KEPCO HSF 12-53, HSF 24-27, HSF 15-43, HSF 28-23, HSF 48-13 Operator's Manual

...
KEPCO®
THE POWER SUPPLIER™
OPERATOR’S MANUAL
HSF 600 WATTS
POWER SUPPLY
SINGLE OUTPUT POWER SUPPLIES
SINGLE PHASE, POWER FACTOR CORRECTED
UNIVERSAL AC INPUT
MODEL
KEPCO INC.
An ISO 9001 Company.
IMPORTANT NOTES:
1) This manual is valid for the following Model and associated serial numbers: MODEL SERIAL NO. REV. NO.
HSF 600 Watts
2) A Change Page may be included at the end of the manual. All applicable changes and
revision number changes are documented with reference to the equipment serial num­bers. Before using this Instruction Manual, check your equipment serial number to identify your model. If in doubt, contact your nearest Kepco Representative, or the Kepco Docu­mentation Office in New York, (718) 461-7000, requesting the correct revision for your particular model and serial number.
3) The contents of this manual are protected by copyright. Reprod uction of any part can be
made only with the specific written permission of Kepco, Inc.
Data subject to change without notice.
HSF 600 WATTS
POWER SUPPLY
HSF 12-53, HSF 15-43, HSF 24-27,
HSF 28-23, HSF 48-13
HSF 12-53C, HSF 15-43C, HSF 24-27C,
HSF 28-23C, HSF 48-13C
©2015, KEPCO, INC P/N 228-1588-R
KEPCO, INC. 131-38 SANFORD AVENUE  FLUSHING, NY. 11355 U.S.A.  TEL (718) 461-7000  FAX (718) 767-1102
email: hq@kepcopower.com World Wide Web: http://www.kepcopower.com
TABLE OF CONTENTS
1 Introduction................................. ................................................ ... .................................................................... 1
1.1 Scope of Manual.................................................. ... .................................................. ...................................... 1
1.2 Description................................................ ................................................ .. .................................................... 1
1.3 Options............................. .. ................................................ ............................................................................. 1
2 Specifications.................................................................................................... ... .............................................. 2
3 Features.......................................................................................................................................................... 6
3.1 DIP Switch Configuration................................................................................................................................ 6
3.2 Front Panel Access......................................................................................................................................... 7
3.3 Keying........................................................................................... .................................................................. 8
3.4 Output Voltage Control ................................ ... .................................................. .............................................. 8
3.4.1 Front Panel Voltage Control......................................................................................................................... 8
3.4.2 Remote Voltage Control............................................................................................................................... 9
3.5 Remote On-Off............................... ............................................... ... .................................. ... ........................ 10
3.6 Protection Circuits......................................................................................................................................... 10
3.6.1 Overvoltage And Overtemperature Protection........................................................................................... 10
3.6.2 Overcurrent Setting and Protection............................................................................................................ 11
3.6.3 Fan Failure..................................................... ... ................................................ ... ................................. ..... 11
3.6.4 Undervoltage.............................................................................................................................................. 11
3.7 Alarm Settings................................... ............................................... ... .......................................................... 11
3.7.1 Vis ual Alarm............................................................ ... ................................................................................ 11
3.7.2 Alarm Signals............................................................. ................................................................................ 12
3.7.2.1 Internal Isolated Relay Alarm.................................................................................................................. 12
3.7.2.2 Optically-Coupled Logical Alarm............................................................................................................. 12
3.8 Local/remote Sensing................................................................................................................................... 13
3.9 Retaining Latches ...................................................... ... ................................................................................ 13
4 Load Connection.............................................................................................................................................. 14
5 Connecting Multiple Power Supplies ...........................................................................................
.................... 14
5.1 Adjusting the Voltage ......................................................... ... ........................................................................ 14
5.2 Parallel Connections, Standard and C Models ............................................................................................. 14
1 HSF Rear Panel Connector and RA 19-4C Rack Adapter I/O Connector.................................................. 1
2 Power Rating Vs. Temperature (Input: 95 to 264V a-c).............................................................................. 3
3 Mechanical Outline Drawing Of The HSF 600W Power Supply ................................................................. 6
4 DIP Switch Configuration............................................................................................................................ 7
5 Front Panel Controls, Indicators and Test Points ....................................................................................... 8
6 DIP Switch Settings for Control of Output Voltage ..................................................................................... 9
7 Connections For Remote Voltage Control................................................................................................ 10
8 DIP Switch Settings for Using RESET button or Remote ON-OFF .......................................................... 10
9 DIP switch settings for Optically Coupled Logical Alarm.......................................................................... 12
10 Output Alarm Circuit Optically Isolated..................................................................................................... 13
11 ±PF Power Failure Optocoupler Timing Diagram..................................................................................... 13
1 HSF Rear Connector Pin Assignments ......................................................................................................2
2 Output Ratings and Specifications ..............................................................................................................3
3 Power Supply Ratings and Specifications ..................................................................................................4
4 Minimum Conditions for Relay and LED Operation ....................................................................................9
SECTION PAGE
FIGURE TITLE PAGE
TABLE TITLE PAGE
i HSF 600W 042315
LIST OF FIGURES
LIST OF TABLES
1 INTRODUCTION
3042951
89
7 12 11 10 15 181617
14
13
21 20 19
21
34 56
22
23
24
1 OUTPUT+OUTPUT+ 2 3 OUTPUT­5 OUTPUT-
7 S­8 IMON+
10 NO
OUTPUT+ 4
OUTPUT- 6
S+ 9
IMON - 11
REF 15 CSB 17
+RC 20
13 NC 14 AL COM 16 +PF 19 -PF
AC IN (GND) 22
AC IN (L) 24
23 AC IN (N)
-COM 12
RV 18
-RC 21
1.1 SCOPE OF MANUAL
This Operator's Manual covers the installation and operation of the Ke pco HSF 600W Series of Switching Power Supplies. This manual covers only standard (no suffix) and Option C models. For service information, write directly to: Kepco Inc., 131-38 Sanford Avenue, Flushing, New York, 11355, U.S.A. Please state Model Designation and Serial Number of your HSF Power Supply. This information can be found on the nameplate of the unit.
