22. Case and strap assembly ............................................................................................. 66
The KT66DL incorporates Anti Trip Technology (ATT) which electronically bypasses RCDs
when performing loop impedance tests. This saves time and money by not having to take
the RCD out of the circuit during testing and is a safer procedure to follow. With the ATT
function enabled, a test of 15mA or less is applied between line & earth. It enables loop
impedance measurements without tripping RCDs rated at 30mA and above.
ATT supports measurements using three wires: Line, Earth, and Neutral and also two
wires: Line and Earth.
Please read this instruction manual carefully before using this tester.
1. Safe testing
This tester has been designed, manufactured and tested according to IEC 61010:
Safety requirements for electrical equipment for measurement, and delivered in the
best condition after passing quality control tests. This instruction manual contains
warnings and safety rules which must be observed by the user to ensure safe operation
of the tester and to maintain it in safe condition. Therefore, read through these
operating instructions before starting to use the tester.
DANGER
● Read through and understand instructions contained in this manual before starting to
use the tester.
● Keep the manual at hand to enable quick reference whenever necessary.
● The tester is to be used only for its intended applications.
● Understand and follow all the safety instructions contained in the manual.
It is essential that the above instructions are adhered to. Failure to follow the above
instructions may cause injury, tester damage and/or damage to equipment under test.
Kewtech is by no means liable for any damage resulting from the tester in
contradiction to these cautionary notes.
The symbol indicated on the tester means that the user must refer to the related
parts in the manual for safe operation of the tester. It is essential to read the instructions
wherever the symbol appears in the manual.
DANGER : is reserved for conditions and actions that are likely to cause serious
or fatal injury.
WARNING : is reserved for conditions and actions that can cause serious or fatal injury.
CAUTION : is reserved for conditions and actions that can cause injury or
tester damage.
DANGER
● Do not apply voltages above 600V, including voltage to earth across the terminals of
this tester.
● The KT66DL is rated to CAT IV 300V/ CAT III 600V. Do not make measurements
under the circumstances exceeding the designed measurement categories.
● For safety reasons, only use accessories (test leads, probes, fuses, cases, etc)
designed to be used with this instrument and recommended by KEWTECH
●Do not attempt to make measurements in the presence of flammable gasses;
otherwise, the use of the tester may cause sparking, which can lead to an explosion.
● Never attempt to use the tester if its surface or your hand is wet.
● Be careful not to short-circuit a power line with the metal part of the test lead during a
measurement. It may cause personal injury.
● Never open the battery compartment cover during a measurement.
● The tester should be used only in its intended applications and conditions; otherwise,
safety functions equipped with the tester will not work, and tester damage or serious
personal injury may be caused.
● Verify proper operation on a known source before use or take actions as a result of the
indication of the tester eg: use KEWPROVE3 proving unit.
1
WARNING
● Do not use the tester or test leads if any abnormal conditions, such as broken cover or
exposed metal parts are noted.
● First, firmly connect the test leads to the tester, and then press the test switch.
● Never install substitute parts or make any modifications to the tester. Send the tester to
your local Kewtech for repair or recalibration.
● Do not try to replace batteries if the surface of the tester is wet.
● Connect each test lead firmly into the corresponding terminals.
● Stop using the test lead if the outer jacket is damaged and the inner metal or color
jacket is exposed.
● Before opening the battery compartment cover for battery or fuse replacement, ensure
that no test leads are connected to the tester and the tester is off.
● Never turn the rotary switch while the test leads are connected to the equipment under
test.
CAUTION
● Always make sure to set the rotary switch to the appropriate position before making a
measurement.
● Power off the tester after use. Remove batteries if the tester is to be stored for a long
period.
● Do not expose the tester to direct sunlight, high temperature, humidity or dew.
● Use a slightly damp cloth with neutral detergent for cleaning. Do not use abrasives or
solvents.
● This tester is not water-proof. Do not let the tester get wet. Otherwise, it may cause
malfunction.
● If the tester is wet, make sure to let it dry before putting it into storage.
● Keep your hand and fingers behind the protective finger guards during a measurement.
● Example of testing parameters are given for demonstrating principles and are from the
International Standard IEC60364 at the time of printing. Local standards are derived
from these. In the UK they are the IET Wiring regulation (BS7671). Please ensure that
you are complying to the correct local standards.
2
2.
Tester
layout
(1)
(2)
(3)
(4)
Item Description
(1) Test switch Starts measurements. (Press and rotate
(2) Touch pad Checks the electrical potential at the PE
(3) Power switch A long press turns on/ off the tester.
(4) Function switch Function setting (F1 ~ F4)
(5) Display (LCD) Color LCD
(6) Rotary switch Selects measurement functions.
(7) MEM switch Saves measured value.
(8) ENTER switch Confirms changes or selections.
Fig. 2-1
for lock down feature.)
terminal
(A short press works as an ESC switch to
return to the previous screen.)
(1) Earth Tests Lead (ACCESKIT) and Auxiliary Earth Spikes
Red H(C) 20m
Yellow S(P)10m
Green E 5m
Fig. 3-5
(2) PAT ADAPTER1
Fig. 3-6
6
4. Features
The KT66DL Multi-function tester has eight test functions in one tester.
1 Continuity test
2 Insulation resistance test
3 Loop impedance test (High current measurement, No trip (ATT) measurement)
4 Prospective short circuit current test (
5 RCD test
6 Voltage test
7 Phase rotation test
8 Earth test
Continuity function has the following features:
Fuse Protection Continuity Function has a fuse protection function to prevent a
fuse blowing when coming into contact with a live circuit. With
this function, a fuse rarely blows while measuring continuity and
touching live circuits.
Continuity Null Allows automatic subtraction of test lead resistance from
continuity measurements.
15mA test Not only 200mA but also 15mA is available.
Continuity 2Ω Buzzer Buzzer sounds at 2Ω or less at Continuity function.
(Switchable on or off)
Insulation function has the following features:
Auto-discharge Electric charges stored in capacitive circuits are discharged
automatically after testing by releasing the test switch.
SPD(VARISTOR) test Breakdown voltage measurement for surge protective device
(varistor)
Loop impedance functions have the following features:
ATT test Enables loop impedance tests without tripping RCDs rated at 30mA
or higher. (applicable to 3 or 2-wire measurements)
LOOP 0.001Ω test High resolution measurement, 0.001Ω, at a test current of 25A
On Loop impedance function
)
7
RCD testing functions have the following features:
Gives an alert, when touching the Touch Pad, while the PE terminal
RCD Type B test Capable of testing Type B RCDs of dc residual current.
VAR(variable test
current):
RCD AUTO TEST Auto-test in the following sequence:
* If a reading is unstable, one upper range digit might be used instead of the display range
to be used.
* For LOOP 3W EV Normal I, ±2dgt is added to the accuracy listed in above table.
For Low I, errors may be larger as it will be more susceptible to noise.
LOOP 20.00/200.0/2000Ω (auto-ranging)
PFC/PSC
LOOP
PFC/PSC
LOOP 0 – 2000Ω0 – 2000Ω
LOOP
PFC/PSC
Test current
@230V
100 – 260V 50/60Hz
(L-N < 20Ω)
2000A/20kA 2000A/20kA(PFC only)
0.00 – 20.99Ω
21.0 – 209.9Ω
210 – 2099Ω
0 – 2099A
2.10 – 20.99kA
230V+10%-15%:±(3%rdg+6dgt)
Other than above voltages:
±(3%rdg+8dgt)
Depending on the accuracies of voltage and LOOP
measurements
L-N:6A/60ms
N-PE:10mA (5.3Hz)
EV mode
Normal I N-PE:6mA (5.3Hz)
Low I N-PE:4mA (5.3Hz)
48 – 260V 50/60Hz
2.10 – 20.99kA
230V+10%-15%:±(3%rdg+10dgt)
Other than above voltages:
0.00 –20.99Ω
21.0 –209.9Ω
210 –2099Ω
0 – 2099A
(PFC only)
±(3%rdg+15dgt)
L-PE: 15mA
11
LOOP HIGH
(Guaranteed
Function L-PE0.01ΩRes L-PE
Mains input
voltage range
LOOP 20.00/200.0/2000Ω2.000Ω20.00Ω
Range
Display
range
Measuring
range
accuracy
range)
Accuracy
Test current
* If a reading is unstable, one upper range digit might be used instead of the display range
to be used.
PFC/PSC
LOOP
PFC/PSC
LOOP 0 – 2000Ω0 – 2Ω0 – 20Ω
LOOP
PFC/PSC
@230V
48 - 260V 50/60Hz 100 - 260V 50/60Hz
2000A/20kA
(PFC only)
0.00 - 20.99Ω
21.0 - 209.9Ω
210 –2099Ω
0 - 2099A
2.10 - 20.99kA
(PFC only)
230V+10%-15%:
±(3%rdg+4dgt)
100V or less:
±(5%rdg+15dgt)
Other than above voltages
±(3%rdg+8dgt)
Depending on the accuracies of voltage and LOOP
20Ω: 6A/20ms
200Ω: 0.5A/20ms
2000Ω: 15mA/500ms
:
0.001ΩRes
2000A/50kA
(PFC only)
0.000 - 2.099Ω0.00-20.99Ω
0 - 2099A
2.10 - 52.49kA
(PFC only)
230V+10%-15%:
±(3%rdg+25mΩ)
Other than above
voltages
±(5%rdg+35mΩ)
measurements
25A/20ms 6A/20ms
L-N/L-L
2000A/20kA
2.10 - 20.99kA
230V+10%-15%:
±(3%rdg+4dgt)
100V or less:
±(5%rdg+15dgt)
:
Other than above
±(3%rdg+8dgt)
48 - 500V
50/60Hz
(PSC only)
0 - 2099A
(PSC only)
voltages
:
12
RCD
G
100%
)
(1) Mains input voltage range: 100V – 260V 50/ 60Hz
For Type AC and A RCDs rated at 100mA or higher: 190 – 260V
(2) Accuracy
The test of “X5” will be skipped when a current is 100mA or higher.
