KEPCO HSP User Manual

QUICK START GUIDE
An ISO 9001 Company.
SINGLE OUTPUT
PROGAMMABLE POWER SUPPLIES

I — INTRODUCTION

SCOPE OF MANUAL This Quick Start Guide covers

the installation and operation of the Kepco HSP Series of voltage and current stabilized d-c power supplies. Full specifications are listed in the applicable Operator’s Man­ual that can be downloaded from the Kepco web site at www.kepcopower.com/support/opmanls.htm/#hsp

FACTORY DEFAULTS This guide covers only units as shipped from the factory with the three DIP switches set to default configuration (see Figure 1). For other configura­tions, refer to HSP Operator Manual.

DESCRIPTION The HSP power supply (Figure 1-1) is basically a voltage and current stabilized d-c source with a relatively sharp crossover between voltage and current mode operation.

HSP
1000W/1500W
HSP power supplies are nominally rated at either 1000 or 1500 Watts of output power, and include active power fac­tor correction (PFC). HSP 1000W power supplies are designed to operate over the universal a-c power mains voltage range of 90-277V (47-63Hz), with operation from 125-420V d-c also available. HSP 1500W products provide full power over the a-c mains range of range of 180-277V a-c, and 1000W output power from 90-132V a-c; contact Kepco for information on operation over other source volt­age ranges. Cooling is provided via an internal d-c fan.
HSP permits adjustment of both output voltage (V current limit (I external (resistance or voltage) methods, selected via DIP switches accessed through the top of the unit. Protection against overvoltage, overcurrent and overtemperature fail­ures is provided.
MODELS 3.3V 5V 12V 15V 24V 28V 48V
1000W HSP 3.3-230R HSP 5-200R HSP 12-84R HSP 15-66R HSP 24-42R HSP 28-36R HSP 48-21R
1500W N/A N/A N/A N/A HSP 24-60R HSP 28-53R HSP 48-30R
NOTE: Options include suffix M or B: M for meter; B for battery charger.
), either by internal (front panel pot) or
MAX

TABLE 1. HSP SERIES MODELS

) and
O

FIGURE 1. DIP SWITCH FACTORY DEFAULTS

The HSP power supply is specifically designed for use with Kepco RA 60 or similar plug-in rack adapters as a hot replaceable module in a redundant power system. Bench top operation is also supported. Forced current sharing and output blocking diodes enhance power system reliability. Mechanical keying eliminates the risk of incorrect module insertion. Tool-operated latches on the front panel guard against casual removal of an operating module.

OPTIONS M models include a digital meter which dis­plays either voltage or current as determined by a front panel switch. Another switch allows display of either actual HSP Output or the setpoint. B models are intended for battery charging applications, and include a Float/ Equalize switch to preset two different voltage values using two separate front panel adjustment pots.

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
©2010, KEPCO, INC 1 Data subject to change without notice 228-1706

II — INSTALLATION

KEYING. The units are keyed by voltage at the factory.

Refer to the Operator Manual for details.

MOUNTING THE POWER SUPPLY To insert in a Kepco Rack Adapter, release the two cap head screw retaining latches (see Figure 4) by loosening the cap-head screw approximately 1/2 turn CCW (use 5/32" hex key) and slide to open (up) position. Insert power supply in the slot, then retighten the cap-head screws CW until snug. DO NOT OVERTIGHTEN! To release, follow the same procedure, except lift the latch to the top of the slot. Be sure to move the latch completely up or down to ensure full engagement/disengagement of the latching mecha­nism. When HSP is not installed in rack adapter, secure latch in open (up) position to prevent damage.

To use as a fixed, rack-mounted unit, see Operator man­ual for details and accessories.
For all installations, provide adequate clearance around air inlet and exhaust locations.

CONNECTIONS: Figure 2 shows proper connection of one or more loads using either remote or local sensing.

If local or remote sensing is not configured, the unit will not work properly. Observe polarities: negative
sensing wire must be connected to negative load wire, and positive sensing wire to positive load wire. When used with plug-in rack adapters, local sense wires must be con­nected from the I/O connector to the ± studs of the rack adapter.
Load connections to the HSP power supply are via bus bars protruding from the rear panel (see Figure 2) or via the rack adapter output studs.
Load cable or bus bar attachment should use either the clearance hole of the HSP bus bar, using a 5/16" UNC nut, bolt and lockwasher, or the rack adapter studs using hardware supplied with the rack adapter. The proper hard­ware is critical to maintaining intimate contact between the load conductor and output bus bar.
LOCAL ERROR SENSING

FIGURE 2. LOAD CONNECTIONS

PRELIMINARY ELECTRICAL CHECK A simple operational check after unpacking and before equipment installation is advisable to ascertain whether the power supply has suffered damage resulting from shipping.

