For potable water heating only.
Not suitable for space heating.
For use only in mobile homes.
LOW LEAD
CONTENT
This water heater shall not be installed in
the occupied space of the manufactured
(mobile) home.
INSTALLER: Affix these instructions to or
near the water heater.
OWNER: Retain these instructions for future
reference.
FOR YOUR SAFETY: An odorant is added to
the gas used by this water heater.
ADVERTENCIA
Si no puede leer o entender el inglés y necesita el manual de
instrucciones en español, puede solicitarlo al 1-800-821-2017. NO
TRATE DE INSTALAR U OPERAR ESTE CALENTADOR DE AGUA
SI NO ENTIENDE LAS INSTRUCCIONES. No hacer caso de esta
advertencia podría originar lesiones graves o mortales.
P/N 321634-001 (0512)
Sears Brands Management Corporation,
Hoffman Estates, IL 60179 U.S.A.
www.kenmore.com
www.sears.com
®
1
SAFE INSTALLATION, USE AND SERVICE
Your safety and the safety of others is extremely important in the installation, use and servicing of this water heater.
Many safety-related messages and instructions have been provided in this manual and on your own water heater to warn you and others of
a potential injury hazard. Read and obey all safety messages and instructions throughout this manual. It is very important that the meaning
of each safety message is understood by you and others who install, use or service this water heater.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards.
Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result
in death or injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, could result
in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous
situation which, if not avoided, could result in property damage.
All safety messages will generally tell you about the type of hazard, what can happen if you do not follow the safety message and
how to avoid the risk of injury.
The California Safe Drinking Water and Toxic Enforcement Act requires the Governor of California to publish a list of substances known to
the State of California to cause cancer, birth defects, or other reproductive harm, and requires businesses to warn of potential exposure
to such substances. WARNING: This product contains a chemical known to the State of California to cause cancer, birth defects, or other
reproductive harm. This appliance can cause low-level exposure to some of the substances included in the act.
This product is certifi ed to comply with a maximum weighted average of 0.25% lead content as required in some areas.
IMPORTANT DEFINITIONS
• Qualifi ed Technician: A qualifi ed technician must have ability equivalent to a licensed tradesman in the fi elds of plumbing, air supply,
venting, and gas supply, including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the
installation of gas fi red water heaters. The qualifi ed technician must also be familiar with the design features and use of fl ammable vapor
ignition resistant water heaters, and have a thorough understanding of this instruction manual.
• Service Agency: A service agency also must have ability equivalent to a licensed tradesman in the fi elds of plumbing, air supply, venting
and gas supply, including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of
gas fi red water heaters. The service agency must also have a thorough understanding of this instruction manual, and be able to perform
repairs strictly in accordance with the service guidelines provided by the manufacturer.
• Gas Supplier: The natural gas or propane utility or service who supplies gas for utilization by the gas burning appliances within this
application. The gas supplier typically has responsibility for the inspection and code approval of gas piping up to and including the natural
gas meter or propane storage tank of a building. Many gas suppliers also offer service and inspection of appliances within the building.
FLAMMABLES
Flammable Vapors
Read and follow water heater warnings and instructions.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity of this
or any other appliance. Storage of or use of
gasoline or other flammable vapors or liquids in the
vicinity of this or any other appliance can result in
serious injury or death.
2
Water temperature over 125°F
(52°C) can cause servere burns
instantly resulting in severe injury or
death.
Children, the elderly, and the
physically or mentally disabled are at
highest risk for scald injury.
Feel water before bathing or
showering.
Temperature limiting valves are
available.
Read instruction manual for safe
temperature setting.
Fire or Explosion Hazard
Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
Avoid all ignition sources if you smell Natural or LP gas.
Do not expose water heater control to excessive gas
pressure.
Use only gas shown on rating plate unless the water heater
has been properly converted.
Follow conversion instructions listed in manual when
converting to opposite gas.
Maintain required clearances to combustibles.
Keep ignition sources away from faucets after extended
period of non-use.
Read instruction manual before
installing, using or servicing
water heater.
Fire or Explosion Harzard
Hydrogen gas can be produced in a hot water system after
a period of non-use (generally two or more weeks).
Hydrogen gas is extremely flammable and can ignite.
After an extended period of non-use, purge gases from hot
water system. To return hot water system to service, open a
hot water faucet in kitchen for several minutes before using
electrical appliances.
Do not smoke or have open flame near faucet while it is open.
Leave hot water faucet open until the sound of escaping
air stops.
3
TABLE OF CONTENTS
SAFE INSTALLATION, USE AND SERVICE ................................................................................................. 2
Removing the Old Water Heater ............................................................................................................................. 12
Site Location ...................................................................................................................................................... 13-14
Securing Water Heater to Floor and Wall ............................................................................................................... 14
Clearances and Accessibility .................................................................................................................................. 15
Filling the Water Heater .......................................................................................................................................... 15
GAS CONVERSION ..................................................................................................................................... 16
GAS SUPPLY .......................................................................................................................................... 17-18
Gas Requirements .................................................................................................................................................. 17
Gas Piping .............................................................................................................................................................. 17
Gas Pressure .......................................................................................................................................................... 17
Gas Pressure Testing.............................................................................................................................................. 17
LP Gas Only............................................................................................................................................................ 18
COMBUSTION AIR SUPPLY & VENTILATION ...................................................................................... 19-20
Vent Pipe System ................................................................................................................................................... 19
Roof Jack Installation .............................................................................................................................................. 19
Water Piping Pressure Test .................................................................................................................................... 22
Temperature and Pressure Relief Valve ................................................................................................................. 22
T&P Relief Valve and Pipe Insulation ........................................................................................................................ 23
OPERATING YOUR WATER HEATER ................................................................................................... 24-27
Checking the Draft .................................................................................................................................................. 26
Emergency Shut Down ........................................................................................................................................... 26
Water Temperature Regulation .......................................................................................................................... 26-27
Operating the Temperature Control System ........................................................................................................... 27
4
SERVICE AND ADJUSTMENT ......................................................................................................... 28-30
Vent System Inspection .......................................................................................................................................... 28
Anode Rod Inspection ............................................................................................................................................ 29
Draining and Flushing ............................................................................................................................................. 30
Service .................................................................................................................................................................... 30
MAINTENANCE OF YOUR WATER HEATER ........................................................................................ 31-33
Replacement Parts ................................................................................................................................................. 31
Removing the Manifold/Burner Assembly ............................................................................................................... 31
Removing the Burner from the Manifold/Burner Assembly .................................................................................... 31
Replacing the Pilot/ Thermopile Assembly ........................................................................................................ 31-32
External Inspection & Cleaning of the Base-Ring Filter ......................................................................................... 32
Cleaning the Combustion Chamber and Flame-arrestor ........................................................................................ 33
Replacing the Manifold/Burner Assembly ............................................................................................................... 33
Piezoelectric Igniter System ................................................................................................................................... 34
Testing the Igniter System ...................................................................................................................................... 34
Removing and Replacing the Gas Control Valve/Thermostat ................................................................................ 34
FVIR System Operational Checklist ....................................................................................................................... 34
Start Up Conditions ............................................................................................................................................ 35-36
PILOT LIGHT TROUBLESHOOTING FLOWCHART ................................................................................... 40
STATUS LIGHT AND DIAGNOSTIC CODE TROUBLESHOOTING CHART ......................................... 41-42
PARTS ORDER LIST ................................................................................................................................... 43
5
PRODUCT WARRANTY
6 - YEAR LIMITED WARRANTY ON WATER HEATER
For six years from the date of purchase, if this water heater is installed and operated in a single-family home in accordance with the
owner’s manual instructions and all local applicable plumbing codes, Sears will:
1. Supply free water heater parts for those that are defective in material or workmanship.
2. Supply a free water heater for one that develops a tank leak. See notes below also.
For the second through sixth year from the purchase date, you must pay the labor cost for installation of parts or water heater.
For commercial, institutional, industrial or residential use by two or more families, the above limited warranty is only for two years. During
the second year you must pay the labor cost for parts or water heater installation.
If governmental regulations prohibit Sears from furnishing a comparable model replacement water heater under this warranty, Sears will
furnish a new water heater of comparable output as permitted by such governmental regulations; however, the Owner will be charged
for the additional cost associated with the changes made to the replacement water heater design to comply with such governmental
regulations.
Replacements and/or repairs furnished under this warranty do not carry a new warranty, and are only covered by the unexpired portion
of the original warranty.
1 - YEAR EXCLUSIVE KENMORE LABOR WARRANTY
For the first year from the date of purchase, Sears will, free of charge, supply and install new water heater parts for defective ones or a
new water heater for one that develops a leak.
WARRANTY SERVICE
To obtain warranty service, call 1-800-4-MY-HOME® (1-800-469-4663).
This warranty applies only while this product is in use in the United States.
This warranty gives you speci c legal rights, and you may also have other rights which vary from state to state.