At the auto-test for Type EV, additional 6 mA DC test is performed.
Current waveform
・
Type AC: Test current is sine wave.
・
Type A and F: Test current is half sine wave.
・
Type B and EV: Direct current
13
(3) Uc (RCD)
Mains input voltage range 100-260V
Range 100V
Display range 0.0 - 104.9V
Measuring range
(Guaranteed accuracy range)
Accuracy +5% to+15%rdg±8dgt @230V
Test current 50 % or less of IΔn
Possible number of tests with fresh batteries.
CONTINUITY : Approx. 2000 times min. at load 1Ω
INSULATION RESISTANCE : Approx. 1500 times min. at load 1M
LOOP : Approx. 3000 times min. (ATT L-PE 3W)
RCD : Approx. 3500 times min. (G-AC
EARTH : Approx. 3000 times min. at load 10Ω
VOLTS/PHASE ROTATION : Approx. 40h
5.2 General specification
Reference conditions
Tester dimensions 235 X 136 X 114mm
Tester weight 1350g (including batteries.)
Battery type Size AA Alkaline battery (LR6) x 8
Operating temperature
and humidity.
Storage temperature
and humidity
Display Color Dot Matrix LCD 320(W) X 240(H) pixels.
Overload protection The continuity test circuit is protected by a 0.5A/600V fast
Specifications are based on the following conditions except
where otherwise stated:-
1. Ambient temperature: 23±5°C:
2. Relative humidity: 45% to 75%
3. Nominal voltage of distribution system (Un) :
4. Altitude: Less than 2000m
-10 to +50°C, relative humidity 80% or less, no condensation
-20 to +60oC, relative humidity 75% or less, no condensation.
acting (HRC) ceramic fuse mounted in the battery
compartment, where a spare fuse is also stored.
The insulation resistance test circuit is protected by a resistor
against 1000V AC for 10 seconds.
0 - 100V
Ω (1000V)
X1 30mA)
230V/400V, 50Hz/60Hz
14
5.3 Applied standards
Tester operating
Standard
Safety standard
Protection degree IEC 60529 IP40
EMC EN 61326-2-2
This manual and product may use the following symbols adopted from International Safety
Standards;
CAT II Measurement category “CAT II” applies to;
Electrical circuits of equipment connected to an AC electrical outlet by a
power cord.
CAT III Measurement category “CAT III” applies to;
Primary electrical circuits of the equipment connected directly to the
distribution panel, and feeders from the distribution panel to outlets.
CAT IV Measurement category “CAT IV” applies to;
The circuit from the service drop to the service entrance, and to the power
meter and primary overcurrent protection device (distribution panel).
To ensure safe operation of measuring testers, IEC 61010 establishes safety standards for
various electrical environments, categorized as O to CAT IV, and called measurement
categories. Higher-numbered categories correspond to electrical environments with
greater momentary energy, so a measuring tester designed for CAT III environments can
endure greater momentary energy than one designed for CAT II.
O (None, other): Circuits which are not directly connected to the mains power supply.
CAT II : Electrical circuits of equipment connected to an AC electrical outlet by a power
CAT III : Primary electrical circuits of the equipment connected directly to the
Equipment protected throughout by DOUBLE INSULATION or
REINFORCED INSULATION;
Caution (refer to accompanying documents)
Caution, risk of electric shock
Protection against wrong connection is up to 600V
Earth Ground
Complies with WEEE Directive (2002/ 96/ EC) marking requirements. (valid
in each EU country)
cord.
distribution panel, and feeders from the distribution panel to outlets.
* When test leads, sometimes with metal tips, are connected
and used with the tester, the measurement category and
voltage rating of the lowest rated item is applied.
15
CAT IV : The circuit from the service drop to the service entrance, and to the power
meter and primary overcurrent protection device (distribution panel).
5.4 Operating uncertainty
Continuity (EN61557-4)
Operating range compliant with EN61557-4
operating uncertainty
0.20 to 2000Ω±30%
The influencing variations used for calculating the operating error are denoted as follows;
Temperature: 0oC and 35oC
Supply voltage: 8V to 13.8V
Insulation Resistance (EN61557-2)
Volt
100V 0.100 to 200.0MΩ
250V 0.250 to 200.0MΩ
500V 0.50 to 1000MΩ
1000V 1.00 to 2000MΩ
The influencing variations used for calculating the operating error are denoted as follows;
Temperature: 0oC and 35oC
Supply voltage: 8V to 13.8V
Operating range compliant with
EN61557-2 operating uncertainty
Maximum percentage operating
uncertainty
Maximum percentage
operating uncertainty
±30%
16
Loop Impedance (EN61557-3)
Operating range compliant
Function
L-PE 0.01Ω Res 0.40 to 2000Ω
HIGH
ATT
The influencing variations used for calculating the operating error are denoted as follows;
RCD (EN61557-6)
The influencing variations used for calculating the operating error are denoted as follows.
Earth Resistance (EN61557-5)
Operating range compliant with EN61557-5
The influencing variations used for calculating the operating error are denoted as follows;
・
Temperature : 0 °C and 35 °C
・
Series interference voltage : 16·2/3Hz, 50Hz, 60Hz, DC:10V
・
Resistance of the probes and auxiliary earth electrode resistance: 100 x RA, 50 kΩ or less
・
Supply voltage : 8V to 13.8V
L-PE 0.001Ω Res 0.400 to 2.000Ω
L-N/L-L 0.40 to 20.00Ω
2Wire 1.00 to 2000Ω
3Wire (Except for EV) 0.40 to 2000Ω
Temperature: 0 °C and 35 °C
Phase angle: At a phase angle 0° to 30°
System frequency: 49.5Hz to 50.5Hz
System voltage: 230V+10%-15%
Supply voltage: 8V to 13.8V
Harmonics: 5% of 3rd harmonic at 0° phase angle
6% of 5th harmonic at 180° phase angle
5% of 7th harmonic at 0° phase angle
DC quantity: 0.5% of the nominal voltage
Function Operating uncertainty of trip current
X1/2 -10% to 0%
X1, X5 0% to +10%
Ramp -10% to +10%
・
Temperature : 0oC and 35oC
・
Earth electrode Resistance (shall not exceed below) :
IΔn Type AC Type A/F Type B Type EV
6mA - - - 400Ω
10mA 400Ω200Ω40Ω30mA 100Ω40Ω10Ω-
100mA 40Ω20Ω10Ω300mA 40Ω20Ω2Ω500mA 40Ω20Ω- -
1000mA 20Ω- - -
・
System voltage: 230V+10%-15%
・
Supply voltage : 8V to 13.8V
operating uncertainty
5.00 to 2000Ω±30%
400Hz: 3V
with EN61557-3 operating
uncertainty
Maximum percentage operating
Maximum percentage
operating uncertainty
±30%
uncertainty
17
5.5 Symbols and marks displayed on the LCD
Battery level indicator
Temperature monitor for internal resistance, applicable to the Loop, RCD function. Further measurements are suspended until
the “
” symbol disappears.
Measurements in progress
Live circuit warning
PE Hi V Caution: Presence of 100V or more at PE terminal, appears
when touching the Touch Pad
L-N >20ΩAlert: Presence of 20Ω or more between Line - Neutral at ATT
measurement
Caution: Presence of noise in the circuit under test during ATT
measurement.
N - PE Hi V Caution: Presence of high voltage between NEUTRAL - EARTH
during LOOP ATT measurement.
Uc > UL Caution: Uc at RCD test is exceeding the preset UL value (25 or
50V).
no Error message: When on the RCD function, RCD tripped before
measuring RCD trip time. Selected IΔn value may not be correct.
When on the LOOP, PSC/PFC function, supply may have been
interrupted.
Wiring check for LOOP, RCD function
Judged result of each test
:
RH Hi, Rs Hi Appears when a Probe resistance of H terminal (RH) or of S
No 3-phase system Appears to indicate wrong connection at Phase Rotation check.
N-PE Hi Ω For RCD Type B and EV, appears to indicate too high resistance
Satisfied the reference value, : Unsatisfied.
: Unjudgeable: Measured result exceeds the measuring range,
and the upper limit of the measuring range is smaller than the
reference value.
Appears when setting PAT for Continuity/Insulation function and
limit value for LOOP measurement.
terminal (RS) at Earth measurement is exceeded the measurable
range.
exists between N-PE to apply test current.
(Continuity / Insulation / Earth Function)
18
6. Setup mode
TIME A
djusts day
, month, year,
minute
and
hour.
LCD Contrast
Up or Down
L
CD Backlight
Up or Down
UL value
25V or 50V
Touch Pad
ON or OFF
Enter in the SETUP mode to change settings of the tester. The following settings are
changeable.
(4) UL value .............Selects a UL value for RCD function
(5) Touch Pad ..........Enables / disables Touch Pad function
Setting method:
(1)
Press F4 “SETUP” while the start-up screen is displayed (approx. 2 sec.) after turning
on the tester.
(2)
SETUP screen appears. (See Fig. 6-2.)
The screen also can be referenced in the HELP menu: press F4 while the LCD is
showing wiring configuration diagram.
(3) Press ▲(F1) or ▼(F2) switch for item selection and confirm the selection with ENTER
switch.
(4) Press ▲(F1) or ▼(F2) switch and change settings. The changeable settings are as
follows.
Fig. 6-1
Press F4.
Item Setting
Selected item
is highlighted
in white.
Fig. 6-2
(5) Press ENTER when settings are done. Then the screen returns to the SETUP MENU
screen as Fig. 6-2. Press ESC to cancel the changes.
(6) Pressing ESC on SETUP MENU screen (Fig. 6-2) gets the tester in stand-by mode.
19
7. Getting started
7.1 Attaching probes / croc clips to test leads
(1) For ACC065 test leads
Either of the following adapters can be attached to.
1. Alligator clip
2. Test probe
Alligator clip
To avoid getting electrical shocks, disconnect the test leads from the tester before
replacing the metal tip or adapter.
Test probe
Fig 7-1
Bananaplugs, both ends
DANGER
20
7.2 Battery voltage check
(1) Please refer to Section 20. “Battery and fuse replacement” in this manual and insert
batteries in to the tester.
