the installation, checkout and operation of the Kepco BIT
4886 Card installed in a BOP power supply. Full specifications and operating procedures are listed in the Operator
Manual that can be downloaded from the Kepco web site:
• www.kepcopower.com/support/opmanls.htm#bit
II — INSTALLATION
CAUTION: If the BIT card was not pre-installed in a
BOP at Kepco, you must install and calibrate the card
by following the instructions in the Operator Manual
which can be downloaded from the Kepco website (see
above). Failure to calibrate the unit could impact the
accuracy of settings and readbacks. It will not impact
remote operation of the unit.
STARTUP DEFAULT. The Device Address (GPIB
address) for the interface card is set by means of DIP
switch S1, positions 1 through 5 (Figure 1) which can be
accessed through the top cover of the BOP. It is factory
preset to address 6. If a different Device Address is
required in your system, there are 31 (1-31) possible
choices (see Table 1).
FIGURE 1. SETTING THE GPIB ADDRESS
KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11355 U.S.A. " TEL (718) 461-7000 " FAX (718) 767-1102
DESCRIPTION. The Kepco BIT Card Series were
designed as an accessory for the Kepco BOP series bipolar power supplies. The BIT 4886 card acts as an interface
between the digital data bus and the BOP, accepting the
digital input data and converting it to an analog signal,
which in turn, controls the BOP output.
TABLE 1. DEVICE ADDRESS SELECTION
DECIMAL
ADDRESS
100001
200010
300011
400100
500101
600110
700111
801000
901001
10 01010
11 01011
12 01100
13 01101
14 01110
15 01111
16 10000
17 10001
18 10010
19 10011
20 10100
21 10101
22 10110
23 10111
24 11000
SELECTOR SWITCH S1 SECTION (SIGNAL
LINE)
A5A4A3A2A1
TABLE 1. DEVICE ADDRESS SELECTION (CONT)
DECIMAL
ADDRESS
25 11001
26 11010
27 11011
28 11100
29 11101
30 11110
31 11111
NOTE:
0 = CLOSED (ON) (Towards printed circuit board)
1 = OPEN (OFF) (Away from printed circuit board)
SELECTOR SWITCH S1 SECTION (SIGNAL
LINE)
A5A4A3A2A1
CHECKOUT PROCEDURE.
1. Connect the BOP-BIT 4886 Interface Card to either:
a) the GPIB bus using a standard GPIB cable
connected to the BIT 4886 24-pin GPIB connector
(J1) or
b) to an external RS-232 controller with a DB9
type connector (male pins) by connecting the RJ45
patch cord to the BIT 4886 RS 232 port (J2), then
using the RJ45 to DB9 adapter supplied (see Figure
2) to connect the RJ45 patch cord to the external controller. On the RJ45 patch cord, the 6-pin connector
plugs into the BIT 4886 RS 232 port, and the 8-pin
connector plugs into the RJ45 to DB9 adapter (see
Table 2 and Figure 2).
TABLE 2. RJ45 TO DB9 ADAPTER WIRE FUNCTIONS
WireDB9 PinPurpose
Green5Return for pins 2 and 3.
Brown3
Yellow2
Carries data from the Kepco power
supply to the controller.
Carries data from the controller to the
Kepco power supply.
2. Apply power to BOP power supply. The BOP-BIT
4886 will beep for less than 1 second, then will be
ready for use.
3. Send the *IDN? query via either the GPIB or RS 232
port.
Assuming the BIT 4886 card is installed in a BOP 72-6
as an example, verify that the unit responds with
KEPCO,BIT488-6 72-6,A38621 11/10/98,1.81-1.81.
If the unit responds with KEPCO,BIT488-6 200-20,A38621 10/01/98,1.81-1.81, it means that the card
was not initialized; refer to Operator Manual to initialize the card. Note that date 10/01/98 is the initial calibration date performed at the factory and indicates the
card has never been calibrated by the user.
4. Send VOLT? Verify that unit responds with 0 (indicating voltage is set to 0, the power-up condition).
5. Send OUTPUT ON;VOLT MAX. Verify that the BOP
power supply provides maximum output voltage (e.g.,
72V d-c. for BOP 72-6).
6. Send FUNC:MODE CURR. Verify that BOP front panel
current LED lights.
7. Send FUNC:MODE VOLT. Verify that BOP front panel
voltage LED lights.
8. Send *TST? and verify response is 0. This verifies the
bit 4886 microprocessor is operating correctly.
FIGURE 2. RJ45 TO DB9 ADAPTER WIRING
9. With no load connected, send DIAG:TST? and verify
response is 0. CAUTION: This test swings the output
to Volt MAx and Volt Min at full power. If a Load is
connected, damage to the load may occur, or the test
may fail due to the load effect on unit output voltage
III — OPERATION
The BOP can now be controlled via either the RS 232 or
GPIB ports using IEEE 488 and SCPI commands. The
applicable commands and queries are listed in Table 3
and 4, respectively. For a full description of all commands
KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11355 U.S.A. " TEL (718) 461-7000 " FAX (718) 767-1102
disables (0 or OFF) the power supply output.
Query shows if output is on (1) or off (0).
lishes operating mode of power supply VOLT =
voltage, CURR = current. Query shows mode.
[SOURce:]FUNCtion:MODE:TRIGger establishes
operating mode of power supply when TRIGger
command is sent. Query returns mode programmed.
entries by setting all pointers to 0.
many times the list is executed. Query shows programmed setting.
[SOURce:]LIST:COUNt:SKIP Command allows
beginning steps of list-generated waveform to be
run once, then ignored. Query shows how many
steps to skip after the first time.
value (in Amps) to list. Query identifies parameters
(main channel) entered for list.
[SOURce:]LIST:CURRent:POINts? Query identifies the total number of points in a list and next
location to be filled.
which direction to run list. Query shows programmed direction.
long the main channel parameters will be active.
Query shows programmed dwell times.
[SOURce:]LIST:DWELl:POINts? Query identifies
number of locations with dwell times.
the order for executing the list. Query shows selection of either default or user sequence.
location to be queried by LIST:SEQ?; Query shows
programmed location.
dwell time resolution SLOW (default) or FAST.
Query shows mode.
execution order for list data points (not recommended for new designs). Query shows user execution sequence for list.
KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11355 U.S.A. " TEL (718) 461-7000 " FAX (718) 767-1102
SYSTem:COMMunication:SERial:ECHO Command enables (ON) or disables (OFF) echo mode.
Query indicates if echo is on or off.
SYSTem:COMMunication:SERial:PACE Command enables (XON) or disables (NONE) data flow
control via the serial interface. Query shows
enabled or disabled.
the output queue.
SYSTem:ERRor:CODE? Query returns 3-character error code without the ASCII definition string.
SYSTem:ERRor:CODE:ALL? Query returns a
comma-separated list of all error codes.
SYSTem:PASSword:CENable Command Sets
password enable if password matches.
SYSTem:PASSword:CDISable Command disables
password access if password matches.
SYSTem:PASSword:NEW Command establishes
new password.
SYSTem:PASSword:STATe? Query shows password state: enabled (1) or disabled (0).
or ON) or local (0 or OFF) mode if using RS 232.
Query shows programmed mode.
izes all NVRAM variables to factory defaults.
Clear, Line Feed, and Reset functions. Query
shows programmed functions.
implemented.
KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11355 U.S.A. " TEL (718) 461-7000 " FAX (718) 767-1102