Kenmore 79043492400, 79043492401, 79043493400, 79043493401, 79043494400 Installation Guide

...
INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUAUFIED INSTALLER.
IMPORTANT: SAVE FOR LOCAL ELECTRICAL INSPECTOR'S USE.
READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE.
_FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and tiquids in the vicinity of this or any other appliance.
IMPORTANT INSTALLATION-INFORMATION
All electric cooktops run off a single phase, three-wire or four-wire cable, 240/208 volt, 60 hertz, AC only electrical supply with ground.
* 30" (76.2 cm) rain. for unprotected cabinet
24" (61 cm) rain. for protected surface
Cooktop Dimensions
C
2t/2" (6.4 cm)
Cooktop Cutout Dimensions H
30"CoilElements 30 (76.2) 2IV2(54.6) 2_/2(6.4) 27_A(69.2) 36"C0iJElements 36 (91.4) 21½ (54.6) 2h (6.4) 33V8(84.I)
MODEL i MINIMUM MAXIMUM MINIMUM i MAXIMUM C00KTOP*
30' C0iJElements 27_A(69.2) 28h (72.4) I9½(49.5) (I9.1) 36"C0ilElements 331/8(84.I) 34(86.4) 191/8(48.6) 19_A(50.2) 7h (I9.1)
All dimensions are in inches (cm). * Allow 2" (5.1 cm) space below cooktop to clear the electric cable and allow for
P/N 318201415 (0404) Rev A
installation of the junction box on the wall at the back of the cooktop.
English - pages 1-6
Espa;_ol- pages 7-12
Overhead Cabinet Should Not Exceed a Maximum Depth of 13" (33 cm)
30" (762cm) Min_Clearance [--_1_
Between the Top of the _'-_..
Cooking Platform and the \
Bottom of an Unprotected
Wood or Metal Cabinet _
24" (61 cm) Min. when
Bottom of Wood or Metal
Cabinet is Protected by Not
Less Than 1/8" Flame Retardant Millboard Covered
With Not Less Than No, 28
MGS Sheet Steel, 0015"
(04 mm) Stainless Steel, 0024" (06 ram) Aluminum
or 0,020" (0,5 ram) Copper
K Min Recommended Distance Between
Edge of Cutout and
-... Nearest Combustible I 0" Surface Above 2E4 cm)
Countertop
18"
(4E7 cm)
J Min From Edge of
.Cooktop to Nearest
Combustible Wall (Either Side of Unit)_
2 1/2" (6_4 cm) Min From Edge of Cutout to
* Letters on this figure refer to chart
on front page except for J and K.
Front Edge of Countertop
_To eliminate the risk of burns or fire by reaching over heated surfaces, cabinet storage space located above the cooktop should be avoided. If cabinet storage is provided, risk can be reduced by installing a range hood that projects horizontally a minimum of 5" (12.7 cm) beyond the bottom
of tile cabinets.
Figure 2 - COUNTERTOP CUTOUT OPENING
It is not recommended to use
Approximate Location of Junction Box
drawer underneath cooktop Empty space is needed for
installation purpose,
30" Coil Elements 7_/2'' (I9.1 cm) 2¼" (5,7 cm) 36" Coil Elements 7_/2"(Ig.I cm) 2¼" (5,7 cm)
Important Notes to the Installer
1. Readallinstructionscontainedintheseinstallation instructionsbeforeinstallingthecooktop.
2. Removeallpackingmaterialbeforeconnectingthe electricalsupplytothecooktop.
3. Observeallgoverningcodesandordinances.
4. Besuretoleavetheseinstructionswiththeconsumer.
Important Note to the Consumer Keeptheseinstructionswithyourowner'sguideforfuture
reference.
IMPORTANT SAFETY INSTRU S
Be sure your cooktop is installed and grounded
properly by a qualified installer or service technician.
These cooktops must be etectrkaHy grounded in accordance with local codes or, in their absence, with the National EJectricat Code ANSJ/NFPA No.
