Kenmore 229965570, 229965560, 229965550, 229965540, 229965530 Owner’s Manual

...
Electronic Ignition
Gas-Fired
Hot Water
Induced Draft
Boiler
Installation
Operation
Repair Parts
service or maintenance can cause injury or property damage. Refer to this manual. For assistance or
information consult a qualified installer, service agency or the gas supplier. Natural gas boilers are not to be
converted to Propanr gas.
Warranty..........................................................2
RulesforSafe Installationand Operation.......3
BoilerRatingsand Capacities.........................4
BeforeYou Start..............................................5
Locatingtheboiler..........................................6
FreshAirforCombustion ................................7
Installation-SystemPiping.................................9
Chimney and VentPipeConnection...............11
HorizontalVenting...........................................14
Gas Supply Piping ........................................ 20
Electrical Wiring/Sequence of Operation ....... 21
Wiring Diagram ............................................. 22
Equipment and Optional Accessories - What
They Do ........................................................ 23
Checking and Adjusting ................................. 27
Maintaining "Your Boiler ................................ 28
Service Hints ................................................. 30
Repair Parts ................................................ 31
SEARS
KENMORE CAST IRON BOILERS
FULL ONE YEAR WARRANTY ON HOT WATER AND GAS STEAM CAST IRON BOILERS
For one (1) year from the date of installation, when this boiler is installed and maintained inaccordance
with our instructions. Sears will repair defects inmaterial or workmanship in the boiler, free of charge.
LIMITED 12 YEAR WARRANTY ON STEAM CAST IRON BOILERS
After one (1)year and thoughtwelve(12) yearfrom the dateofinstallation,Sears willfumish a replacement
heat exchange, ifthe heat exchanger inthe boiler isdefective. YOU PAYFOR LABOR.
LIMITED 20 YEAR WARRANTY ON HOT WATER CAST IRON BOILERS
After one (1) year and through twenty (20) years from the date of installation,Sears willfurnisha
replacement heat exchanger in the boiler is defected YOU PAY FOR LABOR.
SEARS INSTALLATION WARRANTY
In addition to any warranty extended to you on the Sears merchandise involved, which warranty becomes effective the date the merchandise is installed, should the workmanship of any Sears arranged installation
prove faulty with one year, Sears will, upon notice from you, cause such faults to be corrected at no additional cost to you.
FOR WARRANTY SERVICE, SIMPLY CONTACT THE NEAREST SEARS STORE OR SERVICE CENTER THROUGHOUT THE UNITED STATES. This warranty gives you specific
legal rights, and you may also have other rights which vary from state to state.
IMPORTANT
The following are the responsibilities of the user
and are cover by the Warranty.
1. Filter clearing or replacement.
2. Damage to unit or unsatisfactory operation
due to improper cleaning or use of unit in corrosive atmosphere.
3. Damage to unit or unsatisfactory operation due to blown fuses or inadequate or interrupted
electrical protective devices.
4. Damage to unit caused by _e use of components or other accessories not compatible with the unit:
5. If the unit is removed from the place it was originally installed, this Warranty becomes void.
6. Damage to the unit caused by accident, abuse, negligence, misuse, riot,fire, flood,or acts of God.
SEARS ROEBUCK AND COMPANY
D/817WA
Hoffman Estates, IL 60179
2
1. Readthe Owner's Manualfor SaleOperation
carefully. Failure to follow the rules for safe operation and the instructions can cause a malfunction of the boiler and result in death, serious bodily in jury, and/or property damage.
2. Check your local codes and utility requirement before installation. The installation must be in
accordance with their directives.
3. Before servicing, allow boiler to cool. Always shut off any electricity and gas to boiler when working on it. This will prevent any
electrical shocks or burns.
4. Never test for gas leaks with an open flame.
Use soap and check all connections. This
will avoid any possibility of fire or explosion.
5. Be certain your boiler will be using the correct gas. Overfiring will result in
premature failure of the boiler sections and
cause dangerous operation.
