This guide gives a brief introduction to the BOP 1KW-MG/ME/MGL/MEL Power supply, shows simple load connections, and
allows you to verify the power supply is working. The guide also shows you how to use th e front panel controls to perform the
most commonly used functions.
BOP 1KW models with MG and ME suffixes ar e identica l except that the MG unit s h ave a factor y-inst a lled GPIB interface a nd in
the ME units the GPIB interface is replaced with a LAN interface. BOP-MG/ME models with an L suffix have been optimized for
better performance driving inductive loads such as large magnets or motors. Unless otherwise noted this guide applies to all
models.
ACCESSING MANUALS. First determine your Firmware Version (see below), then download the applicable BOP 1KW-
MG/ME Operator’s Manual from www.kepcopower.com/support/opmanls.htm#bop-1k
Refer to the BOP 1KW-MG/ME Operator’s Manual for full specifications, installation considerations and operating instructions,
including an Installation/Operation Summary which includes hyperlinked references to detailed procedures, but which can be
printed as a handy reference. The BOP 1KW-MG/ME Operator’s Manual also includes a full description of the digital interfaces
and the SCPI command language.
FIRMWARE VERSION. Refer to www.kepcopower.com/support/bophifirm.htm to determine which firmware version is
installed.
ACCESSING DRIVERS. Drivers are accessed from www.kepcopower.com/drivers/drivers-dl3.htm.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
www.kepcopower.com email: hq@kepcopower.com
228-1692 REV 91
Page 2
I — DESCRIPTION.
The BOP 1KW-MG/ME Series hereafter referred to as
BOP, are true 4-quadrant programmable voltage and
current power supplies, meaning they are capable of
both sourcing and sinking power (see Figure 61).
These bipolar power supplies pass smoothly through
zero without switching to provide true ± voltage and ±
current. These BOP power supplies use switch mode
technology for low dissipation. A bi-directional, isolating, a-c input power factor correcting (PFC) circuit
recuperates energy sinked from an active load and
sends it back into the line to maintain low dissipation.
These BOP power supplies are controlled digitally from
a menu-driven front-panel keypad or one of the remote
digital interfaces (GPIB or RS 232 on MG models, LAN
or RS 232 on ME models) to set voltage and current
and the four protection limits (+voltage, –voltage, +cur-
II — UNPACKING.
This instrument has been thoroughly inspected and
tested prior to packing and is ready for operation. After
careful unpacking, inspect for shipping dam age before
attempting to operate. Perform the “Load Connections.” on page 5. If any indication of damage is found,
TABLE 1. BOP 1KW-MG/ME MODEL PARAMETERS
rent and –current.) A front panel rotary adjuster allows
real-time adjustment of the output. A large LCD displays the mode of operation, the settings, and the
actual output voltage and current. Additionally, these
BOP models can be remotely controlled by an analog
±10V input for the main channel (voltage or current),
and a +1 to +10V input for the limit channels.
BOP models are suitable for driving inductive loads
such as large magnets or motors, and for exercising
batteries. They are also suitable for characterizing
solar cell arrays, and powering many electrochemical
reactions. Models with L suffix have been optimized for
exceptionally low current ripple and noise and
improved stability (drift and temperature), making them
ideal for driving inductive loads, such as large magnets
or motors.
file an immediate claim with the responsible transport
service.
.
d-c Output RangeClosed Loop GainOutput Impedance
(1)
Model
1000 WATT MODELS
BOP 6-125MG/ME0 to ±60 to ±1250.612.50.051.5241150
BOP 10-100MG/ME0 to ±100 to ±1001.010.00.12.0501100
BOP 10-75MG/ME0 to ±100 to ±751.07.50.132.067976
BOP 20-50MG/ME0 to ±200 to ±502.05.00.408.3200371
BOP 25-40MG/ME0 to ±250 to ±402.54.00.6315.8313165
BOP 36-28MG/ME0 to ±360 to ±283.62.81.3025640103
BOP 50-20MG/ME0 to ±500 to ±205.02.02.5050125055
BOP 72-14MG/ME0 to ±720 to ±147.21.45.14104257033
BOP 100-10MG/ME0 to ±1000 to ±1010.01.010.0163500016
(1) Models with MG suffix include GPIB and RS 232 digital interf aces. Models with ME suffix include LAN and RS 232 digital interfaces.
(2) When connecting active loads, the steady-state voltage of the active load must not exceed the maximum voltage rating of the BOP.
Otherwise the overvoltage protection will shut down the power supply.
NOTES:1. MEL suffix models include LAN and RS 232 interfaces. MGL suffix models include GPIB and RS 232 interfaces.