SEARS BRANDS MANAGEMENT CORPORATION, Hoffman Estates, IL 60179
The price of your water heater does not include a free checkup service call. On water heater installations arranged by Sears, Sears
warrants the installation.
A charge will be made on service calls due to poor or incomplete installation. These include:
a. Adjusting thermostat b. Condensation c. Leaks in pipes or fi ttings
Master Protection Agreements
Congratulations on making a smart purchase. Your new
Kenmore
®
product is designed and manufactured for years
of dependable operation. But like all products, it may require
preventive maintenance or repair from time to time. That’s when
having a Master Protection Agreement can save you money and
aggravation.
The Master Protection Agreement also helps extend the life of your
new product. Here’s what the Agreement* includes:
• Parts and labor needed to help keep products operating
properly under normal use, not just defects. Our coverage
goes well beyond the product warranty. No deductibles, no
functional failure excluded from coverage— real protection.
• Expert service by a force of more than 10,000 authorized
Sears service technicians, which means someone you can
trust will be working on your product.
• Unlimited service calls and nationwide service, as often as
you want us, whenever you want us.
• “No-lemon” guarantee – replacement of your covered product
if four or more product failures occur within twelve months.
• $250 Food Loss Protection annually for any food spoilage
that is the result of mechanical failure of any covered
refrigerator or freezer.
• Rental reimbursement if repair of your covered product takes
longer than promised.
• 10% discount off the regular price of any non-covered repair
service and related installed parts.
Once you purchase the Agreement, a simple phone call is all that it
takes for you to schedule service. You can call anytime day or night,
or schedule a service appointment online.
The Master Protection Agreement is a risk free purchase. If you
cancel for any reason during the product warranty period, we
will provide a full refund. Or, a prorated refund anytime after the
product warranty period expires. Purchase your Master Protection
Agreement today!
Some limitations and exclusions apply. For prices and additional
information in the U.S.A. call 1-800-827-6655.
* Coverage in Canada varies on some items. For full details,
call Sears Canada at 1-800-361-6665.
• Product replacement if your covered product can’t be fixed.
• Annual Preventive Maintenance Check at your request – no
extra charge.
• Fast help by phone – we call it Rapid Resolution – phone
support from a Sears representative on all products. Think of
Sears Installation Service
For Sears professional installation of home appliances, garage door
openers, water heaters, and other major home items, in the U.S.A.
or Canada call 1-800-4-MY-HOME
®
.
us as a “talking owner’s manual.”
• Power surge protection against electrical damage due to
power fluctuations.
6
CUSTOMER RESPONSIBILITIES
Thank You for purchasing a Kenmore water heater. Properly installed
and maintained, it should give you years of trouble free service. If
you should decide that you want the new water heater professionally
installed by Sears call 1-800-4-MY-HOME
prompt, quality installation by Sears authorized contractors.
Abbreviations Found In This Instruction Manual:
®
. They will arrange for
• CSA - Canadian Standards Association
• ANSI - American National Standards Institute
• NFPA - National Fire Protection Association
• ASME - American Society of Mechanical Engineers
• GAMA - Gas Appliance Manufacturers Association
Important Information About This Water Heater:
This gas water heater was manufactured to voluntary safety
standards to reduce the likelihood of a fl ammable vapor ignition
incident. New technology used in meeting these standards makes this
product more sensitive to installation errors or improper installation
environments. Please review the Installation Checklist and make
any required installation upgrades or changes.
IMPORTANT: This water heater is shipped from the factory as a
natural gas unit. However, it may be converted to use LP gas. See
the Gas Conversion section for more information.
This manual contains instructions for the installation, operation,
and maintenance of the gas-fi red water heater. It also contains
warnings through out the manual that you must read and be aware
of. All warnings and all instructions are essential to the proper
operation of the water heater and your safety. Since we cannot put
everything on the fi rst few pages, READ THE ENTIRE MANUAL
BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER
HEATER.
• The installation must conform with these instructions and the
local code authority having jurisdiction. In the absence of local
and state codes, installations shall comply with the
“National
Fuel Gas Code,” ANSI Z223.1 (NFPA 54) -current edition.
Manufactured home manufacturers: The installation must
conform to “The Manufactured Home Construction and
Safety Standard, Title 24 CFR, Part 3280.”
These publications are available as follows:
The “National Fuel Gas Code” is available through The Canadian
Standards Association, 8501 East Pleasant Valley Rd, Cleveland,
Ohio 44131 or The National Fire Protection Association, 1
Batterymarch Park, Quincy, MA 02269.
“The Manufactured Home Construction and Safety
Standard, Title 24 CFR, Part 3280” is available through
The U.S. Department of Housing and Urban Development
(HUD), 451 7th Street S.W., Washington, DC 20410. Offi ces
are also located throughout the United States.
Check your phone listings for the local authorities having
jurisdiction over your installation.
• If after reading this manual you have any questions or do not
understand any portion of the instructions, call the Sears Service
Center.
• Carefully plan the place where you are going to put the water heater.
Correct combustion, vent action, and vent pipe installation are
very important in preventing death from possible carbon monoxide
poisoning and fi res. See Figure 1.
• Examine the location to ensure the water heater complies with
the Installation Instructions section in this manual.
• For California installation, this water heater must be braced,
anchored, or strapped to avoid falling or moving during an
earthquake. See instructions for correct installation procedures.
Instructions may be obtained from California’s Offi ce of the
State Architect, 1102 Q Street, Suite 5100, Sacramento, CA
95811. Instructions can also be downloaded to your computer
at www.dsa.dgs.ca.gov/Pubs.
• Massachusetts Code requires this water heater to be installed in
accordance with Massachusetts 248-CMR 2.00: State Plumbing
Code and 248-CMR 5.00.
• Complies with 40 Ng/J NOx requirements of Texas and most
California AQM Districts.
WARNING
Excessive Weight Hazard
Use two or more people to move and install the water heater.
Failure to do so can result in injury (including back injury).
IMPORTANT: Do not remove any permanent instructions, labels, or
the data label from either the outside of the water heater or on the
inside of water heater panels.
• Remove exterior packaging and place installation components
aside.
• Inspect all parts for damage prior to installation and
start-up.
• Completely read all instructions before attempting to assemble
and install this product.
• After installation, dispose of/recycle all packaging materials.
DANGER
Do not use this water heater with any gas other than the
one listed on the data plate unless the water heater has
been properly converted.
Refer to the “Gas Conversion” section of this manual to
convert from one gas to another. Failure to use the
correct gas can cause problems which can result in
death, serious bodily injury or property damage. If you
have any questions or doubts, consult your gas supplier
or gas utility company. Water heaters using bottled
propane or liquefied petroleum gas (LPG) are different
from natural gas models. A natural gas water heater will
not function safely on bottled propane or liquefied
petroleum gas (LPG) and a propane gas water heater will
not function safely on natural gas.
7
PRODUCT SPECIFICATIONS
MODEL
NUMBER
153.33693030 (113)
153.33694040 (151)
TANK CAPACITY
IN GALS (LTRS)
TYPE
OF
GAS
Natural35,50036.34
LP32,00032.75
Natural/
LP
INPUT
RATE
(Btu/hr)
35,50036.343 (76) OR 4 (102)20 (508)58.25 (1480)
RECOVERY
RATE GALS.
PER HOUR
@ 90°F RISE
MINIMUM
VENT PIPE
DIA. INCHES
(mm)
3 (76) OR 4 (102)18 (457)58 (1473)
DIAMETER
INCHES
(mm)
DIMENSIONS
INCHES (mm)
HEIGHT TO
JACKET TOP
8
MATERIALS AND BASIC TOOLS NEEDED
MATERIALS NEEDED
To simplify the installation, Sears has available the installation parts shown below. You may or may not need all of these materials,
depending on your type of installation.
METAL DRAIN PANS AVAILABLE IN THE
EXPANSION TANKS FOR
THERMAL EXPANSION
CONDITIONS AVAILABLE
IN 2 GALLONS
(7.6 LITERS) AND
5 GALLONS (18.9 LITERS)
CAPACITY THROUGH
LOCAL SEARS STORE
OR SERVICE CENTER.
WATER HEATER INSTALLATION KIT
WITH FLEXIBLE CONNECTORS FOR 3/4”
(19.05 mm) COPPER PLUMBING AND FLEXIBLE
GAS CONNECTOR WITH FITTINGS.
FOLLOWING SIZES:
• 20” (508 mm) DIAMETER FOR WATER
HEATERS HAVING A DIAMETER OF
18” (457 mm) OR LESS.
• 24” (610mm) DIAMETER FOR WATER
HEATERS HAVING A DIAMETER 22”
(559 mm) OR LESS.
BASIC TOOLS
You may or may not need all these tools, depending on your
type of installation. These tools can be purchased at your local
Sears Store.