1.2 DESCRIPTION
The Kepco HSF 600 Watt Series are hot swappable, high frequency switching, plug-in power sup­plies. Five models may be selected for outputs of 12V, 15V, 24V, 28V or 48V. They employ for­ward conversion and power factor correction and are designed to operate in a fault tolerant power system with a nominal a-c input of 100V a-c to 240V a-c (input voltage range 85 to 264 Va-c), 50­60 Hz (input frequency range 47-440Hz). A built-in current balancing cir cuit and OR-ing diodes allow configuration for hot-swap and parallel-redundant N+1 operation.
These power supplies are designed to be used with Kepco's Series RA 19-4C rack adapte rs. The RA 19-4C rack adapter accepts up to four 600W modules. All input/output connections are through a 24-pin connector that plugs in to the rack adapter. All external connections described in the following paragraphs are made through the rack adapter ’s I/O connector (see Figure 1).
1.3 OPTIONS
Option C models allow independent monitoring of output current of non-metered models by p ro­viding an integral sense resistor (Rs). Current monitoring is via ±IMO N assigned to p ins 9 (–) and 1 (+) of the RA 19-4C I/O connector: Monitored Output Current (Amps) = Voltage drop across Rs (Volts) / Rs (Ohms) (see Table 2), where voltage drop across Rs is measured across ± IMON pins (requires millivoltmeter, range 0 to 200mV). Accuracy is ±10%; contact Kepco if greater accuracy is required. There is no isolation between ±IMON, alarm circuit an d d-c output. Refer to the RA 19-4C Manual for details.
RoHS-compliant models are indicated by HSF* (e.g., HSF 28*23).
FIGURE 1. HSF REAR PANEL CONNECTOR AND RA 19-4C RACK ADAPTER I/O CONNECTOR
HSF 600W 042315 1
TABLE 1. HSF REAR CONNECTOR PIN ASSIGNMENTS
Signal
Name
Output + 1, 2, 4 DC output (+) applied to load. Output – 3, 5, 6 DC Output (–) applied to load. SENSE– 7 Sense– connection.
IMON+ 8 Current Monitor+ (not used).
SENSE+ 9 Sense+ connection.
NO 10 Normally Open contact of alarm relay, referenced to AL COM, pin 14 (see PAR. 3.7.2).
IMON– 11 Current Monitor– (not used).
–COM 12 –Signal Common provides return for REF, pin 15, and RV, pin 18, signals.
NC 13 Normally Closed contact of alarm relay, referenced to AL COM, pin 14 (see PAR. 3.7.2).
AL COM 14 Common contact of alarm relay (see PAR. 3.7.2).
REF 15 Reference voltage. When used with RV, pin 18, allows all output voltages of paralleled slave supplies to be
+PF 16 +Power Fail of open-collector alarm circuit. Used with –PF, pin 19 (see PAR. 3.7.2). CSB 17 Current Share Bus - Used whenever several power supplies are connected in parallel (see PAR. 5).
RV 18 Remote Voltage - Used with REF, pin 15, for remotely controlling the output voltage (see PAR. 3.4.2). –PF 19 –Power Fail of open-collector alarm circuit. Used with +PF, pin 16 (see PAR. 3.7.2). +RC 20 +Remote On-off used with –RC, pin 21, to allow remote turn-on turn-off of the unit (see PAR. 3.5). –RC 21 –Remote On-off used with +RC, pin 20, to allow remote turn-on turn-off of the unit (see PAR. 3.5).
GND 22 AC input ground.
N 23 AC Input neutral. L 24 AC input line.
Pin Function
controlled by one voltage adjustment of a master power supply. When REF is connected to RV via an external trimmer, the external trimmer determines output voltage (see PAR. 3.4.2). Connections are made via DIP switches (see PAR. 3.1).
2 SPECIFICATIONS
Table 2 contains specifications and operating limits of individual HSF 600W Series models. Table 3 contains specifications and operating limits common to all HSF 600W Series Models. These specifications are at nominal input voltages at 25°C unless otherwise specified.
2 HSF 600W 042315
TABLE 2. OUTPUT RATINGS AND SPECIFICATIONS
NOTE: Safety agency approvals apply only to operation between -10°C and 40°C.