6. Never vent this boiler into an enclosed space. Always vent to the outside. Never
vent to another room or inside a building.
7. Be sure there is adequate air supply for complete combustion.
8. Follow a regular service and maintenance schedule for efficient and safe operation.
TOOLS
Pipe Wrench Screwdriver
Tin Snips 6 foot tape or folding rule
Hack Saw LP Torch, if you have copper piping
Pipe cutter and threading tools (for iron pipe systems)
The following booklets will help you in making the installation:
Electrical Wiring -Available at Sears from the Plumbing, Heating or Electrical Departments at nominal cost.
Pipe joint compound suitable for natural and propane gas.
Iron or copper pipe for the water lines. Black pipe for the gas lines. Miscellaneous fittings.
Solder and flux if you have copper piping.
MATERIALS
American National Standards, Installation of Gas Appliance and Gas Piping, National Fuel
Gas Code ANSIZ223.1 - latest revision.
Obtain from American Gas Association, 1515 Wilson Boulevard, Arlington (Roslyn), VA 22209
3
ASME
RELIEF
VALVE
TEMPERATURE
PRESSURE
LiMrr & RELAY
CONTROL
23111
®
3 <-'--
LEFT SIDE
MODEL
Natural Propane
Gas Gas
229.965520 229.965320
229.965530 229.965330
229.965540 229,965340
229.965550 229.965350
229.965560 229.965369
229.965570 229,965370
I
I
I I
I
No. Input
Sec. *MBH
2 42,5 3 75.0 4 112.5
5 150.0 6 167.5
7 225.0
I I I I
t I I
DRAII_
VALVE
AGA Heating
I I
I I I-
I I I
Swrm_
IANIFOLD 2
FRONT RIGHT SIDE
NATURAL AND PROPANE GASES
Net IBR Vent Diameter(INCHES)
Capacity
+MGB
36
63
94
125
155
186
Rating
*MBH
31 55
82
109 135
162
Width
14¼ 17%
20¾
24
27¼
U _tTCH
[_ _,_" INTERMnTEHT
_ILOT CONTROL
L
To Chimney
A
11
(Category I)
@
®
DESIGN CER11FIED FOR
NA_nJp_,LAND pRGPANE GA_
Horizontal Vent
(Category III)
4 4
4 4
4 4
3 3
3 3 4
4
* MBH = 1,000 Btuh = British Thermal Unit Per Hour
Boilers are equipped foraltitudes upto2,000 feet only: o U.S.A. Only -For altitudes above 2,000 feet, ratings should be reduced at the rat of4 _ for each 1,000 feet above sea level.
Canada Only - Boilers may be used at highaltitude by using a certified field conversion, kit,resulting in a 10% derate.
+ Heating Capacity based on D.O.E. (Department of Energy}test procedure.
The Ratings marked "Net 1=B=R Ratings" indicate the amount of remaining heat input that can be
used to heat the radiation or terminal units. The Net I=B=R Ratings shown are based on an
allowance of 1.15 in accordance with the factors shown on the I=B=R Standard as published by
The Hydronics Institute.
Selection of boiler size should be based upon "Net I=B=R Rating" being equal to or greater than the calculated heat loss of the building.
The manufacturer should be consulted before selecting a boiler for installations having unusual
piping and pickup requirements. These boilers must stand on a noncombustible floor. If installed on a
combustible floor, use Combustible Floor Base.
These Gas-Fired Hot Water Boilers are low pressure, sectional cast iron boilers Design
Certified by CSA (Canadian Standards
Association) for use with Natural and Propane
Gases. They are constructed and hydrostatically tested for a maximum working pressure of 50psi
(pounds per square inch) in accordance with
A.S.M.E. (American Society of Mechanical
Engineers) Boiler and Pressure Vessel Code Section IV Standards for cast iron heating boilers.