• Pipe Wrenches (2) 14” (356 mm)
• Screwdriver
• Tin Snips
• 6’ (1.82 m) Tape or Folding Ruler
• Garden Hose
• Drill
• Pipe Dope or Tefl on® Tape
SLOT-HEAD SCREWDRIVER
PHILLIPS SCREWDRIVER
ROLL OF TEFLON
TAPE (USE ONLY ON
WATER CONNECTIONS)
®
(SQUEEZE TUBE)
USE FOR WATER AND GAS
CONNECTIONS
DRILL
TIN SNIPS
PIPE DOPE
ADDITIONAL TOOLS NEEDED
WHEN SWEAT SOLDERING
• Tubing Cutters or Hacksaw
• Propane Torch
• Soft Solder
• Solder Flux
• Emery Cloth
• Wire Brushes
TUBING CUTTER
HACKSAW
3/4” (19 mm) WIRE BRUSH
EMERY CLOTH
PROPANE
TORCH
ROLL OF
GARDEN HOSE
6 FOOT TAPE
PIPE WRENCH
1/2” (13 mm) WIRE BRUSH
9
ROLL OF LEAD-FREE
SOFT SOLDER
SOLDER
FLUX
TYPICAL INSTALLATION
GET TO KNOW YOUR WATER HEATER - GAS MODELS
A Vent Pipe
B Draft Hood
C Anode (Not Shown)
D Hot Water Outlet
E Insulation
F Gas Supply Piping
G Manual Gas Shut-off Valve
H Ground Joint Union
I Drip Leg (Sediment Trap)
(Z) ROOF JACK**
TO VENT
TERMINATION
(ROOF JACK)
D
B
A
J Inner Door
K Outer Door
L Union
M Inlet Water Shut-off Valve
N Cold Water Inlet
O Inlet Dip Tube (Not Shown)
P Temperature-Pressure Relief Valve
Q Rating Plate
R Flue Baffle
Gas Control/Temperature Knob
VAC
Igniter
S Gas Control Valve/Thermostat
T Drain Valve
U Manifold/Burner Assembly
V Flue
W Metal Drain Pan
X Piezo Igniter (bottom, Left-hand
Y
Side of Gas Control Valve/Thermostat)
Base-Ring Filter
Z
Roof Jack
(S) GAS CONTROL VALVE/
THERMOSTAT
120°F
Mark
Conversion
Fitting
Status
Light
P
R
F
G
H
I
W
* ALL PIPING MATERIALS TO BE
SUPPLIED BY CUSTOMERS.
** ROOF JACK NOT FURNISHED.
E
DISCHARGE PIPE
(DO NOT CAP
OR PLUG.)
Q
S
V
U
Y
J
X
K
INSTALL THERMAL
EXPANSION TANK
IF WATER HEATER
IS INSTALLED IN
A CLOSED WATER
SYSTEM*
T
L
Temperatures shown are approximates and may vary.
MAIN BURNER
THERMOPILE
M
N
VACUUM RELIEF
DRAIN LINE MUST PASS
THROUGH THE STRUCTURAL
FLOOR AND DISCHARGE
EXTERNAL TO THE BUILDING
FIGURE 1.
(U) MANIFOLD/BURNER ASSEMBLY
MANIFOLD DOOR
VALVE*
INSTALL PER
LOCAL CODES
* INSTALL IN ACCORDANCE
WITH LOCAL CODES.
* DRIP LEG AS REQUIRED
BY LOCAL CODES.
* SECURE WATER HEATER TO
FLOOR AND WALL AS DESCRIBED
IN THIS MANUAL.
* INSTALLATION SHOULD COMPLY
WITH THE “ENCLOSURE
INSTALLATION” SECTION OF THIS
MANUAL.
PILOT TUBE
IGNITER WIRE
MANIFOLD
TUBE
10
IMPORTANT INFORMATION ABOUT THIS WATER HEATER
This gas water heater was manufactured to voluntary safety standards to reduce the likelihood of a flammable vapor ignition incident.
The new technology used in meeting these standards makes this product more sensitive to installation errors. Please review the
following checklist and make any required installation upgrades or changes.
Questions? Contact Sears at 1-800-4-MY-HOME (1-800-469-4663).
Installation Checklist
Water Heater Location
Water heater location is important and can affect system
performance. Please check the following:
□ Installation area free of corrosive elements and flammable
materials.
□ Centrally located with the water piping system (For new
installations). Located as close to the gas piping and vent
pipe system as possible.
□ Located indoors and in a vertical position. Protected from
freezing temperatures.
□ Proper clearances from combustible surfaces
maintained and not installed directly on a carpeted floor.
□ Provisions made to protect the area from water damage.
Metal drain pan installed and piped to an adequate drain.
□ Sufficient room to service the water heater. See Clearances
and Accessibility section of this manual.
□ Water heater not located near an air moving device.
□ Is the installed environment dirty (excessive amounts of
lint, dirt, dust, etc.)? If so, the base-ring filter located on
the bottom of the water heater will need to be cleaned
periodically. Refer to the “Maintenance of your Water
Heater” section of this manual for information on cleaning
the base-ring filter.
□ Fresh air openings must be sized correctly with consideration
given to the blocking effect of louvers and grilles.
Vent Pipe System
Check for proper drafting at the water heater draft hood. Refer
to the “Checking the Draft” section of this manual for the test
procedure. If the procedure shows insufficient draft is present,
please check the following:
□ Draft hood properly installed.
□ Vent connectors securely fastened with screws and
supported properly to maintain six inch clearance.
□ Vent connector made of approved material and sized
correctly.
□ Vent pipe system installed according to all local and state
codes or, in the absence of local and state codes, the
“National Fuel Gas Code”, ANSI Z223.1 (NFPA 54)-current
edition. Manufactured home manufacturers must conform
with the “Manufactured Home Construction and Safety
Standard, Title 24 CFR, Part 3280.”
□ Flue baffle properly positioned in the flue tube.
□ Check the vent system for restrictions/obstructions and
check the vent termination height. Refer to the “Combustion
Air Supply and Ventilation” section of this water heater
manual for specific requirements.
□Recheck for sufficient combustion air supply.
Combustion Air Supply and Ventilation
Check for sufficient combustion air supply. Insufficient air for
the combustion of gas will result in the flame becoming “lazy”,
thereby allowing heat to build up in the combustion chamber.
This excessive heat will cause a thermal switch on the door
assembly to trip. Is the water heater installed in a closet or other
small, enclosed space? If so:
□ Are there openings for make-up air to enter and exit the
room/area?
□Are the openings of sufficient size? Remember, if there
are other gas-fired or air-consuming appliances in the
same room, you need more make-up air. Refer to the
“Installation Instructions” and “Combustion Air Supply and
Ventilation” sections for specific requirements.
□Make sure that fresh air is not taken from areas that contain
negative pressure producing devices such as exhaust fans,
dryers, fireplaces, etc.
□ Is there a furnace/air handler in the same room space as
the water heater? If so, has a return air duct system been
attached that exits the room? If so, check for leaks on the
air duct system. If no air duct system is present, correct
immediately by contacting a local Heating, Ventilation, AirConditioning & Refrigeration (HVAC-R) authorized service
provider.
□ Use a fresh air supply that is free of corrosive elements and
flammable vapors.
Water System Piping
□ Temperature and pressure relief valve properly installed
with a discharge line run to an adequate drain and protected
from freezing.
□ All piping properly installed and free of leaks.
□ Heater completely filled with water.
□ Closed system pressure build-up devices installed.
□ Mixing valve (when applicable) installed per manufacturer’s
instructions (See “Water Temperature Regulation” section).
Gas Supply and Piping
□ Gas type is the same as that listed on the water heater rating
plate unless the water heater has been properly converted.
Refer to the “Gas Conversion” section of this manual.
□ Gas line equipped with shut-off valve, union, and drip leg.
□ Use pipe joint compound or teflon tape marked as being
resistant to the action of petroleum [Propane (L.P.)] gases.
□ Adequate pipe size and approved pipe material.
□ An approved noncorrosive leak detection solution used
to check all connections and fittings for possible gas leaks.
Correct any leak found.
11
INSTALLATION INSTRUCTIONS
O BU
G
Removing the Old Water Heater
5
1
MANUAL GAS
SHUT-OFF VALVE
GROUND
JOINT
UNION
CHECK WITH
LOCAL UTILITY
FOR MINIMUM HEIGHT
3” MINIMUM
DRIP LEG
DRAIN LINE MUST PASS THROUGH FLOOR
AND TERMINATE EXTERNAL T
1. Turn “OFF” the gas supply to
the water heater.
6
3
FIGURE 2.
DISCHARGE PIPE
(DO NOT CAP
OR PLUG)
2
4
ILDIN
4. Attach a hose to the water heater
drain valve and put the other end
in a fl oor drain or outdoors. (See
Figures 2 and 5.) Open the water
heater drain valve. The water
passing out of the drain valve
may be extremely hot. To avoid
being scalded, make sure all
connections are tight and that the
water fl ow is directed away from
any person.