2. When connecting active loads, the steady-state voltage of the active lo ad must n ot exceed the maximu m voltag e rati ng of
the BOP. Otherwise the overvoltage protection will shut down the power supply.
3. The output impedance of the MEL/MGL models is identical to the output impedance of corresponding ME/MG models.
d-c Output RangeClosed Loop Gain
E
O Max
I
O Max
Voltage
Channel
Current
Channel
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
www.kepcopower.com email: hq@kepcopower.com
2228-1692 REV 9 062119
Page 3
III — EQUIPMENT SUPPLIED.
!
See Table 3.
TABLE 3. EQUIPMENT SUPPLIED
ITEMFUNCTION
PART NUMBER
IV — SAFETY. See Table 4
TABLE 4. SAFETY SYMBOLS
SYMBOLMEANING
CAUTION: RISK OF ELECTRIC SHOCK.
Source Power Entry
mating connector
PAR/SER CONTROL
- IN mating connector
Mates with source power
entry connector
Mates with PAR/SER
CONTROL - IN port to
allow access to pins
required for calibration
142-0381
(Kepco) (IEC
320C19)
142-0488
(Kepco)
WARNING
CAUTION
V — PRELIMINARY OPERATIONAL CHECK.
A simple operational check after unpacking and before
equipment installation is advisable to ascert ain wh ether
the power supply has suffered damage resulting from
shipping.
1. With POWER switch set to off position, connect
the power supply to source power (see “Load
Connections.” on page 5).
2. With no load connected, set POWER switch to
the ON position. Each time the unit is turned on
an internal self-test is performed. If all tests pass,
the unit goes into the default mode. If a failure
occurs, the failure is displayed. Figure 5 shows
the factory-configured power on defaults displayed on the LCD.
3. Connect a digital voltmeter (DVM) (resolution and
accuracy of 0.01% or better) to the OUT S and
COM S terminals at the rear panel terminal block.
4. Use the keypad to enter the rated maximum voltage of the power supply (e.g., enter 36 for a
model BOP 36-28MG) and press ENTER. If
STANDBY indicator is lit, press STANDBY key.
5. Verify DVM voltage reading agrees with programmed voltage within 0.03% of rated maximum
voltage and agrees with displayed voltage on
LCD within 0.05% of rated maximum voltage.
CAUTION: REFER TO REFERENCED PROCEDURE.
INDICATES THE POSSIBILITY OF BODILY
INJURY OR DEATH.
INDICATES THE POSSIBILITY OF EQUIPMENT
DAMAGE.
VI — INSTALLATION.
Install units either on a bench or in a 19 inch-wide rack.
For rack mounting: remove four feet first; rack must
provide support at the rear). Optional slides may be
used. Leave the front and rear panels clear of obstructions to ensure adequate cooling. Allow a minimum of
7/8 in. above and below the unit to permit air intake
necessary for proper cooling of the unit. For parallel,
series and master-slave configurations, refer to the
Operator’s Manual.
INPUT CONNECTIONS. Source power is con-
nected to the power supply via three-wire input power
using the source power mating connector supplied
(see Table 5). This power supply operates with an input
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
www.kepcopower.com email: hq@kepcopower.com
062119228-1692 REV 93
a-c voltage in the range of 176 - 264V/47 - 63Hz without any need of range/frequency selection. The unit
can be supplied from either a single phase, or between
phases of a 3-phase a-c system as long as the input
voltage is within the range specified above. The user
must provide a properly sized and rated mains lead
(line cord) and service with a current rating compatible
with the rated input current (9.5A a-c max). Line cords
available as accessories are listed in Table 5. Plug the
source power connector into the source power inlet
connector at the rear panel.
Page 4
1.
FIGURE 1. BOP OUTPUT CHARACTERISTICS
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
www.kepcopower.com email: hq@kepcopower.com
4228-1692 REV 9 062119
Page 5
VII — ACCESSORIES. See Table 5.
TABLE 5. ACCESSORIES
ITEMFUNCTION
Line Cord (250V, 20A)Provides connection to a-c mains via Nema 6-20P connector.118-1087
Line Cord (250V, 20A)Provides connection to a-c mains via Nema L6-20P locking type connector.118-1088
Mating Connector, TriggerMates with Trigger port.142-0527 (Kepco)
IEEE 1118 (BITBUS)
Mating connector
IEEE 488 Cable, (1 meter long) For MG models only. Connects BOP power supply to GPIB bus.SNC 488-1
IEEE 488 Cable, (2 meter long) For MG models only. Connects BOP power supply to GPIB bus.SNC 488-2
IEEE 488 Cable, (4 meter
longs)
Interconnection Kits for parallel/
series configurations.