MODEL HSF 12-53 HSF 15-43 HSF 24-27 HSF 28-23 HSF 48-13
Output Volts d-c (nominal) 12 15 24 28 48
Using front panel trim pot or
Output
Adjustment
(1)
Range
external 5K ohm Trimpot
(Volts d-c)
(2)
Using Voltage source
(Volts d-c)
Output Current (nominal) (Amps d-c) 53 43 27 23 13
Maximum Output Ratings
Overcurrent Setting (Amps d-c)
(3)
(Watts) 636 645 648 644 624
(4)
Short Circuit Current (Amps d-c) 65 55 35 29 19
Overvoltage Protection (OVP) (Volts d-c)
Efficiency % typical
Power Factor
(typ.)
Ripple &
(6)
Noise
(mV, p-p)
AC Input 100V 80 81 82 82 84 AC Input 200V 84 85 86 86 87 AC Input 100V 0.99 0.99 0.99 0.99 0.99 AC Input 200V 0.95 0.95 0.95 0.95 0.95
ripple 180 180 220 220 220
ripple noise 220 220 320 320 320
Sense Resistor (IMON) values (Ohms)
(5)
(7)
(1) Refer to Table 4 for minimum conditions required to maintain proper operation of alarm relay and visual LED indicator. (2) Output voltage may not adjust to 0V due to residual trimmer resistance. (3) See Figure 2 for power derating. (4) Square type. Output voltage returns automatically only if cause is removed within 30 seconds (see PAR. 3.6.2). (5) When overvoltage is detected, output is shut OFF. Recovery is by removing, and after approximately 40 seconds, reapplying
AC input power or by reset (open and close) at ±RC terminals (no delay).
(6) Ripple and noise levels above are satisfied when conditions are 0 to 100% load, 0 to 40°C (load is derated from 40 to 55°C,
see Figure 2), and bandwidth </= 100MHz.
(7) Option C only.
0 - 13.8 0 - 17.4 0 - 28.2 0 - 33 0 - 52.2
0 - 13.8 0 - 17.4 0 - 28.2 0 - 33 0 - 52.2
55.6-68.9 45.1-55.9 28.3-35.1 24.1-29.8 13.7-16.9
14.3 - 16.8 18.0 - 21.0 29.3 - 33.6 34.2 - 39.2 54.5 - 59.8
0.002 0.005 0.01 0.01 0.02
FIGURE 2. POWER RATING VS. TEMPERATURE (INPUT: 95 TO 264V A-C)
HSF 600W 042315 3
TABLE 3. POWER SUPPLY RATINGS AND SPECIFICATIONS
CHARACTERISTIC SPECIFICATION CONDITION/NOTES
Input Voltage Nominal: 100-120V a-c, 200-240V a-c
Range: 85-264V a-c
Input Source Frequency Nominal: 50-60 Hz
Range: 47-440 Hz
Input Current: (Maximum Load At 25°C with Nominal Output Voltage)
Switching Frequency 140KHz typ. Forward Converter Input Protection A limiting resistor in series with a resistor fuse (and thyristor circuit) reduces start-up surge.
Input Surge cold start, interval > 30
sec ( First surge only, not including
current flow into EMI filter) Leakage Current: 0.45mA typ., 0.75mA max. 120V a-c, 60Hz per IEC 950 and UL1950
Power Factor 0.99 typical 100V a-c, max load, nominal output,
Transient Recovery excursion characteristic
recovery time 1 ms maximum
Stabilization
Source Effect (min - max) ±0.1% Typical, ±0.2% Maximum 85 to 132V a-c, 170 to 264V a-c
Load Effect ±0.3% Typical, ±0.6% Maximum
Temperature Effect ±0.5% Typical, ±1.0% Maximum –10° to 40°C
Combined Effect ±0.9% Typical, ±1.8% Maximum Source, Load and Temperature
Time Effect 0.2% Typical, 0.5% Maximum 1/2 to 8 hours at 25°C
Start-up Time 280 msec Typical, 350 msec Maximum 100V a-c
Output Hold-up Time 30 msec Typical, 20 msec Minimum. 100V a-c
Overvoltage Protection When the Power Supply goes into an overvoltage condition, the output is cut OFF. See PAR.
Remote Control ON/OFF: ±RC pins control on/off as follows:
Operating Temperature: -10 to 40°C Startup Temperature -10 to -20°C (see Figure 2.) Storage Temperature: -30°C to +75°C (1) For input voltage between 85 to 95V a-c maximum operating temperature is 35°C.
8.4A rms max. 100 - 120V a-c
4.2A rms max. 200 - 240V a-c
The internal power supply is protected against shorts by an input fuse. Fuse value 15.0A at 250 Volts
15A typ., 30A max. first surge 100 - 120V ac 30A typ., 60 max. first surge
0.60mA typ., 0.75mA max. 240V a-c, 60Hz per IEC 950 and UL1950
0.95 typical 200V a-c, max load, nominal output
±4% maximum
100 msec Typical, 150 msec Maximum 240V a-c
40 msec Typical, 20 msec Minimum. 240V a-c
3.6.1.
