1)This manual is valid for the following Model and associated serial numbers:
MODELSERIAL NO.REV. NO.
HSF 300W
2)A Change Page may be included at the end of the manual. All applicable changes and
revision number changes are documented with reference to the equipment serial numbers. Before using this Instruction Manual, check your equipment serial number to identify
your model. If in doubt, contact your nearest Kepco Representative, or the Kepco Documentation Office in New York, (718) 461-7000, requesting the correct revision for your
particular model and serial number.
3)The contents of this manual are protected by copyright. Reprod uction of any part can be
made only with the specific written permission of Kepco, Inc.
3.4 Output Voltage Control........................................ ................................................... ........................................ 8
3.4.1 Front Panel Voltage Control........................................................................................................................ 8
3.4.2 Remote Voltage Control.............................................................................................................................. 8
3.4.3 VDC ON/Alarm Indicator Power Options............................................ ... .................................................... 10
5. Connecting Multiple Power Supplies............................................................................................................... 14
5.1 Adjusting the Voltage ................................................... .................................................. .............................. 15
5.2 Parallel Connections, M Models................................................................................................................... 15
5.3.2 Voltage Set Restrictions............................................................................................................................ 16
1 HSF Rear Panel Connector and RA 19-4C Rack Adapter I/O Connector.................................................. 1
2 Power Rating Vs. Temperature.................................................................................................................. 3
3 Mechanical Outline Drawing, HSF 300W M and MZ Models...................................................................... 6
2 Output Ratings and Specifications ..............................................................................................................3
3 Power Supply Ratings and Specifications ..................................................................................................4
4 Minimum Conditions for Relay, Meter and LED Operation .........................................................................9
5 Conditions for VDC ON/ALARM LED Operation Powered by Output .......................................................10
SECTIONPAGE
v
FIGURETITLEPAGE
LIST OF FIGURES
TABLETITLEPAGE
iHSF 300W 042315
LIST OF TABLES
Page 3
1.INTRODUCTION
3042951
89
7
12 11
10
15
1816
17
14
13
21 20
19
21
34
56
22
23
24
1.1SCOPE OF MANUAL
This Operator's Manual covers the installation and operation of the Kepco HSF 300W Series,
Models M and MZ, of Metered Switching Power Supplies. For service information, write directly to:
Kepco Inc., 131-38 Sanford Avenue, Flushing, New York, 11355, U.S.A. Please state Model Designation and Serial Number of your HSF Power Supply. This information can be found on the
nameplate of the unit.
1.2DESCRIPTION
The Kepco HSF 300 Watt Series M and MZ models are hot swappable, high frequency switching,
plug-in power supplies that are completely interchangeable with the non-metered HSF Series. Six
models may be selected for outputs of 5V, 12V, 15V, 24V, 28V or 48V. They employ forward conversion and power factor correction and are designed to operate in a fault tolerant power system
with a nominal a-c input of 100V a-c to 240V a-c (input voltage range 85 to 265 Va-c), 50-60 Hz
(input frequency range 47-440Hz). A built-in current balancing circuit and OR-ing diodes allow
configuration for hot-swap and parallel-redundant N+1 operation.
NOTE: HSF 5-60M functions the same as MZ models. Throughout this manual, where there
are differences between M and MZ models, refer to the MZ model information for HSF
5-60M.
The HSF M Models (except for HSF 5-60M) use the HSF output to power the VDC ON indicator,
internal alarm relay, and the meter. A minimum HSF output voltage is needed to maintain functionality for these components.
The HSF MZ Models, as well as the HSF 5-60M, use an au xiliary internal power supply to po wer
the internal relay and the meter, allowing the output voltage to be adjusted down to zero without
affecting meter or alarm performance. The default configuration of MZ mo dels uses an internal
reference voltage to power the VDC ON indicator. An option is provided which allows the VDC ON
indicator to be powered by the HSF output, requiri ng a minimum voltage to maintain functionality
of the indicator.
These power supplies are designed to be used with Kepco's Series RA 19-4C rack adapte rs. The
RA 19-4C rack adapter accepts up to four 300W modules. All input/output connections are
through a 24-pin connector that plugs in to the rack adapter. All external connections described in
the following paragraphs are made through the rack adapter ’s I/O connector (see Figure 1).
FIGURE 1. HSF REAR PANEL CONNECTOR AND RA 19-4C RACK ADAPTER I/O CONNECTOR
HSF (M) 300W 0423151
Page 4
TABLE 1. HSF REAR CONNECTOR PIN ASSIGNMENTS
Signal
Name
Output +1, 2, 4 DC output (+) applied to load.
Output –3, 5, 6 DC Output (–) applied to load.
SENSE–7Sense– connection
IMON+8Current Monitor+ (sense resistor).
SENSE+9Sense+ connection
NO10Normally Open contact of alarm relay, referenced to AL COM, pin 14 (see PAR. 3.8.2.1).
IMON–11Current Monitor– (sense resistor).
–COM12–Signal Common provides return for REF, pin 15, and RV, pin 18, signals.
NC13Normally Closed contact of alarm relay, referenced to AL COM, pin 14 (see PAR. 3.8.2.1).
AL COM14Common contact of alarm relay (see PAR. 3.8.2.1).
REF15Reference voltage. When used with RV, pin 18, allows all output voltages of paralleled slave supplies to be
+PF16+Power Fail of open-collector alarm circuit. Used with –PF, pin 19 (see PAR. 3.8.2.2).