RS 232 Cable KitContains RJ1 1 to RJ45 Patch cord, RJ 45 Patch cord, two RS 232 adapters,
RS 232 Adapter (Male pins)Allows RS 232 port to be connected to DTE equipment. (Supplied in KIT
RS 232 Adapter (Female pins)Allows RS 232 port to be connected to a PC (personal computer). (Supplied
15-pin DSUB ConnectorMating connector for Analog input connector A2A5J6
IDC 6-pin connectorMating connector for RS-232 PORT, connector A1J5 and PROTECTION
IDC 8-pin plugMating connector for PAR/SER PROTECT PORT (IN and OUT) connectors. 142-0535
SlidesAllows easy withdrawal of unit from rack (see Figure 1). (Model CS 04
Heat SinkProvides adequate cooling for calibration sense resistors.136-0451
Output Terminal CoverProtects against inadvertent contact with output and barrier strip terminals129-0423
Allows connection to IEEE 1118 (BITBUS) port.142-0485 (Kepco)
For MG models only. Connects BOP power supply to GPIB bus.SNC 488-4
Cables required to connect multiple BOP models in parallel, series, or parallel/series configurations.
one with male pins to connect to DTE equipment and one with female pins to
connect to a PC (personal computer), two RS 232 Loop Back test Connectors (one 6-pin and one 8-pin) to test RS 232 communication and aid in isolating RS 232 communication problems.
219-0436.)
in KIT 219-0436.)
Dsub 15 pin hood
Dsub 15 pin male
EXT. PORT, connector A2A5J7
includes slides, brackets, all mounting hardware and installation instructions.)
PART NUMBER
SP2501 (CUI Stack)
KMDLA-5P (Kycon Inc.)
See Operator’s Manual.
KIT 219-0436
142-0487
(L-COM RA098M)
142-0506
(L-COM RA098F)
108-0374
(Tyco-Amp 207470-1)
142-0449
(Amphenol 17S-DA15P)
142-0536
(Amphenol 5-555176-3)
(Amphenol 5-555176-3)
CS 04
LOAD CONNECTIONS.
Power connections require wires that are properly rated for the nominal output
current of the unit.
Connect the load to the OUTPUT
and COMMON power terminals on t he rear panel (see
Figure 3). OUT S and COM S terminal of the Monitor
and Sensing Terminal block are for connection of
remote sensing leads (after removing the factoryinstalled local sensing links).
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
062119228-1692 REV 95
www.kepcopower.com email: hq@kepcopower.com
NOTE: Output Sense lines must be connected for
proper operation, either locally, or at the load
(remote). Also use OUT S and COM S to monitor volt-
age at the load using external equipment such as a
DVM, oscilloscope, etc. Use OUT MON and COM
MON to monitor voltage at the BOP output. Use twisted
wire pairs or wires that are tied together for both output
power and output sensing connections.
Page 6
It is critical that configurations comprised of BOP, load,
!
and external programming devices, have a single
earth-ground point. Observe the following caution and
refer to the applicable BOP 1KW-MG Operator Manual
for earth-ground recommendations. Failure to
observe this caution will void the warranty!
CAUTION: Never connect both the load
terminal tied to the BOP COM terminal
and the programming device common
to earth-ground. This compromises
accuracy and will cause catastrophic
damage to the BOP if the connection
between BOP COM and the load terminal tied to earth-ground is lost.
LOCAL SENSING (FACTORY DEFAULT).
Unit is shipped with local sensing links installed: OUT S
connected to OUT MON and COM MON connected to
COM S (see Figure 4A).
REMOTE SENSING SELECT. First remove the
factory-installed local sensing links between OUT S
and OUT MON and between COM MON and COM S.
Then connect the OUT S and COM S lines at the load
(see Figure 4B) using #22 AWG wire, twisted pair.
ANALOG I/O CONNECTIONS. The Analog I/O
Port connector, located on the rear panel of the BOP
1KW power supply (see Figure 3), provides access to
analog programming inputs which can control the
mode of operation (voltage or current), output voltage
or current, and establish positive and negative voltage
and current limits. An output analog corresponding to
output current is also provided. Refer to Operator’s
manual for details.
TRIGGER CONNECTIONS. The Trigger Port
(see Figure 3) provides for an external trigger in put for
use with SCPI *TRG and TRIG commands. Refer to
Operator’s manual for details.
GPIB CONNECTIONS (MG SUFFIX). Your
computer must have a GPIB interface card installed.
Connect the power supply to the computer’s GPIB
interface card. Use a standard GPIB interface cable at
the GPIB port on the rear panel (see Figure 3).