FIGURE 5.
5. Disconnect the vent pipe from the draft hood where it connects
to the water heater. In most installations the vent pipe can
be lifted off after any screw or other attached devices are
removed. Dispose of the draft hood. The new water heater
has a draft hood which must be used for proper operation.
6. If you have copper piping to the water heater, the two copper
water pipes can be cut with a hacksaw approximately four
inches away from where they connect to the water heater.
See Figure 6. This will avoid cutting off pipes too short.
Additional cuts can be made later if necessary. Disconnect the
temperature-pressure relief valve drain line. When the water
heater is drained, disconnect the hose from the drain valve.
Close the drain valve. The water heater is now completely
disconnected and ready to be removed.
If the main gas line shutoff valve
serving all gas appliances is used,
also shut “OFF” the gas at each
appliance. Leave all gas appliances
shut “OFF” until the water heater
installation is completed. See
Figures 2 and 3.
FIGURE 3.
2. Open a nearby hot water faucet
until the water is no longer hot.
When the water has cooled, turn
“OFF” the water supply to the water
heater at the water shut off valve
or water meter. Some installations
require that the water be turned off
to the entire house. See Figures 2
FIGURE 4.
and 4.
3. Check again to make sure the gas supply is “OFF” to the water
heater. Then disconnect the gas supply connection from the
gas control valve.
FIGURE 6.
If you have galvanized pipes to the water heater, loosen
the two galvanized pipes with a pipe wrench at the union in
each line. Also disconnect the piping remaining to the water
heater. See Figure 7. These pieces should be saved since
they may be needed when reconnecting the new water heater.
Disconnect the temperature-pressure relief valve drain line.
When the water heater is drained, disconnect the hose from
the drain valve. Close the drain valve. The water heater
is now completely disconnected and ready to be removed.
Mineral buildup or sediment may have accumulated in the
old water heater. This causes the water heater to be much
heavier than normal and this residue, if spilled out, could
cause staining.
FIGURE 7.
12
Location Requirements
the fire department from a neighbor’s home. Do not attempt to
clean the spill until all ignition sources have been extinguished.
WARNING
Carbon Monoxide Poisoning Hazard
Do not install this water heater in any occupied space of the
manufactured (mobile) home.
Doing so can result in carbon monoxide poisoning and death.
The FVIR System is designed to reduce the risk of flammable
vapor-related fires. The patented system protects your family by
trapping the burning vapors within the water heater combustion
chamber through the special flame-arrestor. The burning vapors
literally “burn themselves out” without escaping back into the
room. In the event of a flammable vapor incident, the FVIR
System disables the water heater by shutting off the gas supply
to the water heater’s burner and pilot, preventing re-ignition
of any remaining flammable vapors in the area. This will not
prevent a possible fire/explosion if the igniter is depressed
and flammable vapors have accumulated in the combustion
chamber with the pilot light off. If you suspect a flammable
vapor incident has occurred, do not use this appliance. Do not
attempt to light this appliance, or depress the igniter button
if you suspect flammable vapors have accumulated inside or
outside the appliance. Immediately call a qualified technician to
inspect the appliance. Water heaters subjected to a flammable
vapors incident will show a discoloration on the flame-arrestor
and require replacement of the entire water heater.
WARNING
FLAMMABLES
FIRE AND EXPLOSION HAZARD
Can result in serious injury or death
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance. Storage of or use of gasoline or other
flammable vapors or liquids in the vicinity of this or any
other appliance can result in serious injury or death.
Read and follow water heater warnings and instructions.
Flammable Vapors
WARNING
Fire or Explosion Hazard
• Read instruction manual before installing, using or
servicing water heater.
• Improper use may result in fire or explosion.
• Maintain required clearances to combustibles.
Keep combustibles such as boxes, magazines, clothes, etc.
away from the water heater area.
Site Location
• DO NOT install this water heater in any occupied space
of the manufactured (mobile) home. There shall be no
openings between the occupied space of the manufactured
(mobile) home and the water heater enclosure.
• The water heater must be installed indoors and in a vertical
position on a level surface. Do not install in bathrooms,
bedrooms, or any occupied room normally kept closed.
• Locate the water heater near the existing gas piping. If
installing a new gas line, locate the water heater to minimize
the pipe length and elbows.
• The water heater should be located in an area not subject
to freezing temperatures. Water heaters located in
unconditioned spaces may require insulation of the water
piping and drain piping to protect against freezing. The
drain and controls must be easily accessible for operation
and service. Maintain proper clearances as specified on
the water heater labeling.
• Do not locate the water heater near an air-moving device.
The operation of air-moving devices such as exhaust fans,
ventilation systems, clothes dryers, fireplaces, etc., can
affect the proper operation of the water heater. Special
attention must be given to conditions these devices may
create. Flow reversal of flue gases may cause an increase
of carbon monoxide inside of the dwelling.
• If the water heater is located in an area that is subjected to
lint and dirt, it may be necessary to periodically clean the
base-ring filter and flame-arrestor (s ee E x ter nal Inspect ion
& Cleaning of the Flame-arrestor).
NOTE: This water heater must be installed according to all local
and state codes or, in the absence of local and state codes,
the “National Fuel Gas Code”, ANSI Z223.1 (NFPA 54)-current
edition. Manufactured home manufacturers must conform with
“The Manufactured Home Construction and Safety Standard,
Title 24 CFR, Part 3280”.
Do not use or store flammable products such as gasoline,
solvents, or adhesives in the same room or area near the
water heater. If such flammables must be used, all gas burning
appliances in the vicinity must be shut off and their pilot lights
extinguished. Open the doors and windows for ventilation while
flammable substances are in use.
If flammable liquids or vapors have spilled or leaked in the
area of the water heater, leave the area immediately and call
13
IMPORTANT: The water heater should be located in an area
where leakage of the tank or connections will not result in damage
to the area adjacent to the water heater or to lower floors of the
structure. Due to the normal corrosive action of water, the tank will
eventually leak after an extended period of time. Also any external
plumbing leak, including those from improper installation, may
cause early failure of the tank due to corrosion if not repaired. If
the homeowner is uncomfortable with making the repair a qualified
technician should be contacted. A suitable metal drain pan should
be installed under the water heater as shown below, to help protect
the property from damage which may occur from condensate
formation or leaks in the piping connections or tank. The pan
must limit the water level to a maximum depth of 1-3/4” and be
two inches wider than the heater and piped to an adequate drain.
NOTE: The pan must not restrict combustion air flow. Locate
the water heater near an adequate drain (Figure 1). In cold
climates, it is recommended that the drain pipe be terminated at
an adequate drain inside the building. The piping should be at
least 3/4” ID and pitched for proper drainage.
METAL
DRAIN
PAN
AT LEAST 2” GREATER THAN THE
DIAMETER OF THE WATER HEATER.
PIPED TO AN
ADEQUATE DRAIN
SEE FIGURE 1
FIGURE 8.
CAUTION: When making pilot holes in the water
heater itself, ensure that you drill only the outer jacket.
Also, to prevent leaks in the metal drain pan, seal each drill
location with a heavy bead of silicone sealant.
2. Secure the top of the water heater with the provided bracket
and screws or install other acceptable means of support
(e.g., support strap).
SCREW
BOTTOM OF WATER HEATER
SCREW
BRACKET
FIGURE 9.
Insulation Blankets
Insulation blankets available to the general public for external
use on gas water heaters are not necessary with Kenmore
products. The purpose of an insulation blanket is to reduce the
standby heat loss encountered with storage tank heaters. Your
Kenmore water heater meets or exceeds the National Appliance
Energy Conservation Act standards with respect to insulation
and standby loss requirements, making an insulation blanket
unnecessary.
Water heater life depends upon water quality, water usage,
water temperature and the environment in which the water
heater is installed. Water heaters are sometimes installed in
locations where leakage may result in property damage, even
with the use of a metal drain pan piped to a drain. However,
unanticipated damage can be reduced or prevented by a leak
detector or water shut-off device used in conjunction with a
piped metal drain pan. These devices are available from some
plumbing supply wholesalers and retailers, and detect and react
to leakage in various ways:
• Sensors mounted in the metal drain pan that trigger an
alarm or turn off the incoming water to the water heater
when water is detected.
• Sensors mounted in the metal drain pan that turn off the
water supply to the entire home when water is detected in
the drain pan.
• Water supply shut-off devices that activate based on the
water pressure differential between the cold water and hot
water pipes connected to the water heater.
• Devices that will turn off the gas supply to a gas water
heater while at the same time shutting off its water supply.
Securing Water Heater to Floor and Wall
The water heater must be secured to the floor and to the wall
of the enclosure as described below. See also “Enclosure
Installation.”
1. After properly locating the water heater, fasten it to the
floor with the brackets and screws that were provided
(Figure 9). Simply pre-drill each screw location in the
metal drain pan and water heater jacket with a 1/8” drill bit.
Because of installation variances, these brackets can be
located at any points around the circumference of the jacket.