(2) Press the Power switch to turn on the tester.
(3) Check the battery status indicator displayed at the upper right corner of the LCD.
””: Normal. Battery voltage is enough.
””: Low battery voltage: For continuous measurement, please refer to
Section 20. “Battery and fuse replacement” and replace the batteries with new ones.“”: Battery voltage is below the lower limit of the operating voltage. In such a condition, accuracy of the measured result isn’t guaranteed. Replace
batteries with new ones immediately.
●Battery status indicator might change from ”” to ”” during a measurement
depending on measured objects; for example, resistance of the object is low.
7.3 Clock adjustment
The KT66DL has clock function. Time is displayed
in the upper right corner of the LCD.
Time display format: Day/ Month/ Year / Hour: Min
Enter the SETUP mode to adjust clock. Press ENTER
when clock adjustment is done.
See Section 6. “Setup mode” for further detail of
“SETUP” mode.
(1) On the clock adjustment screen (Fig. 7-3), select
the parameter (day/ month/ year/ hour/ min) to be
adjusted with ◀(F3) or ▶(F4) switch.
(2) Use ▲(F1) or ▼(F2) switch to alter the value of
the selected parameter and press ENTER to
confirm. (Pressing ESC switch during the
adjustment can one step back.)
Note:
Clock setting will be cleared if the tester does have batteries installed for 10 min. or longer.
When battery replacement is required, be careful not to exceed this period. If the clock
setting is cleared and restored to the default, please do the setting again.
Fig. 7-2
Fig. 7-3 Clock adjustment
Clock
21
7.4 Help function
With this function, correct connection for each test can be displayed on the LCD.
To check a connection diagram;
(1) Hold down HELP (ENTER) switch 1 sec.
(2) Then the LCD shows a connection diagram.
(3) When several connections are available, press F1 switch to toggle the diagrams.
(4) Press ESC to close the currently displayed connection diagram screen.
● The SETUP screen for making each setting will appear by pressing F4 (SETUP) switch
while the LCD is showing a connection diagram.
Fig. 7-4 Connection diagram example
22
8. Continuity (resistance) tests
DANGER
Do not apply voltage to the continuity function. Always check the circuit or equipment
under test is surely de-energized before starting a measurement.
8.1 Test procedure
The object of continuity testing is to measure only the resistance of the parts of the wiring
system under test. This measurement should not include the resistance of any test leads
used. The resistance of the test leads needs to be subtracted from any continuity
measurement. The KT66DL is provided with a continuity null feature which allows automatic
compensation for any test lead resistance.
You should only use the test leads supplied with the tester.
LCD display and function switches
Measured value
Proceed as follows:
(1) Select the continuity test by turning the rotary switch.
(2) Insert the test leads to the L and PE terminals on the KT66DL respectively
as shown in Fig 8-2.
Brown
(3) Connect the ends of the test leads firmly together (see Fig. 8-3) and press and lock
down the test switch. The value of the lead resistance will be displayed. The “ ”
symbol is displayed to the left of the reading during a measurement.
Green
Fig. 8-1
L terminal
Brown test lead, or
ACC064SPN Remote Test Lead
PE terminal
Green test lead
Fig. 8-2
F1 Switches on / off NULL
F2 Switches on / off 2Ω buzzer
F3 Pat mode setting
F4 Test current setting
function
(OFF, 0.1Ω, 0.3Ω,0.5Ω)
200mA or 15mA
23
(4) Press the F1(NULL) switch, this will null out the lead resistance and the indicated
reading should go to zero.
(5) Release the test switch. Then press the test switch again and ensure the display reads
zero before
proceeding. While using the Continuity null function, “NULL ON” is displayed on the LCD
as indicated in Fig.8-3.
●The null value will be stored even if the tester is powered off.
●This memorized null value can be cancelled by disconnecting the test leads and
pressing F1(NULL) switch with the test switch pressed or locked.
●When this is cancelled you will know because NULL OFF is displayed on the LCD.
Before taking any measurements always check the leads have been zeroed.
It is good practice to regularly null the test leads, it is advised that each time this
is done the previous memorized null should be taken off before running through
a new null procedure.
Fig. 8-3
CAUTION
(6) Connect the test leads to the circuit whose resistance is required (see Fig. 8-4 for a
typical connection arrangement), having first made sure that the circuit is not live.
Note that “Live” warning will be displayed on the LCD if the circuit is live - but
check first anyway!
Fig.8-4 Example of continuity test for main equipotential bonding.
24
(7) Press the test switch and read the circuit resistance from the display. The reading will
PAT OFF
-
have the test lead resistance already subtracted if the Continuity null function has been
used.
Note: If the reading is greater than 2099Ω the over range symbol ‘>’ will remain displayed.
WARNING
The results of measurements can be adversely affected by impedances of additional
operating circuits connected in parallel or by transient currents.
Fig. 8-5
● Circuit protection
The tester has circuit protection function: even if touching with a live circuit during
low-resistance measurement unintentionally, the tester will have no damage. There is a
backup fuse in the battery compartment. On the very rare occasion that this blows there
is a replacement fuse, also in the battery compartment.
8.2 2Ω Buzzer ( ) function
Use F2 switch to enable ( ) / disable ( ) the 2Ω Buzzer. The buzzer sounds when
measured resistance is 2Ω or less while this function is enabled.
8.3 Switching test currents
KT66DL can perform continuity test at 200mA and also 15mA. Press F4 switch to switch the
current between 200mA and 15mA.
8.4 Pat function
PAT function is available to do continuity test for portable appliances,
(1) Press F3 to select the criteria value for PAT test. (See the table below.)
Item Criteria of judgement
PAT 0.1Ω
PAT 0.3Ω
PAT 0.5Ω
(2) To conduct PAT testing use the optional accessory PATAdapter1 and refer to section
”✓”: 0.1Ω or less, ”X”: over 0.1Ω
”✓”: 0.3Ω or less, ”X”: over 0.3Ω
”✓”: 0.5Ω or less, ”X”: over 0.5Ω
10 on page 31.
”✓” or ”X” will be displayed next to the reading to show PASS/ FAIL.
25
9. Insulation tests
This tester is used to measure insulation resistance of an electric appliance or circuit to
inspect the insulation performance. Check the voltage rating of the object to be tested
before making a measurement and select the voltage applied to.
● Depending on the object to be measured, displayed insulation resistance value may not
stabilize.
● The tester may give bleep during an insulation resistance measurement; however, this is
not a malfunction.
● Measurement time may be longer when measuring a capacitive load.
● In insulation resistance measurement, the earth terminal outputs positive voltage and
the line terminal negative voltage.
● Connect the earth lead to the earth terminal. It is recommended to connect the positive
side to the earth side when measuring insulation resistance against ground or when a
part of the object under test is earthed. Such connection is known to be more suitable
for insulation testing since insulation resistance values measured with the positive side
connected to earth are typically less than those taken through the reversed connection.
DANGER
● Be extremely careful not to touch the tip of test probe or the circuit under test to avoid
electrical shock during insulation measurement since high voltage is present at the tip
of the test probe continuously.
Wipe the test probe with a soft cloth, if it is wet, and use it after it’s dry.
● The battery compartment cover must be closed before you operate the tester.
CAUTION
Always disconnect power to the equipment under test before starting insulation
measurement. Do not attempt to make measurements on a live circuit; otherwise, it may
damage the tester.
26
9.1 Measurement method
AR/ PI values
uration
On the INSULATION function, breakdown voltage of Surge protect device (SPD,
VARISTOR) can be tested in addition to normal insulation resistance.
LCD display and function switches
Measured value
1-min value
D
D
(1) Select INSULATION function with the rotary switch.
(2) Press F1 switch and select the test you wish to do: ”INSULATION” or SPD:
”SPD (VARISTOR)”.
(3) Press F2 switch and select the desired voltage range.
(When selecting SPD test, the range is fixed to 1000V.)
(4) Insert the test leads to the L and PE terminals on KT66DL respectively as shown
in Fig. 9-2.
(5) Attach the test leads to the circuit or the appliance under test (See Fig. 9-3, Fig. 9-4, and
Fig. 9-5).
Brown
Green
Fig. 9-2
L terminal
Brown test lead, or
ACC064SPN Remote Test Lead
PE terminal
Green test lead
F1 Test mode selection
Insulation or SPD
F2 Voltage setting
(100V,250V,500V,1000V)
F3 Pat mode setting
(OFF, CL1, CL2)
Output voltage
Fig. 9-1
Fig. 9-3 Example of Insulation resistance test on 4 wire-3 phase system
27
(6) If the “Live” warning is displayed on the LCD and/or the buzzer sounds, do not press
the test switch but disconnect the tester from the circuit. Make the circuit dead before
proceeding.
(7) Press the test switch, the display will show the insulation resistance of the circuit or the
appliance to which the tester is connected. At an SPD(VARISTOR) test, the LCD will
show a breakdown voltage.
(8) Auto discharge function
This function allows any capacitance charge in the circuit under test to be automatically
discharged after measurement. Set the test switch or remote-control switch to off with
the test leads connected.
Discharge can be checked with the flashing “ ” symbol and buzzer.
Never touch the circuit under test immediately after measurement.
Capacitances stored in the circuit may cause electric shock. Leave the test leads
connected to the circuit, and do not touch the circuit until flashing ” ” goes off.
● Measurement and elapsed time are displayed on the LCD during insulation resistance
measurement: up to 99 min. 59 sec. Note: The time counter stops and freezes when it
reaches to 99 min. 59 sec.; if the elapsed time exceeds 100 min.
● If the reading measured greater than 2099MΩ (209.9MΩ at 100V/ 250V, 1049MΩ at
500V) the over range reading ‘>’ will be displayed.
For continuous measurement, use the lock-down feature incorporated in the test switch.
Press and turn the test switch clockwise to lock the switch in operating position; to
unlock the switch, turn it counterclockwise.
DANGER
Be extremely careful not to touch the tips of test leads to avoid getting electrical shock
since high voltage is present continuously.