“High”, 2.4V to 24V (or open), unit OFF- Fan Off; “Low”, 0.0V to 0.4V (or closed), unit ON. Source current: 1.6mA maximum at low level Sink current: 1.0 mA maximum at high level.
(1)
(1)
, 110-370V d-c
(0 to 100% load, -10 to 40°C) (0 to 100% load, -10 to 40°C)
At 440 Hz leakage current exceeds
UL/VDE safety spec. limit.
200- 240 V ac
per EN 61000-3-2
per EN 61000-3-2
50% to 100% load,
transient time >50
0%-100% load change
Must be enabled by DIP switch positions 3 and 4 (see PAR. 3.5).
(see Figure 2.)
sec
4 HSF 600W 042315
TABLE 3. POWER SUPPLY RATINGS AND SPECIFICATIONS (CONTINUED)
CHARACTERISTIC SPECIFICATION CONDITION/NOTES
Withstanding voltage : (at 15-35°C ambient, 10-85% relative humidity)
Insulation Resistance: (at 25°C, 65% relative humidity)
Humidity: 10% to 95% relative humidity, noncondensing,
Vibration: 5-10 Hz., 10mm amplitude, 10-55 Hz., accelera-
Shock: Acceleration: 643.5ft./s
Safety: UL 60950-1, 1st Edition, 2007-10-31; CSA C22.2 No. 60950-1-03, 1st Edition, 2006-07;
RoHS Compliance Contact Kepco Sales for further information. EMC Emission - Conducted: Designed to meet FCC Class B, VCCI-Class B, EN55011-B, EN55022-B EMC Emission - Radiated: Designed to meet FCC Class B, VCCI-Class B, EN55011-B, EN55022-B EMC Emission - Input harmonics
current: EMC Immunity Designed to meet EN61000-6-2 EMC Radiated susceptibility: EN61000-4-3 level 3 normal operation EMC Conducted susceptibility: EN61000-4-6 level 3 normal operation ESD: EN61000-4-2, level 4 normal operation Electrical fast transient burst: EN61000-4-4 level 3 normal operation Surge withstand: EN61000-4-5, level 4 No damage Power Frequency Magnetic Field: EN61000-4-8, level 4 normal operation Voltage dips interruptions and
variations Dimensions: 5.22 in. (132.5 mm) x 4.288 in. (108.9 mm) x 16.86 in. (428.2 mm) (See Figure 3) Mounting: Plug-in Cooling: Forced air flow - fan Frame Material/Cover Material: Steel Weight 9 lbs, 4.1Kgs. maximum
2000Va-c for 1 minute. Cutout current is 20mA Between input and ground 500Va-c for 1 minute. Cutout current is 100mA Between output and ground 3000Va-c for 1 minute. Cutout current is 20mA Between input and output terminal 100 Megohms minimum (500Vdc) Between output and ground, input and
ground, and input and output,
Wet Bulb temperature <35°C
tion 64.3ft./s
2
(19.6M/s2) (2g)
2
(196.1M/s2 ) (20g),
Pulse Duration: 11ms ± 5 msec
operating and non-operating
non-operating 1 hr. on each of 3 axes,
sweep time 10 minutes
(non-operating, 1/2 sine pulse, three
shocks on each axis, Power Supply is
fixed on its bottom side)
EN 60950
Designed to meet EN61000-3-2
EN61000-4-11 normal operation
HSF 600W 042315 5
4.288 [108.9]
5
.
2
1
8
[
1
3
2
.
5
]
1.500 [38.1]
0.093 [2.4]
14.667 [372.5]
5
.
0
4
0
[
1
2
8
.
0
]
0.188 [4.8]
0.093 [2.4]
0.093 [2.4]
0.127 [3.2]
0.430 [10.9]
2.065
[52.5]
3.353 [85.2]
0.337 [8.5]
0.085 [2.2]
0.204 [5.2]
0.090 [2.3]
0.943 [23.9]
2.408 [61.2]
0.438 [11.1]
0.394 [10.0]
3.216 [81.7]
0.606 [15.4]
0.690 [17.5]
FRONT VIEW
REAR VIEW
SEE
REAR
VIEW
SEE
FRONT
VIEW
NOTES:
1. MATERIAL: A) BACKPLATE 0.064" THK. ALUM. 5052-H32 B) PCB 0.063" THK FR-4 C) FRONT PANEL 0.090 THK. ALUM. 6061-T6
2. FINISH: FRONT PANEL -KEPCO DUAL TONE GRAY
3. MODULE IS KEYED AS SHOWN IN DETAIL
4. DIMENSIONS ARE IN INCHES, [DIMENSIONS IN BRACKETS ARE IN MILLIMETERS].
3042952
15V12V
= PIN PRESENT = PIN MISSING
KEYING
DETAIL "A"
SEE DETAIL "A"
24V 28V 48V
AIRFLOW
FIGURE 3. MECHANICAL OUTLINE DRAWING OF THE HSF 600W POWER SUPPLY
3 FEATURES
3.1 DIP SWITCH CONFIGURATION
The HSF 600W Series incorporates two DIP switches, SW1 and SW2 (see Figu re 4), which must be configured before the unit is installed in the rack adapter. The DIP switches control the follow­ing parameters:
Positions 1 and 2 allow the output to be controlled either by the front panel Vadj control (see PAR. 3.4.1) or by remote control using either an external trimpot or voltage source (see PAR. 3.4.2). These positions can also be configured to allow a master/slave combi­nation to be controlled either by the front panel Vadj control or by remote control using either an external trimpot or voltage source (see PAR 3.4).
