Kenmore Elite 153.331010, Elite 153.331000, Elite 153.331000 HA Use & Care Manual

http://waterheatertimer.org/New-water-heater-ideas.html
Use & Care Guide
Model No.
153.331010 25 U.S. Gal (94.6 Litres) For installation at elevations from 0-3,500 ft. (0-1,067m).
153.331000 HA 25 U.S. Gal (94.6 Litres) For installation at elevations from 3,501 - 6,500 ft. (1,067 - 1,981m).
Kenmore Elite
®
For potable water heating only. Not suitable for space heating. Not for use in mobile homes.
INSTALLER: Affi x these instructions to or near the water heater.
OWNER: Retain these instructions for future reference.
FOR YOUR SAFETY: An odorant is added to the gas used by this water heater.
IMPORTANT: For installations above 3,500 feet above sea level, verify the proper high altitude water heater model is installed or the proper circuit board has been ordered and installed. See High Altitude section of manual for further details.
P/N 320169-001 (0611)
Sears Brands Management Corporation, Hoffman Estates, IL 60179 U.S.A.
www.kenmore.com www.sears.com
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater. Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and
others of a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning of each safety message is understood by you and others who install, use or service this water heater.
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and how to avoid the risk of injury.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure to such substances.
WARNING: This product contains a chemical known to the State of California to cause cancer, birth defects,
or other reproductive harm.
This appliance can cause low-level exposure to some of the substances listed in the act.
IMPORTANT DEFINITIONS
Quali ed Installer or Service Agency: Installation and service of this water heater requires ability equivalent to that of a Qualifi ed Agency (as defi ned by ANSI below) in the fi eld involved. Installation skills such as plumbing, air supply , venting, gas supply, electrical supply are required in addition to electrical testing skills when performing service.
• ANSI Z223.1 2006 Sec. 3.3.83: “Qualifi ed Agency” - “Any individual, fi rm, corporation or company that either in person or through a representative is engaged in and is responsible for (a) the installation, testing or replacement of gas piping or (b) the connection, installation, testing, repair or servicing of appliances and equipment; that is experienced in such work; that is familiar with all precautions required; and that has complied with all the requirements of the authority having jurisdiction.”.
• Gas Supplier: The Natural Gas or Propane Utility or service who supplies gas for utilization by the gas burning appliances within this application. The gas supplier typically has responsibility for the inspection and code approval of gas piping up to and including the Natural Gas meter or Propane storage tank of a building.
2
GENERAL SAFETY
3
GENERAL SAFETY
WARNING
• Before servicing the water heater, make sure the water heater is unplugged from the electrical supply.
• Label all wires prior to disconnection when servicing controls. Wiring error can cause improper and dangerous opera­tion. Verify proper operation after servicing.
• Failure to do this could result in death, serious bodily injury, or property damage.
WARNING
Breathing Hazard - Carbon Monoxide Gas
• Install vent system In accordance with codes.
• Do not operate water heater if flood damaged.
• Standard model is fitted for operation at altitudes up to 3,500 ft. (1,067m). High Altitude model is suitable for altitudes between 3,501 to 6,500 ft. (1,067m and 1,981m). Specific accessory kits are required for installations above 6,500 ft. (1,981m).
• Do not operate if soot buildup is present.
• Do not obstruct water heater air intake with insulating jacket.
• Do not place chemical vapor emitting products near water heater.
• Gas and carbon monoxide detectors are available.
• No vent damper installation is compatible with this power vented water heater.
• Do not elevate the condensate hose on the bottom of the water heater above the bracket attached to the side of the unit. This must be true for the entire length of the hose including the exit into an appropriate drain.
• Condensate lines must be free and clear of debris and must not allow back flow through the hose. The condensate lines must be able to flow freely to an appropriate drain.
• Do not allow condensate lines to become crimped closed.
• Analyze the entire vent system to make sure that condensate will not become trapped in a section of vent pipe and therefore reduce the open cross sectional area of the vent.
Breathing carbon monoxide can cause brain damage or death.
Always read and understand instruction manual.
DANGER
FLAMMBLE
Vapors from flammable liquids may explode and catch fire causing death or severe burns.
Do not use or store flammable products such as gasoline, solvents or adhe­sives in the same room or area near the water heater.
Keep flammable products:
1. far away from heater,
2. in approved containers,
3. tightly closed and
4. out of children's reach. Installation: Do not install the water heater where flammable
products will be stored or used. It must be installed a minimum of 18 in. (45cm) above the floor if installed in a residential garage. This will reduce, but not eliminate, the risk of flammable vapors bein g i g n ited b y t h e m a i n b u r n e r o r s p a r k igniter.