9.3 Voltage characteristics of measurement terminals
This tester conforms to IEC61557. This standard defines that the rated measurement
current shall be at least 1mA, and the lower limit of the insulation resistance maintaining
the rated measurement voltage at measurement terminals. (See the table below.) This
value is calculated by dividing the rated voltage by rated current. In case that the rated
voltage is 500V, the lower limit of the insulation resistance is found as follows.
Divide 500V by 1mA equals 0.5MΩ.
That is, insulation resistance of 0.5MΩ or more is required to provide the rated voltage
to the tester.
Rated voltage 100V 250V 500V 1000V
Lower limit of the insulation resistance to
provide the rated current of 1mA
0.1MΩ
0.25MΩ
Fig. 9-7
0.5MΩ 1MΩ
29
9.4 DAR/ PI measurement, 1-min value display
PAT OFF
-
DAR (Dielectric Absorption Ratio) and PI (Polarization Index) are automatically measured
during insulation resistance measurement.
When measurement time elapsed:
- 1 min: LCD shows DAR value.
- 10 min: LCD shows PI value.
The LCD shows the measured value, after 1 min has passed since the start of
measurement. Measured value is reviewable when 1 min elapses and also after the end of
measurement.
The table below shows the formula and the display range.
DAR = Resistance (1 min after a start of test) / Resistance (15 sec
Formula
after a start of test),
PI = Resistance (10 min after a start of test) / Resistance (1 min after
a start of test)
Display range 0.00 to 9.99
*DAR and PI value to be displayed will be “no” if the resistance value applied in the above
formula is 0MΩ or out of display rangeWhen DAR and PI values exceed the display range,
the LCD shows “>9.99”.
9.5 Pat function
PAT function is available to do insulation test for portable appliances: this function is (1)
Press F3 to select the criteria value for PAT test. (See the table below).
Item Criteria of judgement
PAT
CL1
”✓”: 1MΩ
PAT
CL2
”✓”: 2MΩ
(2) To conduct PAT testing refer to section 10 on page 31.
or more,
or more,
”X”
: less than 1MΩ
”X”:
less than 2MΩ
”✓” or ”X” will be displayed next to the reading to show PASS/ FAIL.
9.6 SPD(Varistor) test
SPD test can measure a voltage which breakdowns surge protective device(varistor). When
the test starts, the voltage that the KT66DL outputs automatically increases from 0 V until
the SPD breakdowns and the LCD shows the voltage value. (If a 1 mA or higher current
flow is detected, the tester judges it is the breakdown point.)
● Press the Test switch to start a test. Pressing F4 or ESC aborts the test.
● The LCD shows SPD breakdown voltage (DCV) and also the assumed AC voltage (ACV).
The displayed ACV is determined
by the following formula.
ACV = DCV/ 1.4
● If there’s no SPD breakdown,
Breakdown
voltage (DCV)
the LCD shows ”>1049V”.
Breakdown
voltage (ACV)
Fig. 9-8 SPD measurement screen
30
10. PAT FUNCTION
10.1 PAT test with the PAT Adapter1
Using the Kewtech PATAdapter1 with the KT66DL to undertake portable appliance testing.
Before each use the adapter should be inspected to ensure that it is not damaged in any
way. If any damage is noticed the adapter should be withdrawn from service and replaced.
10.2 Earth Bond.
a. This is a continuity test. Connect the test leads to the tester as shown in figure 8.2 on
page 23
b. Connect one test lead from the KT66DL into the PAT Adapter1 at the terminal marked
(Earth Testing)
c. Plug the appliance to be tested into the three pin socket on the front of the PAT Adapter1.
d. Connect the other test lead from the KT66DL to the earthed position on your appliance to
be tested.
e. Conduct a continuity test
Note: The test lead resistance can be auto-nulled from the test result, see section 8.1 on
page 23 for guidance.
10.3 Insulation Class I
a. Connect the test leads to the tester as shown in fig. 9.2 on page 27.
b. Connect one test probe from the KT66DL to the terminal marked (Insulation
Testing) on the PATAdapter1 and the other test lead to the terminal marked (Earth
Testing).
c. Plug the appliance to be tested into the three pin socket on the front of the PAT Adapter.
d. Select either a 250V or 500V whichever is appropriate. Conduct a test.
10.4 Insulation Class II
a. Connect the test leads to the tester as shown in fig. 9.2 on page 27.
b. Connect one test probe from the KT66DL to the terminal marked (Insulation
Testing) on the PATAdapter1.
c. Plug the appliance to be tested into the three pin socket on the front of the PAT Adapter.
d. Connect the other lead from the KT66DL to the parts of your appliance to be tested.
e. Conduct a test.
In PAT CL I or PAT CL II mode the insulation 1000V
range is disabled. Use 250V for:
1. Appliances and extension leads which
include surge protection.
2. Where sensitive electronic equipment
could be damaged.
Refer to the latest publication of the IET
Code of Practice for In-Service Inspection and
Test of Electrical Equipment for the
methodology for testing of electrical equipment.
Fig. 10-1
31
11. LOOP/ PSC/PFC
11.1 Principles of measurement
(1) Principles of measurement of fault loop impedance and PFC
If an electrical installation is protected by over-current protective devices including circuit
breakers or fuses, the earth loop impedance should be measured.
In the event of a fault the earth fault loop impedance should be low enough (and the
prospective fault current high enough) to allow automatic disconnection of the electrical
supply by the circuit protection device within a prescribed time interval. Every circuit must
be tested to ensure that the earth fault loop impedance value does not exceed that specified
or appropriate for the over-current protective device installed in the circuit. The KT66DL
takes a current from the supply and measures the difference between the unloaded and
loaded supply voltages. From this difference it is possible to calculate the loop resistance.
TT System
For a TT system the earth fault loop impedance is the sum of the following impedances;
●Impedance of the power transformer secondary winding.
●Impedance of the phase conductor resistance from the power transformer to the location
of the fault.
●The impedance of the protective conductor from the fault location to the earth system.
●Resistance of the local earth system (R).
●Resistance of the power transformer earth system (Ro).
The figure below shows (dotted line) the Fault loop impedance for TT systems.
Fig. 11-1
32
According to the International Standard IEC 60364, for TT systems the characteristics of the
protective device and the circuit resistance shall fulfill the following requirements:
Ra x Ia ≤ 50V
Where:
Ra is the sum of the resistances in Ω of the local earth system and the protective conductor
for the exposed conductive parts.
50 is the maximum safety touch voltage limit (it can be 25V in particular cases like
construction sites, agricultural premises, etc.).
Ia is the current causing the automatic disconnection of the protective device within the
maximum disconnecting times required by IEC 60364-41 that, for electrical installations at
230 / 400V AC, are:
- 200 ms for final circuits up to 63A for socket, or up to 32A for fixed connected loads.
- 1 s for distribution circuits and circuits above mentioned over 63A and 32A.
The compliance with the above rules shall be verified by:
1) Measurement of the resistance Ra of the local earth system by Loop tester or Earth
tester.
2) Verification of the characteristics and/or the effectiveness of the RCD associated
protective device.
Generally, in TT systems, RCDs shall be used as protective device and in this case, Ia is
the rated residual operating current I∆n. For instance, in a TT system protected by a RCD
the max Ra values are:
Rated residual operating
current I∆n
RA (with touch voltage of 50V) 1667 500 167 100 50
RA (with touch voltage of 25V) 833 250 83 50 25
Shown below is a practical example of verification of the protection by RCD in a TT system
according to the international Standard IEC 60364.
30 100 300 500 1000 (mA)
(Ω)
(Ω)
Fig. 11-2
33
In this example, the max permissible value is 1667Ω (RCD =30mA and contact voltage limit
of 50V). The tester reads 12.74Ω, thus the condition RA ≤ 50/Ia is respected. However,
considering that the RCD is essential for protection, it must be tested (Please refer to RCD
TESTS section).
TN System
For TN systems the earth fault loop impedance is the sum of the following impedances.
●Impedance of the power transformer secondary winding.
●Impedance of the phase conductor from the power transformer to the location of the fault.
●Impedance of the protective conductor from the fault location to the power transformer.
The figure below shows (dotted line) the Fault loop impedance for TN systems.
Fig. 11-3
According to the International Standard IEC 60364, for TN system the characteristics of the
protective device and the circuit impedance shall fulfill the following requirement:
Zs x Ia ≤ Uo
Where:
Zs is the Fault loop impedance in ohm.
Uo is the nominal voltage between phase to earth (typically 230V AC for both single phase
and three phase circuits).
Ia is the current causing the automatic disconnection of the protective device within the
maximum disconnecting times required by IEC 60364-41 that, for installation at 230 / 400V
AC, are:
- 400 ms for final circuits up to 63A for socket, or up to 32A for fixed connected loads.
- 5 s for distribution circuits and circuits above mentioned over 63A and 32A.
The compliance with the above rules shall be verified by:
1)Measurement of the fault loop impedance Zs by Loop tester.
2)Verification of the characteristics and/or the effectiveness of the associated protective
device. This verification shall be made:
- for circuit-breakers and fuses, by visual inspection (i.e. short time or instantaneous tripping
setting for circuit-breakers, current rating and type for fuses);
- for RCDs, by visual inspection and test using RCD testers recommending that the
34
disconnecting times mentioned above are met (Please see RCD TEST section).
P
rotected by BSEN 60898 MCB with
Uo=230V
Time 0.4s)
Time 5s)
B C C D
rating
For instance in a TN system with nominal mains voltage Uo = 230 V protected
by MCBs (Miniature Current Breakers) required by BSEN 60898, the max Zs
values could be:
The most complete Multifunction testers also have such above Zs limit table implemented in
their firmware, so that the verification of the overcurrent protection is automatically made by
comparing the measured value of Loop impedance and the Zs limit of the table.
Below is a practical example of verification of the protection by MCB in a TN system
according to the international Standard IEC 60364.
0.4 and 5s)
Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω)
MCB
(Disconn.
MCB
(Disconn.