The default GPIB address is 6; refer to the Operator’s
Manual to change it.
LAN CONNECTIONS (ME SUFFIX ONLY).
Connect the BOP 1KW to a Microsoft Windows-based
computer via the LAN connector (see Figure 3). Use a
standard ethernet cable whether using a router or hub,
or connecting the BOP 1KW directly to a computer.
The BOP 1KW-ME is Auto-MDI-X enabled and does
not require a crossover cable for direct connection. For
Unix and Safari connections see full Operator Manual
(refer to “Accessing Manuals.” on page 1).
FINDING KEPCO POWER SUPPLIES ON THE LAN.
The PS Find utility can be downloaded from the Kepco
web site at:
www.kepcopower.com/drivers/drivers-dl3.htm#bop1k
This utility finds all operational Kepco power supplies
connected to the LAN and then shows the MAC and IP
addresses of the models found.
To run the utility from your PC download the psfind.zip
file to your computer. Extract psfind.exe from the zip
file to a location of your choice, then double-click
psfind.exe to run the application. A separate window
opens as shown in Figure 1. Once the search is completed, all found units are displayed in the Select a Unit
window (the MAC address appears in parentheses). If
you do not see your device in the Select a Unit window
or if the icon to the left of the selected instrument is red
(not green), make sure it is turned on and connected to
the network, then click the Search Again button.
FIGURE 1. PS FIND SCREEN
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
6228-1692 REV 9 062119
www.kepcopower.com email: hq@kepcopower.com
Page 7
FIGURE 2. BOP 1KW SERIES, FRONT PANEL CONTROLS AND INDICATORS
E
N
T
E
R
RS 232 CONNECTIONS. Connect the BOP 1KW
to a modem using a Null Modem patch cable at the RS
232 port located on the rear panel (See Figure 3). A
Null Modem cable is not required for older MAC com-
puters with D-sub serial port in which the RXD and
TXD line transposition is accomplished via external
hardware. The default baud rate is 9600; refer to the
Operator Manual to change it.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
www.kepcopower.com email: hq@kepcopower.com
062119228-1692 REV 97
Page 8
FIGURE 3. BOP 1KW SERIES, REAR PANEL VIEW, LINKS INSTALLED FOR LOCAL SENSING
A. LOCAL SENSING
B. REMOTE SENSING
GND
NET
OUT
MON
N / C OUT
S
COM
S
COM
MON
GND
FIGURE 4. LOAD CONNECTION
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
www.kepcopower.com email: hq@kepcopower.com
8228-1692 REV 9 062119
Page 9
VIII — OPERATION.
!
Additional features covered in the Operator Manual
are: operation via the LAN interface or analog signals
and setting coarse/fine adjustment preference of the
VOLTAGE and CURRENT controls. An Installation/
Operation Summary is also included in the Operator
Manual. The Operator Manual also covers the GPIB,
Ethernet and RS 232 interfaces, including the use of
the drivers downloadable from:
www.kepcopower.com/drivers/drivers-dl3.htm#bop1k.
TURNING THE POWER SUPPLY ON.
CAUTION:
DO NOT repeatedly toggle the circuit breaker/switch as this may
damage the unit.
Set POWER ON/OFF circuit breaker/switch on front
panel to ON. If actuator does not lock when released,
wait a few seconds before trying again. The circuit
breaker is “trip-free” design; if ov erload exis ts, contacts
cannot be held closed by actuator.
•When the power supply is turned on, it performs a brief self-test that includes testing the
three processors (analog, interface and display), then displays the power-up screen (see
Figure 5). If an error is detected, the FAULT
indicator will light, information about the error
will be briefly displayed on the LCD.
•If the unit powers up in REMOTE mode, pr ess
! to set the unit to LOCAL mode.
•If the display is not viewable, press
The display will cycle through the range of
contrast settings. Press
# again to lock in
the preferred contrast.
ACCESSING THE MENUS.
screen, pressing the Function keys indicated on the
LCD opens the associated menu. The menu opened
may list submenus that may be opened either directly
by pressing the associated Function keys, or by highlighting an item on the list and pressing the View/Modify function key. Menus and submenus will display a list
of parameters, with the top one highlighted. The function key assignments can vary, but generally offer the
following choices:
From the power-up
# twice.
•! allows the highlighted parameter to be
viewed or modified. After changing the parameter, the following choices are available:
SAVE or ENTER to save the change,
$ -
% -
EXIT to abort the change and exit to the previous menu.
@ - RESTORE DEFAULT restores factory
•
defaults for the parameters displayed (except
for GPIB address). The factory defaults may
be saved as power-up defaults by pressing
$.
