OWNER'S MANUAL
CONTINUOUS PILOT
MODEL NO.
KWX - 3V
KWX - 4V
KWX - 5V
KWX - 6V
KWX - 7V
KWX - 8V
KWX - 9V
Gas- Fired
Cast Iron
HOT WATER
BOILER
CAUTION
Read all instructions
carefullybefore starting
the installation.
Save this manual
for future reference.
These instructions must
be affixed on or adjacent
to the boiler.
• Installation
• Operation
• Repair Parts
WAILING: Improper installation, adjustment, alteration, service or
maintenance can cause injury or property damage. Refer to this
manual. For assistance or additional information consult a qualified
installer, service agency or the gas supplier.
Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A
I
KENNMORE CAST IRON BOILERS
FULL ONE YEAR WARRANTY ON HOT WATER AND GAS STEAM CAST IRON BOILERS
For one (1) year from the date of installation, when this boiler is installed and maintained in accordance
with our instructions. Sears will repair defects in material or workmanship in the boiler, free of charge.
LIMITED 12 YEAR WARRANTY ON STEAM CAST IRON BOILERS
After one (1) year and through twelve (12) years from the date of installation, Sears will furnish a replacement
heat exchanger, if the heat exchanger in the boiler is defective. YOU PAY FOR LABOR.
:_ LIMITED 20 YEAR WARRANTY ON HOT WATER CAST IRON BOILERS
After one (1) year and through twenty (20) years from the date of installation, Sears will furnish a replacement
heat exchanger if the heat exchanger in the boiler is defective. YOU PAY FOR LABOR.
SEARS INSTALLATION WARRANTY
In addition to any warranty extended to you on the Sears merchandise involved, which warranty becomes
effective the date the merchandise is installed, should the workmanship of any Sears arranged installation
;_ prove faulty within one year, Sears will, upon notice from you, cause such faults to be corrected at
no additional cost to you.
FOR WARRANTY SERVICE, SIMPLY CONTACT THE NEAREST SEARS STORE OR SERVICE
;_l CENTER THROUGHOUT THE UNITED STATES. This warranty gives you specific legal rights, and
you may also have other rights which vary from state to state.
IMPORTANT
The following are the responsibilities of the user and are not
covered by the Warranty
1. Filter clearing or replacement.
2. Damage to unit or unsatisfactory operation due to improper
cleaning or use of unit in corrosive atmosphere.
3. Damage to unit or unsatisfactory operation due to blown fuses
or inadequate or interrupted electrical protective devices.
4. Damage to unit caused by the use of components or other
accessories not compatible with the unit.
1 Read the Owner's Manual for Safe Operation carefully Failure
to follow the rules for safe operation and the instructions can
cause a malfunction of the boiler and result in death, serious
bodily injury, and/or property damage.
2 Check your local cedes and utility requirements before
installation. The installation must be in acordance with their
directives.
3. Before servicing, allow boiler to cool. Always shut off any
electricity and gas to boiler when working on it. This will prevent
any electrical shocks or burns.
4 Never test for gas leaks with an open flame. Use soap and
i
5. If the unit is removed from the place it was originally installed,
this VCarranty becomes void.
6. Damage to the unit caused by accident, abuse, negligence,
misuse, riot, fire, flood, or acts of God.
SEARS ROEBUCK AND COMPANY
D/817WA
Hoffman Estates, IL 60179
check all connections. This will avoid any possibility of fire
or explosion
5. Be certain your new boiler will be using the correct gas.
Overfiring will result in premature failure of the boiler sections
and cause dangerous operation
6. Never vent this boiler into an enclosed space. Always vent
to the outside. Never vent to another room or inside a building
7. Be sure there is adequate air supply for complete combustion
8 Follow a regular service and maintenance schedule for efficient
and safe operation.
2
FIG. 1
-ASME R[[J_¥ VALVE
C_ VI£NT
DAMPER
--A u
TEMP./PRESS. GAUGE
l
l
,-_ ..... -I,
r---
I
I;[ HPT , \ \
"_ i \.A
?
L ...... ,.Lr'--_l_ [
!
i
LEFT S;DE
BASIC BOILER MODEL NO.