70--Jatest edition in the United States, or with CSA Standard C22.1, Canadian Electrical Code, Part 1, in Canada.
The electrical power to the cooktop must be shut off while line connections are being made. Faiture to do so coutd resutt in serious injury
or death.
Provide Electrical Connection
Install the junction box under the cabinet and run 120/ 240 or 120/208 Volt, AC wire from the main circuit
panel. DO NOT connect the wire to the circuit panel at this time.
NOTE: Wire sizes and connections must conform with the fuse size and rating of the appliance in accordance
with tile National Electrical Code ANS!/NFPA No. 70- latest edition, or with CSA Standard C22.1, Canadian
Electrical Code, Part 1, and local codes and ordinances.
An extension cord must not be used with this appliance. Such use may result in a fire, electrical shock, or other personal injury.
2. Tile appliance should be connected to tile fused
disconnect (or circuit breaker) box through flexible armored or nonmetallic sheathed (:able. The flexible
armored cable extending from this appliance should be connected directly to the grounded junction box. Tile junction box should be located as shown in Figure 2 with as much slack as possible remaining in tile cable between the box and the appliance, so it can be moved if servicing is ever necessary.
3. A suitable strain relief must be provided to attach
the flexible armored cable to the junction box.
Electrical Connection
Connect tile flexible armored (:able that extends from tile surface unit to the junction box using a suitable
strain relief at the point the armored cable enters the
junction box. Then make the electrical connection as
described on next page.
Electrical ground is required on this appliance,
This appliance is equipped with a copper conductor flexible cable. If connection is made to aluminum house
wiring, use only special connectors which are approved
Electrical Requirements
Observe all governing codes and tocaJ ordinances,
1. A 3-wire or 4-wire single phase 120/240 or 120/208 Volt, 60 Hz AC only electrical supply is required on a separate circuit fused on both sides of the line (time- delay fuse or circuit breaker is recommended). DO
NOT fuse neutral. The fuse size must not exceed the circuit rating of tile appliance specified on tile
nameplate.
2. This unit (:an consume up to 7300W at 240Vac, a circuit breaker of 40 Amp with wire gauge #SAWG
shall be used.
WhereIota[codespermitconnectingthe appliance- groundingconductorto theneutral(white)wire (seefigure3): The3-conductorcordorcablemustbereplacedwitha4- conductorcordorcablewherelocalcodesprohibitgrounding throughtheneutralconductor,includingnewbranch-circuit
installations(1996NEC),mobilehomes,or recreational vehicles.
,
Disconnect tile power supply.
2.
In the circuit breaker, fuse box or junction box: connect appliance and power supply cable wires as shown on figure 3.
Where local codes DO NOT permit connecting the appliance-grounding conductor to the neutral (white} wire, or if connecting to 4-wire electrical system (see figure 4}:
1. Disconnect the power supply.
2. Separate the green (or bare copper) and white appliance cable wires.
3. Cap the white wire from tile power supply cable if a 3-wire appliance cable is supplied.
4. In the circuit breaker, fuse box or junction box: connect appliance and power supply cable wires as shown on figure 4.
Cable from Power Supply
Ground Wire
\
Wires Black
Wires
Ground Wire U.L-Listed Conduit (Bare or Green Wire) Connector (or CSA
listed)
Cable from appliance
Figure 3
3-WIRE GROUNDED JUNCTION BOX
Improper connection of aluminum house wiring to copper leads can result in a short circuit or fire. Use only connectors designed for
joining copper to aluminum, and follow the
connector manufacturer recommended procedure closely.
Box
Cable from Power Supply
-White Wire
Ground Wire
Red_.
Wires
Wires
Box
Ground Wire U.L-Listed Conduit (Bare or Green Wire) Connector (or CSA
listed)
Cable from appliance
Figure 4
4-WIRE GROUNDED JUNCTION BOX
DO NOT ground to a gas supply pipe, DO NOT connect to electrical power supply until appliance is permanently grounded. Connect the ground wire before turning on the power,