Fig. 11-4
35
Max value of Zs for this example is 1.37Ω (MCB 16A, characteristic C), the tester reads
1.14Ω (or 202A on Fault current range) it means that the condition
Zs x Ia ≤ Uo is respected.
In fact the Zs of 1.14Ω is less than 1.37Ω (or the Fault current of 202A is more than Ia of
160A).
In other words, in case of fault between phase and earth, the wall socket tested in this
example is protected because the MCB will trip within the disconnection time required.
(2) Principles of the measurement of line impedance and PSC
The method for measuring line – neutral impedance and line-line impedance is exactly the
same as for earth fault loop impedance measurement with the exception that the
measurement is carried out between line and neutral or line and line.
Prospective short circuit or fault current at any point within an electrical installation is the
current that would flow in the circuit if no circuit protection operated and a complete (very
low impedance) short circuit occurred. The value of this fault current is determined by the
supply voltage and the impedance of the path taken by the fault current. Measurement of
prospective short circuit current can be used to check that the protective devices within the
system will operate within safety limits and in accordance with the safe design of the
installation. The breaking current capacity of any installed protective device should be
always higher than the prospective short circuit current.
Fig. 11-5
36
11.2. Measurement method for LOOP high current
LCD display and function switches
Measured value
PFC or
PSC value
(1) Select LOOP HIGH function with the rotary switch.
(2) Connect the test lead into the tester. (Fig. 11-7 or Fig. 11-8)
L PE N
BROWN GREEN
Fig. 11-7 For L-PE and L-N test
L N
Fig. 11-6
BLUE
F1 Switches measurement mode:
L-PE or L-N/L-L
F2 Selects resolution 0.01Ω or 0.001Ω
(In case of L-PE)
F3 Selects test lead (0.001ΩRes)
F4 Limit value setting
or
LOOP limit value
Mains voltage
Wiring check
At L-PE
measurement,
no need to use
N terminal.
BROWN BLUE
Fig. 11-8 For L-N and L-L test
37
(3) Press the F1 switch and select L-N to measure L-N/L-L loop impedance or select L-PE
or
or
Fig
. 11-10
to measure earth loop impedance.
・
Press F2 switch and select the resolution either 0.01Ω or 0.001Ω at L-PE test.
・
Display changes automatically as follows depending on the applied voltages while
LOOP(L-N/L-L) is selected.
LOOP
<48V
LOOP
48 – 300V
LOOP
>300V
L-N/L-L
L-N L-L
Fig. 11-9
(4) Press F4 switch to enter the setting mode for limit value.
Please refer to “11.4 Loop limit value”.
(5) Connection
Connect the KT66DL to the distribution system to be tested with reference to Fig.
11-12, 11-13, 11-14, and 11-15.
(6) Wiring Check
After the connection, ensure that the symbols for Wiring check on the LCD are in the
status indicated in Fig.11-10 before pressing the test switch.
FUNCTION
L-PE
0.01ΩRes
0.001ΩRes
L-N/L-L
If the status of the symbols for Wiring check differ from Fig.11-10 orsymbol is
indicated on the LCD, DO NOT PROCEED AS THERE IS INCORRECT WIRING. The
cause of the fault must be investigated and rectified.
When the tester is first connected to the system, it will display the line-earth voltage (mode
L-PE) or line-neutral voltage (mode L-N/ L-L) which is updated every 1s. If this voltage is
not normal or as expected, DO NOT PROCEED.
38
(7) Test lead selection
In case of LOOP HIGH function, use F3 switch to select the test lead to be used. When
LOOP HIGH function, the resistance of the test lead to be used affects the measured
result; therefore, test lead selection is effective to reduce errors in results. Select either
Model Mains test lead (KAMP12) or Distribution board test lead (ACC065).
(8) Measurement
Press the test switch. A beep will sound as the test is conducted and the value of loop
impedance will be displayed. When LOOP limit value has been set, the LCD shows “✓”
when the measured value is lower than the limit value and “X” if the value exceeds the limit
value. The " ! " symbol appears when the measured result exceeds the measuring range,
and the upper limit of the measuring range is smaller than the reference value: it means
unjudgeable.
● If the display shows '>' then this usually means the value measured exceeds the range.
Mains lead is selected. Distribution board lead is selected.
Fig. 11-11
Fig. 11-12 Connection for using socket
39
Fig. 11-13 Connection for distribution
Fig. 11-14 Connection for Line – Neutral measurement
Fig. 11-15 Connection for Line – Line measurement
40
The test switch may be pressed down and turned clockwise to lock it for auto-mode. In
FC or
this auto mode, when using distribution board lead set ACC065, tests are conducted
by simply disconnecting and reconnecting the brown phase prod avoiding the need to
physically press the test switch i.e. 'hands free'.
● Measured result may be influenced depending on the phase angle of the distribution
system when making measurement near a transformer and the result may lower than the
actual impedance value. Errors in measured result are as follows.
●If the symbol ( )appears, it means that the test resistor is too hot and the automatic cut
out circuits have operated. Allow the tester to cool down before proceeding. The overheat
circuits protect the test resistor against heat damage.
11.3. Measurement method for LOOP ATT (Anti trip technology)
LCD display and function switches
Measured value
P
PSC value
Noise indicator
(1) Press the Power switch and turn on the tester. Turn the rotary switch and set it to the
LOOP ATT position.
System Phase Difference Error (approx.)
10° -1.5%
20° -6%
30° -13%
F1 Switches 3-wire, 3-wire EV & 2 wire Test
F2 Turns on/ off pulse function
F3 Toggles between normal & low current for EVSE
loop testing– only shows if L-PE 3W EV is
selected at F1
F4 Limit value setting
LOOP limit value
Mains voltage
Wiring check
Fig. 11-16
41
(2) Connect the test lead to the tester. (Fig. 11-17 or Fig. 11-18)
(3) Press F1 switch and select either L-PE 2W (2-wire), L-PE 3W (3-wire) or L-PE 3W EV
(4) Pulse function can be turned on or off with F2 switch.
When pulse function is enabled, some RCDs may trip depending on their sensitivity. In
such a case, turn off the pulse function.
BROWN
BROWN
test.
When pulse function is on (enabled), a high current is applied in a short period - RCD
won’t trip - before starting LOOP measurement. This pulse function can remove the
oxidized coating of the circuit under test and contribute to accurate measurements.
L
GREEN
L
GREEN
PE
N
BLUE
Fig. 11-17 For L-PE 3-wire test
PE
Fig. 11-18 For L-PE 2-wire test
or
CAUTION
(5) Press F4 switch to enter the setting mode for limit value.
Please refer to “11.4 Loop limit value”.
(6) Connection
Connect the KT66DL to the distribution system to be tested with reference to Fig. 11-20,
11-21 and 11-22.
(7) Wiring Check
After the connection, ensure that the symbols for Wiring check on the LCD are in the
status indicated in Fig.11-19 before pressing the test switch.
FUNCTION
L-PE 3W (EV)
L-PE 2W
Fig. 11-19
42
If the status of the symbols for Wiring check differ from Fig. 11-19 or thesymbol is
indicated on the LCD, DO NOT PROCEED AS THERE IS INCORRECT WIRING. The
cause of the fault must be investigated and rectified.
When the tester is first connected to the system, it will display the line-earth voltage (mode
L-PE) which is updated every 1s. If this voltage is not normal or as expected, DO NOT
PROCEED.
(8) Measurement
Press the test switch. A beep will sound as the test is conducted and the value of loop
impedance will be displayed. When LOOP limit value has been set, the LCD shows “✓”
when the measured value is lower than the limit value and “X” if the value is higher than
the limit value. The “ ! ” symbol appears when the measured result exceeds the
measuring range, and the upper limit of the measuring range is smaller than the
reference value: it means unjudgeable.
●If the display shows '>' then this usually means the value measured exceeds the range.
Fig. 11-20 3-wire test (Connection for using outlet)
Fig. 11-21 3-wire test (Connection for distribution)
43
Fig. 11-22 L-PE 2-wire test
● ATT mode enables a measurement without tripping the RCDs with the rated residual
current of 30mA or more.
● The L-PE 3W EV setting enables loop testing where sensitive DC monitoring devices are
used. Press F 3 to select the test current.
● Measurement in ATT mode requires longer time than that is required for the other
measurements (approx. 8 sec). When measuring a circuit with a large electrical noise, the
'Noise' Message is displayed on the LCD and the measurement time will be extended.
Noise indicator shows the noise size in three levels. Noise size affects the measurement
Time.
● At L-PE 3W (EV) measurement, when a LOOP impedance between L-N exceeds 20Ω,
the LCD shows “L-N>20Ω” and the tester will not make measurements. In this case, set
the range to “LOOP HIGH” or test with L-PE 2W ATT.
● If a high voltage exists between N-PE at L-PE 3W (EV) test, the LCD shows “N-PE HiV”
and the tester will not make measurements. In this case set the range to “LOOP HIGH” or
test with L-PE 2W ATT.
The test switch may be turned clockwise to lock it down. In this auto mode, when using
the distribution board lead set ACC065, tests are conducted by simply disconnecting
and reconnecting the brown phase prod avoiding the need to physically press the test
switch i.e. 'hands free'.
Level 1
Level 2 Level 3
Fig. 11-23 Noise indicator
44
● Measured result may be influenced depending on the phase angle of the distribution
system when making measurement near a transformer and the result may lower than the
actual impedance value. Errors in measured result are as follows.
● If the symbol ( )appears, this means that the test resistor is too hot and the automatic
cut out circuits have operated. Allow the tester to cool down before proceeding. The
overheat circuits protect the test resistor against heat damage.
11.4 Loop limit value
To set a loop limit value, press F4 switch in the stand-by mode at LOOP test. The
following figure shows the setting mode screen.
・
The table below shows the setting parameters.
(a) Protection type Type of protective deviceMCB: B C, D, Type 1, 2, 3, 4
(b) In Rated current of protective
(c) Time or Uc Trip time of protective deviceFor RCD, Uc limit value setting
(d) Factor Margin of threshold value X 1 or 0.8 (80%)
Limit value setting procedures are shown below.