•
# - The function varies, depending on the
menu. In most cases
change without applying the modified setting.
From the power-up screen
adjust contrast. In the Revisions/TEST submenu of the General Setup Menu,
to execute a test.
•$ - SAVE FOR POWER-UP Saves the configuration shown as a power-up setting so the
changes will not be lost when the unit is
turned off.
% - APPLY EXIT applies the current
•
(changed) setting without saving for power-up
and exits to the previous menu or to the
power-up screen, EXIT leaves the current
menu without saving or applying changes.
The menu structure is as follows (NOTE: BOLD = Fac-
tory Default):
Power-up Screen (Power up menu)
•
! - Save/Recall
•• Saved Setups: Recall one of 99 saved setups.
•• • Saved Setup Details: Mode (voltage/
current/External), main channel reference (internal/external/external reference level) and setting, Protection Type
(internal/external/LesserLimit) and set-
•
•• Saved Waveforms: Choose one of 16
•• • New Waveform Settings: Name (max.
•• • •First segment: type (Square/ +ramp
•• • Edit Waveform: Name, no. of cycles,
•• • •Segment Details: Type ((Square/
ting(s), output status (on/off)
@ - Waveform
saved waveforms.
10 characters), mode (voltage/current)
No. of cycles, +Protect, -Protect)
age max, –Voltage min, ±CProtect max/
min; for current mode: +Current max,
–Current min, ±VProtect max/min
• • Load Type: Active/Resistive/Battery,
Remote On-off: (disabled/high is off/low is
off/high is on/low is on/LowPulseOff)
•• Standby Pin Operation: LowPulse, HighI-
sOn, LowIsOn, HighIsOff, LowIsOff, Disabled
•• Revisions/Test: (Tests: display, keypad,
LAN, interface, serial, analog and output)
•• Calibration: Voltage, Current and External
and Controls calibration. Shows Firmware
versions for Display, Serial, GPIB, LAN
and analog.
•• Power-up Settings: Mode (Voltage/Cur-
rent/External), Main channel Reference
(Internal/External/ExtlRefLev), main setting, Protection: Type (Internal/External/
LesserLimit), Voltage Limit (current mode),
Current Level (voltage mode), output ON/
OFF
•• Password
•• • Password Settings: Menu protection
(Interface/Max-Min/Load/Test/Calibration/Power-up/Keypad @ local/Keypad@power-up), Save Display Change
(Enable/Disable), Passwords (Unprotected/Main/Admin1/Admin2)
•• Series/Parallel: Configuration (Standalone/
Parallel/Series/Master 2X2/Master 3X2);
for parallel or series: Unit Type (Standalone/Master+1 to+4/Slave #1 to #4) and
Configuration: shows Series or Parallel).
HOW TO MODIFY A PARAMETER.
First access the parameter by accessing the proper
FIGURE 5. POWER-UP SCREEN SHOWING GRAPHIC METERS
menu as described above. To modify a parameter
listed in a menu or submenu, proceed as follows:
1. Highlight the parameter using the Y and U keys.
2. When the desired choice is highlighted, press
to modify the active setting. The choices are dis-
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
www.kepcopower.com email: hq@kepcopower.com
!
played with the active setting highlighted. In the
case of numerals, the units digit is highlighted.
•To change a numeric setting, press the number keys, then press ENTER to program the
numbers entered. Use the CLEAR key to
clear numbers entered and start over. The
ADJUST control can also be used to incre-
10228-1692 REV 9 062119
Page 11
ment or decrement the highlighted digit.
Pressing ADJUST while rotating adjusts the
least significant digit. If the output is on (unit
not in Standby) changes made using the
ADJUST control are immediately applied to
the output.
•For alphanumeric characters use multiple
presses of the number keys for letters or sym-
0 (space), 1 (+, –, /), 2 (ABC), 3
bols:
(DEF), 4 (GHI), 5 (JKL), 6 (MNO). 7
(PQRS), 8 (TUV), 9 (WXYZ). Use the T
key to highlight the next character. As an alternative, the
will scroll through numbers, and letters and
symbols. Use the CLEAR key to clear the
entire alphanumeric field and start over
3. Press
menu (to change another parameter, repeat steps
1 and 2). To abort (return to the menu without
applying the change), press
$ to apply the change and return to the
U or Y keys or ADJUST control
%.
NOTE:Press HELP key for more information,
press HELP again to see multiple
screens; press CLEAR key to exit the
help screen.
