Kenmore 41794072300, 41794072301 Installation Guide

Pre-lnstallation Requirements ................................ 2
Electrical Requirements ........................................ 2
Exhaust System Requirements ............................ 3-4
Gas Supply Requirements ..................................... 4
Location of Your Dryer.......................................... 4-5
Mobile Home Installation ....................................... 6
Installation
instructions
Gas &
Electric
Dryer
Rough-In Dimensions .......................................... 6-7
Unpacking ........................................................... 7
Reversing Door Swing ........................................... 7
Electrical Installation ............................................. 8
Grounding Requirements ....................................... 8
Electrical Connections--3-wire .............................. 9
Electrical Connections--4-wire .............................. 9
Replacement Parts.............................................. 10
Before beginning installation, carefully read these instructions. This will simplify the installation and ensure the dryer is installed correctly and safely. Leave these instructions near the Dryer after installation for future
reference. NOTE: The electrical service to the Dryer must conform with local codes and ordinances and the latest edition of the
National Electrical Code, ANSI/NFPA 70. NOTE: The gas service to the Dryer must conform with local codes and ordinances and the latest edition of the
National Fuel Gas Code ANSI Z223.1.
NOTE: The Dryer is designed under ANSI Z 21.5.1 or ANSI/UL 2158 - CAN/CSA C22.2 (latest editions) for HOME USE only. This Dryer is not recommended for commercial applications such as restaurants or beauty salons, etc.
Save These Instructions
Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A.
1 P/N 134235400B (0404)
For your safety the information in
this manual must be followed to minimize the risk of fire or explosion or to prevent property
damage, personal injury or loss of life.
- Do not store or use gasoline or other flammable vapors and liquid in the vicinity of
this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS . Do not try to light any appliance.
. Do not touch any electrical switch; do not
use any phone in your building.
. Clear the room, building or area of all
occupants.
. Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's instructions.
. If you cannot reach your gas supplier, call
the fire department.
POWER SUPPLY - 3 wire or 4-wire, 240 volt, single phase, 60 Hz,Alternating Current.
POWER SUPPLY CORD KIT- The dryer MUST employ a 3-conductor power supply cord NEMA 10-30 type SRDT rated at 240 volt AC minimum, 30 amp., with 3 open end spade lug connectors with upturned ends or closed loop connectors OR a 4-conductor power supply cord NEMA
14-30 type SRDT or ST (as required) rated at 240 volt AC minimum, 30 amp., with 4 open end spade lug connectors with upturned ends or closed loop connectors and marked for use with clothes dryers. If being installed in a manufactured (mobile) home, the dryer MUST employ a 4-conductor power supply cord NEMA 14-30 type SRDTor ST(as required) rated at 240 volt AC minimum, 30 amp., with 4 open end spade lug connectors with upturned ends or closed loop connectors and marked for use with clothes dryers. See ELECTRICAL CONNECTIONS for additional
instructions.
OUTLET RECEPTACLE - NEMA 10-30R (3-wire) receptacle or NEMA 14-30R (4-wire) receptacle to be located so the power supply cord is accessible when the dryer is in the installed position.
Installation and service must be performed by a qualified installer, service agency or the gas
supplier.
PRE-INSTALLATION REQUIREMENTS
Tools and Materials Required for Installation:
1. Phillips head screwdriver.
2. Channel-lock adjustable pliers.
3. Carpenter's level.
4. Flat or straight blade screwdriver.
5. Duct tape.
6. Rigid or flexible metal 4 inch (10.2 cm) duct.
7. Vent hood.
8. Pipe thread sealer (Gas).
9. Plastic knife.
ELECTRICAL REQUIREMENTS
ELECTR/C Dryer
NEMA 10-30R NEMA 14-30R
GAS Dryer
CIRCUIT- Individual 15 amp. branch circuit fused with a 15
amp. maximum time delay fuse or circuit breaker.
POWER SUPPLY - 3 wire, 120 volt single phase, 60 Hz, Alternating Current.
POWER SUPPLY CORD - The dryer is equipped with a 120 volt 3-wire power cord.
NOTE: Do not under any circumstances
remove grounding
prong from plug.
CIRCUIT- Individual 30 amp. branch circuit fused with 30 amp. minimum time delay fuses or circuit breakers.
GROUNDING PRONG
2 Printed in U.S.A.
EXHAUST SYSTEM REQUIREMENTS
Use only 4 inch (10.2 cm) diameter (minimum) rigid or flexible metal duct and approved vent hood which has a swing-out damper(s) that open when the dryer is in operation. When the dryer stops, the dampers automatically close to prevent drafts and the entrance of insects and
rodents. To avoid restricting the outlet, maintain a minimum of 12 inches (30.5 cm) clearance between the vent hood
and the ground or any other obstruction.
The following are specific requirements
forproper and safe operation of your dryer. Failure to
follow these instructions can create excessive drying
times and fire hazards.