ConUnuous Pilot
Vent Damper
KWX-3V
KWX-4V
KWX-5V
KWX-6V
KWX-7V
KWX-8V
KWX-9V
With
[_-----
J
i<\/
ENCLOSED
SCOHTROL_
• _AJN VALVE %
COH_OL
NO. OF
SECTIONS
3
4
5
6
7
8
9
I I I
I I i
i I I
INPUT
*MBH
70
105
140
175
210
245
280
hr _
I I II
_._L_ _.1__ _1__ _
AGA/CGA
GAS VALVE
NATURAL GAS
HEATING
CAPACITY
*MBH
57
85
113
142
170
198
226
J I r ' 'E'r'PPLE
31 ?
RIGHT SIO[
DIMENSIONS (INCHES)
NET
I=B=R
Ratin9*MBH
5O
74
98
123
148
172
197
FLUE
DIAMETER
5
6
6
7
7
7
7
"A"
WIDTH
11 1/4
14 1/2
17 ¾
21
24 1/4
27 1/2
30 ¾
®
* MBH = 1,000 Btuh Btuh = British Thermal Unit Per Hour
For altitudes above 2,000 ft. ratings should be reduced at the rate of 4 _ for each 1,000 ft. above sea level•
Heating Capacity is based on D.O.E (Deparirnent of Energy) test procedure.
**Add 5 ½" to height for Vent Damper.
The Ratings marked "Net I=B-R Ratings" indicate the amount of remaining heat input that can be used to heat the radiation or terminal
Units. The net I=B=R Ratings shown are based on an allowance of 1.15 in accordance with the factors shown on the I=B=R Standard
as published by the Hydronies Institute. Selection of boiler size should be based upon "Net I=B=R Rating" being equal to or greater
than the calculated heat loss of the building. The Manufacturer should be consulted before selecting a boiler for installations having
unusual piping and pickup requirements. These boilers must stand on a non-combustible floor. If installed on a combustible floor, use
Combustible Floor Base Number 42135-1 or 146-14-031 (3-6 section boilers) or 42135-2 or 146-14-032 (7-9 section boilers).
BOILERS FOR USE AT HIGH ALTITUDE
This boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level. For use at altitudes above sea level, the input
ratings are reduced by a change in main orifice size.
For altitudes above 2,000 feet above sea level, input ratings should be reduced at the rate of 4% for each 1,000 feet
above sea level. Consult the National Fuel Gas Code (NFPA54/ANSI Z223.1-1atest edition), or the manufacturer for correct orifice
sizing information. High altitude orifices are available from the boiler manufacturer.
a
Check Io be sure you have the right size boiler before starting the installation.
See rating and capacity table on previous page. Also be sure the new boiler is
for the type of gas you are using. Check the rating plate on the right side of the
boiler.
You must see that the boiler is supplied with the corred type ol gas, fresh air
for combustion, and a suitable electrical supply. Also, the boiler must be con-
nected to a suitable venting system and an adequate piping system. Finally, a
thermostat, properly located, is needed for control of the heating system. If you
have any doubts as to the various requirements, check with local authorities
and obtain professional help where needed. Take the time to complete all of
the steps for SAFE and PROPER operation of the heating system.
If this boiler is installed in a building under construction, special care must be
taken to insure a clean combustion air supply during the construction process.
Airborne particulates such as from drywall dust and lrom fiberglass insulation
can clog the burner ports and cause incomplete combustion and sooting.
Where required by the authority having jurisdiction, the installation must con-
form to American Society of Mechanical Engineers Safety Code for Control_
and Salety Devices for Automatically Fired Boilers, No. CSD-1.
The installation must conform to the requirements ol the authority having
jurisdiction or, in the absence of such requirements, to the National Fuel Gas
Code, ANSI Z223.1-1atest revision.
Installers - Follow local regulations with respect to installation of CO
detectors. Follow maintenance recommendations in this instruction
manual.
Tecbniciens - Veuillez vous conformer d la reglementation en vigueur
coneemant I" installation des defecteurs d'oxyde de carbone. Suivre les
consignes d'entretien figurant dans le manuel dinstrudion cijoinL
I KEEP BOILER AREA CLEAN AND FREE FROM COMBUSTIBLE MATERIALS,
GASOLINE AND OTHER FLAMMABLE VAPORS AND LIQUIDS
1. Selecl level location as centralized with piping system, and as near chim-
ney, as possible.