ADJUSTING LCD BRIGHTNESS, CONTRAST AND BACKGROUND
up screen, (Figure 5), press
trast adjustment. The contrast gradually alternates
between light and dark. When the contr ast is acceptable, press
adjust. Use the
contrast. Contrast can also be adjusted from the
power-up screen by pressi ng
# to apply the change and exit contrast
T and R keys for fine adjustment of
From the power-
# twice to initiate con-
# once, then pressing
T and R as needed for fine adjustment.
To change the background, press
up screen, Highlight Background, press
Black or White, then
save for power-up or
saving for power-up) and exit.
ENABLING/DISABLING AUDIBLE BEEPS
From the power-up screen, press #, then modify the
setting. Even though audible beeps are set to off, the
beeps will still sound upon power-up or detection of a
power supply fault.
SETTING VOLTAGE OR CURRENT MODE
The BOP uses two separate channels, one to set output voltage or current and one to set the correspo nding
protection limit. The main channel is d eter mine d by t he
MODE key (in local mode) which alternately selects
either Voltage mode or Current mode or by SCPI command (in digital remote mode). The protection channel
is determined automatically by the main channel
$ to save. Press $ exit and
% to apply the changes (without
# from the power-
!, highlight
selected. When Voltage mode is selected, the current
protection channel is active, and when Current mode is
selected, the Vo ltage protection channel is active.
PROGRAMMING VOLTAGE OR CURRENT
AND ASSOCIATED PROTECT LIMITS
the power-up screen the settable voltage/current
parameters are displayed at the bottom of the LCD
above the HELP message. Use
the main or protect channel.
1. To verify that the unit is configured for internal references press
verify that Reference Input and Protection Limit
are set to Internal, and External Mode is set to
Disable. If necessary to change a setting, use
or U to highlight the parameter, and press ! to
modify. Highligh t the desired selection and press
$ from the power-up screen and
Y or U to highlight
From
Y
$ to save, then press $ to save for power-up
% to exit. If analog programming is desired,
or
refer to Operator’s Manual.
2. Verify that the load type has been configured
properly to ensure that the unit behaves as
expected when the output is off (see “Max/Min
Setting Menu” on page 13 6 for details).
3. Press MODE key to select the main channel
(VOLTAGE or CURRENT); the associated PROTECT channel is automatically selected and displayed.
4. Set the output on or off as desired using the
STANDBY key. The output is off (disabled) when
the STANDBY indicator is lit, on (enabled) when
not lit.
5. Use
Y or U to highlight the main channel. There
are two ways to program the output in local mode.
These methods can be used either when the output is disabled (STANDBY indicator lit) or
enabled.
WARNING:
When the ADJUST control is
rotated, the active parameter is
immediately effective if the output
is enabled (on = STANDBY indicator not lit). The voltage/current
applied to the load changes as the
ADJUST control is rotated.
•Use the ADJUST control to increase or
decrease the main channel setting (e.g., voltage when the unit is in voltage mode). Start
with the most significant digit of the desired
value, then use
For fine adjustment press the ADJUST control
T to highlight the next digit.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
062119228-1692 REV 911
www.kepcopower.com email: hq@kepcopower.com
Page 12
in while rotating the knob to modify the least
significant digit.
•Ente r the desired value on the keypad using
the number keys. For example, to program the
BOP to 75.8V, press the following keys in
75.8 then press ENTER. For fine
order
adjustment use
significant digit. To correct the entry before
activation press the CLEAR key to set the
value to zero and start over. When the desired
value is displayed, press ENTER. This causes
the new value to appear at the ou tput and be
applied to the load if the output is enabled.
6. To program the corresponding Protect channel,
Y or U as necessary to highlight the Pro-
press
tect channel. Then set the value using either of
the two methods described above. If the Protect
Entry setting is set to Independent, separate
entries for the positive and negative protect channel are possible. Otherwise the value entered is
applied to both positive and negative protect
channels.
Y, and U to modify the least
NOTE: The BOP can be configured to show
the protection limits as either a single
value that applies to both protection
channels or show individual settings
for positive and negative protection
limits. Only voltage protection limits
are available when in current mode;
only current limits are available in voltage mode. See Operator’s Manual for
details.
tive limits). Use number keys to change the setting, then
4. When complete, press
$ to save.
$ to save for power-up,
# to abort, or % to apply the changes (without
saving for power-up) and exit.
5. Upon return to the power-up screen, the main
channel (voltage or current) is compared against
the main channel limits in effect. If the main channel exceeds the limit, it is set to zero.
6. Highlight the ±CPROTECT or ±VPROTECT max/
min value and press
limits are absolute values (do not use minus sign
for negative limits). Use number keys to change
the setting. Press
7. When complete, press
# to abort, or % to apply the changes (with-
or
out saving for power-up) and exit.