6 HSF 600W 042315
Positions 3 and 4 either allow the front panel reset button to be used to reset the unit
3043031
SEE DETAIL VIEW
SEE APPLICABLE
DESCRIPTION
FOR STANDARD
OR C MODELS.
NOTE: NOT ALL COMPONENTS SHOWN.
DETAIL VIEW
SW2 SW1
REF1
1
REF
-NOT USED ALARM LED DISABLE
SW1
SW2
+PF
-COM N/A
-PF
+RC
-RC
RV
+PF
5
5
7 8
6
7 8
-PF
6
3 4
2
3
+RC
-RC
4
RV
2
FACTORY DEFAULT SETTING:
- FRONT PANEL VADJ CONTROL
- RELAY ALARM SELECTED
- VISUAL ALARM DISABLED
- REMOTE ON-OFF DISABLED
Standard and C Models
ON
OFF OFF
ON
6
6
8
7
8
7
3
5
4
1 2
3 4 5
1 2
TAB
after a fault or allow Remote on-off via mechanical switch or logic level (see PAR. 3.5).
Positions 5 and 6 allows alarm signals to be produced from either internal relay, Form C contacts (one NO, one NC) or open-collector logical alarm signals (see PAR. 3.7.2).
For standard or C models position 8 of SW1 either disables (default) or enables the visual alarm indication (see PAR. 3.7.1).
3.2 FRONT PANEL ACCESS.
The front panel provides a power ON/OFF switch controlling input power and a "VDC ON" indica­tor which lights green when the unit is operating. If the unit is connected in a parallel configuration, the indicator lights red if the unit shuts off automatically, or the POWER switch is set to OFF.
CAUTION: DO NOT repeatedly toggle the power ON/OFF switch as this may cause unit to
fault.
NOTE: The ON/OFF switch must be set to OFF before removing unit from rack adapter. If remote on-off is not enabled (see PAR. 3.5), the OUTPUT RESET button restores output power
in the event that overcurrent or overvoltage protection has tripped, or thermal overload or fan mal­function has occurred.
If remote voltage control (see PAR. 3.4.2) is not enabled, the front panel Vadj trimmer (see PAR.
3.4.1) provides adjustment of the output voltage within the limits specified in Table 2; test points are available at the front panel for monitoring the DC output.
HSF 600W 042315 7
FIGURE 4. DIP SWITCH CONFIGURATION
Figure 5 shows the location of all operating controls, indicators and test points followed by an
3042857
1 2
3 4
3
5
6
explanation of each.
3.3 KEYING
Keying of the HSF 600W is established at the factory. The output voltage determines which key pins are installed (see Figure 3, Detail A). When the proper holes in the r ack adapter are b locked by keying screws installed by the user, only a power supply of the correct voltage can be inserted in the rack adapter slot. Refer to the RA 19-4C Manual for rack adapter keying instructions.
1. VDC ON/ALARM indicator. Lights green when unit is operating. Can be configured by DIP switch to light red to indicate loss of output voltage in parallel configurations.
2. V.ADJ Output voltage adjustment tr immer: Adjusts output voltage within limits specified in Table 2 (see PAR. 3.4.1). Not functional if remote voltage control is enabled (see PAR.
3.4.2).
3. DC output test points (+, –): Connect to voltmeter to monitor output voltage.
4. OUTPUT RESET switch. Used to recycle power in the event of an alarm condition (see PAR.
3.6). Not functional when remote on/off control is enabled (see PAR. 3.5).
5. POWER ON/OFF switch. Applies power to the unit. CAUTION: Power must be OFF before
unit is removed from the rack adapter.
6. Retaining Latches (2). Prevents inadvertent removal of unit from rack adapter (see PAR.
3.9)
FIGURE 5. FRONT PANEL CONTROLS, INDICATORS AND TEST POINTS
3.4 OUTPUT VOLTAGE CONTROL
Output Voltage can be controlled from either the front panel (PAR. 3.4.1) or externally using a trimpot or voltage source (PAR. 3.4.2).
3.4.1 FRONT PANEL VOLTAGE CONTROL
Output voltage can be manually adjusted with the voltage adjustment control, Vadj (see Figure 5 for location) when DIP switches SW1 and SW2 (see Figure 4 for location) are configured as
8 HSF 600W 042315
shown in Figure 6A (factory default) To adjust voltage, first place the unit under an operating load.
