KEPCO KDA 24V User Manual

Page 1
OPERATOR MANUAL
An ISO 9001 Company.
KDA 24 SERIES
ALARM MODULE

I — INTRODUCTION

SCOPE OF MANUAL. This Operator Manual covers the

installation, checkout and operation of the KDA 24 Series Alarm Modules.

DESCRIPTION. The Kepco KDA 24 Series Alarm mod­ules are designed to monitor two 24V power supplies, and provide an alarm indication (both visual and Form “C” relay) when voltage is not within a preset range. The KDA 24R models contain built-in blocking (also called ORing or isola­tion) diodes needed for parallel-redundant configurations. KDA 24A is designed to monitor two independent power supplies; it includes neither blocking diodes nor reverse protection diodes.

Each alarm module has two identical circuits (A and B), one for each input. For KDA 24R these circuits are internally connected for parallel redundancy of the two input power supplies (see Figure 2). For KDA 24A the two circuits are completely independent (see Figure 3).
KDA 24
SERIES
Trimpot adjustments from the front (see Figure 1) allow independent adjustment of high and low alarm ranges for both inputs. When input voltage is within the preset range, the internal alarm relay energizes and the OK contact is connected to COM. If voltage is out of range, the relay de­energizes and the FAIL contact is connected to COM. In addition, the DC OK indicator turns off and the appropriate OV (overvoltage) or UV (undervoltage indicator turns on.
Screw terminal connections available at the front panel (top) provide easy access to FAIL, OK, and COM relay con­tacts.

USER CONFIGURABLE OPTIONS. KDA 24 Series are supplied with the DIN Rail clips rotated 180 degrees. Plugs are included to cover the HIGH and LOW trimpots if desired to prevent unauthorized adjustments once they have been preset.

II — FEATURES

• Screw terminals for easy access wiring connec­tions (see “Connections” on page 4 for details).
• Case acts as heat sink with no external fins or extrusions.
• Dual Input.
• Wide Input Operating Range: 12 - 35V d-c.
• Alarm settings maintained within ±1% after set­ting.
• Suitable for n+1 redundancy applications of 24V d-c power systems (KDA 24R).
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
©2011, KEPCO, INC 1 Data subject to change without notice 228-1694 REV 4
• Built-in isolation (ORing) diodes (KDA 24R).
• Alarm relay, isolated contact outputs: N.C., COM, N.O.
• Mounting: DIN rail NS35 MM styles or G-32MM styles or panel/chassis screw mounting; DIN clips are reversible.
• Dual DC OK LED (green).
• Dual Undervoltage LEDs (yellow).
• Dual Overvoltage LEDs (red).
Page 2
KDA 24R KDA 24A
Note: Channels A and B are Identical.
CHANNEL A
CHANNEL B
Note: Channels A and B are Identical.
CHANNEL BCHANNEL A
4
5
OK
FAIL
A
COM
123
12 3
OKDC
B
A
COM
OVUVUV OV
OK
FAIL
B
6
BA
HIGHHIGH
LOWLOW
++-+ - +
BA
10
11
10
11
7
8
9
VOLTAGE LIMIT ADJ.
LEGE ND: 1
COM Terminal (Alarm Relay Common)
Wire routed from top.
2
OK Terminal (Alarm Relay N.O contact)
Relay normally energized when input power OK; provides connection from COM to OK. Wire routed from top.
3
UV Indicator
Lights yellow when input voltage is below LOW setting.
4
OV Indicator
Lights red when input voltage is above HIGH setting.
5
FAIL Terminal (Alarm Relay N.C contact)
Relay deenergizes for alarm; provides connection from COM to FAIL. Wire routed from top.
6
DC OK Indicator
Lights green when input voltage is within HIGH and LOW settings. Light goes off if alarm detected.
4
5
4
321
5
OVUV UV OV
OK
COM
FAIL
COM
A
DC OK
A B
OK
FAIL
B
6
4
321
5
6
6
A B
8
7
9
7
8
9
11
7
LOW trimpot
HIGH HIGH
LOW LOW
VOLTAGE LIMIT ADJ.
+ -- +
BA
7
8
9
11
Adjusts undervoltage (UV) setpoint.
8
HIGH trimpot
Adjusts overvoltage (OV) setpoint.
OUT+ Terminal (KDA 24R only)
9
V+ Terminal (KDA 24A only)
Wire routed from bottom; see appropriate connection diagram.
IN+ Terminal (KDA 24R only)
10
Wire routed from bottom; see appropriate connection diagram.
V- Terminal
11
Wire routed from bottom; see appropriate connection diagram.
3043505