However, they should be spaced apart at equal distances.
WARNING
Should you choose to apply an insulation blanket to this
heater, you should follow these instructions. (See Figure 1
for identification of components mentioned below). Failure to
follow these instructions can restrict the air flow required for
proper combustion, potentially resulting in fire, asphyxiation,
serious personal injury or death.
• Do not apply insulation to the top of the water heater, as
this will interfere with safe operation of the draft hood.
• Do not cover the outer door, thermostat or temperature &
pressure relief valve.
• Do not allow insulation to come within 2” (50.8 mm) of
the floor to prevent blockage of combustion air flow to the
burner.
• Do not cover the instruction manual. Keep it on the side of
the water heater or nearby for future reference.
• Do obtain new warning and instruction labels from Sears
for placement on the blanket directly over the existing
labels.
14
• Do inspect the insulation blanket frequently to make
certain it does not sag, thereby obstructing combustion air
flow.
Clearances and Accessibility
NOTE: Minimum clearances from combustible surfaces are
stated on the label adjacent to the gas control valve/thermostat
of the water heater. The water heater is certified for installation
on a combustible floor.
• IMPORTANT: If installing over carpeting, the carpeting
must be protected by a metal or wood panel beneath the
water heater. The protective panel must extend beyond the
full width and depth of the water heater by at least three
inches (76.2mm) in any direction; or i f in an a lcove o r clo set
installation, the entire floor must be covered by the panel.
• Figure 10 may be used as a reference guide to locate the
specific clearance locations. A minimum of 24 inches of
front clearance should be provided for inspection and
service.
VENT
BACK
SIDES
TOP
TO
CEILING
Filling the Water Heater
Never use this water heater unless it is completely full of water.
To prevent damage to the tank, the tank must be fi lled with water.
Water must fl ow from the hot water faucet before turning “ON” gas
to the water heater. To fi ll the water heater with water:
• Close the water heater drain valve by turning the handle to
the right (clockwise). The drain valve is on the lower front of
the water heater.
• Open the cold water supply valve to the water heater.
NOTE: The cold water supply valve must be left open
when the water heater is in use.
• To ensure complete fi lling of the tank, allow air to exit by
opening the nearest hot water faucet. Allow water to run until
a constant fl ow is obtained. This will let air out of the water
heater and the piping.
• Check all water piping and connections for leaks. Repair as
needed.
TOP
VIEW
FRONT
24” MINIMUM
FOR SERVICE
FIGURE 10.
SIDES
15
WARNING
IGNITER
WIRE
RED WIRE
(LEFT SIDE)
PILOT
T
UBEMANIFOLD TUBE
IGNITER
BUTTON
IGNITER
LEAD
WIRE
WHITE
WIRE
(RIGHT
SIDE)
For your safety, the following procedures should be
t
performed by a qualified technician as it involves
disconnection of gas piping and leak testing.
Do not connect a natural gas water heater to an L.P.
t
gas supply.
Do not connect an L.P. gas water heater to a natural
t
gas supply.
A. Remove the Manifold/Burner Assembly
1. Turn off the gas supply to the water heater at the manual
gas shut-off valve. This valve is typically located beside the
water heater. Note the position of the shut-off valve in the
open/on position, then proceed to turn it off.
2. On the lower front of the water heater, locate the gas control
valve/thermostat.
3. Turn the gas control/temperature knob to the “OFF” position.
With the unit shut-off, allow sufficient time for the water
heater to cool before performing any maintenance.
4. Remove the outer door.
5. Remove the two screws securing the installed manifold
door assembly to the combustion chamber (Figure 11).
6. Disconnect the following from the gas control valve/thermostat:
pilot tube, igniter wire, and manifold tube. See Figure 11.
7. Using needle nose pliers, disconnect the white and red
thermopile wires from the gas control valve/thermostat
(Figure 11).
8. Grasp the manifold tube and push down slightly to free the
manifold tube and pilot tube.
9. Carefully remove the manifold/burner assembly from the burner
compartment. NOTE: Be sure not to damage internal parts.
B. Convert the Gas Control Valve/Thermostat
1. Remove the cap (shown in Figure 12).
2. Remove the conversion fitting by turning it counter-clockwise
with a flathead screwdriver.
3. Thread the opposite end of the conversion fitting into the opening
by turning it clockwise, then tighten it with a flathead screwdriver.
a. LP GAS: If you are converting the unit to use LP gas
GAS CONTROL/
TEMPERATURE KNOB
PIEZO IGNITER BUTTON
PILOTTUBE
VIEWPORT
OUTER DOOR
NOT SHOWN
MANIFOLD SCREW (2)
(propane), verify that “LP” is marked on the exposed end
of the fitting. “LP” must face outward (toward you.) See
GAS CONTROL VALVE/THERMOSTAT CONNECTIONS
CONNECTIONS
MANIFOLDTUBE
VAC
MANIFOLD COMPONENT BLOCK
GAS CONVERSION
b. NATURAL GAS: If you are converting the unit to use
4. Replace the cap.
C. Install the Conversion Manifold/Burner
Assembly
1. Check the door gasket for damage or imbedded debris prior
to installation.
2. Inspect the view port for damage and replace as required.
3. Insert the conversion manifold/burner assembly into the
burner compartment, making sure that the tip of the manifold
tube engages in the slot of the bracket inside the combustion
chamber. NOTE: For 30 gallon models, the LP manifold/
burner assembly is identified by a yellow square (label) on
the packaging. For 40 gallon models, the LP manifold/burner
assembly is identified by a green square on the packaging.
4. Inspect the door gasket and make sure there is no fiberglass
insulation between the gasket and the combustion chamber.
5. Replace the two screws that secure the manifold/burner
assembly door to the combustion chamber, then tighten
them securely. There should be no space between the
gasket part of the manifold door and the combustion
chamber. IMPORTANT: Do not operate the water heater
if the door gasket does not create a seal between the
manifold door and the combustion chamber.
6. Reconnect the manifold tube and pilot tube to the gas
control valve/thermostat (Figure 11). Do not cross-thread
or apply any thread sealant to the fittings. IMPORTANT: If
you were supplied with a new ferrule nut in a parts kit, follow
these steps to connect the pilot tube:
A.) Install the ferrule nut into the gas valve at the pilot tube
location, hand tight only. B.) Insert the pilot tube into the
ferrule nut until the tube bottoms out, then tighten the nut with
a 7/16” wrench until the crimp connection seals to the pilot tube.
C.) Continue to tighten until the nut is tight in the gas valve.
7. Connect the white and red thermopile wires to the gas
control valve/thermostat. See Figure 11.
8. Reconnect the igniter wire.
9. Turn the gas supply on and follow the Lighting Instructions.
10. With the main burner lit, check for leaks at the manifold and
pilot connections by brushing on an approved non-corrosive
leak detection solution. If such a solution is not available,
use a mixture of hand dish washing soap and water (one
part soap to 15 parts water). Bubbles forming indicate a
leak. Correct any leak found.
11. Verify proper operation; replace outer door.
THERMOPILE
WIRE
THERMAL
SWITCH
MANIFOLD
DOOR
GAS CONTROL VALVE/THERMOSTAT
16
Figure 12. If “NAT” faces outward, repeat step 2.
natural gas, verify that “NAT” is marked on the exposed
end of the fitting. “NAT” must face outward (toward you.)
See Figure 12. If “LP” faces outward, repeat step 2.
CONVERSION FITTING
CAP
NATURAL GAS:
“NAT” FACES OUTWARD
(TOWARD YOU).*
LP GAS:
“LP” FACES OUTWARD
(TOWARD YOU).*
* ORIENTATION MAY VARY. FITTING TO BE TIGHT.
FIGURE 12.FIGURE 11.
GAS SUPPLY
WARNING
Explosion Hazard
• Use a new CSA approved gas supply line.
• Install a shut-off valve.
• Do not connect a natural gas water heater to an
L.P. gas supply.
• Do not connect an L.P. gas water heater to a
natural gas supply.
• Failure to follow these instructions can result in
death, explosion, or carbon monoxide poisoning.
Gas Requirements
IMPORTANT: Read the rating plate to be sure the water heater
is made for the type of gas you will be using in your home. This
information will be found on the rating plate located near the gas
control valve/thermostat. If the information does not agree with
the type of gas available, do not install or light. Call your dealer.
NOTE: An odorant is added by the gas supplier to the gas used
by this water heater. This odorant may fade over an extended
period of time. Do not depend upon this odorant as an indication
of leaking gas.
Gas Piping
MANUAL GAS
SHUT-OFF VALVE
GROUND
JOINT
UNION
CHECK WITH
LOCAL UTILITY
FOR MINIMUM HEIGHT
3” MINIMUM
DRIP LEG
FIGURE 13.
Gas Pressure
WARNING
Explosion Hazard
• Gas leaks can not always be detected by smell.
• Gas suppliers recommend that you use a gas
detector approved by UL or CSA.
