installation, checkout and operation of the KDA 24 Series
Alarm Modules.
DESCRIPTION. The Kepco KDA 24 Series Alarm modules are designed to monitor two 24V power supplies, and
provide an alarm indication (both visual and Form “C” relay)
when voltage is not within a preset range. The KDA 24R
models contain built-in blocking (also called ORing or isolation) diodes needed for parallel-redundant configurations.
KDA 24A is designed to monitor two independent power
supplies; it includes neither blocking diodes nor reverse
protection diodes.
Each alarm module has two identical circuits (A and B), one
for each input. For KDA 24R these circuits are internally
connected for parallel redundancy of the two input power
supplies (see Figure 2). For KDA 24A the two circuits are
completely independent (see Figure 3).
KDA 24
SERIES
Trimpot adjustments from the front (see Figure 1) allow
independent adjustment of high and low alarm ranges for
both inputs. When input voltage is within the preset range,
the internal alarm relay energizes and the OK contact is
connected to COM. If voltage is out of range, the relay deenergizes and the FAIL contact is connected to COM. In
addition, the DC OK indicator turns off and the appropriate
OV (overvoltage) or UV (undervoltage indicator turns on.
Screw terminal connections available at the front panel
(top) provide easy access to FAIL, OK, and COM relay contacts.
USER CONFIGURABLE OPTIONS. KDA 24 Series
are supplied with the DIN Rail clips rotated 180 degrees.
Plugs are included to cover the HIGH and LOW trimpots if
desired to prevent unauthorized adjustments once they
have been preset.
II — FEATURES
• Screw terminals for easy access wiring connections (see “Connections” on page 4 for details).
• Case acts as heat sink with no external fins or
extrusions.
• Dual Input.
• Wide Input Operating Range: 12 - 35V d-c.
• Alarm settings maintained within ±1% after setting.
• Suitable for n+1 redundancy applications of 24V
d-c power systems (KDA 24R).
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
Nominal 24V d-c, Operating Range: 12V** to 35V d-c
** Consult factory for operation below 24V nominal.
NUMBER OF INPUTS:
Two (2): A and B
INPUT AND OUTPUT CURRENT: Per input:
30A max.
NOTE: For parallel operation of both circuits
maximum output current of each circuit
must not exceed 30A.
VOLTA G E D R O P: Input to Output
0.5V d-c typ.
REVERSE OUTPUT VOLTAGE:
45V d-c max
ALARM, INPUT VOLTAGE (UNDERVOLTAGE):
Indicators (A and B): UV LED
— Relays (A and B): isolated contacts rated at
28V d-c/1A or 115V a-c/0.5A
— Range: See Figure 5 and Table 2.
— Factory preset: See Figure 5 and Table 2.
— Hysteresis: See Figure 5 and Table 2.
ALARM, INPUT VOLTAGE (OVERVOLTAGE):
— Indicators (A and B) OV LED
— Relays (A and B): isolated contacts rated at
28V d-c/1A or 115V a-c/0.5A
— Range: See Figure 5 and Table 2.
— Hysteresis: See Figure 5 and Table 2.
— Factory preset: See Figure 5 and Table 2.
KDA 24A
Independent
KDA 24R
Parallel Redundant
ENVIRONMENTAL CHARACTERISTICS
OPERATING TEMPERATURE (35V INPUT MAX.):
KDA 24A:-10 to +60°C (all orientations)
KDA 24R:-10 to +50°C (100% load, Figure 7)
-10 to +60°C (60% load, Figure 7)
-10 to +30°C (mounting other than
shown in Figure 4.)
STORAGE TEMPERATURE: -25°C to +85°C
COOLING: Natural convection.
GENERAL CHARACTERISTICS
ISOLATION VOLTAGE:
Between input and ground: 500V.
Between output and ground: 500V.
Relay contacts are galvanically isolated.
SAFETY: All units designed to meet UL 508, UL
60950, TÜV Rheinland EN60950 and EN 60529 (category
IP 20); KDA 24 units are CE marked per the Low Voltage
Directive (LVD), EN60950.
CONNECTIONS: Screw terminals: M3 slotted (use
cabinet tip screwdriver, flat, (0.125” [3mm] x 0.020”
[0.5mm]); Wire gage: solid/stranded AWG (mm
2
): 24-12
(0.25-2.5); strip length: 5/16 in. [8mm], max torque: 5 lb.-in
[0.5Nm].