2. Place crated boiler at selected location, remove crate by pulling crate
sides from top and bottom boards. Combustible floors: When boiler is to
be installed on a combustible floor, a Special Base Plate must be used -
146-14-031 (2-6 Section) or 146-14-032 (7-9 Section). This boiler must
not be installed on carpeting.
3. Boiler is to be level. Metal shims may be used under base legs for final
leveling.
4. Additional clearances for service may exceed clearances for fire protec-
lion. Always comply with lhe minimum fire prolection clearances shown
on the boiler. An !8 inch clearance should be maintained on any side
where passage is required to access another side for cleaning, servicing,
inspection or replacement of any part that may need attention.
Figure 2 shows minimum clearances to combustible construction.
Rooms that are large in comparison with the size of the boiler are defined
as rooms having a volume equal to or greater than 16 times the volume
ol the boiler. Where the actual ceiling height ol a room is greater that 8',
lhe volume ol a room shall be bgured on the basis ota ceiling height of
8' Determination of room size should be based on the total volume of all
gas fired equipment inslalled in the room. Consult section 6.3.1 of the
National Fuel Gas Code lot further inlormatfon, including.approved
methods [or reducing clearances in large rooms
5 Equipment shat! be installed in a location in which the taciblies for yen
tilation permit satistaclory cembushen of gas, proper venbng, and main
tenance o! ambient lempe_alure at safe limits under normal condibons oi
use £qulpment shal! be located so as not to interfere wdh proper circu-
lation o[ air When normal inlfltrabon does not provide the necessary air,
outside ai_ shall be introduced (See Page 4 - Fresh Air for
Combusbon")
6 Advise owner Io keep air passages free of obstrucbons. VenblaPng and
combusbon air musl enter boiler room withoul reskictions
7. The boiler shall be installed such that the automatic gas ignition system
components are protected from water (dripping, spraying, rain, etc.) dur-
ing appliance operation and service (condensate trap, control replace-
ment, etc.).
FIG, 2 - MINIMUM
Alcove, or Room not Large
in Comparison with Boiler
3-5 SECT.
TOP
REAR
RIGHT SIDE
LEFT SIDE
FRONT
FLUE/VENT
CONNECTOR
NEAR BOILER
PIPING
BOILER
BOILER SIZE
VOLUME
(Cu.Ft.)
3 SECT.
4 SECT.
5 SECT.
6 SECT.
7 SECT.
8 SECT.
9 SECT.
FOR ROOM WITH SINGLE BOILER ONLY
THIS UNIT MUST BE SET ON A CONCRETE OR OTHER
NON-COMBUSTIBLE MATERIAL BASE OR FLOOR.
CLEARANCE DTMENSIONS
6-9 SECT.
6"
6"
6"
6"
18"
6 tl
i u
5.4
7.0
8.5
10.1
11.7
13.2
14.8
6"
6"
24"
24"
18"
rq
1" 1"
MINIMUM ROOM VOLUME
REQUIRED TO BE LARGE
ROOM (Cu. Ft.) _
Room Large
Comparison
With B6iier
3-9 SECT.
6"
6"
6"
6"
18"
6 t,
86.6
111.6
136.6
161.7
186.7
211.7
236,7
I Provision for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of
the National Fuel Gas Code, ANSI Z223.1-1atest revision, or applicable provisions of the local building codes.
WARNING
Be sure to provide enough fresh air for combustion.
Enough air insures proper combustion and assures that
no hazard will develop due to the lack of oxygen.
You must provide for enough fresh air to assure proper combustion. The fire
in the boiler uses oxygen. It must have a continuous supply. The air in a
house contains only enough oxygen to supply lhe burner for a short time.
Outside air must enter the house to replace that used by the burner. Study
following examples 1 and 2 to determine your fresh air requirements.
EXAMPLE 1: Boiler Located in Unconfined Space
An unconfined space is defined as a space whose volume is not less than
50 cubic feel per 1,000 Blu per hour of the lotal input rating of all appliances
installed in that space.