Flammable Vapors
Water heater has a main burner and spark generator. The spark generator:
1. can be triggered at any time and
2. the spark will ignite flammable vapors.
Vapors:
1. cannot be seen,
2. are heavier than air,
3. go a long way on the floor and
4. can be carried from other rooms to the the electodes by air currents.
4
TABLE OF CONTENTS
SAFE INSTALLATION, USE AND SERVICE 2 GENERAL SAFETY 3 PRODUCT WARRANTY 6 INTRODUCTION 8
Get To Know Your Water Heater - Gas Models. . . . . 9
INSTALLATION CONSIDERATIONS 10
Rough In Dimensions . . . . . . . . . . . . . . . . . . . . . . . 10
Water Piping - Mixing Valve Usage. . . . . . . . . . . . . 12
Facts To Consider About Location. . . . . . . . . . . . . . 13
Handle Installation. . . . . . . . . . . . . . . . . . . . . . . . . . 14
Earthquake Zones. . . . . . . . . . . . . . . . . . . . . . . . . . 15
Combustion Air And Ventilation. . . . . . . . . . . . . . . . 17
Appliances In Unconfi ned Spaces . . . . . . . . . . . . . 17
Appliances In Confi ned Spaces . . . . . . . . . . . . . . . 17
Chemical Vapor Corrosion . . . . . . . . . . . . . . . . . . . 19
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Closed Water Systems . . . . . . . . . . . . . . . . . . . . . . 19
Thermal Expansion. . . . . . . . . . . . . . . . . . . . . . . . . 19
Hard Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Temperature-pressure Relief Valve. . . . . . . . . . . . . 20
Gas Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Sediment Traps. . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Gas Line Purging . . . . . . . . . . . . . . . . . . . . . . . . . . 23
High Altitude Installations . . . . . . . . . . . . . . . . . . . . 23
Flooding/freezing. . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Filling The Water Heater. . . . . . . . . . . . . . . . . . . . . 23
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Vent Pipe Techniques . . . . . . . . . . . . . . . . . . . . . . . 24
Planning The Vent System . . . . . . . . . . . . . . . . . . . 25
Installation Of Vent System. . . . . . . . . . . . . . . . . . . 26
Vent Terminal Installation, Sidewall. . . . . . . . . . . . . 26
Installation Of Vent System, Sidewall . . . . . . . . . . . 27
Installation Of Vertical Vent System . . . . . . . . . . . . 28
Vent Pipe Preparation. . . . . . . . . . . . . . . . . . . . . . . 28
Connection To Vent Pipe. . . . . . . . . . . . . . . . . . . . . 31
Condensate. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
US. Power Vent. . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Electrical Connections. . . . . . . . . . . . . . . . . . . . . . . 33
Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
OPERATING INSTRUCTIONS 34
Display Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Lighting Instructions . . . . . . . . . . . . . . . . . . . . . . . . 37
Temperature Regulation . . . . . . . . . . . . . . . . . . . . . 38
Unique Hybrid Features . . . . . . . . . . . . . . . . . . . . . 39
Temperature Regulation . . . . . . . . . . . . . . . . . . . . . 41
Constant Output Temperature Control . . . . . . . . . . 42
Start Up Conditions. . . . . . . . . . . . . . . . . . . . . . . . . 42
Operational Conditions . . . . . . . . . . . . . . . . . . . . . . 42
MAINTENANCE 43
Housekeeping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Venting System Inspection . . . . . . . . . . . . . . . . . . . 43
Flood Damage. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Anode Rod Inspection. . . . . . . . . . . . . . . . . . . . . . . 43
Anode Rod Replacement . . . . . . . . . . . . . . . . . . . . 44
Temperature-pressure Relief Valve Operation . . . . 44
Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Snow Accumulation. . . . . . . . . . . . . . . . . . . . . . . . . 45
Cleaning The Inlet Water Filter . . . . . . . . . . . . . . . . 45
Cleaning The Heat Engine . . . . . . . . . . . . . . . . . . . 45
Flushing The Heat Exchanger (Lime Build-up). . . . 45
Draining The Tank . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Fault Indication And Error Codes . . . . . . . . . . . . . . 46
Diagnostic Display. . . . . . . . . . . . . . . . . . . . . . . . . . 47
TROUBLESHOOTING 52
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Leakage Checkpoints . . . . . . . . . . . . . . . . . . . . . . . 54
Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . 55
Parts Identifi cation. . . . . . . . . . . . . . . . . . . . . . . . . . 57
Notes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Model Number _________________________________________ Serial Number __________________________________________ Installation Information: Date Installed __________________________________________ Company’s Name _______________________________________ Street or P.O. Box _______________________________________ City, State, and Zip Code _________________________________ Phone Number ____________ Plumber’s Name _______________
5
Fill out and keep with water heater.