• For more information, contact your gas supplier.
• If a gas leak is detected, follow the “What to do if you
smell gas” instructions on the cover of this manual.
The gas piping must be installed according to all local and
state codes or, in the absence of local and state codes, the
“National Fuel Gas Code”, ANSI Z223.1 (NFPA 54)-current
edition. Manufactured home manufacturers must conform with
“The Manufactured Home Construction and Safety Standard,
Title 24 CFR, Part 3280”.
Tables 1 and 2 on the following page provide a sizing reference
for commonly used gas pipe materials. Consult the “National Fuel
Gas Code” for the recommended gas pipe size of other materials.
NOTE: Use pipe joint compound or teflon tape marked as being
resistant to the action of petroleum [Propane (L.P.)] gases.
(See Figure 13.)
1. Install a readily accessible manual shut-off valve in the gas
supply line as recommended by the local utility. Know the
location of this valve and how to turn off the gas to this unit.
2. Install a drip leg (if not already incorporated as part of
the water heater) as shown. The drip leg must be no less
than three inches long for the accumulation of dirt, foreign
material, and water droplets.
3. Install a ground joint union between the gas control valve/
thermostat and the manual shut-off valve. This is to allow
easy removal of the gas control valve/ thermostat.
4. Turn the gas supply on and check for leaks. Test all
connections by brushing on an approved noncorrosive
leak-detection solution. Bubbles will show a leak. Correct
any leak found.
IMPORTANT: The gas supply pressure must not exceed the maximum
supply pressure as stated on the water heater’s rating plate. The
minimum supply pressure is for the purpose of input adjustment.
Gas Pressure Testing
IMPORTANT: This water heater and its gas connection must be
leak tested before placing the appliance in operation.
• If the code requires the gas lines to be tested at a pressure
exceeding 14” W.C., the water heater and its manual shut-off
valve must be disconnected from the gas supply piping system
and the line capped.
• If the gas lines are to be tested at a pressure less than 14” W.C.,
the water heater must be isolated from the gas supply piping
system by closing its manual shut-off valve.
U.L. recognized fuel gas and carbon monoxide (CO) detectors are
recommended in all applications and should be installed using the
manufacturer’s instructions and local codes, rules and regulations.
NOTE: Air may be present in the gas lines and could prevent the
pilot from lighting on initial start-up. The gas lines should be purged
of air by a qualified technician after installation of the gas piping
system. While purging the gas piping system of air, ensure that
the fuel is not spilled in the area of the water heater installation,
or any source of ignition. If the fuel is spilled while purging the
piping system of air follow the “WHAT TO DO IF YOU SMELL
GAS” instructions on the cover of this manual.
17
LP Gas Only
Liquefi ed petroleum gas is over 50% heavier than air and in the
occurrence of a leak in the system, the gas will settle at fl oor level.
Basements, crawl spaces, skirted areas under mobile homes
(even when ventilated), closets and areas below ground level will
serve as pockets for the accumulation of gas. Before lighting an
L.P. gas water heater, smell all around the appliance at fl oor level.
If you smell gas, follow the instructions as given in the warning on
the front page.
When your L.P. tank runs out of fuel, turn off the gas at all gas
appliances including pilot lights. After the tank is refi lled, all
appliances must be re-lit according to their manufacturer’s
instructions.
WARNING
Explosion Hazard
Have a qualified technician make sure that the L.P.
gas operating pressure does not exceed 13” water
column.
Failure to do so can result in death, explosion, or fire.
18
COMBUSTION AIR SUPPLY & VENTILATION
WARNING
Carbon Monoxide Warning
The vent system must be installed according to all
local and state codes or, in the absence of local and
state codes, the “National Fuel Gas Code”, ANSI
Z223.1 (NFPA 54)-current edition. Manufactured home
manufacturers must comply with the “Manufactured
Home Construction and Safety Standard, Title 24 CFR,
Part 3280.”
Failure to do so can result in death, explosion, or
carbon monoxide poisoning.
IMPORTANT: Air for combustion and ventilation must not come
from a corrosive atmosphere. Any failure due to corrosive elements
in the atmosphere is excluded from warranty coverage.
The following types of installation (not limited to the following)
will require outdoor air for combustion due to chemical exposure
and may reduce but not eliminate the presence of corrosive
chemicals in the air:
• beauty shops
• photo processing labs
• buildings with indoor pools
• water heaters installed in laundry, hobby, or craft rooms
• water heaters installed near chemical storage areas
Combustion air must be free of acid-forming chemicals such as sulfur,
fluorine, and chlorine. These elements are found in aerosol sprays,
detergents, bleaches, cleaning solvents, air fresheners, paint, and
varnish removers, refrigerants, and many other commercial and
household products. When burned, vapors from these products
form highly corrosive acid compounds. These products should not
be stored or used near the water heater or air inlet.
Vent Pipe System
This water heater uses a non-direct, single-pipe vent system
to remove exhaust gases created by the burning of fossil
fuels. Air for combustion is taken from the immediate water
heater location or is ducted in from the outside (see “Enclosure
Installation”).
This water heater must be properly vented for the removal of
exhaust gases to the outside atmosphere. Correct installation
of the vent pipe system is mandatory for the proper and efficient
operation of this water heater and is an important factor in the
life of the unit.
The vent pipe must be installed according to all local and state
codes or, in the absence of local and state codes, the “National
Fuel Gas Code”, ANSI Z223.1 (NFPA 54)-current edition.
Manufactured home manufacturers must conform with “The
Manufactured Home Construction and Safety Standard, Title
24 CFR, Part 3280.” The vent pipe installation must not be
obstructed so as to prevent the removal of exhaust gases to the
outside atmosphere.
IMPORTANT: The use of vent dampers is not recommended
by the manufacturer of this water heater. Although some vent
dampers are certified by CSA International, this certification
applies to the vent damper device only and does not mean they
are certified for use on this water heater.
U.L. recognized fuel gas and carbon monoxide (CO) detectors are
recommended in all applications and should be installed using the
manufacturer’s instructions and local codes, rules, or regulations.
IMPORTANT:
• If you lack the necessary skills required to properly install
this venting system, you should not proceed, but get help
from a qualified technician.
• DO NOT common vent this water heater with any other
appliance.
Draft Hood Installation
SHEET METAL SCREWS (FOUR PROVIDED)
DRAFT HOOD
LEGS
SLOT
SLOT
LEGS
JACKET TOP
INSTALL THE DRAFT HOOD WITH
THE FOUR SCREWS PROVIDED.
FIGURE 14.
Align the legs of the draft hood with the slots provided. Insert
the legs and secure the draft hood to the water heater’s top
with the four screws provided as shown in Figure 14. Do not
alter the draft hood in any way. If you are replacing an existing
water heater, be sure to use the draft hood supplied with this
water heater.
Roof Jack Installation
This water heater must have a properly-installed draft hood
and be connected to a listed roof jack that terminates to the
outdoors. The roof jack vent pipe must be secured to the draft
hood with sheet metal screws. (Roof jack not furnished.)
The following roof jack models are certified for use with this
water heater:
1. Field Controls No. 987
2. Ventline 2073
3. White Metal Products 3RJ
Install the roof jack according to its manufacturer’s instructions.
19
Enclosure Installation
Air for combustion and ventilation must not be supplied from
the occupied spaces of the manufactured (mobile) home.
IMPORTANT: The opening that provides outside air to your
water heater must have a minimum free area of 20 square
inches. Also, ensure that your installation complies with all
applicable code requirements.
The following methods may be used to provide sufficient
combustion and ventilation air to the water heater when it is
installed in the enclosure.
Method I (Figure 15)
Provide a single air opening in the exterior door of the
enclosure. The opening must have a minimum free area of
20 square inches. The bottom of the opening must be within
6 inches from the bottom edge of the door. Cover the opening
with 1/4 inch wire mesh screen or louvers.
Method II (Figure 16)
For enclosures with a solid exterior door, provide an air opening
in the floor. The opening must have a minimum diameter of 5
inches (20 square inches minimum free area) and be covered
with 1/4-inch wire mesh screen.
Also, if the manufactured home is skirted, an air intake opening
with a minimum free area of 32 square inches must be provided
in the skirt. Other gas fired appliances in the home may require
additional free air openings. Consult the manufacturers for
correct sizing.
IMPORTANT:
• When using Method II, ensure that the drain pan does not
cover the air intake opening in the floor.
• A discharge line must be installed as described in the
“Temperature and Pressure Relief Valve” section.
• Do not obstruct the combustion and ventilation air openings.
• Do not use the enclosure as a storage area.
• Secure the water heater as described in “Securing Water
Heater to Floor and Wall.”
Method I:
Door Opening
ROOF JACK
ROOF
CEILING
MAINTAIN MIN. CEILING
CLEARANCE PER LABEL
ON WATER HEATER
MAINTAIN MIN.