CSB17Current Share Bus - Used whenever several power supplies are connected in parallel (see PAR. 5.).
RV18Remote Voltage - Used with REF, pin 15, for remotely controlling the output voltage (see PAR. 3.4.2)
–PF19–Power Fail of open-collector alarm circuit. Used with +PF, pin 16 (see PAR. 3.8.2.2).
+RC20+Remote On-off used with –RC, pin 21, to allow remote turn-on turn-off of the unit (see PAR. 3.4.3)
–RC21–Remote On-off used with +RC, pin 20, to allow remote turn-on turn-off of the unit (see PAR. 3.4.3)
GND22AC input ground
N23AC Input neutral
L24AC input line
PinFunction
controlled by one voltage adjustment of a master power supply. When REF is connected to RV via an
external trimmer, the external trimmer determines output voltage (see PAR. 3.4.2). Connections are made
via DIP switches (see PAR. 3.1).
2.SPECIFICATIONS
Table 2 contains specifications and operating limits of individual HSF 300W Series M and MZ
models. Table 3 contains specifications and operating limits common to all HSF 300W Series M
and MZ Models. These specifications are at nominal input voltages at 25°C unless otherwise
specified.
2HSF (M) 300W 042315
Page 5
TABLE 2. OUTPUT RATINGS AND SPECIFICATIONS
HSF MODEL 5-60*12-27*15-22*24-14*28-12*48-7*
Output Volts d-c (nominal)51215 242848
Output
Adjustment
(1)(2)
Range
Using front
panel trimpot
(Volts d-c)
(3)
Using Voltage source or
external 5K ohm trimpot
M0 to 5.55.5 to 13.8
(3)
MZ
0 to 5.50 to 13.80 to 17.4 0 to 28.2 0 to 33 0 to 52.2
(3)
0 to 5.50 to 13.80 to 17.4 0 to 28.2 0 to 33 0 to 52.2
(Volts d-c)
Output Current (nominal) (Amps)
Maximum Output Power (Watts)
Overcurrent Setting (Amps)
(5)
(4)
300300300300300300
602722
63-7828.4-35.123.1-28.614.7-18.212.6-15.67.4-9.1
Short Circuit Current (Amps)823529201711
Overvoltage Protection (OVP)
Efficiency
(% typ.)
Power Fac-
tor
(typ.)
Ripple &
Noise
(mV, p-p)
(7)
(Volts d-c)
AC Input 100V727475787879
AC Input 200V787879828283
AC Input 100V0.990.990.990.990.990.99
Sense Resistor (IMON) values (Ohms)0.0020.010.010.020.050.02
*Unless otherwise noted, specifications apply to both M and MZ models.
(1) M Models only: To adjust output voltage down to approximately 0V use external voltage source or resistance (see PAR.
3.4.2). Refer to Table 4 for minimum conditions required to maintain proper operation of alarm relay, meter and visual LED
indicator.
(2) If the visual LED indicator is powered from the HSF output (see PAR 3.4.3), refer to Table 5 for minimum conditions required
to maintain functionality of the indicator.
(3) Using trimpot to attain voltages outside the specified adjustment range may trigger undervoltage (PAR 3.7.4) or overvoltage
(PAR 3.7.1) faults. Recovery is by removing, and after approximately 40 seconds, reapplying AC input power or by reset
(open and close) at ±RC terminals (no delay).
(4) See Figure 2 for power derating.
(5) Square type. Output voltage returns automatically only if cause is removed within 30 seconds (see PAR. 3.7.2).
(6) When overvoltage is detected, output is shut OFF. Recovery is by removing, and after approximately 40 seconds, reapplying
AC input power or by reset (open and close) at ±RC terminals (no delay).
(7) Ripple and noise levels above are satisfied when conditions are 0 to 100% load, 0 to 40°C (load is derated from 40 to 55°C,
see Figure 2), and bandwidth 100MHz.
(8) Range shown is operating range; minimum range upon startup is 0.5V higher than minimum operating range shown.
(8)
7 to 17.4
(8)
7 to 28.2
(8)
7 to 33
(8)
14127
7 to 52.2
(8)
HSF (M) 300W 0423153
FIGURE 2. POWER RATING VS. TEMPERATURE
Page 6
TABLE 3. POWER SUPPLY RATINGS AND SPECIFICATIONS
CHARACTERISTICSPECIFICATIONCONDITION/NOTES
Input VoltageNominal: 100-120V a-c, 200-240V a-c
Range: 85-265V a-c, 110-370V d-c
Input Source FrequencyNominal: 50-60 Hz
Range: 47-440 Hz
Input Current: (Maximum Load At
25°C with Nominal Output Voltage)
Switching Frequency140KHz typ.Forward Converter
Input ProtectionA limiting resistor in series with a resistor fuse (and thyristor circuit) reduces start-up surge.
Input Surge cold start, interval > 30
sec ( First surge only, not including
current flow into EMI filter)
Leakage Current: 0.24mA typ., 0.3mA max. 120V a-c, 60Hz per IEC 950 and UL1950
Power Factor0.99 typicalRated output, rated input
Transient Recoveryexcursion
characteristic
recovery time 1 ms maximum
Stabilization
Source Effect (min - max) ±0.1% Typical, ±0.2% Maximum85 to 132V a-c, 170 to 265V a-c
Load Effect ±0.3% Typical, ±2% Maximum (default)
Temperature Effect ±0.5% Typical, ±1.0% Maximum–10° to 40°C
Combined Effect ±0.9% Typical, ±1.8% MaximumSource, Load and Temperature
Time Effect 0.2% Typical, 0.5% Maximum1/2 to 8 hours at 25°C
Overvoltage ProtectionWhen the Power Supply goes into an overvoltage condition, the output is cut OFF. See PAR.