IMPORTANT INFORMATION
PRODUCT WARRANTY
Kenmore Elite® Hybrid Gas Water Heater Warranty
For six years from the date of purchase, if this water heater is installed and operated in a single-family home in accordance with the owner’s manual instructions and all local applicable plumbing codes, Sears will:
1. Supply free water heater parts for those that are defective in material or workmanship.
2. Supply a free water heater for one that develops a tank leak. See notes below also. For the second through sixth year from the purchase date, you must pay the labor cost for installation of parts or water heater.
For commercial, institutional, industrial or residential use by two or more families, the above limited warranty is only for one year.
If governmental regulations prohibit Sears from furnishing a comparable model replacement water heater under this warranty, Sears will furnish a new water heater of comparable output as permitted by such governmental regulations; however, the Owner will be charged for the additional cost associated with the changes made to comply with such governmental regulations.
Replacements furnished under this warranty do not carry a new warranty and are only covered by the unexpired portion of the original warranty.
CONDITIONS AND EXCEPTIONS
This warranty shall apply only when the water heater is installed and operated in accordance with 1) all local fi re codes and plumbing codes, ordinances, and regulations. 2) the printed instructions provided with it, 3) good industry practices, and 4) proper safety practices such as but not limited to a properly sized drain pan if installed in an area where leakage from connections of the tank would result in damage to the area adjacent to the heater. In addition, a new temperature and pressure relief valve, certifi ed by the Canadian Standards Association must have been properly installed and piped to the nearest drain.
This warranty shall apply only when the heater is:
not subjected to excessive water pressure fl uctuations and not subject to an operating pressure greater than 150 P.S.I.
fi lled with potable water, free to circulate at all times and with the tank free of damaging water sediment or scale deposits.
used in a non-corrosive and non-contaminated atmosphere.
sized in accordance with proper sizing techniques for residential water heaters.
bearing a rating plate which has not been altered, defaced or removed.
used in an open system or in a closed system with a properly sized and installed thermal expansion tank.
fi red at the factory rated input using the fuel stated on the face of the rating plate.
operated with the inner and outer doors in place.
maintained in accordance with the instructions printed in the manual included with the heater.
used in a water supply with less than 12 grains per gallon (200 mg/L) of hardness, is not acidic or otherwise impure.
Problems resulting from scale formation are not covered by the warranty. Any accident to the water heater or any part thereof (including freezing, fi re, fl oods, or lightning), any misuse, abuse, or alteration of it, any
operation of it in a modifi ed form, or any attempt to repair tank leaks or parts, will void this warranty.
For the fi rst year from the date of purchase, Sears will, free of charge, supply and install new water heater parts for defective ones or a new water heater for one that develops a leak.
To obtain warranty service, call 1-800-4-MY-HOME This warranty applies only while this product is in use in the United States. This warranty gives you specifi c legal rights, and you may have other rights which vary from state to state.
SEARS BRANDS MANAGEMENT CORPORATION, Hoffman Estates, IL 60179
The price of your water heater does not include a free checkup service call. On water heater installations arranged by Sears, Sears
warrants the installation. A charge will be made on service calls due to poor or incomplete installation. These include: a. Adjusting thermostat b. Condensation c. Leaks in pipes or fi ttings
6
1-YEAR EXCLUSIVE KENMORE LABOR WARRANTY
WARRANTY SERVICE
®
(1-800-469-4663).
Master Protection Agreements
Congratulations on making a smart purchase. Your new Kenmore product is designed and manufactured for years of dependable operation. But like all products, it may require preventive maintenance or repair from time to time. That’s when having a Master Protection Agreement can save you money and aggravation.
The Master Protection Agreement also helps extend the life of your new product. Here’s what the Agreement* includes:
Parts and labor needed to help keep products operating properly
under normal use, not just defects. Our coverage goes well beyond the product warranty. No deductibles, no functional
failure excluded from coverage - real protection.
Expert service by a force of more than 10,000 authorized Sears service technicians, which means someone you can trust will be working on your product.