Upon return to the power-up screen, the new protection
limit (voltage or current) is compared against the protection limits in effect. If the new protection limit setting
is below the existing setting for the protection limit, the
protection channel (voltage or current) is set to zero.
DETERMINING HOW THE UNIT RESPONDS
WHEN OUTPUT IS OFF (LOAD TYPE)
BOP supports three Load Type selections (see T a ble 6)
which determine how the power supply responds when
the output is off: ACTIVE, RESISTIVE and BATTERY.
The Load Type selection does not affect the settings of
the power supply for ON state; it only affects the mode
of operation, main internal reference level and the protection levels during the OFF state.
! to change it. Software
$ to save, or % to abort.
$ to save for power-up,
The
WARNING
SOFTWARE LIMITS. Software limits prevent pro-
gramming of the main channel or the Protect channel
beyond the software limit value. Refer to Operator’s
Manual for a full explanation of software limits.
Changing Main Channel Software limit.
This procedure allows the user to determine the maximum value of voltage or current that can be programmed.
1. Press % from the power-up screen to enter the
General Setup menu, then highlight Max/Min Settings.
2. Press
3. Highlight the voltage or current max/min value
12228-1692 REV 9 062119
! to enter the Max/Min Settings submenu
(Figure 6). (If a Password is required, see Operator’s Manual for instructions.)
and press
absolute values (do not use minus sign for nega-
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
! to change it. Software limits are
www.kepcopower.com email: hq@kepcopower.com
Active. Active mode (default setting) is necessary for
the power supply to function properly and safely with
inductive loads and constant-current-type active electronic loads. Active mode can also be used with resistive loads. Table 6 indicates how the power supply
responds to a command to go from Output ON to OFF.
For inductive loads, and especially
superconducting magnet type
loads, the inherent offset of the
BOP in the OFF state may generate
significant current in the circuit. A
properly rated switch in parallel
with a resistor must be connected
between the power supply and the
load. The switch must be open and
the BOP front panel LCD must read
0V, 0A before removing or installing
connections between BOP and
load.
Page 13
When the output is disabled, the unit is set to voltage
VOLTAGE
SOURCE
VOLTAGE
CURRENT
0.00000.0000
mode, voltage is set to zero and both current protect
and voltage limit are set to maximum. When the unit is
FIGURE 6. MAX/MIN SETTING MENU
enabled, the pre-existing settings for voltage, current
protect and voltage limit are restored.
LOAD TYPE
SETTING
ACTIVE
RESISTIVE
BATTERY
TABLE 6. POWER SUPPLY BEHAVIOR WHEN OUTPUT IS SET TO OFF
If unit was in Voltage Mode when output OFF
command issued.
• Unit remains in voltage mode.
• Voltage set to zero.
• Both ± Current Protect set to maximum.
• Both ± Voltage Limit remain at maximum.
• Unit remains in voltage mode.
• Voltage set to zero.
• Both ± Current Protect set to minimum box values.
• Both ± Voltage Limit. remain at maximum.
• Unit set to current mode.
• Current set to zero.
• Both ± Voltage Protect. remain at maximum.
• Both ± Current Limit set to maximum.
WARNING
For both inductive loads and constant-current-type active electronic
loads when the BOP output is set
to OFF, a path is provided for
absorbing either the energy accumulated in the reactance of the load
during the ON state, or energy
delivered by an electronic load.
This prevents damage to the load
and power supply as well as providing safety for the user. However,
If unit was in Current Mode when output OFF
command issued.
• Unit set to voltage mode.
• Voltage set to zero.
• Both ± Current Protect remain at maximum.
• Both ± Voltage Limit set to maximum.
• Unit remains in current mode.
• Current set to zero.
• Both ± Current Protect set to minimum box values.
• Both ± Voltage Limit set to maximum,
• Unit remains in current mode,
• Current set to zero.
• Both ± Voltage Protect set to maximum.
• Both ± Current Limit remain at maximum.