Remote Control ON/OFF:±RC pins control on/off as follows:
Meter (displays voltage or current;
front panel switch-selectable)
Operating Temperature: -10 to 40°C (see Figure 2.)
Startup Temperature-10 to -20°C(see Figure 2.)
Storage Temperature: -30°C to +75°C
4.4A rms max.100 - 120V a-c
2.2A rms max. 200 - 240V a-c
The internal power supply is protected against shorts by an input fuse. Fuse value 10.0A at
250 Volts
15A typ., 20A max. first surge100 - 120V ac
30A typ., 40 max. first surge
0.31mA typ., 0.38mA max. 240V a-c, 60Hz per IEC 950 and UL1950
±4% maximum
±0.3% Typical, ±0.6% Maximum (see PAR. 3.4)
150 msec Typical, 210 msec Maximum240V a-c
40 msec Typical, 20 msec Minimum.240V a-c
3.7.1.
“High”, 2.4V to 24V (or open), unit OFF- Fan Off;
“Low”, 0.0V to 0.4V (or closed), unit ON.
Source current: 1.6mA maximum at low level
Sink current: 1.0 mA maximum at high level.
Voltmeter Accuracy: ±3%
Ammeter Accuracy: ±5% for loads between 10%100%
0 to 100% load, -10 to 40°C
0 to 100% load, -10 to 40°C
At 440 Hz leakage current exceeds
UL/VDE safety spec. limit.
200- 240 V ac
50% to 100% load,
transient time >50
Individual Mode: 0%-100% load change
Current Sharing: 10%-100% load change
Must be enabled by DIP switch positions 3
and 4 (see PAR. 3.4.3).
Voltmeter reads sense lines; use remote
sensing to display voltage at load.
Ammeter accuracy degrades significantly
for loads less than 10%
sec
4HSF (M) 300W 042315
Page 7
TABLE 3. POWER SUPPLY RATINGS AND SPECIFICATIONS (CONTINUED)
CHARACTERISTICSPECIFICATIONCONDITION/NOTES
Withstanding voltage : (at 15-35°C
ambient, 10-85% relative humidity)
Safety:Designed to meet UL: 60950; CSA:C22.2 60950; TUV: EN60950.
RoHS ComplianceContact Kepco Sales for further information.
EMC Emission - Conducted: Designed to meet FCC Class B, VCCI-Class B, EN55011-B, EN55022-B
EMC Emission - Radiated:Designed to meet FCC Class B, VCCI-Class B, EN55011-B, EN55022-B
EMC Emission - Input harmonics
current:
EMC ImmunityDesigned to meet EN61000-6-2
EMC Radiated susceptibility:EN61000-4-3 level 3normal operation
EMC Conducted susceptibility:EN61000-4-6 level 3normal operation
ESD:EN61000-4-2, level 4 (HSF 5-60M: level 3)normal operation
Electrical fast transient burst:EN61000-4-4 level 3normal operation
Surge withstand:EN61000-4-5, level 4 (HSF 5-60M: level 3)No damage
Power Frequency Magnetic Field:EN61000-4-8, level 4 (HSF 5-60M: level 3)normal operation
Voltage dips interruptions and
variations
Dimensions: 5.22 in. (132.5 mm) x 4.288 in. (108.9 mm) x 16.86 in. (428.2 mm) (See Figure 3)
Mounting: Plug-in
Cooling: Forced air flow - fan
Frame Material/Cover Material:Steel
Weight8 lbs, 3.7Kgs. maximum
2000Va-c for 1 minute. Cutout current is 20mABetween input and ground
500Va-c for 1 minute. Cutout current is 100mABetween output and ground
3000Va-c for 1 minute. Cutout current is 20mABetween input and output terminal
100 Megohms minimum (500Vdc)
Between output and ground, input and
ground, and input and output,
Wet Bulb temperature <35°C
tion 64.3ft./s
2
(19.6M/s2) (2g)
2
(196.1M/s2 ) (20g),
Pulse Duration: 11ms ± 5 msec
operating and non-operating
non-operating 1 hr. on each of 3 axes,
sweep time 10 minutes
(non-operating, 1/2 sine pulse, three
shocks on each axis, Power Supply is
fixed on its bottom side)
Designed to meet EN61000-3-2
EN61000-4-11normal operation
HSF (M) 300W 0423155
Page 8
1.500
[38.1]
0.093 [2.4]
14.667 [372.5]
5
.
0
4
0
[
1
2
8
.
0
]
0.188 [4.8]
0.093 [2.4]
0.093
[2.4]
0.127
[3.2]
0.430 [10.9]
2.065
[52.5]
3.353
[85.2]
0.337 [8.5]
0.085 [2.2]
0.204 [5.2]
0.090 [2.3]
0.943 [23.9]
2.408 [61.2]
0.438 [11.1]
0.394
[10.0]
3.216 [81.7]
0.606 [15.4]
0.690 [17.5]
FRONT VIEW
REAR VIEW
SEE
REAR
VIEW
SEE
FRONT
VIEW
NOTES:
1. MATERIAL:
A) BACKPLATE 0.064" THK. ALUM. 5052-H32
B) PCB 0.063" THK FR-4
C) FRONT PANEL 0.090 THK. ALUM. 6061-T6
2. FINISH:
FRONT PANEL -KEPCO DUAL TONE GRAY
3. MODULE IS KEYED AS SHOWN IN DETAIL
4. DIMENSIONS ARE IN INCHES, [DIMENSIONS IN BRACKETS
ARE IN MILLIMETERS].