BOILERS FOR USE AT HIGH ALTITUDE
This boiler is factory equipped for use at altitudes of 0-2,000 feet above sea level. For use at altitudes
above 2,000 feet above sea level, the input ratings
are reduced by a change in main burner orificesize.
4
Checktobesureyouhavethe rightsizeboilerbefore startinathe installation.Seeratingandcapacitytable onpreviouspage.Also besurethe newboilerisfor
the type of gas you are using. Check the rating
plate onthe rightside of the boiler.
You must see that the boiler is suppliedwith the
correcttypeofgas,fresh airfor combustion,and a
suitable electrical supply. Also, the boiler must be connected to a suitable chimney or horizontal venting system and an adequate piping system. Finally, a
thermostat, properly located, is needed for control
of the heating system. If you have any doubts as to
the various requirements, check with localauthorities
and obtain professional help where needed. Take
the time to complete all of the steps for SAFE and
PROPER operation of the heating system.
Were required by the authority having jurisdiction, the installation must conform toAmerican Society
of Mechanical Engineers Safety Code for Controls and Safety Devices for Automatically Fired
Boilers, No. CSD-I*
The installation must conform to the requirements
of the authority having jurisdiction or, in the absence of such requirements, to the National Fuel Gas Code, ANSI Z223. l-latest revision.
The following steps are all necessary for proper
installation and safe operation of your boiler.
1. LOCATING THE BOILER
2. FRESH AIR FOR COMBUSTION
3. SYSTEM PIPING
4. CHIMNEY & VENT PIPE CONNECTION
5. GAS SUPPLY PIPING
6. ELECTRICAL WIRING
7. CHECKING &ADJUSTING
KEEP BOILERAREA CLEAN AND FREE FROM COMBUSTIBLE MATERIALS, GASOLINE I
AND OTHER FLAMMABLE VAPORS AND LIQUIDS
I
I
If your boiler is part of a planned heating system, locate it where shown on your plan. If boiler isto
be part of an existing system, it is usually best to put itwhere the old one was. !f you plan to change location, you will need additional materials as well
as an adequate base. The following rules apply:
1. The boiler must be level. Metal shims may be used under base legs for final leveling.
2. Use a raised base iffloor can become wet or damp.
3. The vent pipe connection should be as short as possible.
4. Additional clearances for service may exceed clearances for fire protection. Always comply with the minimum fire protection clearances
shown on the boiler.An 18 inch clearance should be maintained on any side where passage is
required to access another side for cleaning, servicing, inspection or replacement of any part
that may need attention. An 18 inch clearance is recommended on the control side for servicing.
Figure 2 shows minimum clearances to combustible construction. Rooms that are large
in comparison with the size of the boiler are defined as rooms having a volume equal to or
greater than 16 times the volume of the boiler. Where the actual ceiling height of a room is
greater that 8', the volume of a room shall be figured on the basis of a ceiling height of 8'.
Determination of room size should be based on the total volume of all gas fired equipment
installed in theroom. Consult section 6.3.1 of the National Fuel Gas Code for further
information, including approved methodes for reducing clearances in large room.
5. Equipment shall be installed in a location in which the facilities for ventilation permit
satisfactory combustion of gas, proper venting, and maintenance of ambient temperature at
safe limits under normal conditions of use. Equipment shall be located so as not to interfere
with proper circulation of air. When normal
infiltration does not provide the necessary air, outside air shell be introduced (See Page 4 -
"Fresh Air for Combustion").
6. Advise owner to keep air passages free of obstructions. Ventilating and combustion air
must enter boiler room without restrictions.
boiler on Combustible Floor Base No 14614031
for 2-5 section boilers, or No. 14614032 for 6-7 section boilers. We use a 2" cloudlet pad as a
combustible floor base. These are available from your Iocalsupplier. Use 24" x 30" pad for 2-5
section boilers, and a minimum 30" x 30" pad for 6-7 sections boilers. The boiler must be centered on the combustible floor base.
