INSTALLATION INSTRUCTIONS
30" (76CM) FREESTANDING ELECTRIC RANGE
WITH DOUBLE OVENS
INSTRUCCIONES DE INSTALACION
ESTUFA ELI_CTRICAAUTONOMA DE 30" (76,2CM)
CON HORNOS DOBLES
Table of Contents/indice
RANGE SAFETY ....................................................................... 1
INSTALLATION REQUIREMENTS .......................................... 2
Tools and Parts ...................................................................... 2
Location Requirements ......................................................... 2
Electrical Requirements ......................................................... 3
INSTALLATION INSTRUCTIONS ............................................ 4
Unpack Range ....................................................................... 4
Adjust Leveling Legs .............................................................. 5
Install Anti-Tip Bracket .......................................................... 5
Electrical Connection - U.S.A. Only ...................................... 6
Verify Anti-Tip Bracket Location .......................................... 10
Level Range ......................................................................... 10
Complete Installation ........................................................... 11
Moving the Range ................................................................ 11
SERVICE NUMBERS ......................................... BACK COVER
SEGURIDAD DE LA ESTUFA ................................................. 12
REQUlSITOS DE INSTALACION ............................................ 12
Piezas y herramientas ........................................................... 12
Requisites de ubicaci6n ....................................................... 13
Requisites electricos ............................................................. t4
INSTRUCCIONES DE INSTALACION ................................... 15
Desempaque la estufa .......................................................... 15
Regule las patas niveladoras ................................................ 16
Instalaci6n del soporte anti-vuelco ...................................... 16
Conexi6n electrica - S61oen EE.UU .................................... 17
Verificaci6n de la ubicaci6n del soporte anti-vuelco ........... 22
Nivelaci6n de la estufa .......................................................... 22
Complete la instalaci6n ........................................................ 22
C6mo mover la estufa ........................................................... 23
NUMEROS DE SERVICO .......................... CONTRAPORTADA
RANGE SAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol.
This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word "DANGER" or "WARNING."
These words mean:
You can be killed or seriously injured if you don't immediately
follow instructions.
You can be killed or seriously injured if you don't follow
instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can
happen if the instructions are not followed.
iMPORTANT:
Save for local electrical inspector's use.
W10166286A
IMPORTANTE:
Guarde para tenerlas a disposici6n del inspector de electricidad local.
A child or adult can tip the range and be killed.
Connect anti-tip bracket to rear range foot.
l_b 1 Tip Over Hazard
Reconnect the anti=tip bracket, if the range is moved.
Failure to follow these instructions can result in death or serious burns to children and adults.
INSTALLATION REQUIREMENTS
Gather the required tools and parts before starting installation.
Read and follow the instructions provided with any tools listed
here.
Tools needed
• Tape measure •
• Level •
• Phillips screwdriver •
• Flat-blade screwdriver •
Parts supplied
Check that all parts are included.
3 - 10-32 hex nuts (attached to terminal block)
3 - Terminal lugs
Oven racks
2 - #12 x 1%" screws (for mounting anti-tip bracket)
Anti-tip bracket (taped inside upper oven with literature
package)
Anti-tip bracket must be securely mounted to back wall or
floor. Thickness of floor may require longer screws to anchor
bracket to sub-floor. Longer screws are available from your
local hardware store.
Parts needed
If using a power supply cord:
• A UL listed power supply cord kit marked for use with ranges.
The cord should be rated at 250 volts minimum, 40 amps or
50 amps that is marked for use with nominal 13/o'' (3.5 cm)
diameter connection opening and must end in ring terminals
or open-end spade terminals with upturned ends.
• A UL listed strain relief.
Check local codes. Check existing electrical supply. See
"Electrical Requirements" section.
It is recommended that all electrical connections be made by a
licensed, qualified electrical installer.
Wrench or pliers
%" nut driver
Hand or electric drill
1/8"(3.2 mm) drill bit
IMPORTANT: Observe all governing codes and ordinances,
• It is the installer's responsibility to comply with installation
clearances specified on the model/serial rating plate. The
model/serial rating plate is located behind the panel,
• The range should be located for convenient use in the
kitchen.