CLEARANCE PER CODE
SECURE TOP
TO WALL WITH
STRAP AND
SCREWS
MAINTAIN MIN.
CLEARANCES
SECURE WATER HEATER
TO FLOOR WITH BRACKETS
AND SHEET METAL
SCREWS (PROVIDED)
FLOOR
* FREE AREA FOR AIR OPENING: 20 SQ. IN. MIN.
(NOT INCLUDED)
METAL
DRAIN PAN
ONE OPENING
IN DOOR *
PROTECTION:
1/4 IN. WIRE
MESH OR
LOUVERS
OPENING:
20 SQ. IN. MIN.
OUTSIDE
FRESH
AIR
6 INCHES MAX.
ABOVE BOTTOM
EDGE OF DOOR
Method II:
Floor Opening
ROOF JACK
ROOF
CEILING
MAINTAIN MIN. CEILING
CLEARANCE PER LABEL
ON WATER HEATER
MAINTAIN MIN.
CLEARANCE PER CODE
SECURE TOP
TO WALL WITH
STRAP AND
SCREWS
MAINTAIN MIN.
CLEARANCES
SECURE WATER HEATER
TO FLOOR WITH BRACKETS
AND SHEET METAL
SCREWS (PROVIDED)
AIR INTAKE
FLOOR
IMPORTANT: DRAIN PAN MUST
NOT BLOCK OR COVER AIR INTAKE
* FREE AREA FOR AIR OPENING: 20 SQ. IN. MIN.
(NOT INCLUDED)
METAL
DRAIN PAN
FLOOR OPENING (5 IN. MIN. DIA.) *
1/4 IN. WIRE MESH PROTECTION
FIGURE 15.
FIGURE 16.
20
WATER SYSTEM PIPING
Piping Installation
Piping, fittings, and valves should be installed according to the
installation drawing (Figure 17). If the indoor installation area
is subject to freezing temperatures, the water piping must be
protected by insulation.
The water supply pressure should not exceed 80 psi. If this
occurs, a pressure reducing valve with a bypass may need to
be installed in the cold water inlet line. This should be placed
on the supply to the entire house in order to maintain equal hot
and cold water pressures.
IMPORTANT: Heat cannot be applied to the water fittings on
the heater as they may contain nonmetallic parts. If solder
connections are used, solder the pipe to the adapter before
attaching the adapter to the hot and cold water fittings.
IMPORTANT: Always use a good grade of joint compound and
be certain that all fittings are drawn up tight.
1. Install the water piping and fittings as shown in Figure 17.
Connect the cold water supply (3/4” NPT) to the cold water
inlet fitting. Connect the hot water supply (3/4” NPT) to the
hot water outlet fitting.
IMPORTANT: Some models may contain energy saving heat
traps to prevent the circulation of hot water within the pipes. Do
not remove the inserts within the heat traps.
2. The installation of unions in both the hot and cold water
supply lines is recommended for ease of removing the
water heater for service or replacement.
3. The manufacturer of this water heater recommends
installing a mixing valve or an anti-scald device in the
domestic hot water line as shown in Figure 18. These
valves reduce the point-of-use temperature of the water by
mixing cold and hot water and are readily available for use.
4. If installing the water heater in a closed water system,
install an expansion tank in the cold water line as specified
under “Closed System/Thermal Expansion.”
5. Install a shut-off valve in the cold water inlet line. It
should be located close to the water heater and be easily
accessible. Know the location of this valve and how to shut
off the water to the heater.
6. A temperature and pressure relief valve must be installed
in the opening marked “Temperature and Pressure
(T & P) Relief Valve” on the water heater. A discharge line
must be added to the opening of the T&P Relief Valve.
Follow the instructions under “Temperature and Pressure
Relief Valve.”
7. After piping has been properly connected to the water
heater, remove the aerator at the nearest hot water faucet.
Open the hot water faucet and allow the tank to completely
fill with water. To purge the lines of any excess air, keep
the hot water faucet open for 3 minutes after a constant
flow of water is obtained. Close the faucet and check all
connections for leaks.
MASSACHUSETTS: INSTALL
A VACUUM RELIEF IN COLD
WATER LINE PER SECTION
19 MGL 142.
TEMPERATURE AND PRESSURE (T&P)
HOT WATER
OUTLET
DISCHARGE PIPE
(DO NOT CAP
OR PLUG)
1” MINIMUM
METAL
DRAIN PAN
RELIEF VALVE (OPTIONAL TOP T&P
RELIEF VALVE NOT SHOWN)
IN A CLOSED SYSTEM,
USE A THERMAL
EXPANSION TANK
COLD WATER
SUPPLY
FIXTURES
PAN DRAIN LINE 3/4” ID MINIMUM
DRAIN LINE TERMINATES
EXTERNAL TO BUILDING
COLD WATER
INLET VALVE
(SHUT-OFF VALVE)
TO
VALVE WITH
COLD WATER
INLET
PRESSURE
REDUCING
BYPASS
FIGURE 17.
TEMPERED WATER
TO FIXTURES
UNTEMPERED
HOT WATER
FROM HOT
WATER
OUTLET
MIXING VALVE
(SET TO 120°F)
FOLLOW THE MIXING
VALVE MANUFACTURER’S
INSTRUCTIONS
FROM COLD
WATER INLET
FIGURE 18.
Please note the following:
• The system should be installed only with piping that is
suitable for potable (drinkable) water such as copper, CPVC,
or polybutylene. This water heater must not be installed
using iron piping or PVC water piping.
• Use only pumps, valves, or fittings that are compatible with
potable water.
• I t is re com mend th at only ful l fl ow ball or g ate va lve s are use d
in water piping installations. The use of valves that may cause
excessive restriction to water flow is not recommended.
• Use only 95/5 tin-antimony or other equivalent solder. Any
lead based solder must not be used.
• Piping that has been treated with chromates, boiler seal, or
other chemicals must not be used.
• Chemicals that may contaminate the potable water supply
must not be added to the piping system.
21
Water Piping Pressure Test
WARNING
If the water piping system is to be air pressure tested, the
water heater must be disconnected from the water piping
system. Failure to disconnect the water heater during air
pressure testing of the water piping system could result in
DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
This section is only for the manufacturer installing the water
heater when the installation is to comply with H.U.D. Standards.
When testing the water ways, H.U.D. standards state: “Water
distribution system. All water piping in the water distribution
system shall be subjected to a pressure test. The test shall be
made by subjecting the system to air or water at 100 psi for 15
minutes without loss of pressure. When air pressure is used, the water heater shall not be connected during the test.”
AIR PRESSURE TESTING
HOT WATER
OUTLET
FIGURE 19.
Closed System/Thermal Expansion
WHEN AIR TESTING,
REMOVE THE WATER
LINES FROM THE WATER
HEATER.
TEMPERATURE AND PRESSURE (T&P)
RELIEF VALVE (OPTIONAL TOP T&P
RELIEF VALVE NOT SHOWN)
DISCHARGE PIPE
(DO NOT CAP OR PLUG)
PAN DRAIN LINE
3/4” ID
1” MINIMUM
METAL
DRAIN PAN
MINIMUM
DRAIN LINE TERMINATES
EXTERNAL TO BUILDING
As water is heated, it expands (thermal expansion). In a closed
system, the volume of water will increase. As the volume of water
increases, there will be a corresponding increase in water pressure
due to thermal expansion. Thermal expansion can cause premature
tank failure (leakage). This type of failure is not covered under the
limited warranty. Thermal expansion can also cause intermittent
temperature-pressure relief valve operation: water discharged from
the valve due to excessive pressure build up. The temperaturepressure relief valve is not intended for the constant relief of thermal
expansion. This condition is not covered under the limited warranty.
A properly sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion. Thermal expansion tanks are available from Sears
stores and through the Sears Service Centers. Contact the
local plumbing inspector, water supplier and/or the Sears
Service Center for assistance in controlling these situations.
(For additional information, see the Troubleshooting Guide later
in this manual.)
FIGURE 20.
For protection against excessive pressures and temperatures,
a temperature and pressure relief valve must be installed in the
opening marked “T & P RELIEF VALVE.” (See Figure 20). This
valve must be design certified by a nationally recognized testing
laboratory that maintains periodic inspection of the production
of listed equipment or materials as meeting the requirements
for Relief Valves for Hot Water Supply Systems, ANSI Z21.22.
The function of the temperature and pressure relief valve is to
discharge water in large quantities in the event of excessive
temperature or pressure developing in the water heater. The
valve’s relief pressure must not exceed the working pressure of
the water heater as stated on the rating plate.
IMPORTANT: Only a new temperature and pressure relief valve
should be used with your water heater. Do not use an old or
existing valve as it may be damaged or not adequate for the
working pressure of the new water heater. Do not place any
valve between the relief valve and the tank.
The Temperature & Pressure Relief Valve:
• Must not be in contact with any electrical part.
• Must be connected to an adequate discharge line.
• Must not be rated higher than the working pressure shown
on the rating plate of the water heater.