Unlimited service calls and nationwide service, as often as you want us, whenever you want us.
“No-lemon” guarantee – replacement of your covered product if four or more product failures occur within twelve months.
Product replacement if your covered product can’t be fi xed.
Annual Preventive Maintenance Check at your request – no extra charge.
Fast help by phone - we call it Rapid Resolution - phone support from a Sears representative on all products. Think of us as a “talking owner’s manual.”
Power surge protection against electrical damage due to power uctuations.
®
$250 Food Loss Protection annually for any food spoilage that is the result of mechanical failure of any covered refrigerator or freezer.
Rental reimbursement if repair of your covered product takes longer than promised.
10% discount off the regular price of any non-covered repair service and related installed parts.
Once you purchase the Agreement, a simple phone call is all that it takes for you to schedule service. Y ou can call anytime day or night, or schedule a service appointment online. The Master Protection Agreement is a risk free purchase. If you cancel for any reason during the product warranty period, we will provide a full refund. Or, a prorated refund anytime after the product warranty period expires. Purchase your Master Protection Agreement today!
Some limitations and exclusions apply. For prices and additional information in the U.S.A. call 1-800-827-6655.
* Coverage in Canada varies on some items. For full details, call Sears Canada at 1-800-361-6665.
Sears Installation Service
For Sears professional installation of home appliances, garage door openers, water heaters, and other major home items, in the U.S.A. or Canada call 1-800-4-MY-HOME
®
.
7
INTRODUCTION
Thank You for purchasing this water heater. Properly installed and maintained, it should give you years of trouble free service. Abbreviations Found In This Instruction Manual:
• CSA - Canadian Standards Association
• ANSI - American National Standards Institute
• NFPA - National Fire Protection Association
• ASME - American Society of Mechanical Engineers
• GAMA - Gas Appliance Manufacturer’s Association
• UL - Underwriters Laboratories Inc. This gas-fi red water heater is design certifi ed by CSA International under American National Standard/CSA Standard for Gas Water Heaters ANSI Z21.10.3 • CSA
4.3 (current edition). PREPARING FOR THE INSTALLATION
Read the “General Safety” section, of this manual
1. first and then the entire manual carefully. If you don’t follow the safety rules, the water heater will not operate properly. It could cause DEATH, SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE.
This manual contains instructions for the installation, operation, and maintenance of the gas-fi red water heater. You must read and be aware of the warnings placed throughout the manual. All warnings and all instructions are essential to the proper operation of the water heater and your safety . Since we cannot put everything on the fi rst few pages, READ THE ENTIRE MANUAL BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER HEATER. The installation must conform with these instructions
2. and the local code authority having jurisdiction. In the absence of local codes, the installation must comply with the current editions of the National Fuel
Gas Code, ANSI Z223.1/NFPA 54 and the National Electrical Code, NFP A 70. Documents are available
from:
Canadian Standards Association, 5060 Spectrum Way, Mississauga, Ontario, Canada L4W 5N6
Carefully plan the place where you are going to put
5. the water heater. Correct combustion, vent action, and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and res (see Figures 1 and 3). Examine the location to ensure the water heater complies with the “Facts to Consider About Location” section in this manual. For California installation this water heater must be
6. braced, anchored, or strapped to avoid falling or moving during an earthquake. See instructions for correct installation procedures. Instructions may be obtained from California Offi ce of the State Architect, 1102 Q Street, Suite 5100, Sacramento, CA 95811. Massachusetts Code requires this water heater to be
7. installed in accordance with Massachusetts 248-CMR
2.00: State Plumbing Code and 248-CMR 5.00, See page 11. Complies with SCAQMD rule #1146 and districts
8. having equivalent NOx requirements.
9.
Complies with California’s legislation AB1953 and Vermont’s legislation Act 193 requirement of a weighted average maximum of 0.25% lead.
NFPA documents are also available from: National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02269.
The water heater when installed must be grounded in
3. accordance with the local codes, or in the absence of local codes: the National Electrical Code (NFPA 70). If after reading this manual you have any
4. questions or do not understand any portion of the instructions, call the local gas utility or the manufacturer whose name appears on the rating plate.