3043284
15V12V
= PIN PRESENT
= PIN MISSING
KEYING
DETAIL "A"
SEE DETAIL "A"
24V 28V 48V
5
.
2
1
8
[
1
3
2
.
5
]
4.288 [108.9]
2.144
[54.46]
AIRFLOW
5V
FIGURE 3. MECHANICAL OUTLINE DRAWING, HSF 300W M AND MZ MODELS
3. FEATURES
3.1DIP SWITCH CONFIGURATION
The HSF 600W Series M and MZ models incorporate two DIP switches, SW1 and SW2 (see Figure 4), which must be configured before the unit is installed in the rack adapter. The DIP switches
control the following parameters:
•Positions 1, and 2 allow the output to be controlled either by the front panel Vadj control
(see PAR. 3.4.1) or by remote control using either an external trimpot or voltage source
(see PAR. 3.4.2). These positions can also be configured to allow a master/slave combination to be controlled either by the front panel Vadj control or by remote control using
either an external trimpot or voltage source (see PAR 3.4).
•Positions 3 and 4 either allow the front panel reset button to be used to reset the unit
after a fault or allow Remote on-of f via mechan ical switch or logic level (see PAR. 3.4.3).
•Positions 5 and 6 allows alarm signals to be produced from either internal relay, Form C
contacts (one NO, one NC) or open-colle ctor logical alarm signals (see PAR. 3.8.2).
6HSF (M) 300W 042315
Page 9
•Position 7 of SW1 either enables (default) or disables using the auxiliary supply to power
OFF
ON
OFF
ON
ALARM LED DISABLE
DC ON PWR BY REF
-PF
+PF
-RC
+RC
RV
REF
3043278
8
8
8
SW1
SW2
4
6
7
5
2
3
1
4
4
5
6
7
6
7
5
1
2
3
2
3
1
DC ON PWR BY OUTP V
8
-RC
4
+PF
-COM
-PF
6
7
5
REF
+RC
RV
2
3
1
FACTORY DEFAULT SETTING:
- FRONT PANEL VADJ CONTROL
- RELAY ALARM SELECTED
- VISUAL ALARM DISABLED
- REMOTE ON-OFF DISABLED
- DC ON PWR BY REF ENABLED
NOTE: NOT ALL COMPONENTS SHOWN.
DETAIL VIEW
SW1SW2
SEE DETAIL VIEW
TAB
the DC ON indicator. Position 8 of SW2 either disables (default) or enables us ing the
HSF output voltage to power the DC ON indicator; requires minimums per Table 4 if
enabled (see PAR 3.9). Only one of these two must be enabled, the other disabled.
•Position 8 of SW1 either disables (default) or enables the visual alarm indication (see
PAR. 3.8.1).
3.2FRONT PANEL ACCESS.
The front panel provides a power ON/OFF switch controlling input power and a "VDC ON" indicator which lights green when the unit is operating. If the unit is connected in a parallel configuration,
the indicator lights red if the unit shuts off automatically, or the POWER switch is set to OFF.
CAUTION: DO NOT repeatedly toggle the power ON/OFF switch as this may cause unit to
NOTE: The ON/OFF switch must be set to OFF before removing unit from rack adapter.
If remote on-off is not enabled (see PAR. 3.4.3), the OUTPUT RESET button restores output
power in the event that overcurrent or overvoltage protection has tripped, or thermal overload or
fan malfunction has occurred.
If remote voltage control (see PAR. 3.4.2) is not enabled, the front panel Vadj trimmer (see PAR.
3.4.1) provides adjustment of the output voltage within the limits specified in Table 2; test points
are available at the front panel for monitoring the DC output.
Figure 5 shows the location of all operating controls, indicators and test points followed by an
explanation of each.
3.3KEYING
Keying of the HSF 300W is established at the factory. The output voltage determines which key
pins are installed (see Figure 3, Detail A). When the proper holes in the rack adapter are b locked
by keying screws installed by the user, only a power supply of the correct voltage can be inserted
in the rack adapter slot. Refer to the RA 19-4C Manual for rack adapter keying instructions.
fault.
FIGURE 4. DIP SWITCH CONFIGURATION
HSF (M) 300W 0423157
Page 10
•VDC ON/ALARM indicator. Lights green when unit is operating. Both M and MZ models permit
3043129
Retaining Latches
POWER ON/OFF switch
OUTPUT RESET switch
TEST POINT (-)
TEST POINT (+)
V. ADJ Output Voltage Adjustment Trimmer
VDC ON/ALARM Indicator
Voltage/Current Meter
Meter Mode switch
V (Voltage) indicator
A (Amperes) indicator
selection of indicator power, either from HSF output or internal reference (see PAR. 3.4.3). When
enabled by DIP switch configuration, lights red to indicate loss of output voltage in parallel configuration only (see PAR. 3.8.1).
•V.ADJ Output voltage adjustment trimmer: Adjusts output voltage within limits specified in Table 2
(see PAR. 3.4.1). Not functional if remote voltage control is enabled (see PAR. 3.4.2).
•TEST POINT (+, –): Connect to voltmeter to monitor d-c output voltage.
•OUTPUT RESET switch. Used to r ecycle power in the event of an alar m condition (see PAR. 3.6).
