the installation and operation of the Kepco RKW 50W
Series of Open Frame. PFC (Power Factor Corrected),
RoHS (Reduction of Hazardous Substances) compliant
switching power supplies.
DESCRIPTION. The Kepco RKW 50W Series consists of
six models of switching power supplies, with a single output
as shown in Table 1. Units may be operated with a nominal
100V a-c to 240V a-c (input voltage range 85 to 265 Va-c),
50-60 Hz (input frequency range 47-66Hz; units operate up
to 440Hz although leakage current, power factor and efficiency specifications may not be met.) They will also operate on 110V to 370V d-c input. The RKW 50W Series
employs a forward converter with a fixed switching frequency of approximately 140kHz. Power Factor Correction
(PFC) is provided by a boost converter operating at 80kHz.
Regulation is provided by pulse width modulation. A therm-
RKW
50W SERIES
istor circuit prevents excessive turn-on current surge.
Remote programming of output voltage using an external
resistance can be implemented. Overvoltage and overcurrent protection is provided. Current limiting with automatic
recovery from short circuit is featured. Units are convection
cooled L-chassis construction. A steel cover (Model
CA 34-R) is available as an option (contact factory for derating with cover).
Specifications and operating limits for individual RKW 50W
models are listed in Table 1. Section II describes RKW 50W
features. Section III contains specifications and operating
limits common to all RKW 50W Series Models. Section IV
describes installation and Section V describes operation.
TABLE 1. OUTPUT RATINGS AND SPECIFICATIONS, RKW 50W SERIES
MODEL
OUTPUT VOLTS, d-c
ADJUSTMENT RANGE, Vd-c
OUTPUT CURRENT (AMPS)
-10 to +50 °C
CURRENT LIMIT
SHORT CIRCUIT CURRENT
OVP SETTING
EFFICIENCY
RIPPLE
AND
(3)
NOISE
(mV p-p)
External Potentiometer
(1)An overvoltage shuts down the output. Recover by recycling a-c input (30 second delay required before resetting).
(2)The current limit is rectangular. After the overload is removed, output is automatically restored.
(3)Bandwidth 100 MHz. Ripple and noise will be approximately 1.5 times these values in the operating temperature range -10 ~ 0°C. The ripple
and noise values tabulated are valid when the output is derated as shown in figure 2 from 50 ~ 65°C
(4)Used for remote programming of output voltage. See Section IV OPERATION, REMOTE VOLTAGE PROGRAMMING.
(5)Peak Current: 3.2A (useful for motor start applications). Thermal protection (24V model only) cuts off output voltage if overtemperature
detected; after sufficient cooling, recover by cycling a-c input.
The following specifications are at nominal input voltages
at 25°C unless otherwise specified.
INPUT:
Voltage: 100-240V a-c nominal; Range 85-265V a-c
(0 to 100% load, -10 to 71°C); 110-370V d-c.
(polarity insensitive; consult factory) Safety
agency approval applies only to a-c input operation.
Frequency: Nominal 50-60 Hz; Range 47-440Hz
to 100% load, -10 to 71°C),
(at 440Hz leakage cur-
rent exceeds UL/VDE safety specification limit).
Current (nominal output at 100% load):
@100-120V a-c rms:
5V - 48V models: 0.8A a-c rms max.
3.3V model: 0.7A rms max.;
@200-240V a-c rms:
5V - 48V models:
0.4A a-c rms max.
3.3V model: 0.35A rms max.;
Input Protection and Soft Start: Thermistor circuit
reduces start-up surge. Units are protected
against shorts by an input fuse. Fuse value 2A,
250V (Littelfuse P/N: 215002PG, Kepco P/N 541-
0040).
Initial Turn-on Surge: (cold start 25 °C, first surge
only, not including the current flow into the EMI filter):
@100V a-c rms: 14A typ.,
@200V a-c rms: 28A typ.
