test the appliance will automatically power on and will operate in its normal manner. It is imperative that the appliance is secured safely before the test is carried out. Extra care needs to taken with appliances which have heating elements and rotating parts. Firmly insert the plug of the appliance to the socket of the Tester. Plugs may get hot if Leakage current test is performed with improper connection. Do not connect/remove the plugs during Leakage current test. It may cause a reading error. Do not use the Tester on the device which has a power consumption of 3 kVA or more.
RUN Leak/ Load current test
ILEAK0.75mA (3.5mA) = PASS
ILEAK>0.75mA (3.5mA) = FAIL
25
CAUTION Where DUT ON Check function detects that DUT is off, blinking ”OFF? appears in the LCD and the test is stopped. Turn on the DUT; then the Tester automatically resumes the test. Depending on DUTs, even they are turned on, blinking ”OFF?” warning sometimes doesn’t disappear and the Tester cannot continue the test automatically. In such a case, press CL I switch to continue the test. Follow the procedure described in 4.3.1 and undertake the NULL setting
before a measurement. The crocodile clip must make good contact with the enclosure of the appliance. Do not touch the appliance under test whilst testing is in progress. Since a high voltage of 250V/500V will be present and the user may get an electrical shock. When the terminal is open or the resistance value exceeds the measuring range, “ > ” (over range display) appears on the LCD.
5.3 Class ll Test
The Class ll appliances have the indication of DOUBLE INSULATION or the symbol. Class II test is performed to confirm insulation resistance and leakage current of the appliance are within the allowable range specified in the related standard. The Tester provides two different measurement methods to measure leakage current flowing on exposed metal parts of Class ll appliance. One is “RUN leakage
current” test with the Tester connected to an outlet, and another is “SUBSTITUTE
leakage current (SUB leak current)” test without connecting the Tester to an outlet. To perform Class II test, connect the mains plug of the appliance to the test socket (1) described in clause 2.4.3. Connector and the PE probe to terminal (3). To perform RUN leak test, connect Mains lead EZYMAIN to Main cord terminal (2). Use the following setups, depending upon the type of appliance.
While the Tester is supplied power via Mains lead EZYMAIN, RUN leak test is automatically performed. If the EZYMAIN cord is not connected and used, the Tester performs SUB leak test.
26
1. Insulation
test
Between LINE, NEUTRAL and EARTH.
2. Leakage
current test
RUN Leak test: Connect Tester to outlet.
(Load current is also measured.)
SUB leak test: No need to connect Tester to outlet.
Connect to exposed metal parts but not rotating parts or heating elements.
Switch ON the power.
Press CLII switch to perform Class II test.
RUN leak test: Connect Tester to outlet
SUB leak test: No need to connect Tester to outlet.
27
CL II Test Flow
1. Insulation resistance test
Stand-by state
Connection Check
"CL I" is displayed if Rpe terminal is integrated in the power cord of DUT.
DUT is OFF.
DUT is ON.
DUT ON Check
Insulation resistance test
DUT is powered on, or CL2 is pressed.
Press to halt a measurement in process.
Tester performs next test when CL II switch is pressed while a test is halted with “FAIL” indication.
Voltage value is displayed while the Tester is connected to an outlet.
Press to proceed to the next; continuity test is regarded as PASS.
28
2. Leakage current test
Rins2 MΩ = PASS
Rins<2 MΩ = FAIL
Mains voltage is 100 V or higher.
Mains voltage is less than 100 V.
SUB Leakage test
ILEAK0.25mA = PASS
ILEAK0.25mA = FAIL
Check screen for RUN leakage test. Buzzer sounds and blue backlight blinks.
29
WARNING
When conducting a leakage test the appliance will automatically power on and will operate in its normal manner. It is imperative that the appliance is secured safely before the test is carried out. Extra care needs to taken with appliances which have heating elements and rotating parts. Firmly insert the plug of the appliance to the socket of the Tester. Plugs may get hot if Leakage current test is performed with improper connection. Do not connect/remove the plugs during Leakage current test. It may cause a reading error. Do not use the Tester on the device which has a power consumption of 3 kVA or more.
CAUTION
Where DUT ON Check function detects the DUT is off, blinking ”OFF? appears in the LCD and the test is stopped. Turn on the DUT; then the Tester automatically resumes the test. Depending on DUTs, even they are turned on, blinking ”OFF?” warning sometimes doesn’t disappear and the Tester cannot continue the test automatically. In such a case, press CL ll switch to continue the test. When the terminal is open or the resistance value exceeds the measuring range, “ > ” mark (over range display) appears on the LCD. Do not touch the appliance under test whilst testing is in progress. Since a high voltage of 250V or 500V will be present and the user may get an electrical shock.
RUN Leak/ Load current test
ILEAK0.25mA PASS
ILEAK0.25mA = FAIL
30
5.3 Extension Leads Test
This test is for extension leads, and checks for;
Protective conductor resistance between accessible conductive parts
and connection of protective earth.
Insulation resistance between L/N and PE. Polarity check of the Line and Neutral terminal of plug and socket.
1. Continuity
test
For PE terminal of Extension Leads
2. Insulation test
Between LINE, NEUTRAL and EARTH, and between LINE and NEUTRAL
3. Polarity
check
For LINE and NEUTRAL
Press the EXT switch to Extension Leads test.
31
Extension Lead test flow
2. Insulation resistance test
1. Continuity test
Stand-by
Press EXT to start a test. Short press: 1 sec of continuity test Long press: 5 sec of continuity test
Continuity test
0.11 - 0.88Ω= tAbL
Rpe>0.88Ω=FAIL
Rpe0.10Ω= PASS
Press to proceed to the next; continuity test is regarded as PASS.