FIGURE 1. KDA 24 SERIES COMPONENT LOCATIONS

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
2 228-1694 REV 4 062411
Page 3
24V PS1
24V PS2
+
+
REQUIRED EXTERNAL
DISTRIBUTION
POINT
(SEE
NOTE 1.)
(SEE
NOTE 1)
IN+
IN+
KDA 24R
OR-ING
DIODE
HIGH
VOLTAGE
LOW
(YELLOW)
UV
MONITOR
DC OK
(GREEN)
OV
(RED)
V-
NC
NO
ALARM RELAY
COM
OUT+
FAIL COM
OK
OPTIONAL
EXTERNAL
DISTRIBUTION
POINT
(+)
+
CHANNEL A
LOAD
V-
(RED)
UV
(YELLOW)
LOW
OV
HIGH
VOLTAGE MONITOR
DC OK
(GREEN)
OR-ING DIODE
CHANNEL B
ALARM RELAY
NO
COM
NC
OK COM FAIL
OUT+
3043497
3043493
NOTES:
1. V- TERMINAL MUST NOT BE USED AS DISTRIBUTION POINT.
2. WIRES CONNECTED TO KDA 24-R MUST BE RATED FOR MAXIMUM CURRENT OF POWER SUPPLY.
3. WIRES CONNECTED TO LOAD MUST BE RATED FOR AT LEAST TWICE MAXIMUM CURRENT OF POWER SUPPLY.

FIGURE 2. KDA 24R, TYPICAL CONNECTION DIAGRAM

KDA 24A
CHANNEL
A
CHANNEL
B
V+
HIGH
VOLTAGE MONITOR
LOW
OV
(RED)
UV
OV
(RED)
(YELLOW)
(YELLOW)
LOW
HIGH
UV
VOLTAGE MONITOR
V-
V-
V+
DC OK
(GREEN)
CHANNEL A
CHANNEL B
DC OK
(GREEN)
NC
NO
ALARM RELAY
ALARM RELAY
NO
NC
COM
COM
FAIL COM
OK
OK COM
FAIL
(+)
(-) (-)
(+)

FIGURE 3. KDA 24A TYPICAL CONNECTION DIAGRAM

KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A.  TEL (718) 461-7000  FAX (718) 767-1102
062411 228-1694 REV 4 3
http://www.kepcopower.com email: hq@kepcopower.com
Page 4

III — SPECIFICATIONS

Specifications for each model are listed below.

TABLE 1. FEATURE SUMMARY, KDA 24 SERIES

SPECIFICATION
Reverse Voltage Protection Yes Yes
ORing (blocking) diodes No Yes
Undervoltage LED Yellow = Alarm Yellow = Alarm
Overvoltage LED Red = Alarm Red = Alarm
Input DC OK LED Green = DC OK Green = DC OK

INPUT CHARACTERISTICS:

INPUT VOLTAGE:
Nominal 24V d-c, Operating Range: 12V** to 35V d-c ** Consult factory for operation below 24V nominal.
NUMBER OF INPUTS:
Two (2): A and B

INPUT AND OUTPUT CURRENT: Per input:

30A max. NOTE: For parallel operation of both circuits
maximum output current of each circuit must not exceed 30A.

VOLTA G E D R O P: Input to Output

0.5V d-c typ.

REVERSE OUTPUT VOLTAGE:

45V d-c max

ALARM, INPUT VOLTAGE (UNDERVOLTAGE):

Indicators (A and B): UV LED — Relays (A and B): isolated contacts rated at 28V d-c/1A or 115V a-c/0.5A — Range: See Figure 5 and Table 2. — Factory preset: See Figure 5 and Table 2. — Hysteresis: See Figure 5 and Table 2.