Number
of
90 °
Turns
0
1 2 3 4
MAXIMUM LENGTH
of 4" (10.2 cm) Dia. Rigid Metal Duct
VENT HOOD TYPE
(Preferred)
Louvered
4-F
(10.2cm)
60ft. (18.28 m)
52ft. (15.84 m) 44ft. (13.41 m) 32 ft. (9.75 m) 28ft. (8.53 m)
(6.35cm:
48 ft.(14.63 m)
40 ft.(12.19 m) 32 ft. (9.75 m) 24ft. (7.31 m) 16ft. (4.87m)
Do not use plastic flexible duct to exhaust the dryer.
Excessive lint can build up inside exhaust system and
create a fire hazard and restrict air flow. Restricted air flow will increase dryer times. If your present system is made up
of plastic duct or metal foil duct, replace it with a rigid or flexible metal duct. Ensure the present duct is free of any lint prior to installing dryer duct.
If the dryer is not exhausted outdoors, some fine
lint will be expelled into the laundry area. An accumulation of lint in any area of the home can create a
health and fire hazard. The dryer exhaust system MUST
be exhausted to the outside of the dwelling!
Do not allow combustible materials (for example:
clothing, draperies/curtains, paper) to come in contact
with exhaust system, The dryer MUST NOT be exhausted
into a chimney, a wall, a ceiling, or any concealed space of
a building which can accumulate lint, resulting in a fire
hazard.
V_ Exceeding the length of duct pipe or number of elbows allowed in the "MAXIMUM LENGTH" charts can
cause an accumulation of lint in the exhaust system.
Plugging the system could create a fire hazard, as well as increase drying times.
Do not screen the exhaust ends of the vent system,
nor use any screws or rivets to assemble the exhaust system. Lint can become caught in the screen, on the
screws or rivets, clogging the duct work and creating a fire
hazard as well as increasing drying times. Use an approved vent hood to terminate the duct outdoors, and seal all joints with duct tape. All male duct pipe fittings MUSTbe installed
downstream with the flow of air.
Explosion hazard. Do not instafl the dryer
where gasoline or other flammables are kept or stored.
If the dryer is installed in a garage, it must be a minimum of
18 inches (45.7 cm) above the floor. Failure to do so can
result in death, explosion, fire or burns.
MAXIMUM LENGTH
of 4" (10.2 cm) Dia. Flexible Metal Duct
VENT HOOD TYPE
(Preferred)
Number
of
90 °
Turns
(10.2 cm)
0
1 2 3
INSTALL MALE FITTINGS IN CORRECT DIRECTION
30ft. (9.14 m) 22ft. (6.71 m)
14ft. (4.27 m)
Louvered
(6.35cm)
18ft. (5.49 m) 14ft. (4.27 m) lOft. (3.05m)
NOTRECOMMENDED
In installations where the exhaust system is not described in the charts, the following method must be used to determine if the exhaust system is acceptable:
1. Connect an inclined or digital manometer between the dryer and the point the exhaust connects to the dryer.
2. Set the dryer timer and temperature to air fluff (cool down) and start the dryer.
3. Readthe measurement on the manometer.
4. The system back pressure MUST NOT be higher than
0.75 inches of water column. If the system back pressure is less than 0.75 inches of water column, the system is acceptable. If the manometer reading is higher than 0.75 inches of water column, the system is too restrictive and the installation is unacceptable.
Althoughverticalorientationof theexhaustsystemis
acceptable,certainextenuatingcircumstancescouldaffect
theperformanceofthedryer:
Onlythe rigid metal duct work should be used. Venting vertical through a roof may expose the exhaust
system to down drafts causing an increase in vent restriction.
Running the exhaust system through an uninsulated area may cause condensation and faster accumulation
of lint. Compression or crimping of the exhaust system will
cause an increase in vent restriction.
The exhaust system should be inspected and cleaned a
minimum of every 18 months with normal usage. The more
the dryer is used, the more often you should check the
exhaust system and vent hood for proper operation.
EXHAUST DIRECTION
All dryers shipped from the factory are set up for rear
exhausting. However, on electric dryers, exhausting can be
to the right or left side of the cabinet or the bottom of the
dryer. On gas dryers, exhausting can be to the right side of
the cabinet or the bottom of the dryer. Directional
exhausting can be accomplished by installing Exhaust Kit, P/N 131456800, available through your parts distributor. Follow the instructions supplied with the kit.
EXHAUST DUCT LOCATING DIMENSIONS
AS OTHER SIDE
j! SAME
5 718"
(15cm)
"--.J<"l-." "'°°'
3 314" _J "_'..2 _
(9.S¢m) -_
GAS SUPPLY REQUIREMENTS
Replace copper connecting pipe that is
not plastic-coa ted. Stainless steel or plastic-coated brass MUST be used.