WARRANTY: One year.
WEIGHT: KDA 24A: 0.5 lbs. (0.255 kg.)
KDA 24R: 1.0 lbs. (0.454 kg.)
DIMENSIONS:
See Figure 6.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
with DIN Rail mounting clips that accommodate: NS
35mm and 32 mm G DIN rails. DIN clips may be reversed
for convenience. The unit may also be chassis mounted
by removing the two clips and using four 4-40 screws
where the clips were installed. See Figure 6 for outline
dimensions. Refer to Figure 4 for operating temperature
derating of KDA 24R models only.
INPUT CONNECTIONS. Input connections are routed
from the bottom and secured via screw terminals from the
front.
KDA 24R. This model consists of two identical channels
(A and B) that connect two power supplies in parallel as
shown in Figure 2. ORing (blocking) diodes are built-in.
Connections to the load must be made through external
distribution points. V– terminal must not be used as distribution points. See Figure 2 for connections; see Figure 1
for component locations.
KDA 24A. This model consists of two independent identical channels (A and B). Each channel may be used to
monitor a voltage for overvoltage and undervoltage. See
Figure 3 for connections; see Figure 1 for component locations.
ALARM CONNECTIONS. Alarm connections are
routed from the top and secured via screw terminals from
the front.
ALARM RELAY. The alarm relay is normally energized
as long as input power is within the HIGH and LOW alarm
setting. Isolated alarm relay contacts of each channel are
available from the front panel: COM (common), Normally
Closed (FAIL) and Normally Open (OK).
DC OK INDICATOR. As long as input voltage is within
the High and Low alarm settings the DC OK indicator lights
green. If an alarm occurs (either undervoltage or overvoltage detected) the DC OK indicator of KDA 24A and KDA
24R models goes from green to off. DC OK returns to
green when input voltage is again within range.
NOTES:
1. FOR MOUNTING OF KDA 24R IN ORIENTATION
OTHER THAN SHOWN BELOW, MAX. OPERATING
TEMPERATURE IS 30°C. RESTRICTION DOES NOT
APPLY TO KDA 24A.
2. 1/2 INCH MINIMUM SEPARATION REQUIRED
BETWEEN KDA 24R AND ANY OTHER HEAT PRODUCING MODULE ON THE DIN RAIL.
SEE NOTE 2
3043540
FIGURE 4. RECOMMENDED MOUNTING ORIENTATION
AIR FLOW
OF MODEL KDA 24R
V — OPERATION
SETTING HIGH AND LOW ALARMS. High (overvolt-
age) and low (undervoltage) alarms for channels A and B
are set independently. To set the alarm limits for a channel,
connect a variable +24V power supply to the channel input
as described in the paragraph titled “Input Connections.”
on page 5 and monitor the power supply output voltage
using a DVM. Hysteresis causes the alarm to trip at a
slightly different value depending on whether the voltage is
decreasing or increasing. Hysteresis must be taken into
account when setting the alarm trip points. Figure 5 shows
this effect. The factory default adjustment values are
shown in Table 2, as well as the guaranteed adjustment
range (actual adjustment range may slightly exceed guaranteed values).
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
To change the HIGH and/or LOW trimpot settings (within
the ranges listed in Table 2) Kepco recommends using an
insulated adjustment tool, Bourns H-90 (Kepco P/N 2181185 or equivalent. In addition, a variable output power
supply with a range exceeding the minimum and maximum
values listed in Table 2 is required. A DVM may be necessary to monitor the power supply output.
Each channel is independent and may be adjusted in any
order.
NOTE: Once all LOW and HIGH alarm adjustments are
acceptable, refer to “Securing Alarm Adjustments”
on page 7 to secure the adjustments.
Low Alarm (Undervoltage) Adjustment. If the
factory adjusted values are not acceptable, proceed as
follows to adjust the low alarm pick-up and drop-off voltages (V2 and V1 of Figure 5). See Table 2 for the adjustment range
Note: Once all LOW and HIGH alarm adjustments are
acceptable, refer to “Securing Alarm Adjustments”
on page 7 to secure the adjustments
1. Connect a variable output power supply (with a range
exceeding the minimum and maximum values listed in
Table 2) to the channel input as described in the paragraph titled “Input Connections.” on page 5. Toggle
voltage points may be monitored using the visual indicators (yellow UV, green DC OK and red OV lights) or
monitoring the relay contacts.