To eliminate the risk of burns or fire by reaching over heated
surface units, cabinet storage space located above the
surface units should be avoided. If cabinet storage is to be
provided, the risk can be reduced by installing a range hood
that projects horizontally a minimum of 5" (12.7 cm) beyond
the bottom of the cabinets.
• Cabinet opening dimensions that are shown must be used.
Given dimensions are minimum clearances.
• The floor anti-tip bracket must be installed. To install the anti-
tip bracket shipped with the range, see "Install Anti-Tip
Bracket" section.
• Grounded electrical supply is required. See "Electrical
Requirements" section.
IMPORTANT: To avoid damage to your cabinets, check with your
builder or cabinet supplier to make sure that the materials used
will not discolor, delaminate or sustain other damage. This range
has been designed in accordance with the requirements of UL
and CSA International and complies with the maximum allowable
wood cabinet temperatures of 194°F (90°C).
Mobile Home - Additional Installation Requirements
The installation of this range must conform to the Manufactured
Home Construction and Safety Standard, Title 24 CFR, Part 3280
(formerly the Federal Standard for Mobile Home Construction
and Safety, Title 24, HUD Part 280). When such standard is not
applicable, the Standard for Manufactured Home Installations,
ANSI A225.1/NFPA 501A or with local codes.
Mobile home installations require:
• When this range is installed in a mobile home, it must be
secured to the floor during transit. Any method of securing
the range is adequate as long as it conforms to the standards
listed above.
• Four-wire power supply cord or cable must be used in a
mobile home installation. The appliance wiring will need to be
revised. See "Electrical Connection" section.
Product Dimensions
C
A. 46%" (119.9cm) C.35%" (91.4cm)
B.Model/serial number plate D.29%" (75.9cm)
(locatedbehind the control E.26%G"- 27'/4" (66.8- 69.2 cm)**
panel)*
*Serial number plate may be rotated up from behind the control
panel for viewing from the front of the range.
**Excludes handle. Dimension given is from wall to front of oven
door and will vary based on electric outlet receptacle
installation.
Cabinet Dimensions
Cabinet opening dimensions shown are for 25" (64.0 cm)
countertop depth, 24" (61.0 cm) base cabinet depth and
36" (91.4 cm) countertop height.
If installing a range hood or microwave hood combination above
the range, follow the range hood or microwave hood combination
installation instructions for dimensional clearances above the
cooktop surface.
A freestanding range may be installed next to combustible walls
with zero clearance.
G
F
H
A. !3" (33 cm) upper cabinet
depth
B. 30" (76.2 cm) min. opening
width
C. For minimum clearance to the
top of the cooktop,
see NOTE.
D. 30" (76.2 cm) min. opening
width
E.Cabinet door or hinge should
not extend into cutout.
Wothing located in shaded areas can extend more than 1_/2"(3.8 cm)
from wall or range will not slide all the wayback.
F. 3-wire shaded area -
7" (17.8 cm) min. from left side
cabinet, 53/4"(14.6 cm) max.
from fleer, 6" (!5.2 cm) max.
width *
G. 4-wire shaded area -
!0" (25.4 cm) min. from right
side cabinet, 5_ '' (14.6 cm)
max. from floor, 6" (15.2 cm)
max. width*
H. !72" (3.8 cm) rain. from floor if
using a flush mount outlet.
NOTE: 24" (61.0 cm) minimum when bottom of wood or metal
cabinet is protected by not less than 1/4"(0.64 cm) flame retardant
millboard covered with not less than No. 28 MSG sheet steel,
0.015" (0.4 mm) stainless steel, 0.024" (0.6 mm) aluminum or
0.020" (0.5 mm) copper.
30" (76.2 cm) minimum clearance between the top of the cooking
platform and the bottom of an unprotected wood or metal
cabinet.
If codes permit and a separate ground wire is used, it is
recommended that a qualified electrical installer determine that
the ground path and wire gauge are in accordance with local
codes.
Do not use an extension cord.
