Kestrel DUO-CEL User's Operation Manual

EQUIPMENT: DUO-CEL WRITTEN BY: RKP PUBLICATION: OM_DUO-CEL_USER CHECKED BY: AJC
ISSUE No. & DATE: 1 13/10/10 APPROVED BY: JBJ
PAGE 1 of 6
DUO-CEL
Fire Detection/Alarm Control Panel and Repeater
User Operation Manual
DANGER
THIS EQUIPMENT CONTAINS HAZARDOUS VOLTAGES THAT CAN CAUSE DEATH, SERIOUS PERSONAL INJURY, OR EQUIPMENT DAMAGE.
THIS EQUIPMENT CONTAINS NO USER-SERVICEABLE PARTS. DO NOT REMOVE THE FRONT COVER. REFER ALL MAINTENANCE TO SUITABLY QUALIFIED PERSONNEL.
EQUIPMENT: DUO-CEL WRITTEN BY: RKP PUBLICATION: OM_DUO-CEL_USER CHECKED BY: AJC
ISSUE No. & DATE: 1 13/10/10
PAGE 2 of 6
List of Contents
1. INTRODUCTION .............................................................................................................................................................. 3
2. USER OPERATION - FIRE AND FAULT CONDITIONS ........................................................................................... 3
2.1 IF A FIRE IS DETECTED: ............................................................................................................................................... 3
2.2 TO SILENCE THE FIRE ALARM SOUNDERS: .................................................................................................................. 3
2.3 TO RESOUND THE FIRE ALARM SOUNDERS AFTER SILENCING: .................................................................................... 3
2.4 TO RESET THE PANEL FROM A FIRE ALARM: .............................................................................................................. 3
2.5 TO OPERATE THE FIRE ALARM SOUNDERS IN EVACUATE MODE: ................................................................................ 3
2.6 IF A FAULT IS DETECTED: ........................................................................................................................................... 3
2.7 TO SILENCE THE BUZZER: .......................................................................................................................................... 3
2.8 SYSTEM FAULT INDICATION: ..................................................................................................................................... 3
2.9 USER ACTIONS IN THE EVENT OF A FAULT: ................................................................................................ ................. 4
3. PANEL OPERATION. ....................................................................................................................................................... 4
3.1 DISABLEMENT & TEST CONDITIONS .......................................................................................................................... 4
3.1.1 To test, disable or re-enable one or more circuits: ......................................................................................... 4
3.1.2 To view only the disabled circuits: .................................................................................................................. 4
3.1.3 To view only the circuits in test: ...................................................................................................................... 4
3.2 DISPLAY TEST ............................................................................................................................................................ 4
4. DUO-CEL REPEATER PANEL OPERATION .............................................................................................................. 4
5. ROUTINE TESTING AND MAINTENANCE ................................................................................................................ 4
6. USER RESPONSIBILITIES ............................................................................................................................................. 4
7. DUO-CEL USER INDICATIONS .................................................................................................................................... 5
7.1 USER INDICATIONS .................................................................................................................................................... 5
7.2 USER CONTROLS ........................................................................................................................................................ 6
EQUIPMENT: DUO-CEL WRITTEN BY: RKP PUBLICATION: OM_DUO-CEL_USER CHECKED BY: AJC
ISSUE No. & DATE: 1 13/10/10
PAGE 3 of 6
1. Introduction
This document contains the necessary information for operating the DUO-CEL Conventional Fire Detection control panel.
2. User Operation - Fire and Fault Conditions
This panel is capable of operating the fire alarm sounders in various ways:
Sounder circuits can operate per zone or all
together.
Sounder circuits can be continuous or pulsed. All users should be fully aware of the particular
configuration of their system and should have received training in the basic operation of the system.
The following information is provided as a quick reference guide only.
2.1 If a fire is detected:
On the DUO-CEL Fire Alarm Panel: o The general Fire LED will flash and the buzzer
will sound
o The relevant zone Fire LED(s) will flash,
indicating the location of the fire.
o The Fire Signal output and LED will operate. o The Fire Alarm sounders will operate
immediately (pulsed or continuous, zonally or together, as per configuration).
o The Fire Relay will operate immediately Locate the source of the fire alarm (an LED will be
visible on the detector which has been activated).
2.2 To Silence the fire alarm sounders:
Turn the Access Key to the vertical position. Press the Silence/Resound Alarms button once
only.
The fire alarm sounders will become silent. The General Fire LED and the Zone Fire
LED(s) will become steady.
Remove the Access Controls Key to lock the
controls.
2.3 To Resound the fire alarm
sounders after silencing:
Turn the Access Controls Key on the panel
door to the vertical position.
Press the Silence/Resound Alarms button once
only.
Remove the Access Controls Key to lock the
controls.
2.4 To reset the panel from a Fire Alarm:
After the fire has been extinguished, turn the
Access Controls Key on the panel door to the vertical position.
