EQUIPMENT: DUO-CEL WRITTEN BY: RKP
PUBLICATION: OM_DUO-CEL_USER CHECKED BY: AJC
ISSUE No. & DATE: 1 13/10/10
PAGE 3 of 6
1. Introduction
This document contains the necessary information
for operating the DUO-CEL Conventional Fire
Detection control panel.
2. User Operation - Fire and Fault
Conditions
This panel is capable of operating the fire alarm
sounders in various ways:
Sounder circuits can operate per zone or all
together.
Sounder circuits can be continuous or pulsed.
All users should be fully aware of the particular
configuration of their system and should have
received training in the basic operation of the
system.
The following information is provided as a quick
reference guide only.
2.1 If a fire is detected:
On the DUO-CEL Fire Alarm Panel:
o The general Fire LED will flash and the buzzer
will sound
o The relevant zone Fire LED(s) will flash,
indicating the location of the fire.
o The Fire Signal output and LED will operate.
o The Fire Alarm sounders will operate
immediately (pulsed or continuous, zonally or
together, as per configuration).
o The Fire Relay will operate immediately
Locate the source of the fire alarm (an LED will be
visible on the detector which has been activated).
2.2 To Silence the fire alarm sounders:
Turn the Access Key to the vertical position.
Press the Silence/Resound Alarms button once
only.
The fire alarm sounders will become silent.
The General Fire LED and the Zone Fire
LED(s) will become steady.
Remove the Access Controls Key to lock the
controls.
2.3 To Resound the fire alarm
sounders after silencing:
Turn the Access Controls Key on the panel
door to the vertical position.
Press the Silence/Resound Alarms button once
only.
Remove the Access Controls Key to lock the
controls.
2.4 To reset the panel from a Fire
Alarm:
After the fire has been extinguished, turn the
Access Controls Key on the panel door to the
vertical position.
Press the Reset button.
The General Fire LED and the Zone Fire
LED(s) will clear.
Remove the Access Controls Key to lock the
controls.
2.5 To operate the fire alarm sounders
in Evacuate Mode:
Turn the Access Controls Key on the panel
door to the vertical position.
Press the Evacuate button.
The Alert/Evac LED will illuminate and the
panel buzzer will operate.
All fire alarm sounders will operate
continuously.
Press the Silence/Resound Alarm button to
silence the fire alarm sounders and clear the
Alert/Evac LED.
Remove the Access Controls Key to lock the
controls.
2.6 If a fault is detected:
The panel buzzer will sound.
The General Fault LED will flash.
One or more fault LEDs will flash; identifying
which element of the system is faulty.
When the fault is corrected the fault indication
will clear automatically, except for the Fuse
Failed indication, which requires the Reset
button to be pressed.
2.7 To Silence the Buzzer:
Press the Silence Buzzer button.
The buzzer will silence.
2.8 System Fault Indication:
In the event of a complete system failure, a System
Fault will be indicated:
The SYSTEM FAULT and GENERAL
FAULT LED illuminate. All other LEDs will
be extinguished.
The internal buzzer will sound continuously.
Warning. In this condition the panel is not
functional and fire alarm cover is no longer
available.