Be sure that the electrical connection and wire size are adequate
and in conformance with the National Electrical Code, ANSI/
NFPA 70-latest edition and all local codes and ordinances.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park
Quincy, MA 02269.
WARNING: Improper connection of the equipment-grounding
conductor can result in a risk of electric shock. Check with a
qualified electrician or service technician if you are in doubt as to
whether the appliance is properly grounded. Do not modify the
power supply cord plug. If it will not fit the outlet, have a proper
outlet installed by a qualified electrician.
Electrical Connection
To properly install your range, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here,
• Range must be connected to the proper electrical voltage
and frequency as specified on the model/serial number rating
plate. The model/serial number rating plate is located behind
the control panel or on the oven frame behind the storage
drawer panel. Refer to the figures in the "Product
Dimensions" section of the "Location Requirements" section.
• This range is manufactured with the neutral terminal
connected to the cabinet. Use a 3-wire, UL listed, 40- or
50-amp power supply cord (pigtail) (see Range Rating chart
below). If local codes do not permit ground through the
neutral, use a 4-wire power supply cord rated at 250 volts,
40 or 50 amps and investigated for use with ranges.
Range Rating* Specified Rating of
Power Supply Cord Kit
and Circuit Protection
120/240 Volts 120/208 Volts Amps
8.8- 16,5 KW 7,8- 12.5 KW 40 or 50"*
16.6 - 22.5 KW 12.6 - 18.5 KW 50
If connecting to a 4-wire system:
This range is manufactured with the ground connected to the
cabinet. The ground must be revised so the green ground wire of
the 4-wire power supply cord is connected to the cabinet, See
"Electrical Connection."
Grounding through the neutral conductor is prohibited for new
branch-circuit installations (1996 NEC); mobile homes; and
recreational vehicles, or an area where local codes prohibit
grounding through the neutral conductor.
When a 4-wire receptacle of NEMA Type 14-50R is used, a
matching UL listed, 4-wire, 250-volt, 40- or 50-amp, range power
supply cord (pigtail) must be used. This cord contains 4 copper
conductors with ring terminals or open-end spade terminals with
upturned ends, terminating in a NEMA Type 14-50P plug on the
supply end.
The fourth (grounding) conductor must be identified by a green or
green/yellow cover and the neutral conductor by a white cover.
Cord should be Type SRD or SRDT with a UL listed strain relief
and be at least 4 ft (1.22 m) long.
*The NEC calculated load is less than the total connected load
listed on the model/serial rating plate.
**If connecting to a 50-amp circuit, use a 50-amp rated cord with
kit. For 50-amp rated cord kits, use kits that specify use with a
nominal 1%" (34,9 mm) diameter connection opening,
• A time-delay fuse or circuit breaker is recommended.
The range can be connected directly to the fused disconnect
(or circuit breaker box) through flexible or nonmetallic
sheathed, copper or aluminum cable. See "Electrical
Connection."
• Allow 2 to 3 ft (61.0 cm to 91.4 cm) of slack in the line so that
the range can be moved if servicing is ever necessary.
• A UL listed conduit connector must be provided at each end
of the power supply cable (at the range and at the junction
box).
• Wire sizes and connections must conform with the rating of
the range.
• The wiring diagram is located on the back of the range or
inside the storage drawer in a clear plastic bag.
INSTALLATION INSTRUCTIONS
4-wire receptacle (14-50R)
The minimum conductor sized for the copper 4-wire power
cord are:
40-amp circuit
2 No.-8 conductors
1 No.-10 white neutral
1 No.-8 green grounding
If connecting to a 3-wire system:
Local codes may permit the use of a UL listed, 3-wire, 250-volt,
40- or 50-amp range power supply cord (pigtail). This cord
contains 3 copper conductors with ring terminals or open-end
spade terminals with upturned ends, terminating in a NEMA Type
10-50P plug on the supply end. Connectors on the appliance end
must be provided at the point the power supply cord enters the
appliance. This uses a 3-wire receptacle of NEMA Type 10-50R.
3-wire receptacle (10-50R)
' ,'k, ........