8.The boiler shall be installed such that the automatic gas ignition system components are protected
from water (dripping, spraying, rain, etc.) during
appliance operation and service(circulator replacement, control replacement, etc..)
Alcove, or
Room Not Large Room Large
In Comparison In Comparison
With Boiler With Boiler
Top 6" 6" Rear 6" 6"
Control Side 8" 8" Opposite Side 6" 6"
Front 18" 18" FlueNent Connector 6" 6"
Near Boiler Piping 1" 1"
Minimum Room
Boiler Boiler Volume Required
Size Volume To Be Large
(Cu. Ft.) Room (Cu. Ft)*
2 sect. 4.3 68.7 3 sect. 5.6 89
4 sect. 6.8 109.3
5 sect. 8.1 129.5 6 sect. 9.4 149.8 7 sect. 10.6 170.1
THIS UNIT MUST BE SET ON A CONCRETE OR OTHER
NONCOMBUSTIBLE MATERIAL BASE OR FLOOR. IT MUST NOT BE INSTALLED ON CARPETING
I
I
7.The floor supporting the boiler must be noncombustible. If it is combustible, place the
6
Combustion and Ventilation, of the National fuel Gas Code, ANSI Z223.1-latest revision, or
I Provision for combustion and ventilation air must be in accordance with Section 5.3, Air for I
applicable provisions of the local building codes.
I
WARNING
Be sure provide enough fresh airfor combustion. Enough air insures proper combustion and
assures that hazard will develop due to the lack oxygen.
You must provide for enough fresh air to assure
proper combustion. The fire in the boiler uses
oxygen. It must have a continuous supply. The air
in a house contains only enough oxygen to supply
the burner for a short time. Outside air must enter the house to replace that used bythe burner. Study
following examples I and 2 to determine your fresh air requirements.
EXAMPLE 1: Boiler Located in Unconfined Space An unconfned space is defined as a space whose
volume is not less than 50 cubic feet per 1,000 Btu per hour ofthe total input rating of allappliances
installed in that space.
If your boiler is in an open area (unpartitioned
basement) in a conventional house, the air that leaks through the cracks around doors and
windows will usually be adequate to provide air for combustion. The doors should not fit tightly.
Do not caulk the cracks around the windows. Equipment located in buildings of unusually tight
construction shall be provided with air for combustion, ventilation, and dilution of flue gases
using the methods described in example 2B or shall be specially engineered. The authority having
jurisdiction must approve specially engineered
installations.
EXAMPLE 2: Boiler Located in Confined Space
A. All Air from Inside the Building: The confined space shall be provided with two permanent openings communicating directly with an additional
room(s) of sufficient volume so that the combined
volume of all spaces meets the criteria for an unconfined space. The total input of all gas
utilization equipment installed in the
NOTE
If you use a fireplace or a kitchen or bathroom
exhaust fan, you should install an outside air
intake. These devices will rob the boiler and
water heater of combustion air.
combined space shall be considered in making this
determination. Each opening shall have a
minimumfree area of one square inch per 1,000 Btu per hour of the total input rating of all gas utilization
equipment in the confined space, but not less that
100 square inches. One opening shall be within 12 inches of the top and one within 12 inches of the
bottom of the enclosure. The minimum dimension of
air openings shall not be less than 3 inches.
B. All Air from Outdoors: The confined space
shall communicate with the outdoors in accordance with methods 1 or 2. The minimum dimension of
air openings shall not be less than 3 in. Where ducts are used, they shall be of the same cross- sectional area as the free area of the openings to
which they connect.
1.Two permanent openings, one commencing within 12 inches of the top, and one commencing
within 12 inches of the bottom, of the enclosure
shall be provided. The openings shall communicate directly, or by the ducts, with the
outdoors or spaces (crawl or attic) that freely communicate with the outdoors.
a) Where directly communicating with the
outdoors or where communicating to the outdoors through vertical ducts, each
opening shall have a minimum free area of
1 sq. in, per 4000 Btu per hour oftotal input
rating of all equipment in the enclosure.