(Press ESC switch to step back one during the process.)
(1) Press F1(▲) or F2(▼) on LOOP LIMIT setting screen to move the cursor on the item to
be set, and then press ENTER switch.
(2)The LCD shows the selectable items. Press F1(▲) or F2(▼) and confirm the selection
with ENTER switch. For some items, F3(◄) and F4(►) switches are also used.
(3) When changes are done, press ESC to return to LOOP test screen.
System Phase Difference Error (approx.)
10° -1.5%
20° -6%
30° -13%
Fig. 11-24 LOOP LIMIT setting screen
device
Fuse 88.2, 88.3, 3036, 1362,
1361, RCD
In: 6 - 100 A
IΔn: 30 mA-1000 mA
45
Selectable parameters and reference values for limit value are as shown below.
type
ref BS7671:2008 (20
15)
ref BS7671:2008 (20
15)
@80%Z
@80%Z
@80%Z
@80%Z
Z
s(Ω) Z
s(Ω) Z
s(Ω) Z
s(Ω) Z
s(Ω) Z
s(Ω) Z
s(Ω) Zs(Ω)
5 --- --- --- --- 9.93 1
4.60 7.94 1
1.68
6 7.80 12.00 6.24 9.60 --- --- --- ---
10 4.65
6.80 3.72 5.44 --- --- --- ---
16 2.43
4.00 1.95 3.20 2.30 3.90 1.84 3.12
20 1.68 2.80 1.35 2.24
1.93 3.20 1.54 2.56
25 1.29 2.20 1.03 1.76 --- --- --- ---
40 --- 1.30 --- 1.04 --- --- --- ---
45 --- --- --- --- --- 1.00 --- 0.80
50 --- 0.99 --- 0.79 --- --- --- ---
80 --- 0.55 --- 0.44 ---
0.51 --- 0.41
100 --- 0.42 --- 0.34 --- 0.38 --- 0.30
type
ref BS7671:2008 (20
15)
ref BS7671:2008 (20
15)
@80%Z
@80%Z
@80%Z
@80%Z
Z
s(Ω) Z
s(Ω) Z
s(Ω) Z
s(Ω) Z
s(Ω) Z
s(Ω) Z
s(Ω) Z
s(Ω)
3 --- --- --- --- 1
5.60 22.0 1
2.48 1
7.60
5 9
.10 16.80 7.28 13.44 --- --- --- ---
13 --- --- --- --- 2.30 3.64 1.84
2.91
15 2.43 5.08
1.94 4.07 --- --- --- ---
30 1.04 2.51 0.83 2.01 --- --- --- ---
45 --- 1.51 --- 1.21 --- --- --- ---
60 --- 1.07 --- 0.86 --- --- --- ---
type
ref BS7671:2008 (20
15)
@80%Z
@80%Z
Z
s(Ω) Z
s(Ω) Z
s(Ω) Z
s(Ω)
5 10.36 1
6.25 8.28 13.00
15 3.26
4.96 2.61 3.97
30 1.14 1.82 0.91 1.46
45 0.57
0.95 0.46 0.76
60 --- 0.69 --- 0.55
100 --- 0.36 --- 0.29
●
Loop Limit value for fuse protection
Protection
Rating
(A)
32 0.99 1.70 0.79 1.36 0.91 1.60 0.73 1.28
63 --- 0.78 --- 0.62 --- 0.68 --- 0.55
0.4s 5s
BS88-2 Fuse
0.4s
5s
0.4s 5s
BS88-3 Fuse
0.4s
Protection
Rating
(A)
20 1.68 3.64 1.35 2.91 --- --- --- ---
0.4s 5s
BS3036
0.4s
5s
0.4s 5s
BS1362
0.4s
5s
5s
100 --- 0.51 --- 0.41 --- --- --- ---
Protection
Rating
(A)
20 1.69 2.78 1.35 2.23
80 --- 0.49 --- 0.40
0.4s 5s
BS1361
0.4s
5s
46
●Loop Limit value for RCD protection
@80%Z
@80%Z
@80%Z
@80%Z
30mA 1667Ω
1334Ω
833Ω
666Ω
100.0Ω
80.0Ω
200.0Ω
160.0Ω
300mA
167.0Ω 133.6Ω 83.0Ω
66.4Ω
100.0Ω
80.0Ω --- ---
500mA
100.0Ω 80.0Ω 50.0Ω
40.0Ω --- --- --- ---
1000mA
50.0Ω
40.0Ω 25.0Ω
20.0Ω --- --- --- ---
Zs BSEN 60898 MCB & BSEN 61009
-
1 RCBO table
B C D D B C D D
6 7
.28 3
.64 1
.82 3
.64 5.82 2.91 1
.46 2.91
10 4.37 2
.19 1
.09 2
.19 3
.50 1
.75 0
.87 1
.75
16 2.73 1
.37 0
.68 1
.37 2
.18 1
.09 0
.55 1
.10
20 2.19 1
.09 0
.55 1
.09 1
.75 0
.87 0
.44 0
.87
25 1.75 0
.87 0
.44 0
.87 1
.40 0
.70 0
.35 0
.70
32 1.37 0
.68 0
.34 0
.68 1
.09 0
.55 0
.27 0
.54
40 1.09 0
.55 0
.27 0
.55 0
.87 0
.44 0
.22 0
.44
50 0.87 0
.44 0
.22 0
.44 0
.70 0
.35 0
.17 0
.35
63 0.69 0
.35 0
.17 0
.35 0
.55 0
.28 0
.14 0
.28
Zs BSEN 3871 MCB table
MCB (Disconn. time 0.4 and 5s)
MCB (Disconn. time 0.4 and 5s) 80%Z
1 2 3 4 1 2 3 4
rating
5 1
0.93 6.41 4.37 0.87 8.74 5
.13 3.50 0.70
6 9.10 5.21 3.64 0.73 7.28 4.16 2.91 0.59
10 5.46 3.10 2.19 0.44 4.37 2.48 1.75 0.35
15 3.64 2.08 1.45 0.29
2.91 1.66 1.16 0.24
16 3.41
1.95 1.37 0.28 2.73 1.56 1.09 0.22
20 2.73 1.56 1.09 0.22 2.18 1.25 0.87 0.17
25 2.19 1.24 0.87 0.17 1.75 1.00 0.70 0.14
30 1.82 1.05 0.73 --- 1.46 0.84 0.59 ---
32 1.71
0.98 0.68 --- 1.37 0.78 0.55 ---
40 1.36 0.78 0.55 --- 1.09 0.62 0.44 ---
50 1.09 0.63 0.44 --- 0.87 0.50 0.35 ---
63 0.86 0.49 0.35 --- 0.69 0.40 0.28 ---
Limit Uc 50V
100mA 500Ω400Ω250Ω200.0Ω100.0Ω80.0Ω200.0Ω160.0Ω
IΔn
(mA)
Uc 50V
Uc 25V
Uc 25V
100Ω
100Ω
200Ω
200Ω
Note: Displayed Loop Limit value may not be the same as listed above depending on the
countries and regions
Current
rating
Current
MCB (Disconn. time
0.4 and 5s)
Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω)
Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω) Zs(Ω)
MCB(Disc
0.4s)
MCB(Disc
5s)
MCB (Disconn. time
0.4 and 5s) 80%Z
MCB(Disc
0.4s)
80%Z
MCB(Dis
80%Z
c 5s)
47
12. RCD tests
12.1 Principles of RCD measurement
The RCD tester is connected between phase and protective conductor on the load side of
the RCD after disconnecting the load.
A precisely measured current for a carefully timed period is drawn from the phase and
returns via the earth, thus tripping the device. The tester measures and displays the
exact time taken for the circuit to be opened.
An RCD is a switching device designed for breaking currents when the residual current
attains a specific value. It works on the basis of the current difference between phase
currents flowing to different loads and returning current flowing through the neutral
conductor (for a single-phase installation). In the case where the current difference is higher
than the RCD tripping current, the device will trip and disconnect the supply from the load.
There are two parameters for RCDs; the first due to the shape of the residual current wave
form (types AC and A) and the second due to the tripping time (types G and S).
●
RCD type AC will trip when presented with residual sinusoidal alternating currents
whether applied suddenly or slowly rising.
●
RCD type A will trip when presented with residual sinusoidal alternating currents
(similar to type AC) and residual pulsating direct currents whether suddenly applied or
slowly rising.
●
RCD Type F will the trip when presented with residual sinusoidal alternating currents
at the rated frequency, residual pulsating direct currents and composite residual
currents.
Tests of RCD type F with KT66DL use halfwave rectified current the same
as testing Type A RCD.
●
RCD type B can detect residual sinusoidal alternating currents up to 1000 Hz,
residual pulsating direct currents as well as smooth DC residual currents.
●
RCD type G. In this case G stands for general type (without tripping time delay) and is
for general use and applications.
●
RCD type S where S stands for selective type (with tripping time delay). This type of
S
RCD is specifically designed for installations where the time delay characteristic is
required.
●
RCD Type EVs are designed specially for EV (electric vehicle) charging systems. They
trip by 6mA smooth DC residual currents.
Given that when the protective device is an RCD, Ia is typically 5 times the rated residual
operating current I∆n, then the RCD must be tested recommending the tripping time,
measured by RCD testers or multifunction testers, shall be lower than the maximum
disconnecting times required in IEC 60364-41 at 230V / 400V AC (see also LOOP section)
that are:
TT system 200ms for final circuits up to 63A for socket, or up to
TN system 400ms
TT system 1000ms for distribution circuits and circuits above
TN system 5s
32A for fixed connected loads
mentioned over 63A and 32A.
48
However, it is also good practice to consider even more stringent trip time limits, by
max allowed value
max allowed value
min allowed value
min allowed value
following the standard values of trip times at I∆n defined by IEC 61009 (EN 61009) and IEC
61008 (EN 61008). These trip time limits are listed in the table below for IΔn and 5IΔn:
Type of RCD IΔn 5IΔn
General(G) 300ms
max allowed value
Selective(S) 500ms
40ms
max allowed value
150ms
130ms
Examples of tester connections
Practical example of 3-phase + neutral RCD test in a TT system.
