Ketotek KT1210W Operating Manual

KT1210W TemperatureController
OperatingManual
1. Overview
Widerangeworkingvoltage.
Supportdelaystartandtimeshutdown.
Heatingorcoolingmodecanbeset.
Allparameterssettingcanbesavedaftershortcircuit.
Canbeusedfordomesticfreezer,watertanks,refrigerator,
industrialchiller,steamer,industrialequipmentandother temperature-controlledsystem.
2. Specifications
PowerSupply:AC90~250V50/60HZ/DC12V/DC24V
Temperaturecontrolrange:-50~110°C
DifferenceSetValue:0.1~30°C
ResolutionRatio:0.1°C(-9.9-99.9);1°C(otherrange)
Measurementaccuracy: ±0.1°C
Controlaccuracy:0.1°C
Measuringinputs:NTC(10K0.5%)Waterproofsensor
Output:RelayContactCapacity10A/220Vnormallyopen
Environmentalrequirements:-20-70°C,humidity20%
-85%RH
Size:75mm(L)*34mm(W)*85mm(Depth)
Holesize:71(L)*29(W)mm
Powerconsumption:Staticcurrent: ≤35MA,attractcurrent:65MA
4. KeyInstruction S:Setkey,Confirmthesettingvalue,EntryandSetparameter.
:powron/off,orquitthesetting.
:increasevalue :decreasevalue
Work:outputindicator Set:Settingindicator
5. KeyOperationInstruction
Innormalworkingstatus,hold 3secondstopoweroff, hold 3secondstopoweron.
Innormalworkingstatus,press S.Theledflash.Press
or toincreaseordecreasethesettingtemperature
value.Press S tosaveitandbacktonormalscreen.
Innormalworkingstatus,press S for3stoentersetmode. Press toswitchfromHC-A7.(seemenucode).Press S toenteranycode,press tochangecodesetting.
Bothpress
3secondstoresetthecontroller.
for
3. WiringDiagram
Connection1:Independentpowersupplyforload
Connection2:Samepowersupplyforload
6. OperationInstruction
Innormalworkingstatus,thescreendisplay RT(realtime temperaturevalue).
Coolingmode: HCsettoC.usecoolerasload.When RT≥ST (temperaturesetvalue)+D(differencevalue),
workindicatorturnon.outputrelayconnect.Loadstartto work.When RTST,workindicatorturnoff,output relaydisconnect,loadstopworking.
Forexample,set10℃,difference3℃,coolerworkwhen
RT≥13℃.coolerstopwhen RT≤10℃.
Forexample,set10,difference3,heaterworkwhen
Heatingmode: HCsettoH,useheaterasload.When
RTST-D,workindicatorturnon.outputrelayconnect. loadstarttowork.When RTST,workindicatorturnoff, outputrelaydisconnect,loadstopworking.
RT≤7.heaterstopwhen RT≥10.
Code explain
HC Heating/Cooling H/C C D ReturnDifference 0.1-30 2.0 LS SetlowLimit -50 -50 HS Sethighlimit +110 110 PU DelayStart 0-90minute 0 CA Tempcorrection -10-10 0.0
Setting Range
Factory Setting
A7 Timingstopoutput 0-999minute 000