OFF
SW1
3043032
COM 7
REF 1
RV 2
7
7
SW2
7 COM
1
ON
2
1 2
OFF
1 REF 2 RV
ON
7
7
1 2
OFF
ON
1 2
OFF
ON
USING Vadj CONTROL
FRONT PANEL VOLTAGE CONTROL
A
B
(FACTORY DEFAULT)
REMOTE VOLTAGE CONTROL
OR VOLTAGE SOURCE
USING EXTERNAL TRIMPOT
COM 7
REF 1
RV 2
2 RV
1 REF
7 COM
SW1
SW2
TAB
Then monitor the (+) and (–) test points on the front panel with a precision voltmeter and turn the voltage control to the desired operating value. Refer to Table 2 for the recommended Adjustment Range of all the HSF 600W Models.
3.4.2 REMOTE VOLTAGE CONTROL
For remote voltage control, set positions 1, 2 and 7 as shown in Figure 6B. This removes control from the front panel Vadj control and allows the output voltage to be adjusted by either an external trimmer pot (resistance) or by an external variable voltage source connected across the rack adapter I/O connector pin 12 (RV, Remote Voltage) and pin 10 (–COM, Common) as shown in Figure 7. At the rack adapter I/O connector use a shielded wire 6.6 feet (2M) maximum in length, for connection of REF (pin 2), RV (pin 12), a nd –COM (pin 10) to the trim mer control or external voltage source.
NOTE: If remote voltage control is not implemented, the factory default for positions 1, 2 and 7 of DIP switches SW1 and SW2 must be restored (Figure 6A).
FIGURE 6. DIP SWITCH SETTINGS FOR CONTROL OF OUTPUT VOLTAGE
It is possible that overvoltage protection may be triggered if the output voltage is decreased to a low level very quickly when the power supply is at a low load condition.
RESIST ANCE: Connect the external trimmer as shown in Figure 7A. Suggested value for the trim­mer control is 5K ohms. Referring to Figure 7 (A), Resistor R is used to obtain minimum output voltage required to ensure proper operation of the alarm relay and LED indicator; see Table 4 for values. NOTE: Output voltage may not adjust to 0V due to residual trimmer resistance.
VOLTAGE. By adjusting an external 0 to 6V voltage source (0 to 5.5V for the 48V model), the HSF power supply output voltage can be adjusted as specified in Table 2. To ensure proper operation of the alar m rel ay an d LED indi cator do not adjust external voltage below minimum listed in Table 4. Connect the voltage source across the RV and –COM pins as shown in Figure 7B.
TABLE 4. MINIMUM CONDITIONS FOR RELAY AND LED OPERATION
MODEL HSF 12-53 HSF 15-43 HSF 24-27 HSF 28-23 HSF 48-13
Minimum HSF output voltage required for relay and LED functioning (Volts d-c)
Minimum resistance of Limit resistor R (Figure 7A) in series with 5K ohm Trimpot to ensure proper operation of LED and relay (Ohms)
Minimum external voltage (Figure 7B) to ensure proper operation of LED and relay. (Volts d-c)
1 - If operating below minimums listed, see PAR. 3.7.2.2 to implement ±PF alarm signals to monitor power supply status.
1
1
1
9.0 11.5 17 21.5 35
9.1K 9.1K 7.5K 9.1K 10K
3.8 3.8 3.6 3.9 3.4
HSF 600W 042315 9
FIGURE 7. CONNECTIONS FOR REMOTE VOLTAGE CONTROL
3042877
3
3 +RC
+RC 3
3
SW1
-RC 4
4
SW2
4
4 -RC
OFF
ON OFF
ON
(FACTORY DEFAULT)
USE FRONT PANEL
RESET BUTTON
A
B
(LOGICAL LEVEL OR
MECHANICAL SWITCH)
USE REMOTE ON-OFF
3
3
SW2 SW1
4
4
ON
OFF
OFF
ON
3 +RC 4 -RC
+RC 3
-RC 4
TAB
3.5 REMOTE ON-OFF
When power is ON at the source, the output may be turned ON or OFF using the ±R C signals if the remote ON-OFF feature is enabled. Note that when remote ON-OFF is enabled, the RESET OUTPUT switch does not function. Remote ON-OFF is enabled by setting DIP switch positions 3 and 4 as shown in Figure 8B. The +RC and –RC signals (at the rack ad apter I/O connector, pins 15 and 8, respectively) then turn the unit on or off. These pins accept a logic level (2.4V to 24V “high” and 0.0 to 0.4V “low”), or a contact closure. When the ±RC pins are open, using either a mechanical switch or a high level logic signal, the HSF 600W output is cut OFF. When the ±RC pins are shorted, the output returns to within specifications. At low level logic, the maximum source current is 1.6mA and at high level the sink current is 1.0mA. Positions 3 and 4 of bo th DIP switches must be restored to the factory default setting (Figure 8A) if remote ON-OFF is not used. The ±RC pins are isolated from DC output pins and a-c input terminals.
FIGURE 8. DIP SWITCH SETTINGS FOR USING RESET BUTTON OR REMOTE ON-OFF
3.6 PROTECTION CIRCUITS
The following protection features are implemented in the HSF 600W Series: overvoltage and overtemperature (PAR. 3.6.1), overcurrent (PAR. 3.6.2), fan failure (PAR. 3.6.3), and undervolt­age (PAR. 3.6.4). The HSF 600W Series provides a configurable visual alarm (see PAR. 3.7.1) as well as an option to use either relay contacts or logic levels for alarm signals (see PAR. 3.7.2)
3.6.1 OVERVOLTAGE AND OVERTEMPERATURE PROTECTION
When the output voltage of the HSF 600W Power Supply increase s beyond the specified values (see Table 2), the output is cut OFF and the fan turns OFF. To restart (reset) the unit, press and release the OUTPUT RESET switch on the front panel or, if the remote on/off feature is in use (see PAR. 3.5), open connection between the RC p ins and then reco nnect the pin s. The un it may also be restarted by turning the POWER ON/OFF switch to OFF, waiting 40 second s, then setting the POWER switch to ON.