1. Power supply will not operate unless remote
sense lines are properly connected to output ter­minals! Connect remote sense terminals to output
bus bars using mating I/O Connector (Kepco P/N 142-
0422) or other means as shown in Figure 2.
2. Connect power supply to source power. Connection can be made using either a North American linecord set (Kepco P/N 118-0776) or using a custom linecord
REMOTE ERROR SENSING
terminated at one end with an IEC 320/C19 plug (Kepco P/N 142-0381).
3. Connect a static load, R, across output terminals. Load value is determined by HSP nominal output volt­age and must be capable of handling 2% of power supply output rating (20 watts minimum). R is calcu­lated as approximately equal to output voltage
2
(R = E
/P). For example, for the HSP 48-21, R = 482/
2
/20
20 = 115.2; use load of 120 ohms, 20W.
4. CAUTION: DO NOT repeatedly toggle circuit breaker as this may damage unit. Set Power ON/ OFF circuit breaker on front panel to ON. If actuator
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
2 228-1706 091410
does not lock when released, wait a few seconds before trying again. The circuit breaker is "trip-free" design; if overload exists, contacts cannot be held closed by actuator. Verify that POWER indicator is lit, and that all other front panel indicators are not lit.
5. Using a DVM, measure voltage across output bus bars; this voltage is factory set to value shown in Table
1. If necessary, adjust output voltage using V
trim pot
O
accessed through front panel.
6. Using DVM, measure voltage across test points V and COM; it should read 1/10 of output voltage mea­sured in step 5 above, ±1%.
7. Using DVM, measure voltage across test points I
MAX
and COM. This voltage is factory adjusted to 10.0V, and corresponds to 100% of maximum current. Refer to Operator manual for adjustment.

III — OPERATION

CAUTION: DO NOT repeatedly toggle the circuit breaker/switch as this may damage the unit. Set Power
ON/OFF circuit breaker to ON. When output voltage is available, the green POWER LED is on (see Figure 4).
8. Verify that front panel indicators still appear as in step 4 above.
9. Disconnect sense lines with power supply still operat­ing (remove mating I/O connector or open sense line connected to pin 37. Verify that HSP output turns off, and DC FAIL indicator is now lit along with POWER indicator. (NOTE: At no load the output voltage will drop slowly.) Turn circuit breaker off and wait until DC FAIL indicator blinks. Reconnect sense lines, then turn circuit breaker back on. Verify that output voltage
O
returns to value measured in step 5 above, and that indicator LEDs appear as in step 4 above.
10. Turn off front panel circuit breaker and remove source power connection.
programming range, this corresponds to 62% of the rated module current, but for the high programming range the number is 62% of 110%, or 68.2% of rated module current. Current setpoint monitor accuracy is ±5%.

OUTPUT VOLTAGE PROGRAMMING Monitor out­put voltage setpoint across V adjusting V

pot on front panel. Voltage across VO and
O
and COM jacks while
O
COM represents 1/10 of the programmed output voltage. As an example, V
of 4.63V corresponds to a programmed
O
output voltage of 46.3V ±1%. This relationship is constant, regardless of the programming range selected.
Default programming resolution is set to high range: output can be adjusted to 110% of nominal V 28V models, 125% of nominal V
for 48V models. For low
O
for 3.3V through
O
range (which offers increased resolution, while limiting out­put to V
), or for external voltage programming using either
O
resistance or voltage refer to Operator manual.
For metered (M option) units, if the V/A switch is set to V, actual output voltage is displayed on the meter in Volts. While the ACTUAL/SETPOINTS switch is held in, the pro­grammed output voltage setpoint is displayed in Volts.

CURRENT LIMIT PROGRAMMING Monitor current limit setpoint across I I

pot on front panel. Voltage across I
MAX
and COM jacks while adjusting
MAX
and COM rep-
MAX
resents the percentage of available power supply current as a percentage of rated current, with 10V corresponding to 100%. Available current is defined as the maximum cur­rent limit available based on the programming range. This voltage is always based on a 0-10V scale, regardless of the range selected. For example, I
= 6.2V corresponds
MAX
to 62% of the maximum programmable current. For the low
Minimum programmable current limit is 50-60% of nominal. Default programming resolution is set to high range: cur­rent limit can be adjusted to 110% of nominal I
. For low
O
range (which offers increased resolution, while limiting out­put to I
), or for external programming using voltage
O
source refer to Operator manual.
For metered (M option) units, if the V/A switch is set to A, actual output current is displayed on the meter in Amperes. While the ACTUAL/SETPOINTS switch is held in, the pro­grammed current limit is displayed in Amperes.