Not functional when remote on/off control is enabled (see PAR. 3.4.3).
•POWER ON/OFF switch. Applies power to the unit. CAUTION: Power must be OFF before unit is
removed from the rack adapter.
•Retaining Latches (2). Prevents inadvertent removal of unit from rack adapter (see PAR. 3.10).
•Voltage/Current meter: Monitors output voltage or current according to setting of Meter Mode
switch. NOTE: Use remote sensing for voltmeter to display voltage at the load.
•Meter Mode slide switch: Set to V for display to show output voltage, set to A to show output current.
•V indicator: Lights green to indicate meter is showing Volts.
•A indicator: Lights amber to indicate meter is showing Amperes.
3.4OUTPUT VOLTAGE CONTROL
Output Voltage can be controlled from either the front panel (PAR. 3.4.1) or externally using a
trimpot or voltage source (PAR. 3.4.2).
3.4.1 FRONT PANEL VOLTAGE CONTROL
Output voltage can be manually adjusted with the voltage adjustment control, Vadj (see Figure 5
for location) when DIP switches SW1 and SW2 (see Figure 4 for location) are configured as
shown in Figure 6A (factory default) To adjust voltage, first place the unit under an operating load.
Then monitor the (+) and (–) test points on the front panel with a precision voltmeter and turn the
voltage control to the desired operating value. Refer to Table 2 for the recommended Adjustment
Range of all the HSF 300W M and MZ Models.
3.4.2 REMOTE VOLTAGE CONTROL
For remote voltage control, set positions 1, 2 and 7 as shown in Figure 6B. This removes control
from the front panel Vadj control and allows the output voltage to be adjusted by either an external
8HSF (M) 300W 042315
FIGURE 5. FRONT PANEL CONTROLS, INDICATORS AND TEST POINTS
Page 11
trimmer pot (resistance) or by an external variable voltage source connected across the rack
OFF
SW1
3043279
COM 7
REF 1
RV 2
7
SW2
1
ON
2
1
2
OFF
1 REF
2 RV
ON
SW1SW2
7
1
2
OFF
ON
1
2
OFF
ON
USING Vadj CONTROL
FRONT PANEL VOLTAGE CONTROL
A
B
(FACTORY DEFAULT)
REMOTE VOLTAGE CONTROL
OR VOLTAGE SOURCE
USING EXTERNAL TRIMPOT
COM 7
REF 1
RV 2
2 RV
1 REF
TAB
adapter I/O connector pin 12 (RV, Remote Voltage) and pin 10 (–COM, Common) as shown in
Figure 7. At the rack adapter I/O connector use a shielded wire 6.6 feet (2M) maximum in length,
for connection of REF (pin 2), RV (pin 12), a nd –COM (pin 10) to the trim mer control or external
voltage source.
NOTE:If remote voltage control is not implemented, the factory d efault for positions 1, 2 and 7 of DIP
switches SW1 and SW2 must be restored (Figure 6A).
FIGURE 6. DIP SWITCH SETTINGS FOR CONTROL OF OUTPUT VOLTAGE
It is possible that overvoltage protection may be triggered if the output voltage is decreased to a low
level very quickly when the power supply is at a low load condition.
RESIST ANCE: Connect the external trimmer as shown in Figure 7A. Suggested value for the trimmer control is 5K ohms. For M Models only: Resistor R (se e Figure 7A) is used to obtain minimum output voltage required to ensure proper operation of the alarm relay and LED indicator; see
Table 4 for values. NOTE: Output voltage may not adjust to 0V due to residual trimmer resistance.
VOLTAGE. By adjusting an external 0 to 6V voltage source (0 to 5.5V for the 48V model), the HSF
power supply output voltage can be adjusted as specified in Table 2.
For M Models (except HSF 5-60M) only: To ensure proper operation of the alarm relay, meter
and L ED indic ators, do not adjust external voltage below minimum list ed in Tabl e 4. Connect the
voltage source across the RV and –COM pins as shown in Figure 7B.
For MZ Models and HSF 5-60M only: The meter and relay are powered internally and are not
dependent on HSF output to maintain function.
Minimum HSF output voltage required for continuous
relay, meter and LED functioning (Volts d-c); startup
minimum are 0.5V higher except for HSF 5-60M.
Minimum resistance of Limit resistor R (Figure 7A) in
series with 5K ohm Trimpot to ensure proper operation
of LEDs, meter and relay (Ohms).
Minimum external voltage (Figure 7B) to ensure proper
operation of LEDs, meter and relay. (Volts d-c).
Voltage source range (Volts d-c)0 - 60 - 60 - 60 - 60 - 60 - 5.5
1 - If operating below minimums listed, see PAR. 3.8.2.2 to implement ±PF alarm signals to monitor power supply status.
2 - 5V model includes auxiliary supply that powers the relay, meter and LED independent of output voltage.