Press the Reset button. The General Fire LED and the Zone Fire
LED(s) will clear.
Remove the Access Controls Key to lock the
controls.
2.5 To operate the fire alarm sounders in Evacuate Mode:
Turn the Access Controls Key on the panel
door to the vertical position.
Press the Evacuate button. The Alert/Evac LED will illuminate and the
panel buzzer will operate.
All fire alarm sounders will operate
continuously.
Press the Silence/Resound Alarm button to
silence the fire alarm sounders and clear the Alert/Evac LED.
Remove the Access Controls Key to lock the
controls.
2.6 If a fault is detected:
The panel buzzer will sound. The General Fault LED will flash. One or more fault LEDs will flash; identifying
which element of the system is faulty.
When the fault is corrected the fault indication
will clear automatically, except for the Fuse Failed indication, which requires the Reset button to be pressed.
2.7 To Silence the Buzzer:
Press the Silence Buzzer button. The buzzer will silence.
2.8 System Fault Indication:
In the event of a complete system failure, a System Fault will be indicated:
The SYSTEM FAULT and GENERAL
FAULT LED illuminate. All other LEDs will be extinguished.
The internal buzzer will sound continuously.
Warning. In this condition the panel is not functional and fire alarm cover is no longer available.
EQUIPMENT: DUO-CEL WRITTEN BY: RKP PUBLICATION: OM_DUO-CEL_USER CHECKED BY: AJC
ISSUE No. & DATE: 1 13/10/10
PAGE 4 of 6
2.9 User actions in the event of a fault:
Determine the area affected by the fault and
decide whether special actions (such as fire patrols) are needed in that area.
Call your service engineer immediately. Record the event in the system log book.
3. Panel Operation.
3.1 Disablement & Test Conditions
Each zone circuit can be disabled or placed into the test mode individually.
All sounder circuits can be disabled or placed into the test mode as a group.
The Fire Signal output can be disabled or placed into test mode.
3.1.1 To test, disable or re-enable one or more circuits:
1. Turn the Access Key to the vertical position.
2. Press the Select button to enter the Select
Mode.
The Controls On LED will flash. The cursor indication will pulse rapidly on
the yellow Zone 1 fault LED.
The yellow fault LED for any circuit
currently in test or disabled will be illuminated.
3. Press the Select button to move the cursor to
the required circuit fault LED. For each circuit the cursor is on, the General
Disablement & General Test LEDs will indicate the current status for that circuit:
i. General Test & General Disablement LEDS
OFF: - Circuit is in normal operating mode.
ii. General Test LED pulsing: - Circuit is in
Test mode.
iii. General Disablement LED pulsing: -
Circuit is Disabled.
4. To change the status of the selected circuit,
press the Disable or Test button as required: Circuit is currently not disabled or in test: -
Press the Disable button to disable, Press the Test button to test.
Circuit is currently disabled: - Press the
Disable button to re-enable, Press the Test button to test (the disabled condition will also be cleared).
Circuit is currently in test: - Press the Test
button to clear the test, press the Disable button to disable (the test condition will also be cleared).
5. To exit from the Select mode, either remove the
Access Controls Key to lock the controls or press the Select button repeatedly to scroll the flashing cursor through the remaining circuits until the Controls On LED stops flashing and the flashing cursor is cleared.
3.1.2 To view only the disabled circuits:
1. Turn the Access Key to the vertical position.
2. Press and hold the Disable button. Only the
General Disablement LED and the fault LEDs of any disabled circuits will be illuminated.
3. Release the Disable button to return the display
to normal.
3.1.3 To view only the circuits in test:
1. Turn the Access Key to the vertical position.
2. Press and hold the Test button. Only the
General Test LED and the fault LEDs of any circuits in test will be illuminated.
3. Release the Test button to return the display to
normal.
3.2 Display Test
1. Remove the Access Controls Key to lock the
controls.
2. Press the Test button. All LEDs on the display
will illuminate and the internal buzzer will sound for 5 seconds.
4. DUO-CEL Repeater Panel Operation
The repeater panel operation is identical to the Alarm panel except that the disablement & Test facilities cannot be controlled from the repeater.
The display is similar but the Disable and Select buttons are not present.
5. Routine Testing and maintenance
See DUO-CEL Log Book for details.
6. User responsibilities
See DUO-CEL Log Book for details.
EQUIPMENT: DUO-CEL WRITTEN BY: RKP PUBLICATION: OM_DUO-CEL_USER CHECKED BY: AJC
ISSUE No. & DATE: 1 13/10/10
PAGE 5 of 6
7. DUO-CEL User Indications
This section gives an overview of the functions available to the end user.