10 HSF 600W 042315
When the internal temperature of the HSF (M) 600W Power Supp ly increases beyond allowable limit, the output is cut OFF and the fans turn OFF. The restart cycle (Power ON) should not begin until the temperature returns to within specifications. To restart (reset) the unit, set the POWER ON/OFF switch to OFF, wait until unit cools, then set the POWER switch to ON. The power supply cannot be reset using the remote ON-OFF feature unless the power supply remains shut down for at least 40 seconds.
3.6.2 OVERCURRENT SETTING AND PROTECTION
The output characteristic of the power supply is a square type, and the unit is set to produce an alarm (see PAR. 3.7.2) and shut down if output current exceeds specifications (see Table 2) for more than 30 se con ds . After the cause of overcurrent is removed, the power supply output is auto­matically restored.and shut down if output current exceeds specifications (see Table 2) for more than 30 seconds. Once unit shuts down, to recover either: a) press and release the front panel OUTPUT RESET switch, or b) open and close connection across ±RC terminals, or c) remove a-c input power (set POWER switch to OFF), wait 40 seconds, then restore a-c input power.
3.6.3 FAN FAILURE
A cutoff of the fan supply voltage or a decrease in fan speed causes the output to sh ut down and the fans to turn OFF. Fan failure and all the other protection circuit operations produce an alarm (see PAR. 3.7.2). To restart (reset) the unit, press and release the OUTPUT RESET switch on the front panel or, if the remote on/off feature is in use (see PAR. 3.5), open the connection between the ±RC pins and then reconnect the pins. The unit may also be restarted by turning the POWER ON/ OFF switch to OFF, waiting 40 seconds, then setting the POWER switch to ON. If fan rotation is out of specification the power supply will not recover.
3.6.4 UNDERVOLTAGE
If power supply output voltage either falls below 80% of the programmed (set) value, or if output voltage is programmed below the minimum values li ste d in Table 4, an alarm occurs if the internal relay alarm (factory default, see PAR. 3.7.2.1) is enabled. To restart (reset) the unit, press and release the OUTPUT RESET switch on the front panel or, if the remote on/off feature is in use (see PAR. 3.5), open the connection between the RC pins and then reconnect the pins. The unit may also be restarted by turning the POWER ON/OFF switch to OFF, waiting 40 seconds, then setting the POWER switch to ON. To enable the alarm function when operating below the mini­mum values listed in Table 4, refer to PAR. 3.7.2.2 to configure the optically-coupled alarm.
3.7 ALARM SETTINGS
3.7.1 VISUAL ALARM.
When the unit is connected in a parallel configuration, the front panel VDC ON/ALARM indicator can be configured to light red if the respective power supply output voltage is lost or if the POWER switch is set to OFF. This is enabled when DIP switch 1, position 8 set to ON. This can be useful to indicate the loss of output voltage from one parallel-connected power supply that may not be readily apparent. The visual alarm is normally disabled: DIP switch SW1, position 8 set to OFF (factory default).
HSF 600W 042315 11
3.7.2 ALARM SIGNALS.
3042878
55 +PF
+PF 5
5
SW1
-PF 6
6
SW2
6
6 -PF
OFF
ON OFF
ON
USE N.O. AND N.C CONTACTS
(FACTORY DEFAULT)
OF INTERNAL RELAY
A
LOGICAL ALARM
USE OPTICALL Y-COUPLED
B
(+PF AND -PF)
5 6
6
SW1
5
SW2
OFF
ON
ON
OFF
+PF 5
-PF 6
6 -PF
5 +PF
TAB
Either of two options are available for signalling alarms: isolated relay contacts (factory default, PAR. 3.7.2.1) or logic level alarm signals ±PF (PAR. 3.7.2.2). The ±PF logic level alarm option must be used if the power supply is intended to operate below the minimum voltages listed in Table 4.
3.7.2.1 INTERNAL ISOLATED RELAY ALARM
The first option, the factory default setting, uses an isolated internal relay offering normally closed (NC) and normally open (NO) contacts referenced to an isolated common (AL COM). Th ese con­tacts may be used to configure “close on failure” or “open on failure” alarm circuits. (Refer to the Series RA 19-4C Manual for alarm configurations for multiple HSF power supplies.) Setting posi­tions 5 and 6 of the DIP switches as shown in Figure 9A selects this option. The NC (pin 6 of the rack adapter I/O connector) and NO (pin 7) signals are referenced to Alarm common (pin 14).
