FLUE SYSTEMS
The flue system should be vertical and without bends. If an offset is req uired, it should be as close to the heater as practicable and
should not be offset more than 500mm from the centreline of the flue stub. Clearances from the flue pipe to combustible materials
must be maintained (refer Table 1 and Fig 1). Restrictions or leaks in the flue system may reduce the draught, and, in severe
conditions, could cause smoke to enter the room. The flue pipe shall extend not less than 4.6m above the top of the floor protector.
The flue cowl must be at least 600mm above the highest point of the roof if within 3 metres of it, or 1000mm above the roof
penetration if more than 3 metres from the ridge. No part of the building, or any adjacent building may be in, or above, a circular
area of a horizontal radius of 3 metres from the flue exit (Fig 2 *).
SEISMIC RESTRAINT
The heater must be restrained against movement due to earthquakes. The Tilefire is restrained by fixing the heater to the floor with
two b olts of 6mm diameter through the holes provided in the plinth base, through the hearth and floor and fixed with heavy
washers and nuts. For solid concrete floors, use 8mm DYNABOLTS® or similar with a minimum depth of engagement into the floor of
50mm. Location of fixing bolts (Refer Fig. 5)
Fig 5
DOOR HANDLE AND DOOR
Table 1
* These heights are given as a general minimum, and in actual
practice the presence of surrounding structures, trees, fences, etc.
may necessitate additional height for satisfactory performance. The
cowl must be fitted to prevent entry of birds, snow and rain.
At all flue joints, the swaged end of the upper piece must be fitted to
the plain end of the lower piece.
FLOOR PROTECTOR
An insulating floor protector is not required for the Tilefir e heater, but a
floor protector of non-combustible material must be used. The floor
protector must extend under the heater, a minimum of 300mm in front
of the door opening, and 180mm to either side of the heater. The
minimum floor protector size for a wall installation is 890mm wide and
1120mm front to back, excluding trim. For a corner installation the
minimum length along the wall is 1000mm and diagonally from the
corner to the front edge is 1350mm, also excluding trim.
ASSEMBLY
The Tilefire is supplied with additional component packs that contain
the ash spill tray, fire bricks, baffle and air tube and plinth.
Before starting assembly, please unpack these and familiarise yourself
with the components as you read these instructions.
CAUTION: when lifting the heater, always lift from under the cabinet
outer surround. DO NOT LIFT from the door, ash spill tray or front air slide
as these will be damaged.
Begin assembly by laying the heater carefully on its back on a padded
surface. Place the 4 coach-bolts from the bolt pack through the holes in
the floor of the firebox from inside and screw on the hexagonal spacer
nuts. Place the heat-shield onto the bolts with the turned up edge
facing the door frame. Fit the plinth wrapper onto the bolts and fix in
place with lock washers and nuts. Note that the open side of the plinth
wrapper mu st face to the rear of the heater (Refer Fig. 3). Screw the
plinth base to the wrapper using 4 screws provided (Refer Fig. 4). Place
the heater back onto its base, taking care to lift the heater, not roll it, to
avoid damage to components.
Fig 3
Fig 4
Fig 2
The door handle is pre-fitted and should not require any adjustment
on assembly of the heater. Any adjustment required to maintain the
correct fit of the door is made at the door catch pin on the right side
of the door lip. To adjust the fit of the door catch, loosen th e lock nut
and turn the eccentric pin to loosen or tighten the fit. Re-tighten the
lock nut (refer Fig. 6).
AIR CONTROL KNOB
The air control knob is fitted to the stem with a grub-screw to retain it.
If this requires replacing, it will be necessary to loosen this screw before
pulling off the knob. Refit the knob by lining up the flats in the knob
with the flats on the stem and pushing home. Tighten the grub-screw.
ASH SPILL TRAY
Fit the ash spill tray under the door opening by placing the hex head
bolts through the two holes u nder the door lip, from inside the firebox,
and screw them into the two captive nuts i n the back face of the ash
spill tray.
FIREBRICKS, BAFFLE PLATE AND AIR TUBE
Fit the secondary air tube, if not already fitted. The tube has a notch in
one end - this is the right hand end. Slide the sleeve from the
component pack onto the tube. Place the tube into the firebox and
insert the left end into the hole in the left side of the firebox. Lift the
right end up and slide it into the hole in the right side of the firebox,
rotating it to allow the notch to fit over the tab in the hole (refer Fig. 7).
Slide the sleeve to the left until it en ters the hole in the left side of the
firebox, and retain it with the pin supplied. The pin should pass
completely through the sleeve and air tube. Note that the sleeve
should not project outside the firebox. If necessary, reverse the sleeve
on the air tube (refer Fig. 8).
The brick pack comprises 8 bricks 280mm x 115mm x 25mm, and two
bricks 250mm x 188mm x 25mm. Place the baffle plate into the firebox
and hold up against the roof while 4 bricks are placed on end on
either side of the firebox. Note that the baffle is placed with the
concave surface down. Lower the baffle plate down onto the bricks
so the tops of the bricks are retained behind the angles on either side
of the plate. Fit the two remaining wide bricks on end across the back
of the firebox. It may be necessary to fit these by putting the two outer
edges of the bricks into position against the side bricks and then
pushing both inner edges back at the same time like a folding door
(refer Fig. 9). Ensure the baffle plate is pu shed hard against the back
wall of the firebox.
Fig 6
Fig 7
Fig 8
Fig 9