TABLE 4. MINIMUM CONDITIONS FOR RELAY, METER AND LED OPERATION
HSF MODEL
1
1
1
2
5-60M
12-27M15-22M24-14M28-12M48-7M
No limit5.57777
No limit2.61K1.91K1.3K1.1K634
No limit2.32.431.431.280.68
HSF (M) 300W 0423159
Page 12
FIGURE 7. CONNECTIONS FOR REMOTE VOLTAGE CONTROL
3043492
7
7 DC ON PWR BY REF
7
SW1
8
SW2
8
OFF
ONOFF
ON
USE REFERENCE SUPPLY
(FACTORY DEFAULT)
TO POWER "DC ON"
A
TO POWER "DC ON"
USE HSF OUTPUT VOLTAGE
B
(REQUIRES MINIMUM OUTPUT VOLTAGE)
7
8
8
SW1
7
SW2
OFF
ON
ON
OFF
DC ON PWR BY OUTPUT V 8
8
7
7
8
8
7
TAB
3.4.3 VDC ON/ALAR M INDICATOR POWER OPTIONS
To use the internal power supply reference voltage to power the VDC ON/ALARM indicator, set
Position 7 of SW1 to ON and Position 8 of SW2 to OFF (default) (see Figure 8A). Load effect is
±1% maximum. To use the HSF output voltage to power the VDC ON/ALARM indicator, set Position 7 of SW1 to OFF and Position 8 of SW2 to ON (see Figure 8B). Load effect is ±0.6% maximum, however the minimums specified in Table 5 must be observed for the indicator to function.
FIGURE 8. DIP SWITCH SETTINGS FOR VDC ON/ALARM POWER OPTIONS
Table 5 lists the minimum HSF output voltage required to maintain VDC ON indicator function for
this case. Maximum output voltage of unit might cause overvoltage trip if SW2, position 8 is
enabled. If this occurs, turn Vadj trim pot counterclockwise to reduce output voltage, then reset the
unit.
TABLE 5. CONDITIONS FOR VDC ON/ALARM LED OPERATION POWERED BY
Minimum HSF output voltage
required for VDC ON LED to
function when SW 2 position 8 is
ON and SW 1 position 7 is OFF
(Volts d-c).
3.33.33.54.558
3.5REMOTE ON-OFF
When power is ON at the source, the output may be turned ON or OFF using the ±R C signals if
the remote ON-OFF feature is enabled. Note that when remote ON-OFF is enabled, the RESET
OUTPUT switch does not function. Remote ON-OFF is enabled by setting DIP switch positions 3
and 4 as shown in Figure 9B. The +RC and –RC signals (at the rack ad apter I/O connector, pins
15 and 8, respectively) then turn the unit on or off. These pins accept a logic level (2.4V to 24V
10HSF (M) 300W 042315
OUTPUT
Page 13
“high” and 0.0 to 0.4V “low”), or a contact closure. When the ±RC pins are open, using either a
3042877
3
3 +RC
+RC 3
3
SW1
-RC 4
4
SW2
4
4 -RC
OFF
ONOFF
ON
(FACTORY DEFAULT)
USE FRONT PANEL
RESET BUTTON
A
B
(LOGICAL LEVEL OR
MECHANICAL SWITCH)
USE REMOTE ON-OFF
3
3
SW2SW1
4
4
ON
OFF
OFF
ON
3 +RC
4 -RC
+RC 3
-RC 4
TAB
mechanical switch or a high level logic signal, the HSF output is cut OFF. When the ±RC pins are
shorted, the output returns to within specifications. At low level logic, the maximum source current
is 1.6mA and at high level the sink current is 1.0mA. Positions 3 and 4 of both DIP switches must
be restored to the factory default setting (Figure 9A) if rem ote ON-OF F is not used. The ±RC pins
are isolated from DC output pins and a-c input terminals.
FIGURE 9. DIP SWITCH SETTINGS FOR USING RESET BUTTON OR REMOTE ON-OFF
3.6RESET (RESTART)
There are three ways to reset the unit:
3.7PROTECTION CIRCUITS
3.7.1 OVERVOLTAGE AND OVERTEMPERATURE PROTECTION
•If remote on/off feature (see PAR. 3.4.3) IS NOT in use, press and release the OUTPUT
RESET switch on the front panel.
•If the remote on/off feature IS in use (see PAR. 3.4.3), open the connection between the
±RC pins and then reconnect the pins.
•The unit may also be restarted by turning the POWER ON/OFF switch to OFF, waiting
40 seconds, then setting the POWER switch to ON.
The following protection features are implemented in the HSF 300W Serie s M and MZ Models:
overvoltage and overtemperature (PAR. 3.7.1), overcurrent (PAR. 3.7.2), fan failure (PAR. 3.7.3),
and undervoltage (PAR. 3.7.4). The HSF provides a configurable visual alarm (see PAR. 3.8.1) as
well as an option to use either relay contacts or logic levels for alarm signals (see PAR. 3.8.2)
When the output voltage of the HSF increases beyond the specified values (see Table 2), the output is cut OFF and the fan turns OFF. After shut down, reset (restart) the unit per PAR. 3.6.
When the internal temperature of the HSF increases beyond allowable limit, the ou tput is cut OF F
and the fans turn OFF. The restart cycle (Power ON) should not begin until the temperature
returns to within specifications. To restart (reset) the unit, set the POWER ON/OFF switch to OFF,
wait until unit cools, then set the POWER switch to ON. The power supply cannot be reset using
the remote ON-OFF feature unless the power supply remains shut down for at least 40 seconds.
HSF (M) 300W 04231511
Page 14
3.7.2 OVERCURRENT SETTING AND PROTECTION
The output characteristic of the power supply is a square type, and the unit is set to produce an
alarm (see PAR. 3.8.2) and shut down if output current exceeds specifications (see Table 2) for
more tha n 30 seconds . After the cause of overcurrent is removed, the power supply output is automatically restored.and shut down if output current exceeds specifications (see Table 2) for more
than 30 seconds. After shut down, reset (restart) the unit per PAR. 3.6.