Switching Frequency: 140kHz typical, PFC boost
converter: 80kHz typical, nominal load
LEAKAGE CURRENT:
@120V a-c and 60 Hz: 24mA max, 0.15mA typ.
@240V a-c and 60 Hz: 0.48mA max, 0.30mA typ.
(operating in conformance with UL 1950/IEC 950)
POWER FACTOR:
@100V a-c: 0.99 typ.
@200V a-c: 0.95 typ.
STABILIZATION:
Source Effect (Range 85 to 132Va-c or
170-265 Va-c): 0.1% typ., 0.2% max.
Load Effect measured at sensing terminals
(0% - 100% of rated output current):
0.1% typ., 0.4% max.
Temperature effect (-10 to 71°C):
0.5% typ., 1.0% max.
Combined effect: 0.9% typ., 1.8% max.
Drift (1/2 to 8 hr. at 25°C): 0.2% typ., 0.5% max.
(0
• SEMI-47 compliant
• RoHS compliant
• DIN-Rail mountable
• Remote Voltage Programming
• Parallel/Series Operation
NOTE:
SEE FIGURE 4 FOR MOUNTING DIRECTION.
MOUNTING A, WITHOUT COVER
MOUNTING B, C, WITHOUT COVER
MOUNTING A, WITH COVER
MOUNTING C, WITH COVER
MOUNTING B, WITH COVER
(*)
100
)
90
%
(
g
80
n
i
t
a
70
R
r
60
e
w
o
50
P
t
u
40
p
t
u
30
O
20
10
-20
FIGURE 1. OUTPUT POWER VS. TEMPERATURE
THE POWER SUPPLY WILL
STARTUP BETWEEN -20
AND -10°C BUT MAY
NOT MEET PUBLISHED
SPECIFICATIONS.
-1001020 254035
Ambient Temperature (°)
(*) 24 VOLT MODEL: RMS OUTPUT POWER
30
45
55
5060
71
TRANSIENT RECOVERY: A step load change from
50% to 100% of rated output current in 50 microseconds
or more, produces no more than 4% output voltage excursion. Recovery time is 1ms maximum.
OUTPUT HOLDING TIME: Upon input interruption
the output is maintained for:
@100V a-c:
5V to 48V Models: 40 mS typ. (20 mS min.)
3.3V Model: 30 mS typ. (20 mS min.)
@240V a-c:
5V to 48V Models: 50 mS typ. (25mS min.).
3.3V Model: 40 mS typ. (25 mS min.)
START UP TIME:
@100V a-c: 500mS max., 300mS typ.
@240V a-c: 200mS max., 100mS typ.
OVERVOLTAGE PROTECTION: Fixed, factory set.
See Table 1. The overvoltage circuit is set by Zener diode
clamp, latching will occur.
OVERCURRENT: Square type, output voltage returns
to rated level upon removal of cause of malfunction.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
OPERATING TEMPERATURE: -10 to 71°C (start up 20 to -10°C). See the derating, Figure 1. Do not allow the
power supply to become dust covered because that will
decrease the cooling efficiency of the unit and cause insulation to deteriorate.
STORAGE TEMPERATURE: -30°C to + 75°C.
COOLING: Natural convection.
ORIENTATION: Vertical or horizontal.
HUMIDITY: 10% to 95% RH, operating and storage,
noncondensing, wet bulb temperature < or = 35°C.
DIELECTRIC STRENGTH: (at 15 to 35°C ambient, 10
to 85% relative humidity, cutout current 20 ma):
Between input and output terminals:
3.0 KV a-c for one minute.
Between input terminals and ground:
2 KV a-c for one minute.
Between output terminals and ground:
500V a-c for one minute.
