Kenmore 41209, 41219 Owner's Manual

INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER.
iMPORTANT: SAVE FOR LOCAL ELECTRICAL iNSPECTOR'S USE.
READ AND SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE.
_FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and Hquids in the vicinity of this or any other appliance.
IMPORTANT [NSTALLATtON4NFORMATJON
All electric cooktops run off a single phase, three-wire or four-wire cable, 240/208 volt, 60 hertz, AC only electrical supply with ground.
* 30" (76.2 cm) rain. for unprotected cabinet
24" (61 cm) rain. for protected surface
Cooktop Dimensions
Cooktop Cutout Dimensions H
Figur
30"CoilElements 30 (76.2) 213A(55.2) 4Y2(11.4) 27(68.6) I9 (48.3) 36' CoilElements 36 (91.4) 213A(55.2) 4Y2(11.4) 33Y4(84.5) 19(48.3)
MODEL MINIMUM MAXIMUM I MINIMUM I MAXIMUM ' COOKTOP_
I I
30"CoilElements 27Y4(69.2) 28_/2(72.4) 19Ys(48.6) 19sA(50.2) 7 (17.8) 36"CoilElements 33:/s(86) 34_/4(87) 19Ys(48.6) 19sA(50.2) 7(I7.8)
All dimensions are in inches (cm).
* Allow 2" (5.1 cm) space below cooktop to clear the electric: cable and allow for
installation of the junction box on the wall at the back of the cooktop.
P/N 318201423 (0506) Rev A
Printedin United States
English - pages 1-6
Espa¢_ol- pages 7-12
Overhead Cabinet Should Not Exceed a Maximum Depth of 13" (33 cm)
Bottom of an Unprotected
Wood or Metal Cabinet _
24" (61 cm) Min when
Bottom of Wood or Metal
Cabinet isProtectedby Not
LessThan 1/8" Flame RetardantMiJlboard Covered
With Not LessThanNo. 28
MGSSheetSteel, 0015"
(04 mm) Stainless Steel,
0024" (06 ram)Aluminum or 0,020" (0.5 ram) Copper
* Letters on this figure refer to chart
on front page except for J and K.
Surface Above
.., earest Combustible
Countertop
18" F
(45J cm)
2 1/2" (6_4 cm) Min From Edge of Cutout to
Front Edge of Countertop
10"
2E4 cm)
Approximate Location of Junction Box
J Min From Edge of
.Cooktop to Nearest
Combustible Wall (Either Side of Unit)_
It is not recommended to use drawer underneath cooktop
Empty space is needed for installation purpose.
_To eliminate the risk of burns or fire by reaching over heated surfaces, cabinet storage space located above the cooktop should be avoided. If cabinet storage is provided, risk can be reduced by installing a range hood that projects horizontally a minimum of 5" (12.7 cm) beyond the bottom
of the cabinets.
Figure 2 - COUNTERTOP CUTOUT OPENING
30" C0il Elements 7Y2"(I9.1 cm) IY2" (3.8 cm) 36" C0il Elements 7Y2"(I9,I cm) IY2" (3.8 cm)
Important Notes to the Installer
1. Readallinstructionscontainedintheseinstallation instructionsbeforeinstallingthecooktop.
2. Removeallpackingmaterialbeforeconnectingthe electricalsupplytothecooktop.
3. Observeallgoverningcodesandordinances.
4. Besuretoleavetheseinstructionswiththeconsumer.
Important Note to the Consumer Keeptheseinstructionswithyourowner'sguideforfuture
reference.
IMPORTANT SAFETY INSTRU S
Be sure your cooktop is installed and grounded
properly by a quaJified installer or service technician.
These cooktops must be electrically grounded in accordance with locat codes or, in their absence, with the Nationa! Electrical Code ANSI/NFPA No.
70--latest edition in the United States, or with CSA Standard C22.1, Canadian Electrical Code, Part 1, in Canada.