3.7.3 FAN FAILURE
A cutoff of the fan supply voltage or a decrease in fan speed causes the ou tput to sh ut down and the
fans to turn OFF. Fan failure and all the other protection circuit operations produce an alarm (see
P AR. 3.8.2). After shut down, reset (restart) the unit per PAR. 3.6. If fan rotation is out of specification the power supply will not recover.
3.7.4 UNDERVOLTAGE
M MODELS ONLY: If power supply output voltage either falls below 80% of the programmed (set)
value, or if output voltage is programmed below the minimum values listed in Table 4, an alarm
occurs if the internal relay alarm (factory default, see PAR. 3.8.2.1) is enabled. After shut down,
reset (restart) the unit per PAR. 3.6. To enable the alarm function when operating below the minimum values listed in Table 4, refer to PAR. 3.8.2.2 to configure the optically-coupled ala rm.
MZ MODELS ONLY: If power supply output voltage falls below 80% of the programmed (set)
value, an alarm occurs. After shut down, reset (restart) the unit per PAR. 3.6.
3.8ALARM SETTINGS
3.8.1 VISUAL ALARM.
When the unit is connected in a parallel configuration, the front panel VDC ON/ALARM indicator
can be configured to light red if the respective power supply output voltage is lost or if the POWER
switch is set to OFF. This is enabled when DIP switch 1, position 8 set to ON. This can be useful
to indicate the loss of output voltage from one parallel-connected power supply that may not be
readily apparent. The visual alarm is normally disabled: DIP switch SW1, position 8 set to OFF
(factory default ); requires minimums per Table 4 if enabled (see PAR 3.9). Only one of these two
must be enabled, the other disabled.
NOTE: On MZ models, the meter is powered by an independent internal power supply and will
most likely remain lit after a failure. Visual inspection of the front panel VDC ON/
ALARM indicator and/or monitoring of the alarm signals is required to detect a failure.If
the ALARM indicator is enabled to light red, the VDC ON/ALARM indicator must be
powered from the HSF output (see PAR. 3.4.3).
3.8.2 ALARM SIGNALS.
Either of two options are available for signalling alarms: isolated relay contacts (factory default,
PAR. 3.8.2.1) or logic level alarm signals ±PF (PAR. 3.8.2.2). The ±PF logic level alarm option
must be used if the power supply is intended to operate below the minimum voltages listed in
Table 4.
3.8.2.1 INTERNAL ISOLATED RELAY ALARM
The first option, the factory default setting, uses an isolated internal relay offering normally closed
(NC) and normally open (NO) contacts referenced to an isolated common (AL COM). Th ese contacts may be used to configure “close on failure” or “open on failure” alarm circuits. (Refer to the
Series RA 19-4C Manual for alarm configurations for multiple HSF power supplies.) Setting positions 5 and 6 of the DIP switches as shown in Figure 10A selects this option. The NC (pin 6 of the
rack adapter I/O connector) and NO (pin 7) signals are referenced to Alarm common (pin 14).
12HSF (M) 300W 042315
Page 15
3.8.2.2 OPTICALLY-COUPLED LOGICAL ALARM
3042878
5
5 +PF
+PF 5
5
SW1
-PF 6
6
SW2
6
6 -PF
OFF
ONOFF
ON
USE N.O. AND N.C CONTACTS
(FACTORY DEFAULT)
OF INTERNAL RELAY
A
LOGICAL ALARM
USE OPTICALLY-COUPLED
B
(+PF AND -PF)
5
6
6
SW1
5
SW2
OFF
ON
ON
OFF
+PF 5
-PF 6
6 -PF
5 +PF
TAB
The second option uses optically-coupled logic level alarm signals, +PF (pin 5 of the rack adapter
I/O connector) and -PF (pin 13), provided directly from the Kepco RKW power supply that is the
heart of the HSF. This option is selected by setting positions 5 and 6 of the DIP switches as shown
in Figure 10B. Use this option if the power supply will operate below the minimum voltages specified in Table 4.
FIGURE 10. DIP SWITCH SETTINGS FOR OPTICALLY COUPLED LOGICAL ALARM
The logic alarm circuit is a diode transistor optical coupler (see Figure 11). The transistor is normally conducting. When the alarm is activated upon detection of power loss, overvoltage, fan
fault, overtemperature or overcurrent condition, the transistor cuts off and the collector emitter circuit is open. Figure 12 is a timing diagram of the power fail signal.
The default state of the alarm is logic low. The sink current for the optocoupler is 50mA maximum,
the maximum collector to emitter saturation voltage is 0.40 Volts, and the collector to emitter voltage is 40 volts maximum. The PF signals are isolated from the AC input and DC output.
FIGURE 12. ±PF POWER FAILURE OPTOCOUPLER TIMING DIAGRAM
3.9LOCAL/REMOTE SENSING
HSF (M and MZ) 300W Power Supplies allow remote error sensing which can compensate up to
0.4 Volts per load wire. Local/Remote error sensing is configured by means of separate DIP
switches mounted on the RA 19-4C Rack Adapter (see RA 19-4C Rack Adapter Opera tor Manual). Either local or remote sensing MUST be used, otherwise the units will not operate.