8
GET TO KNOW YOUR WATER HEATER - GAS MODELS
A Mixing Valve*** B Hot Water Outlet (Tempered)*** C Pipe Insulation*** D Inlet Water Shutoff Valve*** E Cold Water Inlet*** F Expansion Tank*** G Vent Termination Elbow** H Access Door (Heat Engine) I Earthquake Strap*** J Power Cord* K Main Manual Gas Shutoff Valve*** L Gas Supply*** M Sediment Pocket*** N Condensate Tube O Drain Pan*** P Drain Valve Q Heat Engine Hose - Cold In R Casing Door (Plastic) S Display Enclosure (Plastic) T Heat Engine Hose - Hot Out
U Side Casing (Plastic) V Top Casing Enclosure (Plastic) W Exhaust Elbow Assembly X T&P Relief Valve Y Anode Z Inlet Dip Tube
* CAUTION HARNESS HAS 120 VAC. IN
OPERATION.
** See “Planning the Vent System,” “Installation
of Vent System” and “Condensate” for more information.
*** These items not included.
A
V
U
T
S
C
EDB
F
X
G
H
I
W
J
K
L
Y
M
N
Z
R
9
O
PQ
N
FIGURE 1
INSTALLATION CONSIDERATIONS
ROUGH IN DIMENSIONS
Dimension shown are in inches [cm]
Top View
Left Side View
FIGURE 2
Capacity, Gas and Electrical Characteristics
Model Approx. Capacity Input Gas
U.S. Gals. Litres BTU/hr Max.
153.331010 25 94.6 100,000 Nat. 14.0 (3.49) 5.0 (1.25) 4.2 (1.05) 120/60 2.5
153.331000 HA 25 94.6 100,000 Nat. 14.0 (3.49) 5.0 (1.25) 4.2 (1.05) 120/60 2.5
Minimum gas supply pressure must be maintained under both load and no load (dynamic and static) conditions. Manifold Pressure is preset on the gas valve by the manufacturer; DO NOT ATTEMPT TO ADJUST! Thermal effi ciency is 90%. If the hardness of your water supply is more than of 12 grains per gallon (200 mg/L), if your water supply is acidic or otherwise impure, the water supply must be treated with approved methods.
Minimum Clearance To Combustibles Service Clearance
Top Front Vent Back Sides Floor Front Sides
00000021” (53.3 cm) 12” (30.5 cm) 300
This appliance must be installed in accordance with local codes or, in the absence of local codes, the “National Fuel Gas Code” ANSI Z223.1/NFPA 54. Not for installation in a Manufactured Home (Mobile Home). This water heater is suitable for water (potable) heating only. This water heater is suitable for installation in a closet or alcove.
Type
Gas Supply Pressure Manifold Pressure Electrical Characteristics
in. WC (kPa)
Min.
in. WC (kPa)
in. WC (kPa) Volts/Hz Amperes
Test Pressure
P.S.I.
10
INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS
For all side wall terminated, horizontally vented power vent, gas fueled water heaters installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfi tter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the fl oor level where the gas equipment is to be installed. In addition, the installing plumber or gasfi tter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualifi ed licensed professionals for the installation of hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent fl oor level.
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certifi ed.
SIGNAGE A metal or plastic identifi cation plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT
DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.” INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve
the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a) 1 through 4.
EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the Board; and
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building, or structure used in whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED When the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the fl ue gases, but identifi es “special venting systems,” the following requirements shall be satisfi ed by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
11
WATER PIPING - MIXING VALVE USAGE
TEMPERED
POTABLE WATER
SUGGESTED PIPING
ARRANGEMENT
FOR TOP
CONNECTIONS
SHUT-OFF VALVE
COLD WATER
INLET
THERMAL
EXPANSION
TANK
MIXING
VALVE
(OPTIONAL)
PIPE INSULATION (RECOMMENDED)
TEMPERED POTABLE WATER
TEMPERATURE­PRESSURE RELIEF VALVE
DISCHARGE PIPE (DO NOT CAP OR PLUG)
DRAIN PAN
DRAIN VALVE
FIGURE 3
This appliance has been design certifi ed as complying with ANSI Z21.10.3/CSA 4.3 (latest revision) for water heaters and is considered suitable for: Water (Potable) Heating: All models are considered suitable for water (potable) heating.
The Hybrid water heater is a unique design that combines the technology of both the storage tank and tankless type water heaters. A tankless water heater ensures a fi xed constant outlet water temperature. This is achieved by modulating the water fl ow to ensure that this temperature is maintained. In the Hybrid the water supply is heated as it fl ows through the heat exchanger over the burners similar to the tankless water heaters. The heated water is then stored in the top of the storage tank. The tank outlet water temperature will be within a maximum of 5°F (2.8°C) of the display set-point when the unit ends the call for heat. If required by local codes or if a higher fi xed temperature is required, a mixing valve can be installed as shown on Figure3.