If your boiler is in an open area (unpartitioued basement) in a conventional
house, the air that leaks through the cracks around doors and windows will
usually be adequate to provide air for combustion. The doors should not fit
tightly. Do not caulk the cracks around the windows.
Equipment located in buildings of unusually tight construction shall be pro-
vided with air for combustion, ventilation, and dilution ol flue gases using
the methods described in example 2B or shall be specially engineered. The
authority having jurisdiction must approve specially engineered installa-
tions.
EXAMPLE 2: Boiler Located in Confined Space
/L All Air from Inside the Building: The confined space shall be pro-
vided with two permanent openings communicating directly with an addi-
tional room(s) of sufficient volume so that the combined volume of all
spaces meets the criteria for an unconfined space. The total input of all
gas :utilization equipment installed in the combined space shall be con-
sidered in making this determination. Each opening shall have a mini-
mum free area of one square inch per 1,000 Btu per hour ol the total input
rating of all gas utilization equipment in the confined space, but not less
that 100 square inches. One opening shall be within 12 inches of the top
and one within 12 inches of the bottom of the enclosure. The minimum
dimension of air openings shall nol be less than 3 inches.
B. All Air from Outdoors: The confined space shall communicate with the
outdoors in accordance with methods 1 or 2. The minimum dimension of
air openings shall not be less than 3 in. Where ducts are used, they shall
be of the same cross-sectional area as the free area of the openings to
which they connect.
1. Two permanent openings, one commencing within 12 inches of the
top, and one commencing within 12 inches of the boltom, ol the enclo-
sure shall be provided. The openings shall communicate directly, or by
the ducts, with the outdoors or spaces (crawl or attic) thai freely com-
municate with the ouldoors.
a) Where directly communicating with the outdoors or where commu-
nicating to the outdoors through vertical ducts, each opening shag
have a minimum tree area of 1 sq. in. per 4000 Btu per hour of total
input rating of all equipment in the enclosure. (See Figure 3A.)
b) Where communicating with the outdoors through horizontal ducts,
each opening shal! have a minimum free area of 1 sq. in. per 2000
Blu per hour of total input rating of all equipment in the enclosure.
(See Figure 3B.)
2. One permanent opening commencing with 12 inches of the lop of the
enclosure, shall be permitted where the equipment has clearance of at
NOTE
If you use a fireplace or a kitchen or bathroom exhaust
fan, you should install an outside air intake. These
devices will rob the boiler and water heater of combus-
tion air.
least 1 inch from the sides and back and 6 inches lrom Ihe fronl of the
appliance. The opening shall directly communicate with Ihe outdoors
or shall communicate through a vertical or horizonlal duct to the oub
doors or spaces (crawl or attic) that freely communicate with the out-
doors, and shall have a minimum free area of:
a) 1 sq. inch per 3000 Btu per hour ol the Iolal input of aft equipment
located in lhe enclosure (See Figure 4), and
b) Not less than the sum of the areas of all venl connectors in the con-
fined space.
Figure 3A - FRESH AIR DUCT CAPACITIES (Btuh) i
1 Square Inch per 4,000 Btuh
100% Free 75% Free
Area Area
Fresh Air
Duct Size
3"x 12"
8" x 8"
8" X 12"
81/2" X 16"
Figure
I 3B - FRESH AIR DUCT CAPACITIES (Btuh) I
1/4" Wire Metal
Mesh Louvers
144,000 108,000
256,000 192,000
384,000 288,000
512,000 384,000
25% Free
Area
Wood
Louvers
36,000
64,000
96,000
128.000
1 Square Inch per 2,000 Btuh
100% Free 75% Free
Area Area
Fresh Air
Duct Size
3" x 12"
! 8" x 8"
8"x 12"
81/2" x 16"
Figure
I FRESH AIR DUCT CAPACITIES (Btuh) i
4
V4" Wire Metal
Mesh Louvers
72,000 54,000
128,000 96,000
192,000 144,000
256,000 192,000
25% Free
Area
Wood
Louvers
18,000
32,000
48,000
64,000
1 Square Inch per 3,000 Bruh
100% Free 75% Free 25% Free
Area Area Area
Fresh Air V,¢' Wire Metal Wood
Duct Size Mesh Louvers Louvers
3" x 12" 108,000 81,000 27,000
8" x 8" 192,000 144,000 48,000
8" x 12" 288,000 216,000 72,000
8V2" x 18" 384,000 288,000 96,000
I
5
1. Place boiler in the selecled Iocalion (as near chimney as possible.) Your
boiler is shipped assembled. You need only Io insfall the Relief Valve and
a drain line to carry any waler or steam Io a drain.
