KT1210W TemperatureController
OperatingManual
1. Overview
• Widerangeworkingvoltage.
• Supportdelaystartandtimeshutdown.
• Heatingorcoolingmodecanbeset.
• Allparameterssettingcanbesavedaftershortcircuit.
• highControlprecision0.1centigrade
• Canbeusedfordomesticfreezer,watertanks,refrigerator,
industrialchiller,steamer,industrialequipmentandother
temperature-controlledsystem.
2. Specifications
• PowerSupply:AC90~250V50/60HZ/DC12V/DC24V
• Temperaturecontrolrange:-50~110°C
• DifferenceSetValue:0.1~30°C
• ResolutionRatio:0.1°C(-9.9-99.9);1°C(otherrange)
• Measurementaccuracy: ±0.1°C
• Controlaccuracy:0.1°C
• Measuringinputs:NTC(10K0.5%)Waterproofsensor
• Output:RelayContactCapacity10A/220Vnormallyopen
• Environmentalrequirements:-20-70°C,humidity20%
-85%RH
• Size:75mm(L)*34mm(W)*85mm(Depth)
• Holesize:71(L)*29(W)mm
• Powerconsumption:Staticcurrent: ≤35MA,attractcurrent:
≤65MA
4. KeyInstruction
S:Setkey,Confirmthesettingvalue,EntryandSetparameter.
:powron/off,orquitthesetting.
:increasevalue :decreasevalue
Work:outputindicator Set:Settingindicator
5. KeyOperationInstruction
• Innormalworkingstatus,hold 3secondstopoweroff,
hold 3secondstopoweron.
• Innormalworkingstatus,press S.Theledflash.Press
or toincreaseordecreasethesettingtemperature
value.Press S tosaveitandbacktonormalscreen.
• Innormalworkingstatus,press S for3stoentersetmode.
Press toswitchfromHC-A7.(seemenucode).Press
S toenteranycode,press tochangecodesetting.
• Bothpress
3secondstoresetthecontroller.
for
3. WiringDiagram
Connection1:Independentpowersupplyforload
Connection2:Samepowersupplyforload
6. OperationInstruction
• Innormalworkingstatus,thescreendisplay RT(realtime
temperaturevalue).
• ①Coolingmode: HCsettoC.usecoolerasload.When
RT≥ST (temperaturesetvalue)+D(differencevalue),
workindicatorturnon.outputrelayconnect.Loadstartto
work.When RT≤ ST,workindicatorturnoff,output
relaydisconnect,loadstopworking.
• Forexample,set10℃,difference3℃,coolerworkwhen
RT≥13℃.coolerstopwhen RT≤10℃.
•
• Forexample,set10℃ ,difference3℃,heaterworkwhen
Heatingmode: HCsettoH,useheaterasload.When
②
RT≤ ST-D,workindicatorturnon.outputrelayconnect.
loadstarttowork.When RT≥ST,workindicatorturnoff,
outputrelaydisconnect,loadstopworking.
RT≤7℃.heaterstopwhen RT≥10℃.
Code explain
HC Heating/Cooling H/C C
D ReturnDifference 0.1-30 2.0
LS SetlowLimit -50 -50
HS Sethighlimit +110 110
PU DelayStart 0-90minute 0
CA Tempcorrection -10-10 0.0
Setting
Range
Factory
Setting
A7 Timingstopoutput 0-999minute 000