ALARM, INPUT VOLTAGE (OVERVOLTAGE):

— Indicators (A and B) OV LED — Relays (A and B): isolated contacts rated at 28V d-c/1A or 115V a-c/0.5A — Range: See Figure 5 and Table 2. — Hysteresis: See Figure 5 and Table 2. — Factory preset: See Figure 5 and Table 2.
KDA 24A
Independent
KDA 24R
Parallel Redundant

ENVIRONMENTAL CHARACTERISTICS

OPERATING TEMPERATURE (35V INPUT MAX.):

KDA 24A: -10 to +60°C (all orientations) KDA 24R: -10 to +50°C (100% load, Figure 7)
-10 to +60°C (60% load, Figure 7)
-10 to +30°C (mounting other than shown in Figure 4.)

STORAGE TEMPERATURE: -25°C to +85°C

COOLING: Natural convection.

GENERAL CHARACTERISTICS

ISOLATION VOLTAGE:

Between input and ground: 500V. Between output and ground: 500V. Relay contacts are galvanically isolated.

SAFETY: All units designed to meet UL 508, UL 60950, TÜV Rheinland EN60950 and EN 60529 (category IP 20); KDA 24 units are CE marked per the Low Voltage Directive (LVD), EN60950.

CONNECTIONS: Screw terminals: M3 slotted (use cabinet tip screwdriver, flat, (0.125” [3mm] x 0.020” [0.5mm]); Wire gage: solid/stranded AWG (mm

2
): 24-12 (0.25-2.5); strip length: 5/16 in. [8mm], max torque: 5 lb.-in [0.5Nm].

WARRANTY: One year.

WEIGHT: KDA 24A: 0.5 lbs. (0.255 kg.)

KDA 24R: 1.0 lbs. (0.454 kg.)

DIMENSIONS:

See Figure 6.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
4 228-1694 REV 4 062411
Page 5

IV — INSTALLATION

MOUNTING. The KDA 24 Series Alarm modules come

with DIN Rail mounting clips that accommodate: NS 35mm and 32 mm G DIN rails. DIN clips may be reversed for convenience. The unit may also be chassis mounted by removing the two clips and using four 4-40 screws where the clips were installed. See Figure 6 for outline dimensions. Refer to Figure 4 for operating temperature derating of KDA 24R models only.

INPUT CONNECTIONS. Input connections are routed from the bottom and secured via screw terminals from the front.

KDA 24R. This model consists of two identical channels (A and B) that connect two power supplies in parallel as shown in Figure 2. ORing (blocking) diodes are built-in. Connections to the load must be made through external distribution points. V– terminal must not be used as distri­bution points. See Figure 2 for connections; see Figure 1 for component locations.

KDA 24A. This model consists of two independent iden­tical channels (A and B). Each channel may be used to monitor a voltage for overvoltage and undervoltage. See Figure 3 for connections; see Figure 1 for component loca­tions.

ALARM CONNECTIONS. Alarm connections are routed from the top and secured via screw terminals from the front.

ALARM RELAY. The alarm relay is normally energized as long as input power is within the HIGH and LOW alarm setting. Isolated alarm relay contacts of each channel are

available from the front panel: COM (common), Normally Closed (FAIL) and Normally Open (OK).

DC OK INDICATOR. As long as input voltage is within the High and Low alarm settings the DC OK indicator lights green. If an alarm occurs (either undervoltage or overvolt­age detected) the DC OK indicator of KDA 24A and KDA 24R models goes from green to off. DC OK returns to green when input voltage is again within range.

NOTES:
1. FOR MOUNTING OF KDA 24R IN ORIENTATION OTHER THAN SHOWN BELOW, MAX. OPERATING TEMPERATURE IS 30°C. RESTRICTION DOES NOT APPLY TO KDA 24A.
2. 1/2 INCH MINIMUM SEPARATION REQUIRED BETWEEN KDA 24R AND ANY OTHER HEAT­ PRODUCING MODULE ON THE DIN RAIL.
SEE NOTE 2
3043540
FIGURE 4. RECOMMENDED MOUNTING ORIENTATION
AIR FLOW
OF MODEL KDA 24R