2. The gas supply line should be of 1/2 inch (1.27 cm) pipe.
3. If codes allow, flexible metal tubing may be used to connect your dryer to the gas supply line. The tubing MUST be constructed of stainless steel or plastic-
coated brass.
4. The gas supply line MUST have an individual shutoff valve.
5. A 1/8 inch (0.32 cm) N.RT. plugged tapping, accessible for test gauge connection, MUST be installed immediately upstream of the gas supply connection to the dryer.
6. The dryer MUST be disconnected from the gas supply piping system during any pressure testing of the gas supply piping system at test pressures in excess of 1/2 psig (3.45 kPa).
7. The dryer MUST be isolated from the gas supply piping system during any pressure testing of the gas supply piping system at test pressures equal to or less than
1/2 psig (3.45 kPa).
LOCATION OF YOUR DRYER
DO NOT INSTALL YOUR DRYER:
1. In an area exposed to dripping water or outside weather conditions.
2. In an area where it will come in contact with curtains, drapes, or anything that will obstruct the flow of
combustion and ventilation air.
3. On carpet. Floor MUST be solid with a maximum slope of 1 inch (2.54 cm).
INSTALLATION IN RECESS OR CLOSET
1. A dryer installed in a bedroom, bathroom, recess or closet, MUST be exhausted outdoors.
2. No other fuel burning appliance shall be installed in the same closet as the Gas dryer.
3. Your dryer needs the space around it for proper ventilation.
DO NOT install your dryer in a closet with a solid door.
4. A minimum of 120 square inches (774.2 square cm) of opening, equally divided at the top and bottom of the door, is required. Air openings are required to be
unobstructed when a door is installed. A Iouvered door with equivalent air openings for the full length of the door
is acceptable.
1. Installation MUST conform with local codes, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z223.1 (latest edition).
4
MINIMUM INSTALLATION CLEARANCES - inches (cm)
SIDES REAR TOP FRONT
Alcove 0 (0 cm) 0 (0 cm) 15 (38.1 cm) Closet O(Ocm) O(Ocm) 15(38.1 cm) 1(2.54cm)
Closet door ventilation required: 2 Iouvered openings each 60 square inches (387 square centimeters) -- 3 inches (7.6 cm) from bottom and top of door.
NOTE: Under counter and stack models - 0 inches (0 cm)
for sides, rear, and top.
This dryer MUST be exhausted outdoors.
5. The following illustrations show minimum clearance dimensions for proper operation in a recess or closet
installation.
60 sq. inches (387.1 sq. cm)
60 sq. inches (387.1 sq. cm)
CLOSET DOOR
"" O"
_'ii_ (0cm)
ii
II
II
_1_ 1" (2.54 cm)
ii _ii_ 0" (0 cm)
o" (Ocm)
_,i_ 0" (0 cm)
T
T
1" (2.54 cm)
" (38.1 cm)
v
0"(0 cm)
MOBILE HOME INSTALLATION
UNDER COUNTER & STACK MODELS
1. Dryer MUST be exhausted outside (outdoors, not beneath
the mobile home) using metal ducting that will not support combustion. Metal ducting must be 4 inches (10.16 cm) in diameter with no obstructions. Rigid metal duct is preferred.
2. If dryer is exhausted through the floor and area beneath the mobile home is enclosed, the exhaust system MUST
terminate outside the enclosure with the termination securely fastened to the mobile home structure.
3. When installing a gas dryer into a mobile home, a provision must be made for outside make up air. This provision is to
be not less than twice the area of the dryer exhaust outlet.
4. This dryer MUST be fastened to the floor. Mobile Home Installation Kit No. 346764 is available from your dealer.
5. Refer to pages 2 and 3 for other important venting requirements.
6. Installation MUST conform to current Manufactured Home
Construction & Safety Standard (which is a Federal
Regulation Title 24 CFR-Part 32-80) or when such standard is not applicable, with American National Standard for
Mobile Homes.
The dryer is designed under ANSI Z 21.5.1 or
ANSI/UL2158 - CAN/CSA C22.2 (latest editions) for HOME
USE only.
/
iL DO
/_
DON'T
\\\
\\\
ROUGH-IN DIMENSIONS
[_ ELECTRIC CONNECTION
131/2" --_
(34.4 cm) I
-E:3
33/4"
(9.5cm)
©
/ _-J,
3/8" (0.96 cm) Dia.
GAS PIPE
REAR WEW
35 1/4"
(89.5 cm)
1'12.54cm)
Correct
i_:i i ii i
¸¸¸DO
Correct
I ..........................
Incorrect
L
/
i ii :
DON'T
/\
\ J
\ J
..... 471/2"
(120.7 cm)
21/4"
(5.7 cm)
L
DOOR OPEN 90 °
D
Incorrect
43/8"
(11.1 cm) --_
OPTIONAL
VENT KNOCKOUT_._
27 _ _
(68.6cm)
SIDE VIEW
Incorrect
-f
3 3/4"
(9.5 cm)