3.10 RETAINING LATCHES
HSF power supplies are provided with (2) retention latches located at each side of the bottom
edge of the front panel (see Figure 5). These latches work in conjunction with the RA 19-4C rack
adapters to prevent unauthorized or inadvertent module extraction from an operating power system. The latch is engaged by loosening the cap-head screw approximately 1/2 turn CCW (u se 5/
32" hex key) and sliding the latch down to the bottom of the slot, then retightening the cap-he ad
screw CW until snug. DO NOT OVERTIGHTEN! To release, follow the same procedure, except lift
the latch to the top of the slot. Be sure to move the latch completely up or down to ensure full
engagement and disengagement of the latching mechanism. When the HSF power supply is not
installed in its plug-in rack adapter, it is recommended that the latch be secured in the open (up)
position to prevent damage.
NOTE: Retaining latches must not be used to secure the HSF power supply in the rack
adapter for shipping purposes.
4.LOAD CONNECTION
Connect the load to (+) and (–) terminals at the rear panel of the Rack Adapter (see RA 19-4C
Instruction Manual for details).
5.CONNECTING MULTIPLE POWER SUPPLIES
All connections to multiple HSF power supplies must be made via the I/O mating connectors at
rear of the Rack Adapter or by the Rack Adapter DIP switches. These connections, including the
configuration of the two internal HSF DIP switches, are described in the Rack Adapter Instruction
manual, and include:
•Using one power supply to control the output of multiple supplies.
•Using parallel master/slave configurations (for increased current or redundancy) where
the user either predetermines the master or allows the load to determine which is the
master. These configurations also cover the use of the Current Balancing feature of the
HSF power supply.
•Using series configurations (for increased voltage).
•Using open-on-fail or close-on-fail alarm schemes with multiple power supplies.
14HSF (M) 300W 042315
Page 17
5.1ADJUSTING THE VOLTAGE
NOTE: Refer to the RA 19-4C Rack Adapter manual for alternatives to the standard master/
slave parallel configuration described below.
To adjust the paralleled units, turn off all the units except one (designated as the master) and
adjust to desired voltage using the front page trimmer and monitoring the front panel voltmeter.
•Each slave must be adjusted to a slightly lower voltage than the previous unit. The difference between the master and the lowest voltage slave must not exceed 2% of E
NOM
.
•The voltage separation between master and subsequent slave(s) (V
SEP
) = 2% E
where N = number of units in parallel.
SLAVE3
to E
to V
Adjust the first slave V
Adjust the third slave V
SLAVE1
As an example, for three HSF 24-27M units in parallel, 2% of E
NOM
SLAVE2
- V
. Adjust the second slave V
SEP
- V
and so on.
SEP
SLAVE2
is 0.48V and V
NOM
to V
SLAVE1
SEP
0.16V. Turn off the master, then turn on another unit (slave 1) and adjust for 160mV less than the
master. Turn off slave 1 and turn on slave 2 and adjust for 160mV less than slave 1.
When all units are turned on, the unit adjusted to the highest voltage will be the master. The
meters of all units read the voltage on the bus. If a unit fails, the VDC ON indicator of that unit is
either off or red, however the meter of a failed MZ Model may continue to read the voltage on the
bus since it is powered by a separate internal power supply.
5.2PARALLEL CONNECTIONS, M MODELS
When using parallel-connected M Models, a minimum load is req uired to avoid the slave becoming “idle.” When the slave is idle, the output is off, no lights are lit, and the alarm is set. The minimum load (Amperes) = N x (I/10) where N = the number of units in parallel, I = Nominal current
rating of individual power supply (Amperes). For applications requiring either no load or lower
than minimum load conditions, the MZ Models are recommended.
5.3PARALLEL CONNECTIONS, MZ MODELS
If parallel-connected MZ models are controlled individually, either a minimum load or voltage set
restrictions are required to avoid slave “idle” or slave “oscillating output” conditions; the idle and
oscillating output conditions show slightly different indications depending on the position of SW1
position 7 as defined below. NOTE: If the minimum load is maintained, voltage set restric-
tions are not required.
/ N
NOM
- V
SEP
is 0.48/3 =
.
If position 7 of SW1 is set to off (default, see PAR. 3.1), the VDC ON indicator is powered from the
output; therefore when a slave is idle, the output is o ff, VDC ON is off, and the alarm is set. The
oscillating output condition means that the unit alternates between briefly idle and output on (the
VDC ON indicator will appear dim as it goes on and off, and the toggling relay will be audible).
If position 7 of SW1 is set to on (see PAR. 3.1) so that the VDC ON indicator is powered from the
internal power supply, when a slave is idle, the output is off, VDC ON lights red, and the alarm is
set. The oscillating output condition means that the unit alternates between briefly idle and output
on (the VDC ON indicator will toggle between briefly amber and green, and the toggling relay will
be audible).
HSF (M) 300W 04231515
Page 18
5.3.1 MINIMUM LOAD
The minimum load (Amperes) = N x (I/10) where N = the number of units in parallel, I = Nominal
current rating of individual power supply (Amperes). For applications requiring no load o r lower
than minimum load conditions, see voltage set restrictions of PAR. 5.3.2. Load effect specifications will not be met when units are operated in redundant mode with load less than 10% per unit.
For loads less than 10%, voltage stabilization may be affected if units are turned off and on via the
front panel, causing voltage on the paralleled bus to rise as high as 8% for 5 seconds maximum.
This can be avoided by using the remote on-off feature to turn the units off and on.
5.3.2 VOLTAGE SET RESTRICTIONS
To avoid slave “idle” all parallel-connected units’ output voltage must be set within 1% or 200mV
of each other (whichever is lower) and be at least 80% of their nominal (rated) output voltage
(90% for 48V model).
16HSF (M) 300W 042315
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.