V — OPERATION

SETTING HIGH AND LOW ALARMS. High (overvolt-

age) and low (undervoltage) alarms for channels A and B are set independently. To set the alarm limits for a channel, connect a variable +24V power supply to the channel input as described in the paragraph titled “Input Connections.” on page 5 and monitor the power supply output voltage using a DVM. Hysteresis causes the alarm to trip at a slightly different value depending on whether the voltage is decreasing or increasing. Hysteresis must be taken into account when setting the alarm trip points. Figure 5 shows this effect. The factory default adjustment values are shown in Table 2, as well as the guaranteed adjustment range (actual adjustment range may slightly exceed guar­anteed values).
KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A.  TEL (718) 461-7000  FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
062411 228-1694 REV 4 5
To change the HIGH and/or LOW trimpot settings (within the ranges listed in Table 2) Kepco recommends using an insulated adjustment tool, Bourns H-90 (Kepco P/N 218­1185 or equivalent. In addition, a variable output power supply with a range exceeding the minimum and maximum values listed in Table 2 is required. A DVM may be neces­sary to monitor the power supply output.
Each channel is independent and may be adjusted in any order.
NOTE: Once all LOW and HIGH alarm adjustments are
acceptable, refer to “Securing Alarm Adjustments” on page 7 to secure the adjustments.
Page 6
VOLTAGE
V2
UVP
V4
OVP
V3
OVD
V1
UVD
V4 - OVP (OVERVOLTAGE PICK-UP) V3 - OVD (OVERVOLTAGE DROP-OUT) V2 - UVP (UNDERVOLTAGE PICK-UP) V1 - UVD (UNDERVOLTAGE DROP-OUT)
DC OK LIGHT ON, RELAY ENERGIZED (OK-COM CLOSED) DC OK LIGHT OFF, RELAY DE-ENERGIZED (FAULT-COM CLOSED)
UV LIGHT ON UV LIGHT OFF
OVERVOLTAGE
}
HYSTERESIS
UNDERVOLTAGE
}
HYSTERESIS
3043498

FIGURE 5. DEFAULT SETTINGS FOR HIGH/LOW ALARMS SHOWING HYSTERESIS EFFECTS

TABLE 2. HIGH AND LOW ALARM ADJUSTMENT SETTINGS

VOLTAGE
CONDITION
(ADJUSTMENT POT)
UNDERVOLTAGE
(LOW)
OVERVOLTAGE
(HIGH)
* Contact factory for alarm settings outside tested max./min. range.
V2: UVP (UNDERVOLTAGE PICK-UP) 16.9V * 21.8V * 19.0V
V1: UVD (UNDERVOLTAGE DROP-OUT) 16.5V * 21.2V * 18.4V
V4: OVP (OVERVOLTAGE PICK-UP) 27.3V * 31.8V * 30.2V
V3: OVD (OVERVOLTAGE DROP-OUT) 26.5V * 31.0V * 29.4V
SETTING
(SEE FIGURE 5)

Low Alarm (Undervoltage) Adjustment. If the factory adjusted values are not acceptable, proceed as follows to adjust the low alarm pick-up and drop-off volt­ages (V2 and V1 of Figure 5). See Table 2 for the adjust­ment range

Note: Once all LOW and HIGH alarm adjustments are
acceptable, refer to “Securing Alarm Adjustments” on page 7 to secure the adjustments
1. Connect a variable output power supply (with a range exceeding the minimum and maximum values listed in Table 2) to the channel input as described in the para­graph titled “Input Connections.” on page 5. Toggle voltage points may be monitored using the visual indi­cators (yellow UV, green DC OK and red OV lights) or monitoring the relay contacts.
2. Turn the LOW trimpot fully CW, then adjust the power supply to the desired LOW threshold voltage (UVP, V2
OV LIGHT ON OV LIGHT OFF
GUARANTEED ADJUSTMENT
RANGE
MIN MAX
FACTORY DEFAULT
VAL UES
(±2%)
shown in Figure 5). If necessary, use a DVM to moni­tor the power supply voltage.
3. Observe that the UV (yellow) light is lit; no other lights are lit (relay is deenergized). Slowly (approximately one complete turn in five seconds) turn the LOW trim pot CCW until the toggle point (yellow UV LED goes out, green DC OK goes on, and the relay energizes). This is V2 - UVP (undervoltage pick-up voltage) as indicated in Figure 5 and Table 2.
4. To verify the settings lower the voltage of the variable power supply by about 1.2V. Observe that the yellow UV light is lit; no other lights are lit (relay is deener­gized).
5. Then slowly increase the voltage until the toggle point occurs (yellow UV LED goes out, green DC OK light goes on, and the relay energizes).
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
6 228-1694 REV 4 062411
Page 7
6. Verify that this toggle point is the desired value for UVP voltage. If this voltage is not correct, proceed to step 7 for fine tuning. If this voltage is correct, slowly lower the variable power supply voltage and verify that value of UVD (V1, Figure 5) is adequate (Hysteresis value 0.6V typ. see Figure 5)
7. If the toggle point is missed, fine tune as follows: Adjust power supply voltage to the desired UVP value (Under­voltage pick-up voltage). Turn the LOW trimpot CW about two to three turns until the system toggles back again (yellow UV light on, DC OK light off, relay deen­ergized). Very slowly turn LOW trimpot CCW until the toggle point is reached: yellow UV light goes out, green DC OK light goes on, and the relay energizes. Reverify again per step 6.