Excessive Weight Hazard
Use two or more people to move and install range.
Failure to do so can result in back or other injury.
1. Remove shipping materials, tape and protective film from the
range. Keep cardboard bottom under range.
2. Remove oven racks and parts package from inside oven.
3. To place range on its back, take 4 cardboard corners from the
carton, Stack one cardboard corner on top of another.
Repeat with the other 2 corners. Place them lengthwise on
the floor behind the range to support the range when it is laid
on its back.
4. Using 2 or more people, firmly grasp the range and gently lay
it on its back on the cardboard corners.
5. Pull cardboard bottom firmly to remove.
6. Use an adjustable wrench to loosen the leveling legs.
7. Place cardboard or hardboard in front of range. Using 2 or
more people, stand range back up onto cardboard or
hardboard.
L;eve g Legs
If range height adjustment is necessary, use a wrench or
pliers to loosen the 4 leveling legs.
This may be done with the range on its back or with the range
supported on 2 legs after the range has been placed back to
a standing position.
NOTE: To place range back up into a standing position, put a
sheet of cardboard or hardboard in front of range. Using 2 or
more people, stand range back up onto the cardboard or
hardboard.
Tip Over Hazard
A child or adult can tip the range and be killed.
Connect anti=tip bracket to rear range foot.
Reconnect the anti=tip bracket, if the range is moved.
Failure to follow these instructions can result in death
or serious burns to children and adults.
3=
Determine and mark edge of range in the cutout space. The
mounting bracket can be installed on either the left side or
right side of the cutout. Position mounting bracket in cutout
so that right (or left) edge of the bracket is 15/16"(2.4 cm) from
the marked edge of the range, as shown.
..........I
B ......... i __
A. Anti-tip bracket
B. Mark edge of range
C. _A6" (2.4 cm)
4. Drill two W' (3 mm) holes that correspond to the bracket
holes of the determined mounting method. See below.
Floor Mounting
A B
2=
Adjust the leveling legs to the correct height. Leveling legs
can be loosened to add up to a maximum of 1" (2.5 cm). A
minimum of 3/16"(5 mm) is needed to engage the anti-tip
bracket.
NOTE: If height adjustment is made when range is standing,
tilt the range back to adjust the front legs, then tilt forward to
adjust the rear legs.
3=
When the range is at the correct height, check that there is
adequate clearance under the range for the anti-tip bracket.
Before sliding range into its final position, check that the anti-
tip bracket will slide under the range and onto the rear
leveling leg prior to anti-tip bracket installation.
1. Remove the anti-tip bracket that is taped inside the upper
oven with the literature package.
2. Determine which mounting method to use: floor or wall.
If you have a stone or masonry floor you can use the wall
mounting method.
A. #12x 1%" screws
B.Anti-tip bracket
Wall Mounting
A. #12x 1%"screws
B.Anti-tip bracket
5=
Using the Phillips screwdriver, mount anti-tip bracket to the
wall or floor with the two #12 x 1%" screws provided.
Power Supply Cord
Direct Wire
Electrical Shock Hazard
Disconnect power before servicing.
Use a new 40 amp power supply cord.
Plug into a grounded outlet.
Failure to follow these instructions can result in death,
fire, or electrical shock.
Disconnect power before servicing.
Use 8 gauge copper or 6 gauge aluminum wire.
Electrically ground range.
Failure to follow these instructions can result in death,
fire, or electrical shock.
1. Disconnect power.
2. Use Phillips screwdriver to remove the terminal block cover ........
screw located on the back of the range. Pull cover down and
toward you to remove cover.
• Feed the power supply cord through the strain relief in the
3. Remove plastic tag holding three 10-32 hex nuts from the
middle post of the terminal block.
cord/conduit plate on bottom of range. Allow enough
slack to easily attach the wiring to the terminal block.
• Tighten strain relief screw aqainst the power supply cord.
Electrical Shock Hazard
A, UL listed strain relief
4. Add strain relief.
Style 1: Power supply cord strain relief
• Assemble a UL listed strain relief in the opening.