OVERVOLTAGE PROTECTION The overvoltage pro­tection (OVP) circuitry latches the output regulator off if out­put voltage rises above a predetermined level. To reset, remove source power for a minimum of 30 seconds (refer to Operator manual to enable remote reset). The trip level is preset at the factory for 130% of the nominal output volt­age. The trip point can be adjusted from 100% to 140% of the nominal output (except Model HSP 48-21, which can be adjusted from 100% to 160% of the nominal output). To alter the preset OVP trip point, refer to the Operator man­ual.

CURRENT LIMIT CHARACTERISTIC The factory default setting is Continuous Limiting: When the output cur­rent of the power supply reaches the programmed current limit, the output regulator switches to current mode opera­tion and maintains the output current by modulating output voltage. Current mode is maintained indefinitely, and

KEPCO, INC.  131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A.  TEL (718) 461-7000  FAX (718) 767-1102
091410 228-1706 3
http://www.kepcopower.com email: hq@kepcopower.com
recovery to voltage regulation mode is automatic upon reduction of output current below the current limit point.
Current Limit can also be set to Undervoltage Lockout: if current mode is maintained for more than 15 seconds, the output is turned off, and source power must be recycled to restart the unit. Refer to Operator manual for details.

OTHER FEATURES The following features of the HSP power supplies are covered in detail in the Operator man­ual:

• Parallel Operation, including load sharing require­ments.
• Remote Inhibit, Remote Reset
• Remote Voltage and Current Limit adjustment
• Protection Circuits
• Status Flags and Indicators
Output
Bus Bar
(+)
Output
Bus Bar
(-)
For Standalone operation, replace connector mounting screws using instructions and components supplied in Standalone accessory KIT 219-0240 or KIT 219-0249.
I/O
Connector
Pin 20
Pin 1
• Load Monitor (Current)
• Current “Walk-In” for battery charging applications
• Load monitor
• Auxiliary supply
•Keying
• I/O Connector pin functions
• Options
Insertion/Extraction Handle
Power ON/OFF circuit breaker Applies
power to the unit. CAUTION: Power must be OFF before unit is removed from the rack adapter.
Voltage/Current Meter (M Suffix only) Monitors output voltage or current Meter Mode switch. Remote sensing required
for
voltmeter to display voltage at the load.
V (Voltage) indicator (M Suffix only)
Lights green when meter shows Volts.
Meter Mode switch (M Suffix only)
Set to V to show output voltage on meter, set to A to show output current.
A (Amperes) indicator (M Suffix only)
amber when meter shows Amperes.
Lights
ACTUAL/SETPOINTS momentary switch (M Suffix only) Meter normally shows actual
output voltage or current. Meter shows setpoints while switch is pressed.
Retaining Latches (2) Prevents inadvertent removal of unit from rack adapter.
3043522
per
Keyways and Plugs for module keying (for use with Kepco plug-in Rack Adapters)
Power Inlet Connector
Line (Hot) Ground Neutral

FIGURE 3. HSP SERIES REAR PANEL CONNECTIONS

EQ Adjust pot (B suffix only) Used to adjust
Equalize voltage while monitoring Vo and COM.
FL/EQ Select switch (B suffix only) Allows either Float or Equalize voltage to be monitored across Vo and COM jacks. CAUTION: Adjust
only the pot selected by FL/EQ switch.
Vo Adjust pot Used to adjust output voltage
setpoint. Used to adjust Float voltage on B suffix models. POWER Indicator Lights green when is operating.
DC FAIL Indicator Normally off. Lights red to
indicate failure.
OVERTEMP indicator Lights amber to indicate
overtemperature detected.
FAN FAIL indicator Lights red to indicate fan
failure.
Vo Setpoint monitor jack Used with COM jack to monitor voltage setpoint.
COM jack Provides return for Vo and I
setpoint monitor jacks.
MAX Setpoint monitor jack Used with COM jack to
I
monitor current limit setpoint.
MAX Adjust pot Used to adjust current limit from
I
front panel.
Off when fault detected.
unit
MAX

FIGURE 4. COMPONENT LOCATIONS

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
4 228-1706 091410
Loading...