High Alarm (Overvoltage) Adjustment. If the fac­tory adjusted values are not acceptable, proceed as follows to adjust the high alarm pick-up and drop-off voltages (V3 and V4 of Figure 5). See Table 2 for the adjustment range

NOTE: Once all LOW and HIGH alarm adjustments are
complete, refer to “Securing Alarm Adjustments” on page 7 to secure the adjustments.
4. To verify the settings lower the voltage of the variable power supply by about 2V. Observe that the green DC OK light is lit, relay is deenergized and red OV LED is off.
5. Slowly increase the voltage until the toggle point occurs (red OV LED goes on, no other lights are lit and the relay deenergizes.
6. Verify that this toggle point is the desired value for OVP voltage. If this voltage is not correct, proceed to step 7 for fine tuning. If this voltage is correct, slowly lower the variable power supply voltage and verify that value of OVD (V3, Figure 5) is adequate (Hysteresis value 0.9V typ. see Figure 5)
7. If the toggle point is missed, fine tune as follows: Adjust power supply voltage to the desired OVP value (Over­voltage pick-up voltage). Turn the HIGH trimpot CW about two or three turns until the system toggles back again (green DC OK light is lit, relay is deenergized and red OV LED is off). Very slowly turn HIGH trimpot CCW until the toggle point is reached: red OV LED goes on, no other lights are lit and the relay deener­gizes. Reverify again per step 6.
1. Connect the variable power supply described above to the channel input as described in the paragraph titled “Input Connections.” on page 5. Toggle voltage points may be monitored using the visual indicators (yellow UV, green DC OK and red OV lights) or monitoring the relay contacts.
2. Turn the HIGH trimpot fully CW, then adjust the power supply to the desired HIGH threshold voltage (OVP, V4 shown in Figure 5). If necessary, use a DVM to monitor the power supply voltage.
3. Observe that the green DC OK light is lit and relay is deenergized. Slowly (approximately one complete turn in five seconds) turn the HIGH trim pot CCW until the toggle point (red OV LED goes on, no other lights are lit and the relay deenergizes.

Securing Alarm Adjustments. Once HIGH and LOW alarm settings for both channels are acceptable, the adjust­ments can be covered to prevent tampering by installing four plugs (supplied) into the trimpot adjustment access holes (see Figure 7). Once these plugs have been installed, they can only be removed by first removing the KDA cover (remove two screws and slide cover off) and then releasing the plug prongs while pushing the plug out.

KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A.  TEL (718) 461-7000  FAX (718) 767-1102
062411 228-1694 REV 4 7
http://www.kepcopower.com email: hq@kepcopower.com
Page 8
4.38
[111.4 mm]
0.78 [19.9 mm]
[117.1 mm]
3010306
4.61
0.30
[7.5 mm]
DIN RAIL NS35/7,5
4.62
[117.4 mm]
0.03 [0.8 mm]
3.60
[91.4 mm]

FIGURE 6. KDA 24 SERIES OUTLINE DIMENSIONS

DIN RAIL NS35/15
"G" DIN RAIL NS32
NOTE: TO REMOVE PLUG, REMOVE TWO SCREWS AND SLIDE KDA COVER OFF CHASSIS. THEN RELEASE PLUG PRONGS WHILE PUSHING PLUG OUT.
PLUG ( QTY 4)
KDA COVER
3043531
SCREW (QTY 2)
P/N 101-0092
(BHPH, 4-40 x 0.312 ST NA)
P/N 108-0473
PLUG
DETAIL
PRESS
TO
RELEASE
KDA CHASSIS

FIGURE 7. SECURING ALARM ADJUSTMENTS

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
8 228-1694 REV 4 062411
Loading...