Style 2: Direct wire strain relief
• Use Phillips screwdriver to remove screws and slide
cord/conduit plate down and out.
Positioncord/conduitplateasshowninthefollowing
illustration.
• Replacecord/conduitplateandinsertscrews.
Electrical Connection Options
If your home has: And you will be Go to Section:
connecting to:
4-wire receptacle A UL listed, 4-wire connection:
(NEMA type 14-50R) 250-volt Power supply cord
40-amp, range
minimum,
power supply
cord
4-wire direct A fused 4-wire connection:
disconnect or Direct wire
(12.7 ore) box
3-wire receptacle
(NEMA type 10-50R)
circuit breaker
A UL listed,
250-volt
minimum,
40-amp, range
power supply
cord
3-wire connection:
Power supply cord
• AssembleaULlistedconduitconnectorintheopening•
J
t
B
A. Removableretaining nut
B.Strain relief
• Feed the flexible conduit through the strain relief, allowing
enough slack to easily attach wiring to the terminal block•
• Tighten strain relief screw against the flexible conduit•
3-wire direct A fused
1" disconnect or
(2•5o_.\ circuit breaker
box
4-wire connection: Power Supply Cord
Use this method for:
• New branch-circuit installations (1996 NEC)
• Mobile homes
• Recreational vehicles
• In an area where local codes prohibit grounding through the
neutral
1. Part of metal ground strap must be cut out and removed.
A. Metal ground strap
B. Discard
C. Ground-link screw
3-wire connection:
Direct wire
A
B
C
5=
Replace back panel and screws on rear of range•
6.
Complete installation following instructions for your type of
electrical connection:
4-wire (recommended)
3-wire (if 4-wire is not available)
2=
Use Phillips screwdriver to remove the ground-link screw
from the back of the range• Save the ground-link screw and
the end of the ground-link under the screw•
3,
Feed the power supply cord through the strain relief in the
cord/conduit plate on bottom of range. Allow enough slack to
easily attach the wiring to the terminal block.
C
A. Terminalblock
B. Ground-linkscrew
C. Cord/conduit plate
D. Powersupply cord wires
4,
Use Phillips screwdriver to connect the green ground wire
from the power supply cord to the range with the ground-link
screw. The ground wire must be attached first.
5,
Use %" nut driver to connect the neutral (white) wire to the
center terminal block post with one of the 10-32 hex nuts.
3-wire connection: Power Supply Cord
Use this method only if local codes permit connecting chassis
ground conductor to neutral wire of power supply cord.
1. Feed the power supply cord through the strain relief in the
cord/conduit plate on bottom of range. Allow enough slack to
easily attach the wiring to the terminal block.
A. Terminal block
B. Ground-link screw
C. Cord/conduit plate
D. Power supply cord wires
2,
Use %" nut driver to connect the neutral (white) wire to the
center terminal block post with one of the 10-32 hex nuts.
B
D
A. 10-32 hex nut
B. Ground-link screw
C. Line ! (black)
6,
Connect line 1 (black) and line 2 (red) wires to the outer
D. Green ground wire
E.Neutral (center) wire
F. Line 2 (red)
terminal block posts with 10-32 hex nuts.
7.
Securely tighten hex nuts.
NOTE: For power supply cord replacement, only use a power
cord rated at 250 volts minimum, 40 amps or 50 amps that is
marked for use with nominal 1%" (3.5 cm) diameter
connection opening, with ring terminals and marked for use
with ranges.
8. Replace terminal block access cover.
E
A ..............
B _ _s i
C
A. 10-32 hex nut
B. Line ! (black)
C. Ground-link screw
3,
Connect line 1 (black) and line 2 (red) wires to the outer
D. Neutral (white) wire
E. Line 2 (red)
terminal block posts with 10-32 hex nuts.
4.
Securely tighten hex nuts.
NOTE: For power supply cord replacement, only use a power
cord rated at 250 volts minimum, 40 amps or 50 amps that is
marked for use with nominal 1%" (3.5 cm) diameter
connection opening, with ring terminals and marked for use
with ranges.
5. Replace terminal block access cover.