INSULATION RESISTANCE: Between input and out-
put, input and ground, output and ground: 100
megohms minimum (500V d-c, 15 to 35°C ambient, 10 to 85% relative humidity)
VIBRATION: Three axes, one hour each, sweep time 10
SHOCK: (non-operating, one-half sinusoidal pulse, three
shocks to each axis):
Acceleration: 60G (588m/s
Duration: 11mS +
5mS
2
),
EMC - EMISSIONS:
Radiated Noise 30MHZ to 1GHz:
FCC Class B, VCCI-B, EN55011-B, EN55022-B
Conducted Noise 0.15MHz to 30MHz:
FCC Class B, VCCI-B, EN55011-B, EN55022-B
Input Harmonics (on AC Mains) 0 to 2kHz:
EN 61000-3-2.
EMC - IMMUNITY:
ESD: EN 61000-4-2 Level 4, Normal operation.
Radiated Field Noise:
EN 61000-4-3 Level 3, Normal operation.
Electrical Fast Transient/Burst (EFT):
EN 61000-4-4 Level 3, Normal operation.
Surge: EN 61000-4-5 Level 4, no damage.
Conducted Noise:
EN 61000-4-6 Level 3, Normal operation.
Power Frequency Magnetic Field:
EN 61000-4-8 Level 4, Normal operation.
Voltage Dips, Short Interruptions, Voltage Variation:
EN 61000-4-11, Normal operation.
SAFETY: All units designed to meet EN 60950 (U.S. UL
60950 3rd Ed.; Canada: CAN/CSA-22.2 No. 60950-00 3rd
Ed. (ambient temp. 50°C). RKW 50W units are CE marked
per the Low Voltage Directive (LVD), EN60950. [The standards do not apply with DC input operation.]
WEIGHT: 13.3 oz. (380 grams) max
WARRANTY: One year.
IV — INSTALLATION
MOUNTING THE POWER SUPPLY: Refer to Fig-
ures 4 and 5. The unit may be mounted on one mounting
surface. Note the restrictions for maximum penetration of
mounting screws. The air surrounding the power supply
must not exceed the ambient values given in the graph in
Figure 1.
CONNECTIONS: Connect the load to the power supply
as shown in Figure 3A, B or C. The unit is shipped with
shorting links in place for Local sensing. The AC input
power is applied via the terminal block. Make sure to connect the AC input Neutral, Line and Ground wires to the
respective terminals of the terminal block (see Figure 2).
Sensing (either Local or Remote) MUST be used.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
LOCAL/REMOTE SENSING: Figure 3 shows proper
connection of multiple loads using either remote or local
sensing. If local or remote sensing is not configured,the unit will not work properly. The unit is shipped with
shorting links in place for Local sensing. For remote sensing, remove the shorting links and connect the +S and –S
terminals to the load. Remote sensing compensation is up
to 0.4V per load wire (0.15V for RKW 3.3-12K, 0.25V for
RKW 5-10K). Transient recovery specs may not be met
when remote sensing is used. If oscillations set off overvoltage protection, install one electrolytic capacitor (470µF
min) between +S and + and one between – and –S terminals.
Page 4
V — OPERATION
When output voltage is available, the green LED is on.
The Output Voltage Adjust trimmer (see Figure 2) allows
adjustment of the output voltage within the range specified
in Table 1.
FIGURE 2. COMPONENT LOCATIONS
REMOTE VOLTAGE PROGRAMMING: In addition
to the integral trimmer, output voltage can also be
adjusted via an external variable resistance (see Figure
3B). The variable resistance specified in Table 1 must be
substituted for the shorting link between + and +S terminals. Note that load effect for RKW 50W is increased
using this technique, and may exceed values listed above
under STABILIZATION.
SERIES OPERATION: When a number of power supplies are operating in series, the current rating is to be limited to the rating of the power supply with the lowest
rating. A diode (Vr>2 Vo, If>2Io, Vf<< low) must be con-
Σ
nected to the power supply output terminals to protect the
unit from reverse voltage.
PARALLEL OPERATION: Identical units may be operated in parallel for increased current capability. Use either
local or remote sensing for all supplies in the parallel
group.
FIGURE 3. LOAD CONNECTIONS
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102