2. Install Reliel Valve into the 3/,,- pipe on the top ol Ihe boiler. See Figure 5.
Use ¾" Pipe and an elbow (nol furnished) to carry the waler or steam to
a nearby drain. Do not connect directly to a drain bul leave an air gap. No
shutoll ol any description shall be placed between the safdy rebel valve
and the boiler, or on discharge pipes between such safety valves and the
atmosphere. Installation ol the safety reliel valve shall conform to the
requirements of the ANSI/ASME Boiler and Pressure Vessel Code,
Seclion IV. The manulacturer is not responsible for any water damage.
Install Drain Valve in lower left side of boiler as marked.
3. Connect Supply and Return Lines to boiler. The conneclions may require
certain additional filtings and parts, as shown on diagram (Figs. 5 and 6).
4. This boiler is equipped wilh 11/4" supply and return connections on both
the left and right sides ol the boiler.
In connecting the cold water supply to the waler inlel valve, make sure that
a clean waler supply is available. When the water supply is from a weft or
pump, a sand strainer should be installed at the pump.
A hot waler boiler installed above radiation level must be equipped wilh a
low water cutoff device. A periodic inspection is necessary, as is flushing of
float type devices, per manufacturers specific instruction.
FOR USE WITH COOUNG UNITS
A. This boiler, when used in connection with chilled water systems, must be
installed so that the chilled water is piped in parallel with the heating
boiler. Appropriate valves must be used 1o prevenl the chilled water from
entering the heating boiler (Fig. 6).
B. When this boiler is connected to heating coils located in air handling
units where they may be exposed to refrigerated air circulation, the pip-
ing syslem shall be equipped with flow control valves or other automaf-
ic means to prevenl gravgy circulation of the boiler waler during the cool-
ing cycle.
LOW DESIGN WATER TEMPERATURE SYSTEMS
(BELOW 140 ° )
If Ihe boiler is to be used in a heating sysfem where design water lempera-
lures below 140 ° F are desired (e.g. radianl floor healing), a 3-way or 4-way
mixing valve or suitable alternative is required to prevent low femperature
return water from enlering the boiler. Follow Ihe mixing valve manufacturer's
installation instructions.
The minimum design return water Lemperature Io the boiler to prevenl con-
densation in the boiler and venting is 120 ° E The minimum high limil set-
ting is 140 ° F.
THE ISOLATION BALL VALVES CONTAIN TEFLON
SEATS AND SEALS. OVERHEATING THIS VALVE
I CAUTION
MAY CAUSE PREMATURE FAILURE.
COt.o WATE_ LNLET.
TO SYSTEM
VALVES A & B
OPEN FOR HEATING;
CLOSE FOR COOLING
VALVES C & O
CLOSE FOR HEATING:
OPEN FOR COOLING
c d
WAFER
CHILLER
For boilers for connection to gas vents or chimneys, vent Installations shall be
in accordance with Part 7, Venting of Equipment, of the National Fue| Gas Code,
ANSI Z223.1-1atest revision and applicable provisions of the local building codes.
CHECK YOUR CHIMNEY
This is a very imporfant part of your heating system It must be clean,
the right size, properly constructed and in GOOD CONDITION No boiler
can lunction properly with a bad chimney. Fig. 7 gives typical chimney
sizes. Fig. 8 gives you an idea how a boiler might be vented to a chimney
Nofe tha_ the height (HT) is measured from the vent pipe to the lop.
CHIMNEY SIZING
Chimney sizing, and all other aspects of the vent installation must be
in accordance with Part 7 of the National Fuel Gas Code, ANSI Z223.1
- lalesl revision, and applicable provisions of the local building codes.