In addition to the built-in safety features, constant-current-type active
electronic loads must be adjusted
to zero and the BOP front panel
LCD must read 0V, minimum cur-
Resistive. This mo de, as the n ame sugg ests, is us eful
for resistive loads. Table 6 indicates how the power
supply responds to a command to go from Output ON
to OFF.
rent, before handling the power
supply-to-load connections.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
062119228-1692 REV 913
www.kepcopower.com email: hq@kepcopower.com
Page 14
WARNING
Accessing the BOP after the output
is disabled in BATTERY mode is
hazardous because (1) high current
arcing is possible and (2) either the
external battery voltage, or the voltage (±Voltage Protection max) on
the BOP output terminals may be
dangerous. Therefore, for battery
and constant-voltage-type active
electronic loads it is recommended
that two properly rated external
switches be installed for safety:
one in series with the battery, and
one across the BOP output. After
the unit is set to OFF, first open the
switch in series with the battery,
then close the switch across the
BOP output to ensure safety before
handling BOP connections. When
connecting the battery, the switch
across the output should be
opened after the connections are
complete and then the switch in
series with the battery should be
closed. If the constant-voltage-type
active electronic load is adjusted to
zero before handling the power
supply-to-load connections, only
the switch across the BOP output
is required.
IX — ADDITIONAL FEATURES.
The user is urged to refer to the Operator’s Manual for
full explanations all BOP 1KW features, including:
•Passwords - three independent levels of
access
•Changing the Default Power up Settings
•Digital Remote Operation - using SCPI commands via RS 232, GPIB or LAN ports; operation via web pages
•Analog Remote Operation - via Analog I/O
port
•Details about Protect Limits and Softwarecontrolled limits
Battery. This mode is necessary for the pow er supply
to function properly and safely with either battery or
constant-voltage-type active electronic loads. This
mode prevents the battery from discharging during the
OFF state. When the output is disabled (set to OFF),
the BOP will go to current mode, current will be set to
zero, with voltage protect and current limit set to maximum. In this way the battery will not be discharged
while the output is OFF. For constant-voltage-type
active electronic loads this mode stops energy flow
during the OFF state. Table 6 indicates how the power
supply responds to a command to go from Output ON
to OFF.
CONFIGURE LOAD TYPE. To configure, press
% from the power-up screen, then highlight Load
Type and press
required, see Operator’s Manual for instructions.) Highlight Active, Resistive or Battery (see explanations and
associated WARNINGS above) and press
Then press
! to modify. (If a Password is
$ to save.
$ to save for power-up, # to abort, or
% to apply the changes (without saving for power-up)
and exit. After configuring, the new setting will be effective when the power supply goes from output on to output off.
To restore factory default (Active), press
power-up screen, highlight Load Type, press
press
power-up or
ENABLING/DISABLING OUTPUT POWER.
The BOP output can be disabled (OFF) or enabled
(ON) by toggling the STANDBY k ey in local mode. The
behavior of the unit when disabled depends on the
Load Type setting (See “Max/Min Setting Menu” on
@ to restore default. Press $ to save for
% to exit
•Storing/Recalling Power Supply Output Settings
•Waveform Generation - Sine, Triangle,
±Ramp, Square and Level segments. Local
operation allows up to 16 waveforms, maximum 10 segments per waveform. Remote
operation allows 1 waveform, maximum of
126 segments, or using LIST commands.
•Operator Testing
•Calibration - via either local keypad or remote
SCPI commands
•Parallel/Series Configurations -increase current capability, voltage capability, or both.
% from the
!, then
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
14228-1692 REV 9 062119
www.kepcopower.com email: hq@kepcopower.com
Page 15
2
0
.
0
0
0
[
5
0
8
.
0
0
]
2
1
.
4
3
9
[
5
4
4
.
5
4
]
2
2
.
8
0
0
[
5
7
9
.
1
1
]
2
1
.
5
6
4
[
5
4
7
.
7
3
]
2
2
.
0
0
0
[
5
5
8
.
7
9
]
2
3
.
8
6
3
[
6
0
6
.
1
2
]
18.235 [463.16]
18.985 [482.21]
1
.
4
7
0
[
3
7
.
3
4
]
1
.
7
3
8
[
4
4
.
1
5
]
5
.
2
1
8
[
1
3
2
.
5
4
]
2
.
2
1
5
[
5
6
.
2
7
]
OBROUND 0.25x0.453 (4 LOC.)
16.835 [427.60]
17.675 [448.93]
18.018 [457.64]
18.805 [477.63]
FIGURE 1. BOP 1KW OUTLINE DIMENSIONS (SHEET 1 OF 2)
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
062119228-1692 REV 915
www.kepcopower.com email: hq@kepcopower.com
Page 16
SLIDES TRAVEL DISTANCE: 23.000 [584.2]
22.000 [558.79]
SEE NOTE 6.
REAR VIEW
REMOVE FEET FOR
RACK MOUNTING.
KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A. TEL (718) 461-7000 FAX (718) 767-1102
FIGURE 1. BOP 1KW OUTLINE DIMENSIONS (SHEET 2 OF 2)
www.kepcopower.com email: hq@kepcopower.com
16228-1692 REV 9 062119
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.