(See Figure 3A.)
b) Where communicating with the outdoors
throughhorizontal ducts, each opening shall have a minimum free area of 1 area ofsq.
in. per 2000 Btu per hour of total rating of all equipment in the enclosure. (See Fig.3B.)
7
2, One permanentopeningcommencingwith 12
inches of the top of the enclosure, shall be permitted where the equipment has clearance
of at least 1 inch from the sides and back and 6 inches form the front of the appliance. The
opening shell directly communicate with the outdoorsor shallcommunicate through avertical
or horizontal duct to the outdoors or spaces (crawl or attic) that freely communicate with the outdoors, and shall have a minimum free area of:
a) 1sq. inch per3000 Btu per hour ofthe total
inputof allequipment locatedinthe enclosure (See Fig. 4), and the front of the appliance
b) Not less than the sum of the areas of all
vent connectors in the confined space.
1 Square Inch
100% Free
Area
Fresh Air 1/4, Wire Duct Size Mesh
3" x 12" 72,000 8" x 8" 128 000
8"x 12" 192,000 81/2"x 16" 256,000
)er 2,000 Btuh
75% Free 25% Free
Area Area
Metal Wood
Louvers Louvers
54,000 18,000 96,000 32,000
144,000 48,000 192,000 64,000
1 Square Inch )er 4,000 Btuh
100% Free 75% Free 25% Free
Area Area Area
Fresh Air 1/4" Wire Metal Wood Duct Size Mesh Louvers Louvers
3"x 12" 144,000 108,000 36,000 8" x 8" 256,000 192,000 64,000 8" x 12" 384,000 288 000 96,000
81/2" x 16" 512,000 384,000 128,000
1 Square Inch
100% Free
Area Fresh Air 1/4" Wire Duct Size Mesh
3" x 12" 108,000 8" x 8" 192,000 8" x 12" 288,000
81/2"x 16" 384,000
oer 3,000 Btuh
75% Free 25% Free
Area Area
Metal Wood
Louvers Louvers
81,000 27,000 144,000 48,000 216,000 72,000
288,000 96,000
8
1. Place boiler in the selected location (as near chimney as possible). Your boiler is shipped
assembled.Youneedonlyto installthecirculator, ball valves the relief valve with a drain line to
carryanywater to a drain, andthe drain valve.
2. Install ReliefValve on 3/4"pipenippleintapped openinginthe leftend section. Connecta drain line of the same pipe size (3/4" to carry any
water away to a drain. No shutoff of any
descriptionshall be placed betweenthe safety reliefvalveand theboiler,or ondischargepipes betweensuchsafetyvalvesandtheatmosphere.
Installationofthe safetyreliefvalveshallconform
to the requirements of the ANSI/ASME Boiler
and PressureVessel Code,Section IV.
3. Install Drain Valve on lower left side of boiler as marked.
4. Connect Supply and Return Lines to boiler. The connections may require certain
additional fittings and parts, as shown on
diagram (Figs. 5 and 6).
When this boiler isconnected to heating coils located in air handling units where they may be exposed to refrigerated air circulation, the piping system shall be equipped with flow control valves or other automatic means to prevent gravity circulation of the boiler water during the cooling cycle.
LOW DESIGN WATER TEMPERATURE SYSTEMS (BELOW 140 ° F)
If the boiler is to be used in a heating system where design water temperatures below 140 °
F are desired (e.g. radiant floor heating), a 3-
way or 4-way mixing valve or suitable alternative is required to prevent low temperature return
water from entering the boiler. Follow the mixing valve manufacturers installation instructions.The
minimum design return water temperature to the boiler to prevent condensation in the boiler
and venting is 120 ° F The minimum high limit setting is 140 ° F.
Ifyou are installing an entire newheatingsystem,
first install all of your radiation units (panels,
radiatorsor cabinets) and the Supply and Return Mains- then make the connections atthe boiler.