In Canada, follow CSA B149.1 and B149.2, Installabon Codes for
Gas Burning Appliances and Equipment.
6
CONNECTING THE VENT DAMPER
AND VENT CONNECTOR
Refer to Fig. 1 flue diagram for the size and location of the
vent (flue opening). Use a 28 gauge (minimum) galvanized
pipe to connect to the chimney
IMPORTANT - The damper blade on the furnished vent
damper has a !/2 square inch hole (approximately 3/4" diame-
ter). On boilers equipped with standing pilot, the hole must
be left open. On boilers equipped with intermittent ignition,
the hole should be plugged by using the plug supplied with
the vent damper.
1. Position furnished vent damper on top of flue outlet collar.
Fasten damper securely to flue outlet collar with sheet
metal screws. Make sure damper blade has clearance
to operate inside of diverter.
On 2 section boilers equipped with vent damper, the
supplied 4-inch vent damper is equipped with a 3- to
4-inch adapter so that the 4-inch vent damper may be
installed on the boiler's 3-inch flue outlet collar. Fasten
all fittings securely
As An Option
The damper may be installed in any horizontal or vertical
position, closer to the flue outlet collar preferred. Follow
the diagrams - Figures 9, 10 and 11.
2. Install the vent damper to service only the single boiler
for which it is intended. The damper position indicator
shall be in a visible location following installation. Locate
the damper so that it is accessible for servicing.
3. The damper must be in the open position when appliance
main burners are operating.
4. The boiler is equipped with a factory wired harness that
plugs into the vent damper.
5. Vent pipe must be same size as the flue outlet collar,
except 2 section boilers with vent damper as noted above.
6. Slope pipe up from boiler to chimney not less than V4"
per foot.
7. Run pipe as directly as possible with as few elbows as
possible.
8. Do not connect to fireplace flue.
9. End of vent pipe must be flush with inside face of chimney
flue. Use a sealed-in thimble for the chimney connection.
10. Horizontal run should not be longer than 3/4 the chimney
height (HT) (Fig. 8)
The sections of vent pipe should be fastened with sheet metal
screws to make the piping rigid. Horizontal portions of the
vent system must be supported to prevent sagging. Use
stovepipe wires every 5' to support the pipe from above.
If the vent pipe must go through a crawl space, double wall
vent pipe should be used. Where vent pipe passes through
a combustible wall or partition, use a ventilated metal thimble.
_he thimble should be 4 inches larger in diameter than the
vent pipe
Boiler Input
Btuh
Up to 100,000
Up to 155,000
Up to 230,000
Up to 350,000
"HT - top of thimble to top of flue. See F_g 8.
For boiler input refer to table, page 2
For intormaliOn only - no{ meant to imply minimum s_zes
10-15 Ft.
6x6
6x7
7x8
9x9
FLUE AREA IN INCHES
"HT
"HT.
15-25 Ft.
6x5
6x6
7x7
8x9
"HT
25 Ft Up
5×5
6×5
6×7
8×8
MINIMUM VENT PIPE CLEARANCE
Wood and other combustible materials must not be closer
than 6" from any surface of single wall metal vent pipe. Listed
Type B vent pipe or other listed venting systems shall be
installed in accordance with their listing.
REMOVING EXISTING BOILER FROM
COMMON VENTING SYSTEM
When an existing boiler is removed from a common venting
system, the common venting system is likely to be too large
for proper venting of the appliances remaining connected
to it.
At the time of removal of an existing boiler, the following
steps shall be followed with each appliance remaining
connected to the common venting system placed in operation,
while the other appliances remaining connected to the
common venting system are not in operation.
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch and determine there is no blockage or
restriction, leakage, corrosion and other deficiencies which
could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows
and all doors between the space in which the appliances
remaining connected to the common venting system are
located and other spaces of the building. Turn on clothes
dryers and any appliance not connected to the common
venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate at
maximum speed. Do not operate a summer exhaust fan
Close fireplace dampers
4. Place in operation the appliance being inspected. Follow
the lighting instructions Adjust thermostat so appliance
will operate continuously.
