QUICK START GUIDE
KEPCO
An ISO 9001 Company.
SINGLE OUTPUT
PROGAMMABLE POWER SUPPLIES
I — INTRODUCTION
SCOPE OF MANUAL This Quick Start Guide covers
the installation and operation of the Kepco HSP Series of
voltage and current stabilized d-c power supplies. Full
specifications are listed in the applicable Operator’s Manual that can be downloaded from the Kepco web site at
www.kepcopower.com/support/opmanls.htm/#hsp
FACTORY DEFAULTS This guide covers only units as
shipped from the factory with the three DIP switches set to
default configuration (see Figure 1). For other configurations, refer to HSP Operator Manual.
DESCRIPTION The HSP power supply (Figure 1-1) is
basically a voltage and current stabilized d-c source with a
relatively sharp crossover between voltage and current
mode operation.
HSP
1000W/1500W
HSP power supplies are nominally rated at either 1000 or
1500 Watts of output power, and include active power factor correction (PFC). HSP 1000W power supplies are
designed to operate over the universal a-c power mains
voltage range of 90-277V (47-63Hz), with operation from
125-420V d-c also available. HSP 1500W products provide
full power over the a-c mains range of range of 180-277V
a-c, and 1000W output power from 90-132V a-c; contact
Kepco for information on operation over other source voltage ranges. Cooling is provided via an internal d-c fan.
HSP permits adjustment of both output voltage (V
current limit (I
external (resistance or voltage) methods, selected via DIP
switches accessed through the top of the unit. Protection
against overvoltage, overcurrent and overtemperature failures is provided.
MODELS 3.3V 5V 12V 15V 24V 28V 48V
1000W HSP 3.3-230R HSP 5-200R HSP 12-84R HSP 15-66R HSP 24-42R HSP 28-36R HSP 48-21R
1500W N/A N/A N/A N/A HSP 24-60R HSP 28-53R HSP 48-30R
NOTE: Options include suffix M or B: M for meter; B for battery charger.
), either by internal (front panel pot) or
MAX
TABLE 1. HSP SERIES MODELS
) and
O
FIGURE 1. DIP SWITCH FACTORY DEFAULTS
The HSP power supply is specifically designed for use with
Kepco RA 60 or similar plug-in rack adapters as a hot
replaceable module in a redundant power system. Bench
top operation is also supported. Forced current sharing and
output blocking diodes enhance power system reliability.
Mechanical keying eliminates the risk of incorrect module
insertion. Tool-operated latches on the front panel guard
against casual removal of an operating module.
OPTIONS M models include a digital meter which displays either voltage or current as determined by a front
panel switch. Another switch allows display of either
actual HSP Output or the setpoint. B models are intended
for battery charging applications, and include a Float/
Equalize switch to preset two different voltage values
using two separate front panel adjustment pots.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
©2010, KEPCO, INC 1
Data subject to change without notice 228-1706
II — INSTALLATION
KEYING. The units are keyed by voltage at the factory.
Refer to the Operator Manual for details.
MOUNTING THE POWER SUPPLY To insert in a
Kepco Rack Adapter, release the two cap head screw
retaining latches (see Figure 4) by loosening the cap-head
screw approximately 1/2 turn CCW (use 5/32" hex key)
and slide to open (up) position. Insert power supply in the
slot, then retighten the cap-head screws CW until snug.
DO NOT OVERTIGHTEN! To release, follow the same
procedure, except lift the latch to the top of the slot. Be
sure to move the latch completely up or down to ensure
full engagement/disengagement of the latching mechanism. When HSP is not installed in rack adapter, secure
latch in open (up) position to prevent damage.
To use as a fixed, rack-mounted unit, see Operator manual for details and accessories.
For all installations, provide adequate clearance around
air inlet and exhaust locations.
CONNECTIONS: Figure 2 shows proper connection
of one or more loads using either remote or local sensing.
If local or remote sensing is not configured, the unit
will not work properly. Observe polarities: negative
sensing wire must be connected to negative load wire,
and positive sensing wire to positive load wire. When used
with plug-in rack adapters, local sense wires must be connected from the I/O connector to the ± studs of the rack
adapter.
Load connections to the HSP power supply are via bus
bars protruding from the rear panel (see Figure 2) or via
the rack adapter output studs.
Load cable or bus bar attachment should use either the
clearance hole of the HSP bus bar, using a 5/16" UNC
nut, bolt and lockwasher, or the rack adapter studs using
hardware supplied with the rack adapter. The proper hardware is critical to maintaining intimate contact between the
load conductor and output bus bar.
LOCAL ERROR SENSING
FIGURE 2. LOAD CONNECTIONS
PRELIMINARY ELECTRICAL CHECK A simple
operational check after unpacking and before equipment
installation is advisable to ascertain whether the power
supply has suffered damage resulting from shipping.
1. Power supply will not operate unless remote
sense lines are properly connected to output terminals! Connect remote sense terminals to output
bus bars using mating I/O Connector (Kepco P/N 142-
0422) or other means as shown in Figure 2.
2. Connect power supply to source power. Connection
can be made using either a North American linecord
set (Kepco P/N 118-0776) or using a custom linecord
REMOTE ERROR SENSING
terminated at one end with an IEC 320/C19 plug
(Kepco P/N 142-0381).
3. Connect a static load, R, across output terminals.
Load value is determined by HSP nominal output voltage and must be capable of handling 2% of power
supply output rating (20 watts minimum). R is calculated as approximately equal to output voltage
2
(R = E
/P). For example, for the HSP 48-21, R = 482/
2
/20
20 = 115.2; use load of 120 ohms, 20W.
4. CAUTION: DO NOT repeatedly toggle circuit
breaker as this may damage unit. Set Power ON/
OFF circuit breaker on front panel to ON. If actuator
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
http://www.kepcopower.com email: hq@kepcopower.com
2 228-1706 091410