2. Turn the LOW trimpot fully CW, then adjust the power
supply to the desired LOW threshold voltage (UVP, V2
OV LIGHT ON
OV LIGHT OFF
GUARANTEED ADJUSTMENT
RANGE
MINMAX
FACTORY DEFAULT
VAL UES
(±2%)
shown in Figure 5). If necessary, use a DVM to monitor the power supply voltage.
3. Observe that the UV (yellow) light is lit; no other lights
are lit (relay is deenergized). Slowly (approximately
one complete turn in five seconds) turn the LOW trim
pot CCW until the toggle point (yellow UV LED goes
out, green DC OK goes on, and the relay energizes).
This is V2 - UVP (undervoltage pick-up voltage) as
indicated in Figure 5 and Table 2.
4. To verify the settings lower the voltage of the variable
power supply by about 1.2V. Observe that the yellow
UV light is lit; no other lights are lit (relay is deenergized).
5. Then slowly increase the voltage until the toggle point
occurs (yellow UV LED goes out, green DC OK light
goes on, and the relay energizes).
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
6. Verify that this toggle point is the desired value for UVP
voltage. If this voltage is not correct, proceed to step 7
for fine tuning. If this voltage is correct, slowly lower the
variable power supply voltage and verify that value of
UVD (V1, Figure 5) is adequate (Hysteresis value 0.6V
typ. see Figure 5)
7. If the toggle point is missed, fine tune as follows: Adjust
power supply voltage to the desired UVP value (Undervoltage pick-up voltage). Turn the LOW trimpot CW
about two to three turns until the system toggles back
again (yellow UV light on, DC OK light off, relay deenergized). Very slowly turn LOW trimpot CCW until the
toggle point is reached: yellow UV light goes out, green
DC OK light goes on, and the relay energizes. Reverify
again per step 6.
High Alarm (Overvoltage) Adjustment. If the factory adjusted values are not acceptable, proceed as follows
to adjust the high alarm pick-up and drop-off voltages (V3
and V4 of Figure 5). See Table 2 for the adjustment range
NOTE: Once all LOW and HIGH alarm adjustments are
complete, refer to “Securing Alarm Adjustments”
on page 7 to secure the adjustments.
4. To verify the settings lower the voltage of the variable
power supply by about 2V. Observe that the green DC
OK light is lit, relay is deenergized and red OV LED is
off.
5. Slowly increase the voltage until the toggle point
occurs (red OV LED goes on, no other lights are lit and
the relay deenergizes.
6. Verify that this toggle point is the desired value for OVP
voltage. If this voltage is not correct, proceed to step 7
for fine tuning. If this voltage is correct, slowly lower the
variable power supply voltage and verify that value of
OVD (V3, Figure 5) is adequate (Hysteresis value 0.9V
typ. see Figure 5)
7. If the toggle point is missed, fine tune as follows: Adjust
power supply voltage to the desired OVP value (Overvoltage pick-up voltage). Turn the HIGH trimpot CW
about two or three turns until the system toggles back
again (green DC OK light is lit, relay is deenergized
and red OV LED is off). Very slowly turn HIGH trimpot
CCW until the toggle point is reached: red OV LED
goes on, no other lights are lit and the relay deenergizes. Reverify again per step 6.
1. Connect the variable power supply described above to
the channel input as described in the paragraph titled
“Input Connections.” on page 5. Toggle voltage points
may be monitored using the visual indicators (yellow
UV, green DC OK and red OV lights) or monitoring the
relay contacts.
2. Turn the HIGH trimpot fully CW, then adjust the power
supply to the desired HIGH threshold voltage (OVP, V4
shown in Figure 5). If necessary, use a DVM to monitor
the power supply voltage.
3. Observe that the green DC OK light is lit and relay is
deenergized. Slowly (approximately one complete turn
in five seconds) turn the HIGH trim pot CCW until the
toggle point (red OV LED goes on, no other lights are
lit and the relay deenergizes.
Securing Alarm Adjustments. Once HIGH and LOW
alarm settings for both channels are acceptable, the adjustments can be covered to prevent tampering by installing
four plugs (supplied) into the trimpot adjustment access
holes (see Figure 7). Once these plugs have been
installed, they can only be removed by first removing the
KDA cover (remove two screws and slide cover off) and
then releasing the plug prongs while pushing the plug out.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102