Inconnecting the cold water supply to the water
valve, make sure that a clean water supply is available. When the water supply isfrom a well
or pump, a sand strainer should be installed at the pump.
A hot water boiler installed above radiation level
must beequipped with a lowwater cutoff device.
Aperiodic inspection is necessary,as isflushing of float type devices, per manufacturers specific
instructions.
When boiler is used in connection with
refrigeration systems it shall be installed so that
the chilled medium is piped in parallel with the
heating boiler with appropriate valves to prevent
the chilled medium from entering the heating boiler (Fig. 7).
9
VALVES A & B - OPEN FOR HEATING; CLOSED FOR COOLING VALVES C & D - CLOSED FOR HEATING; OPEN FOR COOLING
TO SYSTEM
B
10
with Part 7, Venting of Equipment, of the National Fuel Gas Code, ANSI Z223.l-latest issue
I For boilers for connection to gas vents or chimneys, vent installations shell be in accordance
and applicable provisions of the local building codes.
CHECK YOUR CHIMNEY
5. Outside chimneys should not be used unless
This is a very important part of your heating system.
Itmust be clean, the right size, properly constructed
and in GOOD CONDITION. No boiler can function properly with a bad chimney.
1. Use local codes for installation or National Fuel
Gas Code Z223.1-1atest issue. In Canada, follow CSA 13149.1 or .2 Installation Codes. It
is very important to properly size the venting system for induced draft appliances. Consult the Vent Sizing Tables, in the National Fuel
Gas Code ANSI Z223.1-1atest revision for correct sizing information In Canada, consult
the Vent Sizing Tables, Amendment #1 to CSA-
13149.1 and .2 Installation Codes.
2. The boiler's induced draft blower has a 3" outlet. A 3" X 4" increaser fitting isincluded in the parts
bag. Locate the increaser fitting on the outlet of the induced draft blower, and secure gastight
with a bead of the furnished silicone sealant.
The increaser fitting is required on this boiler
for Category I venting, and 4" is the minimum
permissible vent diameter. This does not imply
that the vent connector is intended to be 4"
diameter pipe. The vent connector shall be sized
according to the appropriate venting tables in
the National Fuel Gas Code or the Canadian
Installation Codes, and may be required to be larger than 4" diameter.
they are either:
a. enclosed in a chase, or b. lined with Type B vent pipe, or listed flexible
vent liner, or other certifEEI chimney lining system.
6. The vent connector from the boiler to the chimney should run as directly as possible with
as few elbows as possible.
7. Where possible, itis recommended to common
vent the water heater and boiler. Consult the appropriate Vent Sizing Tables in either the
National Fuel Gas Code, or the Canadian Installation Codes for specific requirements
of multiple appliance venting.
8. If the boiler is the only appliance connected to
the vent, Type B vent pipe is recommended for the vent connector.
9. Slope pipe up from boiler to chimney not less
than 1/4" per foot.
10. End of vent pipe must be flush with the inside
face of the chimney flue. Use a sealed-in thimble for the chimney connection.
11. The sections of vent pipe should be fastened
with sheet metal screws to make the piping rigid. Use stovepipe wires to support the pipe
from above.
12. Do not connect to fireplace flue.
13. Do not install a damper on this boiler.
The boiler installation for chimney venting
is not complete unless the 3" x 4" increaser
fitting is located and secured.
3. These are high efficiency boilers with a low stack or exhaust temperature.
4. Ifventing into a masonry chimney without a liner, line the chimney from top to bottom with either:
a, listed Type B vent pipe
b. listed fexible vent liner
c. poured ceramic liner.
MINIMUM VENT PIPE CLEARANCE
if the vent pipe must go through a crawl space,
Type B vent pipe should be used. Where vent
pipe passes through a combustible wall or partition, use a ventilated metal thimble. The
thimble should be 4 inches larger in diameter than the vent pipe.
11
Loading...
+ 25 hidden pages