50ms
18.7 ms
Practical example of single phase RCD test in a TN system.
Fig. 12-1
18.7 ms
Fig. 12-2
49
Practical example of RCD test with distribution leads.
18.7 ms
12.2 Principles of Uc measurement
When earth resistance is high as in Fig 12-1, where R exists and if a fault current flows, a
potential difference occurs. If a person touches the earthing system then the person will be
subjected to this voltage. This is the Uc voltage.
If an RCD is protecting the circuit then the maximum value of Uc can be calculated by
multiplying the measured loop by the selected IΔN of the RCD selected.
Fig. 12-3
12.3 Measurement method for RCD
LCD display and function switches
Measured
value
F1 Measurement mode setting
(X1/2, X1, X5, Ramp, Auto, Uc)
F2 IΔn setting
F3 RCD Type setting
AC-G AC-S
A-G A-S
F-G B-S
B-G
TYPE EV
F4 Phase Setting (0o (+) or 180o (-))
Preset UL value
L-PE voltage
Wiring check
Fig. 12-4
S
S
S
50
(1) Press the Power switch and turn on the tester. Turn the rotary switch and set it to the
RCD position.
(2) Connect the test lead to the tester. (Fig. 12-5)
L PE N
or
For AC/ A/F measurement,
no need to use N terminal.
BROWN
GREEN
BLUE
Fig. 12-5 For RCD test
(3) Press the F1 switch and select any desired measurement mode.
X1/2 For testing RCD to verify that they are not too sensitive.
X1 For measuring the trip time.
X5 For testing at IΔn X5
RAMP( )
AUTO
For measuring the tripping level in mA.
For automatic measurement in the following
(4) Press the F2 switch to set Rated Tripping Current (IΔn) to the rated trip current of the
RCD.
(5) Press F3 switch to select the RCD type.
Refer to "12.1 Principles of RCD measurement" for the details of RCD type.
(
Except for Uc measurement
)
(6) Press (F4) to select phase at which the test current should start.
(
Except for Uc measurement)
*UL value change
As a UL value, 25V or 50V is selectable. Refer to ”6. Setup mode” in this manual and
select either of them.
(7) Connect the test leads to the circuit to be tested. (Fig. 12-1,12-2, and 12-3)
(8) Wiring Check
After the connection, ensure that the symbols for Wiring check on the LCD are in the
status indicated in Fig.12-6 before pressing the test switch.
RCD TYPE
AC/A/F
or
B/EV
Fig. 12-6
If the status of the symbols for Wiring check differ from Fig. 12-6 orsymbol is
indicated on the LCD, DO NOT PROCEED AS THERE IS INCORRECT WIRING. The
cause of the fault must be investigated and rectified.
51
When the tester is connected to the system for the first time, it will display the line-earth
voltage (mode L-PE) which is updated every 1s. If this voltage is not normal or as
expected, DO NOT PROCEED.
NOTE: This is a single phase (230V AC) tester and under no circumstances should it be
connected to 2- phases or a voltage exceeding 230VAC+10%.
If the input voltage is greater than 260V the display will indicate '>260V' and RCD
measurements can not be made even if the test switch is pressed.
(9) RCD Measurement
Press the test switch. A beep will sound as the test is conducted and the measured
results are displayed.
● X1/2...................The Breaker should not trip.
● X1......................The Breaker should trip.
● X5......................The Breaker should trip.
● Auto Ramp( )..The Breaker should trip. The tripping current should be displayed.
● Uc......................Uc values are displayed.
In case of RCD type S test, you need to wait 30 sec. before starting a test: this waiting time
is to reduce the influence of the previous test.
(10) Press the F4(0°(+)/180°(-)) switch to change the phase and repeat step (1).
The test switch may be turned clockwise to lock it down. In this auto mode, when using
distribution board lead set ACC065, tests are conducted by simply disconnecting and
reconnecting the brown phase prod of the avoiding the need to physically press the
test switch i.e. 'hands free'.
● If the symbol ( )appears, this means that the test resistor is too hot and the automatic
cut out circuits have operated. Allow the tester to cool down before proceeding. The
overheat circuits protect the test resistor against heat damage.
● Be sure to return the tested RCD to the original condition after the test.
● When the Uc voltage rises to UL value or greater, the measurement is automatically
suspended and "Uc > UL" is displayed on the LCD.
● If " IΔn" setting is greater than the rated residual current of the RCD, the RCD will trip and
"no" may be displayed on LCD.
● If a voltage exists between the protective conductor and earth, it may influence the
measurements.
● If a voltage exists between neutral and earth, it may influence the measurements,
therefore, the connection between neutral point of the distribution system and earth
should be checked before testing.
● If leakage currents flow in the circuit following the RCD, it may influence the
measurements.
● The potential fields of other earthing installations may influence the measurement.
● Special conditions of RCDs of a particular design, for example S- type, should be taken
into consideration.
● The earth electrode resistance of a measuring circuit with a probe shall not exceed the
earth electrode resistance values, specified in the table below RCD-related description,
in 5.4 Operating uncertainty .
● Equipment following the RCD, e.g. capacitors or rotating machinery, may cause a
significant lengthening of the measured trip time.
52
12.4 Auto test
Measurements are automatically performed under the Auto Test function in the following
sequence: X1/2(0o), X1/2(180o), X1(0o),X1 (180o), X5(0o), X5(180o).
(1) Press F1 to select Auto.
(2) Press F2 & F3 to select IΔn & RCD type.
(3) The KT66DL performs an RCD test in the sequence described above.
(4) When an RCD trips, turn it back on. Then a next test begins automatically.
(5) The LCD shows results as follows.
12.5 VAR (variable current value) function
At RCD test, any I∆n value – between 10mA and 1000mA - is selectable. However, X 5 test
or depending on the selected RCD test settings, variable range of current value will be
limited.
Follow the procedures below to change the current value.
(Pressing ESC switch during the changing process moves one step back.)
(1) Press F1 & F3 to select measurement mode & RCD type.
(2) Press F2 switch to select “VAR”.
(3) The LCD shows current value 2 sec. (Fig. 12-8). Press F1 (SET) switch within this 2 sec.
(If 2 sec or longer are elapsed without pressing the switch, press F2 switch again to
reshow Fig. 12-8 screen.)
(4) The LCD shows current value changing screen (Fig. 12-9). Press F3(◄) or F4(►) to
select the digit to be changed and alter the values with F1(▲) or F2(▼).
(5) Press ENTER to confirm the change. Then the screen returns to stand-by mode for RCD
test.
Note: At VAR test, X1/2, X1, and X5 tests are performed; these tests are not available at Uc,
AUTO, and RAMP tests.
Fig. 12-8 Fig. 12-9
Fig. 12-7
53
12.6 EV RCD
When selecting “EV” for RCDTYPE, the tester can test RCDs for EV charger which trip by
6 mA DC: x1, RAMP( ), and AUTO TEST are selectable.
●
At RAMP, current is steadily increased up to 6 mA DC (100%).
When it reaches to 6 mA DC, the current is kept for 10 sec.
●
At AUTO TEST, the tester performs tests at 6 mA DC and ×1/2, ×1, and ×5 tests at
30 mA A as shown below.
DC6mA(+) → DC6mA(-) → X1/2(0o) → X1/2(180o)
→
X1(0o) → X1(180o) →X5(0o) → X5(180o).
Type A 30mA
Fig. 12-10
(Comply with IEC62752)
54
13. Earth tests
13.1 Principles of earth measurement
This tester performs the earth resistance measurement with the fall-of-potential method,
which is a method to obtain earth
Resistance value Rx by applying AC constant
current I between the measurement object E
(earth electrode) and H(C) (current electrode),
and finding out the potential difference V
between E and S(P) (potential electrode).
Rx = V / I
13.2 Earth resistance measurement
WARNING
The tester will produce a maximum voltage of about 50V between terminals E-H(C) in
earth resistance function. Take enough caution to avoid electric shock hazard.
CAUTION
When measuring earth resistance, do not apply voltage between measuring terminals.
13.3 Measurement method for earth
(1) Press the Power switch and turn on the tester. Turn the rotary switch and set it to the
EARTH position.
(2) Press F1 switch to select 3W (3-wire precise measurement) or 2W (2-wire simplified
measurement).
(3) Connect the test lead into the tester. (Fig. 13-2, Fig. 13-3)
Red Green Yellow
H(C) E S(P)
Fig.13-2 For 3W test (Precise measurement)
H(C) E
Fig.13-3 For 2W test (Simplified measurement)
Constant Current Generator
Voltmeter
H(C)CurrentS(P)Potential
E(Earth)
Fig.13-1
H(C) terminal
Red test lead
E terminal
Green test lead
S(P) terminal
Yellow test lead
H(C) terminal
Red test lead , or
ACC064SPN Remote Test Lead
E terminal
Green test lead
55
(4)Connection
3W test (Precise measurement)
Stick the auxiliary earth spikes S(P) and H(C) into the ground deeply. They should be
aligned at an interval of 5-10m from the earthed equipment under test. Connect the green
test lead to the earthed equipment under test, the yellow test lead to the auxiliary earth
spike S(P) and the red test lead to the auxiliary earth spike H(C) from terminals E, S(P) and
H(C) of the tester in order.
Note:
●Make sure to stick the auxiliary earth spikes in the moist part of the soil. Give enough
water where the spikes have to be stuck into the dry, stony or sandy part of the earth so
that it may become moist.
●In case of concrete, lay the auxiliary earth spike down and water it, or put a wet dust cloth
etc. on the spike when making measurement.
2W test (Simplified measurement)
Use this method when the auxiliary earth spike cannot be used. In this method, an existing
earth electrode with a low earth resistance, such as a metal water pipe, a common earth of
a commercial power supply and an earth terminal of a building, can be used with two-pole
method.
Rx = Re – re
Rx: True earth resistance
Re: Indicated value
re: Earth resistance of earth electrode
Fig.13-4
Fig.13-5
56
(5) If the “Live” warning is displayed on the LCD and/or the buzzer sounds, do not press
the test switch but disconnect the tester from the circuit. Make the circuit dead before
proceeding.