Please note the following: The system should be installed only with piping that is suitable for potable (drinkable) water such as copper,
METAL
TO SUITABLE
DRAIN
CPVC, PEX or polybutylene. DO NOT use PVC water piping. DO NOT use any pumps, valves, or fi ttings that are not compatible with potable water. DO NOT use valves that may cause excessive restriction to water fl ow. Use full fl ow ball or gate valves only. DO NOT use any lead based solder in potable water lines. Use appropriate tin-antimony or other equivalent material. DO NOT tamper with the gas control/thermostat, igniter or temperature and pressure relief valve. Only qualifi ed service technicians should service these components. DO NOT use with piping that has been treated with chromates, boiler seal, or other chemicals. DO NOT add any chemicals to the system piping which will contaminate the potable water supply.
HOT WATER CAN SCALD: Water heaters are intended to produce hot water. Water heated to a temperature which will satisfy space heating, clothes washing, dish washing, and other sanitizing needs can scald and permanently injure you upon contact. Some people are more likely to be permanently injured by hot water than others. These include the elderly, children, and the physically or developmentally disabled. If anyone
6 in.
(15cm)
MAX.
AIR GAP
FLOOR
DRAIN
12
using hot water from this heater fi ts into one of these groups or if there is a local code or state law requiring a certain temperature water at the hot water tap, then you must take special precautions. In addition to using the lowest possible temperature setting that satisfi es your hot water needs, a means such as a Mixing Valve should be used at the hot water taps used by these people or at the water heater (see Figure 3). Mixing valves are available at plumbing supply or hardware stores. Consult a Qualifi ed Installer or Service Agency. Follow the mixing valve manufacturer’s instructions for installation of the valves. Before changing the factory setting on the thermostat, read the “Temperature Regulation” section in this manual.
control of this water heater are polarity sensitive. Ensure the electrical supply is connected correctly in the receptacle box. Failure to connect correctly will prevent the unit from functioning properly.
Installation of the water heater must be accomplished in such a manner that if the tank or any connections should leak, the fl ow will not cause damage to the structure. For this reason, it is not advisable to install the water heater in an attic or upper fl oor. When such locations cannot be avoided, a suitable metal drain pan should be installed under the water heater. Drain pans are available at your local hardware store. Such a drain pan must have a clearance of at least 1.0 in. (2.5cm) greater than any point on the water heater’s outer jacket and must be piped to an adequate drain. The pan must not restrict combustion air fl ow. See Figure 1.
FACTS TO CONSIDER ABOUT LOCATION
Carefully choose an indoor location for the new water heater, because the placement is a very important consideration for the safety of the occupants in the building and for the most economical use of the appliance. This
water heater is not for use in manufactured (mobile) homes or outdoor installation.
Whether replacing an old water heater or putting the water heater in a new location, the following critical points must be observed:
Select a location indoors as close as practical to the
1. vent terminal or location to which the water heater vent piping is going to be connected, and as centralized with the water piping system as possible. A pressure-reducing valve and/or an expansion tank
2. may be required for installations where the water pressure is high. The pressure-reducing valve should be located on the supply to the entire house in order to maintain equal hot and cold water pressure. Selected location must provide adequate clearances
3. for servicing and proper operation of the water heater. Avoid locations that could cause the water heater to
4. freeze from outside air. Selected location must provide access to a properly
5. grounded electrical branch circuit. A dedicated circuit is preferred. Do not use a GFI outlet.
Important: Do not use an extension cord to connect the water heater to an electrical outlet. Important: The electrical controls used inside the gas
Water heater life depends upon water quality, water pressure and the environment in which the water heater is installed. Water heaters are sometimes installed in locations where leakage may result in property damage, even with the use of a drain pan piped to a drain. However, unanticipated damage can be reduced or prevented by a leak detector or water shut-off device used in conjunction with a piped drain pan. These devices are highly recommended and are available from some plumbing supply wholesalers and retailers, and detect and react to leakage in various ways:
• Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater when leakage is detected.
• Sensors mounted in the drain pan that turn off the water supply to the entire building when water is detected in the drain pan.
• Water supply shut-off devices that activate based on the water pressure differential between the cold water and hot water pipes connected to the water heater.
• Devices that will turn off the gas supply to a gas water heater while at the same time shutting off its water supply.