7.1 User Indications
General Indicator Section
Indicator
Colour
Operating Condition
Supply On
Green
OFF: No mains or battery power, ON: Panel has power (battery and/or mains)
General Fire
Red
OFF: Quiescent, FLASH: New Alarm Condition, ON: Alarm Accepted
General Fault
Yellow
OFF: No faults present, FLASH: One or more faults present
General Test
Yellow
OFF: No circuits in Test, ON: One or more circuits in Test
General Disablement
Yellow
OFF: No circuits Disabled, ON: One or more circuits Disabled
Alert/Evac On
Red
OFF: No Alert or Evacuate, FLASH: Remote Alert/Evacuate active, ON: Panel Evacuate active
Fire Signal On
Red
OFF: Fire Routing output not active, ON: Fire Routing output active
Fire Signal Flt / Dis / Tst
Yellow
OFF: No fault on Fire Routing output, FLASH: Fault on Fire Routing output, ON: Fire Routing output Disabled or in Test
Sounder Flt / Dis / Tst
Yellow
OFF: No Fault on Sounder circuits, FLASH: Fault on one or more Sounder circuits, ON: Sounder circuits Disabled or in Test
System Fault
Yellow
OFF: System is working correctly, ON: System is in the SAFE state (Microcontroller failed or EEPROM data corrupted)
PSU Fault
Yellow
OFF power supply is healthy, FLASH: PSU fault and/or battery fault
Fuse Failed
Yellow
OFF: Auxiliary 24Vdc output available, FLASH: Electronic Fuse on Auxiliary 24Vdc output activated
Earth Fault
Yellow
OFF: No cable faults to Earth, FLASH: One or more cable faults to Earth
Repeater Fault
Yellow
OFF: No Repeater faults, FLASH: One or more Repeater faults
Remote Control Fault
Yellow
OFF: No faults on Remote Control input, FLASH: Fault on Remote Control input
Controls On
Yellow
OFF: User Controls disabled, ON: User Controls enabled, FLASH: Select mode active
SILENCE
BUZZER
SILENCE/
RESOUND
ALARMS
RESET
DISABLE
TEST
SELECT
EVACUATE
1
2
3
4
5
6
7
8
DUO-CEL
SUPPLY ON GENERAL FIRE GENERAL FAULT GENERAL TEST GENERAL DISABLEMENT ALERT/EVAC ON FIRE SIGNAL ON FIRE SIGNAL FLT / DIS / TST SOUNDER FLT / DIS / TST SYSTEM FAULT PSU FAULT FUSE FAILED EARTH FAULT REPEATER FAULT REMOTE CONTROL FAULT CONTROLS ON
Zone Location Indications
Indicator
Colour
Operating Condition
User Zone Location Text
Red
OFF: No Alarm on zone, FLASH: New Alarm on zone, ON: Alarm accepted on zone. NOTE: With Detector/MCP discrimination, the left LED is for MCPs (EVACUATE), the right LED for Detectors (ALERT).
User Zone Location Text
Yellow
OFF: No Fault on zone circuit, FLASH: Fault on zone circuit, ON: Zone circuit Disabled or in Test
EQUIPMENT: DUO-CEL WRITTEN BY: RKP PUBLICATION: OM_DUO-CEL_USER CHECKED BY: AJC
ISSUE No. & DATE: 1 13/10/10
PAGE 6 of 6
7.2 User Controls
SILENCE
BUZZER
SILENCE/
RESOUND
ALARMS
RESET
DISABLE
TEST
SELECT
EVACUATE
1
2
3
4
5
6
7
8
DUO-CEL
SUPPLY ON GENERAL FIRE GENERAL FAULT GENERAL TEST GENERAL DISABLEMENT ALERT/EVAC ON FIRE SIGNAL ON FIRE SIGNAL FLT / DIS / TST SOUNDER FLT / DIS / TST SYSTEM FAULT PSU FAULT FUSE FAILED EARTH FAULT REPEATER FAULT REMOTE CONTROL FAULT CONTROLS ON
Switch
Functionality
Button Availability
Evacuate
Operates all sounders continuously and illuminates the Alert/Evac On LED until the Silence/Resound Alarms button is operated
When controls are unlocked.
Silence Buzzer
Silences the internal buzzer on the Panel & Repeaters.
When controls are locked or unlocked
Silence/Resound
Alarms
When any sounders are active, press to silence sounders. Press again to resound the silenced sounders.
When controls are unlocked
Reset
Press to clear any fault & alarm conditions and return the panel to the quiescent state
When controls are unlocked
Disable
Displays Alarm Counter
When controls are locked
Illuminates only the currently disabled circuits
When controls are unlocked
Toggles the selected circuit between Disabled & Enabled states.
When controls are unlocked and in circuit select mode
Test
Press to illuminate all LEDs and sound the buzzer for 5 seconds.
When controls are locked Illuminates only the circuits currently in test
When controls are unlocked
Toggles the selected circuit between Test & Normal states.
When controls are unlocked and in circuit select mode
Select
First operation enables the circuit select mode; subsequent operations move the flashing cursor through the available circuits until the last circuit, then exits the circuit select mode.
When controls are unlocked
Access Controls Keyswitch