(6) Press the test switch, the display will show the earth resistance of the circuit.
● If measurement is made with the probes twisted or in touch with each other, the reading of
the tester may be affected by induction. When connecting the probes, make sure that
they are separated.
● If the earth resistance of auxiliary earth spikes is too large, it may result in inaccurate
measurement. Make sure to stick the auxiliary earth spikes in the moist part of the soil,
and ensure sufficient connections between the respective connections. High auxiliary
earth resistance may exist if “RS Hi” or “RH Hi” is displayed during measurements.
(”Rs Hi” is displayed only when you press the test button to start a measurement. It won’t
appear if any incidents, such as auxiliary earth spikes are disconnected, happen during a
measurement,)
● When an earth voltage of 10V or higher (400Hz: 3V) exists, measured earth resistances
may include large errors. In this case, power off the devices which is using earth
resistance under test to reduce the earth voltages.
57
14. Phase rotation tests
1. Press the Power switch and turn on the tester. Turn the rotary switch and select
the PHASE ROTATION function.
2. Insert the test leads into the tester. (Fig.14-1)
3. Connect each test leads to a circuit. (Fig.14-2)
4. Results are displayed as follows.
Phase sequence (Clockwise)
BROWN
L1 L2 L3
GREEN
Fig. 14-1
BLUE
Fig.14-2
Phase sequence (Counter-clockwise)
Fig. 14-3 Correct phase sequence
● When a message “No 3-phase system” or “---” is displayed, the circuit may not be a
3-phase system or a wrong connection may have been made. Check the circuit and the
connection.
● Presence of harmonics in measurement voltages, such as an inverter power supply, may
influence the measured results.
Voltage across the terminals and
Frequency of L1-L2 voltage
Fig.14-4 Reversed phase sequence
58
15. Volts
(1) Press the Power switch and turn on the tester. Turn the rotary switch and select the
VOLTS function.
(2) Insert the test leads into the tester. (Fig.15-1)
(3) Voltage value and frequency will be displayed on the LCD when applying AC voltage.
Note : A message “DC V” may be displayed when measuring AC voltages with frequencies
BROWNGREENBLUE
out of the range 45Hz - 65Hz.
Voltages
between L-N
and N-PE
L1 L2 L3
or
Fig.15-1
Voltage between L-PE
Voltage
frequency
between L-PE
Fig. 15-2
16. Touch pad
(1) The touch pad measures the potential between the operator and the tester’s PE terminal.
A message “PE HiV” is displayed on the LCD with the audible buzzer if a potential
difference of 100V or more is present between the operator and the PE terminal at
touching the Touch pad.
(2) Touch Pad function can be enabled and disabled (ON / OFF).
See ”6. Setup mode” in this manual and select ON or OFF. In case that OFF is
selected, a warning for “PE HiV” does not appear and the buzzer does not sound.
* Initial setting: ON
Note :
A message “PE HI V” may be displayed when testing inverters or measuring voltages
containing high frequencies even if a user isn’t touching with the Touch Pad.
59
17. Memory function
Measured result at each function can be saved in the memory of the tester.
(MAX: 1000)
17.1 How to save the data
Save the result according to following sequence.
(Press ESC switch during the process to one step back.)
(1) When measurement is done, press MEM switch to
enter the save mode. (Fig. 17-2)
(2) Make setting for following items.
In case of PAT test
Other
(Insulation or
Continuity function)
1.ID No
2.SITE No.
3.APPLIANCE CODE
4.DATE No
1.TYPE
2.CIRCUIT No
3.BOARD No
4.SITE No
5.DATA No
● Press the F1(▲) or F2(▼) switch to choose
the parameter to change.
In case of PAT test :
ID No → SITE No → APPLIANCE CODE → DATA No →ID No…..
Other : TYPE → CIRCUIT No → BOARD No → SITE No → DATA No → TYPE…..
● Press ENTER switch to select the parameter to be changed.
● Use F1(▲) or F2(▼) to alter the value of the parameter and confirm with ENTER switch.
The selectable range is shown in the table below.
Type Depending on
test function
ID No 0-99
APPLIANCE
0-99
CODE
TYPE Selection
Continuity r1, r2, rn, R1+R2, R2
Insulation L/L, L/N, L/E, N/E
Loop (L-PE) Zs, Ze
RCD 1st RCCB,
CIECUIT No. 0-99
BOARD No. 0-99
SITE No. 0-99
DATA No. 0-999
(3) A press of F4 or MEM switch saves the measured data.
Note: Pressing ESC switch moves one step back.
2nd RCCB,
3rd RCCB, RCBO
Fig.17-1
Fig.17-2
Data is saved.
60
17.2 Recall the saved data
Save data can be displayed on the LCD according to the following sequence.
(Pressing ESC switch during the adjustment moves one step back.)
(1) Hold down MEM switch 1 sec in stand-by mode
enters RECALL mode and the LCD shows a list of
the save data. (Fig. 17-3)
Fig.17-3
(2)Press ▲(F1) or ▼(F2) switch and select the data
you wish to review, and then press ENTER.
(Fig. 17-4)
Fig.17-4
(3)The selected data will be displayed. (Fig. 17-5)
Fig.17-5
(4) Press F4 (EDIT) switch to edit the parameters that have been set at saving.
The LCD display will be as follows. Change the parameters - procedures are the same as
the saving data – and overwrite and save again; however, DATA No. is unchangeable.
Fig.17-6
61
17.3 Delete the saved data
(1) To delete the saved data:
Press F3 switch in the state as Fig. 17-5 shows to delete data.
Confirmation message appears as shown below.
Press F3 switch to delete data.
Fig.17-7
(2) To delete whole data:
Press F4 switch in the state as Fig. 17-4 shows to delete all data.
Confirmation message appears as shown below.
Press F4 switch to delete all data.
Fig.17-8
62
18 Transfer the stored data to PC
The stored data can be transferred to PC via Optical Adapter Model 8212USB
● How to transfer the data:
(1) Connect Model 8212USB to the USB Port
of a PC. (Special driver for Model 8212USB
should be installed. See the instruction
manual for Model 8212USB for further
details.)
(2) Insert Model 8212USB into the KT66DL as
shown in Fig 18-2. Test leads should be
removed from the KT66DL at this time.
(3) Power on the KT66DL. (Any
function is OK.)
(4) Start special software "KEW Report" on
your PC and set the communication port.
Then click "Download" command, and the data in the KT66DL will be transferred to
your PC. Please refer to the instruction manual of Model 8212USB and HELP of
KEW Report for further details.
Note: Use "KEW Report" version 2.90 or later.
The latest "KEW Report" can be downloaded from our web site.
Fig.18-1
Fig.18-2
63
19. Auto-power-off
This tester has auto-power-off function.
When the tester is inactive for about 10 minutes, it turns off automatically.
Auto-power-off function doesn’t work during a measurement, while applying voltage.
If there’s no key operation for 2 min, backlight will dim automatically. Pressing any key
restores the brightness.
20. Battery and fuse replacement
DANGER
● Do not open the battery compartment cover if the tester is wet.
● Do not replace batteries nor fuse during a measurement. To avoid getting electrical
shock, power off the tester and disconnect all test leads before replacing batteries or
fuse.
● The battery compartment cover must be closed and screwed before making
measurement.
20.1 Battery replacement
Replace batteries with new ones when the battery indicator shows “ ”; battery level is
almost empty.
●Do not mix new and old batteries nor different types of batteries.
●Install batteries in correct polarity as marked inside.
CAUTION
(1) Power off the tester and disconnect all test leads from the terminals.
(2) Unscrew two screws and remove the battery compartment cover. (Fig. 20-1)
(3) Replace all eight batteries with new ones at once. Observe correct polarity when
inserting new batteries, Battery: Size AA Alkaline battery (LR6) x 8 pcs.
(4) Attach the battery compartment cover, and secure it with the two screws,
Note:
Clock setting will be cleared if no batteries were inserted in the tester for 10 min. or longer.
When battery replacement is required, be careful not to exceed this period. If the clock
setting is cleared and restored to the default, please do the setting again.
20.2 Fuse replacement
The continuity test circuit is protected by a 600V 0.5A HRC ceramic type fuse situated in the
battery compartment, together with a spare.
Fuse : F 0.5A 600V (
SIBA 7009463.0,5
Φ
6.3 x 32mm)
64
● Procedures
(1) If the tester fails to operate in the continuity test mode, first disconnect the test leads
from the tester.
(2) Unscrew two screws and remove the battery compartment cover. (Fig. 20-1)
(3) Take out the fuse and check for continuity with another continuity tester. If the fuse has
blown, replace it with the spare fuse.
(4) Attach the battery compartment cover, and secure it with the two screws,
Screw
+
-
+
-
Fuse
-
+
Spare Fuse
-
+
Fig. 20-1
21. Servicing
If this tester should fail to operate correctly, return it to your distributor or directly to Kewtech
stating the exact nature of the fault. Before returning the tester ensure that:
(1) The leads have been checked for continuity and signs of damage.
(2) The continuity mode fuse (situated in the battery compartment) has been checked.
(3) The batteries are in good condition.
Please remember to give all the information possible concerning the nature of the
fault, as this will mean that the tester will be serviced and returned to you more
quickly.
65
22. Case and strap assembly
Attach the strap belt according to the following procedures. By hanging the tester around
the neck, both hands will be left free for testing.
(1) Attach the Buckle to the KT66DL as shown in Fig.22-1.
(2) How to attach the shoulder pad:
(3) How to install the strap belt:
Fig. 22-2
Fig. 22-3
Pass the strap belt down through
the buckle from the top, and up.
Match the hole of the Buckle and the protrusion at
the side face of the KT66DL and slide it upwards.
Fig. 22-1
Lead the shoulder pad through the
strap belt.
(4) How to fasten the strap belt:
Pass the strap through the buckle,
adjust the strap for length and secure.
Fig. 22-4
66
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.