3.7.2.2 OPTICALLY-COUPLED LOGICAL ALARM
The second option uses optically-coupled logic level alarm sig nals, +PF (pin 5 of the rack adapter I/O connector) and -PF (pin 13), provided directly from the Kepco RKW power supply that is the heart of the HSF. This option is selected by setting positions 5 and 6 of the DIP switches as shown in Figure 9B. Use this option if the power supply will operate below the minimum voltages speci­fied in Table 4.
FIGURE 9. DIP SWITCH SETTINGS FOR OPTICALLY COUPLED LOGICAL ALARM
The logic alarm circuit is a diode transistor optical coupler (see Figure 10). The transistor is n or­mally conducting. When the alarm is activated upon detection of power loss, overvoltage, fan fault, overtemperature or overcurrent condition, the transistor cuts off and the collector emitter cir­cuit is open. Figure 11 is a timing diagram of the power fail signal.
The default state of the alarm is logic low. The sink current for the optocoupler is 50mA maximum, the maximum collector to emitter saturation voltage is 0.40 Volts, and the collector to emitter volt­age is 40 volts maximum. The PF signals are isolated from the AC input and DC output.
12 HSF 600W 042315
FIGURE 10. OUTPUT ALARM CIRCUIT OPTICALLY ISOLATED
FIGURE 11. ±PF POWER FAILURE OPTOCOUPLER TIMING DIAGRAM
3.8 LOCAL/REMOTE SENSING
HSF 600W Power Supplies allow remote error sensing which can compensate up to 0.4 Volts per load wire. Local/Remote error sensing is configured b y means of separate DIP switch es mounted on the RA 19-4C Rack Adapter (see RA 19-4C Rack Adapter Operator Manual). Either local or remote sensing MUST be used, otherwise the units will not operate.
3.9 RETAINING LATCHES
HSF 600W series power supplies are provided with (2) retention latches located at each side of the bottom edge of the front panel (see Figure 5). These latches work in conjunction with the RA 19-4C rack adapters to prevent unauthorized or inadverte nt module extraction from an operating power system. The latch is engaged by loosening the cap-head screw approximately 1/2 turn CCW (use 5/32" hex key) and sliding the latch down to the bottom of the slot, then retightening the cap-head screw CW until snug. DO NOT OVERTIGHTEN! To release, follow the same procedure, except lift the latch to the top of the slot. Be sure to move the latch completely up or down to ensure full engagement and disengagement of the latching mechanism. When the HSF power supply is not installed in its plug-in rack adapter, it is recommended that the latch be secured in the open (up) position to prevent damage.
NOTE: Retaining latches must not be used to secure the HSF power supply in the rack
adapter for shipping purposes.
HSF 600W 042315 13
4 LOAD CONNECTION
Connect the load to (+) and (–) terminals at the rear panel of the Rack Adapter (see RA 19-4C Instruction Manual for details).
5 CONNECTING MULTIPLE POWER SUPPLIES
All connections to multiple HSF power supplies must be made via the I/O mating connectors at rear of the Rack Adapter or by the Rack Adapter DIP switches. These connections, including the configuration of the two internal HSF DIP switches, are described in the Rack Adapter Instruction manual, and include:
Using one power supply to control the output of multiple supplies.
Using parallel master/slave configurations (for increased current or redundancy) where the user either predetermines the master or allows the load to determine which is the master. These configurations also cover the use of the Current Balancing feature of the HSF power supply.
Using series configurations (for increased voltage).
Using open-on-fail or close-on-fail alarm schemes with multiple power supplies.
5.1 ADJUSTING THE VOLTAGE
NOTE: Refer to the RA 19-4C Rack Adapter manual for alternatives to the standard master/
slave parallel configuration described below.
To adjust the paralleled units, turn off all the units except one (designated as the master) and adjust to desired voltage using the front page trimmer and monitoring the front panel voltmeter.
Each slave must be adjusted to a slightly lower voltage than the pr evious unit. The dif fer­ence between the master and the lowest voltage slave must not exceed 2% of E
The voltage separation between master and subsequent slave(s) (V
SEP
) = 2% E
where N = number of units in parallel.
Adjust the first slave V Adjust the third slave V
As an example, for three HSF 24-27 units in parallel, 2% of E
SLAVE1
SLAVE3
to E
to V
NOM
SLAVE2
- V
. Adjust the second slave V
SEP
- V
and so on.
SEP
SLAVE2
is 0.48V and V
NOM
to V
SLAVE1
SEP
0.16V. Turn off the master, then turn on another unit (slave 1 ) and adjust for 160 mV less than the master. Turn off slave 1 and turn on slave 2 and adjust for 160mV less than slave 1.
When all units are turned on, the unit adjusted to the highest voltage will be the ma ster. If a unit fails, the VDC ON indicator of that unit is either off or red.
5.2 PARALLEL CONNECTIONS, STANDARD AND C MODELS
When using parallel-connected standard (no suffix) and C Models, a minimum load is required to avoid the slave becoming “idle.” When the slave is idle, the output is off, no lights are lit, and the alarm is set.
.
NOM
/ N
NOM
- V
SEP
is 0.48/3 =
.
The minimum load (Amperes) = N x (I/10) where N = the number of units in parallel, I = Nominal current rating of individual power supply (Amperes).
14 HSF 600W 042315
Loading...