The electrical power to the cooktop must be shut off while line connections are being made. Faiture to do so coutd resutt in serious injury
or death.
Provide Electrical Connection
Install the junction box under the cabinet and run 120/ 240 or 120/208 Volt, AC wire from the main circuit
panel. DO NOT connect the wire to the circuit panel at this time.
Electrical Requirements
Observe all governing codes and tocaJ ordinances.
1. A 3-wire or 4-wire single phase 120/240 or 120/208 Volt, 60 Hz AC only electrical supply is required on a separate circuit fused on both sides of the line (time- delay fuse or circuit breaker is recommended). DO
NOT fuse neutral. The fuse size must not exceed the circuit rating of the appliance specified on the
nameplate.
2. This unit can consume up to 7300W at 240Vat, a circuit breaker of 40 Amp with wire gauge #8AWG
shall be used.
NOTE: Wire sizes and connections must conform with the fuse size and rating of the appliance in accordance
with tile National Electrical Code ANSI/NFPA No. 70- latest edition, or with CSA Standard C22.1, Canadian
Electrical Code, Part 1, and local codes and ordinances.
An extension cord must not be used with this appliance. Such use may result in a fire, eJectricat shock, or other personat injury.
2. The appliance should be connected to the fused
disconnect (or circuit breaker) box through flexible armored or nonmetallic sheathed cable. The flexible
armored (.able extending from this appliance should be connected directly to the grounded junction box. Tile junction box should be located as shown in Figure 2 with as much slack as possible remaining in the cable between the box and the appliance, so it (.an be moved if servicing is ever necessary.
3. A suitable strain relief must be provided to attach
the flexible armored (.able to the junction box.
Electrical Connection
Connect tile flexible armored cable that extends from the surface unit to the junction box using a suitable
strain relief at tile point the armored cable enters the
junction box. Then make tile electrical connection as
described on next page. Electrical ground is required on this appliance. This appliance is equipped with a copper conductor
flexible cable. If connection is made to aluminum house wiring, use only special connectors which are approved
for joining copper and aluminum wires in accordance with the National Electrical Code and local codes and ordinances.
This appliance is manufactured with a frame connected green (or bare copper) ground wire.
Wheretocalcodes permit connecting the appliance-
grounding conductor to the neutral (white) wire
(see figure 3): The 3-conductor cord or cable must be replaced with a 4- conductor cord or cable where local codes prohibit grounding through the neutral conductor, including new branch-circuit
installations (1996 NEC), mobile homes, or recreational
vehicles.
.
Disconnect tile power supply.
2.
In the circuit breaker, fuse box or junction box: connect appliance and power supply cable wires as shown on figure 3.
Where tocat codes DO NOT permit connecting the appliance-grounding conductor to the neutral (white} wire, or if connecting to 4-wire electrical system (see figure 4}:
1. Disconnect the power supply.
2. Separate the green (or bare copper) and white appliance cable wires.
3. Cap the white wire from tile power supply cable if a 3-wire appliance cable is supplied.
4. In tile circuit breaker, fuse box or junction box: connect appliance and power supply cable wires as shown on figure 4.
Cable from Power Supply
Ground Wire
\
Wires Black
Wires
Ground Wire U.L-Listed Conduit (Bare or Green Wire) Connector (or CSA
listed)
Cable from appliance
Figure 3
3-WIRE GROUNDED JUNCTION BOX
Improper connection of aluminum
house wiring to copper leads can result in a short circuit or fire. Use only connectors designed for
joining copper to aluminum, and follow the
connector manufacturer recommended procedure closely.
Box
Cable from Power Supply
-White Wire
Ground Wire
Red_.
Wires
Wires
Box
Ground Wire U.L.-Listed Conduit (Bare or Green Wire) Connector (or CSA
listed)
Cable from appliance
Figure 4
4-WIRE GROUNDED JUNCTION BOX
DO NOT ground to a gas supply pipe. DO NOT connect to electrical power supply until appliance is permanentJy grounded. Connect the ground wire before turning on the power.