5 Test for spillage at the draft hood relief opening after 5
minutes of main burner operation. Use the flame of a match
or candle, or smoke from a cigarette, cigar or pipe
6. After it has been determined that each appliance remain-
ing connected to the common venting system properly
vents when tested as outlined above, return doors,
windows, exhaust fans, fireplace dampers and any other
gas-burning appliance to their previous conditions of use.
7 Any _mproper operation of the common venting system
should be corrected so the installation conforms with the
National Fuel Gas Code, ANSI Z223.1 -latest revision. When
res_ztng any portion of the common venting system, the
common venting system should be resized to approach
the minimum size as determined using the appropriate
tables in Part 11 in the National Fue! Gas Code, ANSI
Z2231-latest revision
For boilers for connection to gas vents or chimneys,
vent installations shall be in accordance with Part 7,
Venting of Equipment, of the National Fuel Gas Code,
ANSI Z223.1-1atest revision and applicable provisions
of the local building codes.
Vent connectors serving appliances vented by natural
draft shall not be connected into any portion of
mechanical draft systems operating under positive
pressure.
ROOF
RIDGE
3/4 HT MAXIMUM
HT
'MUST SLOPE UP
AT LEAST 1/4 INCH
PER FOOT OF
HORIZONTAL RUN
HORIZONTAL INSTALLATION
FLOW _ NO
TO FURNACE VENT TO CHIMNEY
OR BOILER DAMPER INSTALL VENT DAMPER WITH
ACTUATOR TO SIDES OF
VENT ONLY. DO NOT MOUNT
ABOVE OR BELOW VENT
VERTICAL INSTALLATION
TO CHIMNEY
FLOW VENT
TO FURNACE_ iNSTALLEDIN ANY POSITION
OR BOILER
DAMPER
ACTUATOR MAY BE
U
C_N: IX) NOT INSTALL
THE VENT DAMPER
WITHIN 6 in. (152 mm) OF
COMBUS33BLE MATERIAL
3HIMNEY
BOILER WATER HEATER
TYPICAL INSTALLA'nON FOR VENT DAMPER
NOTE CAUTION AND FOOTNOTES
1 Install the vent damper to service only the single ap_iance for
which it is intended, if improperly installed, a hazardous cond_on,
such as an explosion or carbon monoxide pe,,sening, could result.
2_ Do not install the vent damper on vent pipe curve.
3 Do not run wires near high temperature surfaces. Use staed_ff
brackets Jf necessary
8
For safe, efficient operation, the vent damper and all flue
product carrying areas of the appliance must be checked
annually by you, with particular attention given to deterioration
from corrosion or other sources. If you see corrosion or other
deterioration, contact your heating contractor tor repairs.
Check vent damper operation as follows:
1. When the boiler is off, check that the vent damper position
indicator points to the closed position, Fig. 11.
2. Turn the thermostat or controller up to call for heat and
check that the vent damper indicator points to the open
position, Fig. 11.
3. Turn the thermostat or controller down again and check
that the vent damper position indicator returns to the closed
position.
MANUAL OPERATION OF THE VENT DAMPER
The Effikal vent damper may be placed in the open position
to permit burner operation by using the "HOLD DAMPER
OPEN" switch, located on the damper controller. The
thermostat will control the burner firing as before, while the
damper will remain open. DO NOT turn damper open manu-
ally or motor damage will result. Set switch to "AUTOMATIC
OPERATION" to close vent damper during burner off cycle.
For further information, and for a vent damper !roubleshooting
guide, refer to the Effikal manual that was packaged with
the vent damper.
The vent damper must be inspected at least once a
year by a trained, experienced service technician, The
name of the person who originally installed your vent
damper is shown on the installation label,
i6 °
iI 010
DAMPER CLOSED OAMPER OPEN
SHOWING OPEN AND CLOSED POSmON
° 1
CHECK GASSUPP_
The gas pipe to your boiler must be the correct size for the
length of the run and for the total Btu per hour input of all
gas utilization equipment connected to it. See Fig. 12 for
the proper size. Be sure your gas line complies with local
codes and gas company requirements.
The boiler and its individual shutoff valve must be
disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess
of I/2 psig (3.5 kPa).