A VOID AREAS WHERE FLAMMABLE LIQUIDS (V APORS) ARE LIKEL Y TO BE PRESENT OR ST ORED (GARAGES, STORAGE AND UTILITY AREAS, ETC.): Flammable liquids (such as gasoline, solvents, propane (LP or butane, etc.) and other substances (such as adhesives, etc.)) emit ammable vapors which can be ignited by a gas water heater’s igniter or main burner. The resulting fl ashback and fi re can cause death or serious burns to anyone in the area. Also, the water heater must be located and/or protected so
13
it is not subject to physical damage by a moving vehicle.
DANGER
HANDLE INSTALLATION
For ease of handling and carrying, plugs are provided in the side of the shroud that can be removed and pipe handles inserted (see Figure 4).
• Remove plastic plugs from shroud side panels.
• Screw a short length of 3/4” NPT pipe into the sides of the water heater.
• Use the handles to move the water heater to the desired location.
• Remove the handles.
• Reinstall the plastic plugs in the shroud side panels.
FLAMMBLE
Vapors from flammable liquids may explode and catch fire causing death or severe burns.
Do not use or store flammable products such as gasoline, solvents or adhe­sives in the same room or area near the water heater.
Keep flammable products:
1. far away from heater,
2. in approved containers,
3. tightly closed and
4. out of children's reach. Installation: Do not install the water heater where flammable
products will be stored or used.
Flammable Vapors
Water heater has a main burner and spark generator. The spark generator:
1. can be triggered at any time and
2. the spark will ignite flammable vapors.
Vapors:
1. cannot be seen,
2. are heavier than air,
3. go a long way on the floor and
4. can be carried from other rooms to the the electodes by air currents.
Handle
FIGURE 4
14
Handle
This water heater must not be installed directly on carpeting. Carpeting must be protected by metal or wood panel beneath the appliance extending beyond the full width and depth of the appliance by at least 3in. (7.6cm) in any direction, or if the appliance is installed in an alcove or closet, the entire fl oor must be covered by the panel. Failure to heed this warning may result in a fi re hazard.
When installing the heater, consideration must be given to proper location. Location selected should be as close to the wall as practicable and as centralized with the water piping system as possible.
FIGURE 5
Minimum clearances between the water heater and combustible construction are 0 in. at the sides and rear, 0 in. (0cm) from the front and 2 in. (5.08cm) from the top (see Figure 5). If clearances stated on the heater differ from these distances, install water heater according to clearances stated on the heater.
Adequate top clearance of 24 in. (61cm) for servicing this appliance, such as changing the anodes etc., should be considered before installation.
Remove the right side panel
Use a screwdriver to remove the screw from the
1. bottom, front of the right side panel. Remove the three screws from the right side panel
2. towards the rear of the unit. Remove the screw from the top of the unit.
3. Push the panel back and lift out.
4.
Remove the left side panel
Use a screwdriver to remove the screw from the
1. bottom, front of the left side panel. Remove the three screws from the left side panel
2. towards the rear of the unit. Remove the screw from the top of the unit.
3. Push the panel back and lift out.
4.
Top Casing (Front)
Access To
Door Pins Door Lock
Screws
A minimum front clearance of 20 in. (51cm) and 10 in. (26cm) of side clearance must be allowed for access to replaceable parts.
EARTHQUAKE ZONES
In Earthquake Zones the water heater must be braced, anchored, or strapped to avoid moving during an earthquake. Contact local utilities for code requirements in your area. Follow the manufacturer’s instructions for installing the braces. Be sure to wear protective goggles and gloves when handling any kind of sheet metal product.
Tabs have been provided on each side of the rear portion of the shroud. The top and bottom of each tab must be cut and gently bent “inwards” thus allowing the straps to exit the shroud (see Figure 9).
In order to access the tabs and install the earthquake straps it is necessary to remove the top, front and side panels of the shroud as follows (see Figures 6 - 8): Door opening
Unlock the door by rotating the lock counter-clockwise
1. with a wide, slot screwdriver. Release the top and bottom door pins by prying the
2. pins out, using a small screwdriver. Open the door (the door remains fastened to the left
3. side panel).
FIGURE 6
Remove the top casing (front).
Use a screwdriver to remove the six screws securing
1. the top casing. Lift up and remove casing top (front).
2.
15
Screws Screws
Top Casing (Front)
FIGURE 7
Screws
FIGURE 9
After the heater has been positioned and the earthquake straps have been installed, re-assemble the shroud in the reverse order.