Insulation resistance test between: (1) L&N - E, (2) L-N
L&N-E <1MΩ= FAIL
L&N-E1MΩ = PASS
L-N <0.1MΩ = FAIL
Press to halt a measurement in process.
Tester performs next test when EXT switch is pressed while a test is halted with “FAIL” indication.
32
Note: The IEE Code of Practice states that the maximum resistance should be no greater than 0.1 Ohms + the resistance of the mains cable. Therefore, if the appliance has a long mains lead then the allowable resistance can be higher than the pre-programmed 0.1Ω.
CAUTION
Follow the procedure described in 4.3.1 and do Null setting before a
measurement, but use the short EZYEXT lead instead of the MODEL7208 test lead, by plugging the EZYEXT into the Extension Lead Adaptor terminal and the UK socket on the front of the unit.
When the terminal is open or the resistance value exceeds the measuring
range, “ > ” (over range display) appears on the LCD.
Do not touch the device under test whilst testing is in progress. Since a high
voltage of 250V or 500V will be present, the user may get an electrical shock.
3. Polarity check
Polarity check
Polarity of L and N is correct. (Pass)
Polarity of L and N is reversed. (Cross)
Break in L or N (Open)
33
5.4 RCD TEST
(1) PRCD test This test is to test and confirm a PRCD (Portable Residual Current Device) trips within the rated time by applying specified current. The Tester incorporates a circuit to test PRCD with Rated Tripping Current (IΔn) of 10 mA or 30 mA. PRCD trip time is measured in sequence: ×1(0°)→×1(180°)→×5(0°)→×5(180°). After each test, reset the tripped PRCD to proceed to the next test. PASS result is given where the PRCD tripped within the rated time through all the tests.
TEST
RESET
PRCD
Press the RCD switch to perform RCD test.
34
RCD Test Flow
30mA
10mA
Stand-by
Long press switches IΔn: 10 mA and 30 mA
RCD test stand-by screen
×1(0°) test
×1( 0°) test result
Reset the tripped RCD.
Press to halt a measurement in process.
35
×1(180°) test
×1( 180°) test result
Reset the tripped RCD.
×5(0°) test
×5( 0°) test result
Reset the tripped RCD.
×5(180°) test
Test results are all "PASS":
If any one of test results is "FAIL": "FAIL" is displayed.
"PASS" is displayed.
36
Check the connection if symbol is displayed in the LCD. Connection may be incorrect and a test doesn’t start even RCD switch is pressed.
If " IΔn" setting is greater than the rated residual current of the RCD, the RCD
will trip and "no" may be displayed on LCD.
Special conditions of RCDs of a particular design, for example S- type, should
be taken into consideration. (2) PRCD test via socket outlet
Make connection as the following illustration indicates when testing a PRCD connected to a socket outlet. For this test, use EZYEXT for connection.
● If a fault voltage exceeds 50 V while applying a test current to test a built-in type RCD, the LCD shows “Uf. Hi” and the test is halted.
If a voltage exists between the protective conductor and earth, it may influence
the measurements.
If a voltage exists between neutral and earth, it may influence the
measurements, therefore, the connection between neutral point of the distribution system and earth should be checked before testing.
The potential fields of other earthing installations may influence the
measurement.
The earth electrode resistance of a measuring circuit with a probe shall not
exceed table1.
Equipment following the RCD, e.g. capacitors or rotating machinery, may cause
a significant lengthening of the measured trip time.
EZYEXT
Press the RCD switch to perform RCD test.
PRCD
37
6. Remote testing (SMART PAT)
SMARTPAT incorporates Wi-Fi communication function. Tablet devices that has a special application “SimplyPats” can remotely control SMARTPAT.
The special application “SimplyPats” can be downloaded from the internet site. (Internet access is required and charges may be incurred.) For further detail, please refer to Help for “SimplyPats”.
Remote settings: To use the remote-control function of SMARTPAT, enable Wi-Fi function and remote mode. Hold down the backlight switch at least 2 sec. to get the Tester into remote mode. The symbol appears to indicate the remote mode is enabled. Hold down the backlight switch 2 sec. or longer to disable the remote mode.
● Wi-Fi interface (1) Wireless protocol: IEEE802.11b/g/n (2) Frequency: 2.4 – 2.495 GHz
Appears in remote mode.
38
7. Backlight
Press the backlight switch to turn on the backlight. Press the switch again to turn off the backlight. The backlight automatically turns off if there is no activity for about 2 min.
8. Battery / Fuse replacement
DANGER
Never open the Battery cover during a measurement. Dispose the used batteries according to the rules, which is defined by each community.
WARNING
To avoid possible electric shock, remove test leads before opening the battery cover. After replacing batteries, be sure to tighten up the screws for battery cover.
CAUTION
Do not mix new and old batteries. Install batteries in correct polarity as marked inside the battery compartment.
8.1 Battery Replacement
(1) Disconnect the test probe from the Tester. (2) Open the battery cover by unscrewing the metal captive screw to reveal battery compartment. (3) Always replace all six batteries with new ones at the same time. Six size AA alkaline batteries (LR6)” (4) Screw the battery cover back on before using the Tester.
39
8.2 Fuse Replacement
(1) Disconnect the test probe from the Tester. (2) Unscrew the metal captive and open the battery compartment cover to
replace the fuse. Fuse type: 10A/250V(F) Fast acting type ceramic fuse Φ 5 x 20mm.
(3) Screw the battery cover back on
before using the Tester.
9. Maintenance
Use a very slightly damp cloth for cleaning the Tester. Do not use abrasives or solvents.
- + - + -
+
FUSE