The boiler must be isolated from the gas supply piping system
by closing its individual manual shutoff valve during any
pressure testing of the gas supply piping system at test
pressures equal to or less than 1/z psig (3.5 kPa).
CONNECTING THE GAS PIPING
Refer to Fig. 13 for the general layout at the boiler. It shows
the basic fittings you will need. The gas line enters the boiler
from the right side.
The following rules apply:
1. Use only those piping materials and joining methods
listed as acceptable by the authority having jurisdiction,
or in the absence of such requirements, by the National
Fuel Gas Code, ANSI Z223.1-1atest revision.
2. Use pipe joint compound suitable for LP gas on male
threads only
3. Use ground joint unions.
4. Install a sediment trap upstream of gas controls.
5. Use two pLpe wrenches when making the connection
to the gas valve to keep it from turning.
6. Install a manual shut-off valve in vertical pipe about 5
feet above floor.
7 Tighten all joints securely
NATURAL GAS
Length of Includes Fittings
Pipe - Ft.
20 92,000 190,000 350,000 625,000
40 63,000 130,000 245,000 445,000
60 50,000 105,000 195,000 365,000
The length of pipe of tubing should be measured from the gas meter
Pipe Capacity - BTU per Hour Input
V2" 3/4" 1" 11/4"
CHECKING THE GAS PIPING
Upon completion of piping, check immediately for gas leaks
Open the manual shut-off valve. Test for leaks by applying
soap suds (or a liquid detergent) to each joint. Bubbles
forming indicate a leak CORRECT EVEN THE SMALLEST
LEAK AT ONCE
WARNING
Never use a match or open flame to test for leaks.
10
WARNING
TURN OFF ELECTRICAL POWER AT FUSE BOX BEFORE MAKING ANY LINE VOLTAGE CONNECTIONS.
FOLLOW LOCAL ELECTRICAL CODES.
II I
All electrical work must conform to local codes as well as the National Electrical Code, ANSI/NFPA-70, latest revision. In
Canada, electrical wiring shall comply with the Canadian Electrical Codes, CSA-C22.1 and .2.
ELECTRIC POWER SUPPLY
Prior to making any line voltage connections, service switch at boiler should be in the offpnsition and the power turned offat
the fuse box.
Run a separate 120 volt circuit from a separate over current protection device in the electrical service entrance panel. This
should be a 15 ampere circuit. A ser+ice switch has been provided and should be mounted to the Junction box located on the
exterior boiler jacket. See Fig. 13-1 for diagram showing power supply connection points.
The boiler, when installed, must be eleotrically grounded in accordance with the requirements of the authority having
jurisdiction or, in the absence of such requirements, with the National Electrical Code, ANSI/NFPA-70, latest revision. In
Canada, electrical wiring shall comply with the Canadian Electrical Codes, CSA-C22.1 and .2.
Run a 14 gauge or heavier copper wire from the boiler to a grounded connection in the service panel or a properly driven and
electrically grounded ground rod.
INSTALL YOUR THERMOSTAT
The thermostat location has an important effect on the operation of your boiler system. BE SURE TO FOLLOW THE
INSTRUCTIONS INCLUDED WITH YOUR THERMOSTAT.
Locate the thermostat about five feet above the floor on an inside wall. It may be mounted directly on the wall or on a
vertical mounted outlet box. It should be sensing average room temperature. Avoid the Following:
DEAD SPOTS:
Behind doors
Comers and alcoves
Set heat anticipator at 0.1 amps. Connect 24 volt thermostat leads to the two(2) yellow wires located in service switch
junction box, located on outer jacket of boiler. See Fig.13-1 for service switch junction box and thermostat field wiring
connections.
VENT DAMPER WIRING
The boiler is equipped with a factory wired harness with 4 pin molex plug, that plugs into a 4 pin molex receptacle inside the
vent damper operator. The vent damper must be connected for the boiler to operate. Wiring diagrams follow for the various
different models.
COLD SPOTS:
Concealed pipes or ducts
Stairwells - drafts
Unheated rooms on
other side of wall
HOT SPOTS:
Concealed pipes Lamps
Fireplace Direct sunlight
TV sets Kitchens
Radios
CAUTION
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and
dangerous operation. Verify proper operation after servicing.
11