FIGURE 8
16
COMBUSTION AIR AND VENTILATION
A gas water heater cannot operate properly without the correct amount of air for combustion. Do not install in a confi ned area such as a closet, unless you provide air as shown in the “Facts to Consider About Location” section. Never obstruct the fl ow of ventilation air. If you have any doubts or questions at all, call your gas supplier. Failure to provide the proper amount of combustion air can result in a fi re or explosion and cause death, serious bodily injury, or property damage.
FIGURE 10
In unconfi ned spaces in buildings, infi ltration may be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air may need to be provided using the methods described in “Appliances in Confi ned Space” that follows.”
APPLIANCES IN CONFINED SPACES CONFINED SPACE is a space whose volume is less
than 50 cubic feet per 1,000 Btu per hour (4.8m3 per kW) of the aggregate input rating of all appliances installed in that space.
When drawing combustion air from inside a building to a confi ned space, such a space should be provided with two permanent openings. ONE WITHIN 12 in. (30cm) OF THE ENCLOSURE TOP AND ONE WITHIN 12 in. (30cm) OF THE ENCLOSURE BOTTOM. Each opening should have a free area of 1 square inch per 1000 Btu/hr (22 cm2/kW) of the total input of all appliances in the enclosure, but not less than 100 square in. (645 cm2).
If the confi ned space is within a building, air for combustion and ventilation must be obtained from outdoors. When directly communicating with the outdoors or communicating through vertical ducts, two permanent openings, located in the above manner, should be provided. Each opening should have a free area of not less than 1 square inch per 4000 Btu/hr (5.5 cm2/kW) of total input of all appliances in the enclosure. If horizontal ducts are used, each opening should have a free area of not less than 1 square inch per 2000 Btu/hr (1 1 cm2/kW) of the total input of all appliances in the enclosure.
If this water heater will be used in beauty shops, barber shops, cleaning establishments, or self-service laundries with dry cleaning equipment, it is imperative that the water heater(s) be installed so that all air for combustion and ventilation is taken from outdoors. Note: Vent length should be long enough that the outside air will not freeze the water heater.
Propellants of aerosol sprays and volatile compounds, (cleaners, chlorine based chemicals, refrigerants, etc.) in addition to being highly fl ammable in many cases, will also react to form corrosive hydrochloric acid when exposed to the combustion products of the water heater. The results can be hazardous, and also cause product failure.
APPLIANCES IN UNCONFINED SPACES UNCONFINED SP ACE is space whose volume is not less
than 50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the aggregate input rating of all appliances installed in that space. Rooms communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the unconfi ned space.
A. ALL AIR FROM INSIDE BUILDINGS: (See Figures 10
& 11)
The confi ned space should be provided with two permanent openings communicating directly with an additional room(s) of suffi cient volume so that the combined volume of all spaces meets the criteria for an unconfi ned space. The total input of all gas utilization equipment installed in the combined space should be considered in making this determination. Each opening should have a minimum free area of 1 square inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of all gas utilization equipment in the confi ned space, but not less than 100 square in. (645 cm2). One opening should commence within 12 in. (30cm) of the top and one commencing within 12 in. (30cm) of the bottom of the enclosures.
17
FIGURE 11
B. ALL AIR FROM OUTDOORS: (See Figures 12, 13 and
14)
The confi ned space should be provided with two permanent openings, one commencing within 12 in. (30cm) of the top and one commencing within 12 in. (30cm) from the bottom of the enclosure. The openings should communicate directly , or by ducts, with the outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
1. When directly communicating with the outdoors, each
opening should have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure (see Figure
12).
FIGURE 12
FIGURE 13
4. When ducts are used, they should be of the same cross-sectional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts should not be less than 3 in. (7.6cm) (see Figure 14).
FIGURE 14
5. Alternatively a single permanent opening may be used when communicating directly with the outdoors, or with spaces that freely communicate with the outdoors. The opening should have a minimum free area of 1 square inch per 3,000 BTU per hour (7.3 cm2/kW) of total input rating of all equipment in enclosure (see Figure 15).
2. When communicating with the outdoors through vertical ducts, each opening should have a minimum free area of 1 square inch per 4,000 Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the enclosure (see Figure 13).
3. When communicating with the outdoors through horizontal ducts, each opening should have a minimum free area of 1 square inch per 2,000 Btu per hour (11 cm2/kW)) of total input rating of all equipment in the enclosure (see Figure 14).
18
FIGURE 15
Loading...
+ 42 hidden pages