Kewtech KEWISO2, KEWISO1 User Manual

Procedure for Proving LV Systems are Dead
For your safety please read and follow each step carefully!
STEP 1
Check with the user that it is OK to isolate the circuit.
STEP 2
Visually inspect the voltage detector and proving unit that they are not damaged in any way.
STEP 3
Prove your voltage detector is working using your proving unit.
STEP 5
Re-test your voltage detector using your proving unit. Make sure that your voltage detector is working.
STEP 6
Replace the cover on the circuit board and lock off.
STEP 4
Test the circuit you wish to isolate is powered off by checking line-neutral, line-earth and neutral-earth.
STEP 7
Test again on the circuit being worked on. In the case of a ring main, test at the socket and then test the voltage tester in the proving unit again, to
conrm isolation.
STOP!!!
If the voltage detector fails to operate correctly when used with the proving unit remove it from service and start the procedure again with another voltage detector.