The Discharge Line:
• Must not be smaller than the pipe size of the relief valve or
have any reducing coupling installed in the discharge line.
• Must not be capped, blocked, plugged or contain any valve
between the relief valve and the end of the discharge line.
• Must pass through the structural floor and terminate
external to the building. In cold climates, it is recommended
that the discharge pipe be terminated at an adequate drain
inside the building.
22
• Must be capable of withstanding 250°F (121°C) without distortion.
• Must be installed to allow complete drainage of both the
valve and discharge line.
T&P Relief Valve and Pipe Insulation (Some Models)
1. Locate the temperature and pressure relief valve on the water
heater (also known as a T&P relief valve). See Figure 21.
2. Locate the slit running the length of the T&P relief valve
insulation.
3. Spread the slit open and fit the insulation over the T&P relief
valve. See Figure 21. Apply gentle pressure to the insulation
to ensure that it is fully seated on the T&P Relief Valve. Once
seated, secure the insulation with duct tape, electrical tape,
or equivalent. IMPORTANT: The insulation and tape must not
block the discharge opening or hinder access to the manual
relief lever (Figure 21). Ensure a discharge pipe is installed into
the T&P valve discharge opening per the instructions in this
manual.
4. Locate the hot water (outlet) & cold water (inlet) pipes to the
water heater.
5. Locate the slit running the length of a section of pipe
insulation.
6. Spread the slit open and slip the insulation over the cold water
(inlet) pipe. Apply gentle pressure along the length of the
insulation to ensure that it is fully seated around the pipe. Also,
ensure that the base of the insulation is flush with the water
heater. Once seated, secure the insulation with duct tape,
electrical tape, or equivalent.
7. Repeat steps 5 and 6 for the hot water (outlet) pipe.
8. Add additional sections of pipe insulation as needed.
T&P Relief Valve Insulation
Manual Relief Lever
T&P Relief Valve
T&P Relief Valve
Drain Line
FIGURE 21.
23
OPERATING YOUR WATER HEATER
Lighting Instructions
Read and understand these directions thoroughly before
attempting to light or re-light the pilot. Make sure the view port is
not missing or damaged. (See Figure 29.) Make sure the tank
is completely filled with water before lighting the pilot. Check the
rating plate near the gas control valve/thermostat for the correct
gas. Do not use this water heater with any gas other than the
one listed on the rating plate unless the water heater has been
properly converted. Refer to the “Gas Conversion” section of
this manual. If you have any questions or doubts, consult your
gas supplier or gas utility company.
Lighting the Pilot:
1. Read and follow the lighting instructions on the water
heater’s label.
2. Turn the Control Knob to Pilot. Press the Knob in fully and
hold it in. (The knob will travel in about 1/4-inch if it is set
to Pilot correctly.)
3. Click the Igniter button continuously for up to 90 seconds
or until the Status Light begins to blink.
If the Status Light does not begin to blink after 90
seconds, STOP. Wait 10 minutes before attempting
to relight the Pilot. Repeat these steps 2-3 times, if
necessary.
The circuitry in this gas valve requires that you wait 10
minutes between lighting attempts.
If the Status Light blinks, release the Control Knob and
turn it to the desired setting. (“Hot” is approximately
120°F)
.
If the Status Light Does Not Blink:
1. Wait 10 minutes before another lighting attempt.
2. If the Status Light did not blink, repeat the lighting
procedure by following the lighting instructions on the
water heater’s label. Remove the outer door. The Control
Knob must be set to Pilot and held in continuously while
clicking the igniter button (about once per second for up
to 90 seconds). To observe the Pilot, remove the outer
door and look through the view port (sight glass). See
Figure 29.
3. Continue clicking the Igniter button (for up to 90 seconds)
until Pilot lights.
4. Once the Pilot is lit, continue to hold the Control Knob in
until the Status Light begins to blink.
5. Release Control Knob and set Knob to desired
temperature setting. (“Hot” is approximately 120°F.)
6. Replace the outer door.
If the Pilot Does Not Light:
1. Wait 10 minutes before another lighting attempt.
If the pilot does not light, the Igniter may not be
sparking or the unit may not be getting gas (or for a new
installation, there may still be air in the gas line).
Each time you click the igniter button, you should be able
to see the spark by looking through the view port. See
WARNING
Explosion Hazard
Replace view port if glass is missing
or damaged.
Failure to do so can result in death,
explosion or fire.
Figure 29. (You may have to darken the room lights to
see the spark.) You do not have to push the Control Knob
in to check the Igniter button. Simply look through the
sight glass while clicking the Igniter button and look for
a spark. If you can’t see a spark when the Igniter button
is clicked, check the wiring connections from the Igniter
button and make sure that they are tight.
2. If you see the Igniter spark, try relighting the pilot by
following the instructions on the water heater’s label.
Ensure that the gas supply is turned on. There may
be air in the gas line, and several lighting attempts
may be needed to completely fill the line with gas and
successfully light the pilot.
If the Pilot Lights but the Status Light Does Not
Blink:
1. If the pilot lights, continue to hold the Control Knob in until
the Status Light blinks. If the pilot is lit and remains lit for
90 seconds and the Status Light still does not blink, the
thermopile connections may be loose, the thermal switch
may need to be reset, or the thermopile may be defective.
2. Remove the outer door.
3. Press the reset button on the thermal switch (Figure 29).
4. If switch clicks, it may have tripped. Do not light the Pilot
if flammable vapors are present. Check flame arrestor
for signs of discoloration (which could be caused by
flammable vapors). If the flame arrestor is discolored,
do not attempt to relight the Pilot. Have the water heater
inspected by a qualified service technician.
5. Check the wiring connections from the thermopile and
the thermal switch to the gas control valve/thermostat.
Ensure that all wiring connections are tight.
See Figure 29.
6. Replace the outer door.
7. Wait 10 minutes and try to light the Pilot according to the
instructions on the water heater’s label.
8. While clicking the Igniter button continuously, the Control
Knob must be set to Pilot and held in until the Status Light
blinks. Once the Status Light blinks, release the Control
Knob and set the Knob to the desired temperature setting.
(“Hot” is approximately 120°F.)
24
FOR YOUR SAFETY READ BEFORE LIGHTING
WARNING:
fire or explosion may result causing property damage, personal
injury or loss of life.
If you do not follow these instructions exactly, a
FLAMMABLE
BEFORE LIGHTING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES
Use only your hand to push in or turn the gas control
This appliance has a pilot which is lit by a piezo-
A.
electric spark gas ignition system. Do not open
the inner door of the appliance and try to light
the pilot by hand.
B.
BEFORE LIGHTING
area for gas. Be sure to smell next to the floor
smell all around the appliance
because some gas is heavier than air and will
settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor's
phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier, call the fire
department.
C.
knob. Never use tools. If the knob will not push in or
turn by hand, don't try to repair it, call a qualified
service technician. Force or attempted repair may
result in a fire or explosion.
Do not use this appliance if any part has been under
D.
water. Immediately contact a qualified installer or
service agency to replace a flooded water heater.
Do not attempt to repair the unit! It must be replaced!
DO NOT USE THIS APPLIANCE IF THERE HAS
E.
BEEN AN IGNITION OF VAPORS. Immediately
call a qualified service technician to inspect the
appliance. Water heaters subjected to a
flammable vapors ignition will show a
discoloration on the air intake grid and require
replacement of the entire water heater.
LIGHTING INSTRUCTIONS
Gas Control/Temperature Knob
Status
Light
VAC
Igniter
GAS CONTROL
FIGURE 'A'
120°F
120°F
Mark
Mark
"OFF" POSITION
FIGURE 'B'
120°F
120°F
Mark
Mark
"PILOT" POSITION
CONTROL KNOB
1. STOP! It is imperative that you read all safety
warnings before lighting the pilot.
2. Turn the gas control/temperature knob
counterclockwise to the "OFF" setting.
3. Wait ten (10) minutes to clear out any gas. If you then
smell gas, STOP! Follow “ B” in the safety
information above on this label. If you do not
smell gas, go to the next step.
4. Turn the gas control/temperature knob clockwise to
“ PILOT”. See Figure ‘B’.
5. Press the gas control/temperature knob all the way
in and hold it in. The knob should travel in about
1/4 inch (6.35 mm) if it is set to "PILOT" correctly.
While holding the gas control/temperature knob in,
click the igniter button continuously (about once a
second) for up to 90 seconds or until Status Light
begins to blink.
6. When the status light starts blinking, release the
gas control/temperature knob. Set the gas control/
temperature knob to the desired setting. See Figure ‘C’.
If the status light does not start blinking within 90
seconds, repeat steps 2 through 5 up to THREE (3)
times, waiting 10 minutes between lighting attempts.
The circuitry in this advanced gas valve requires
that you wait 10 minutes between lighting attempts.
If the status light turns solid red, release the gas
control/temperature knob and repeat steps 2 through 5
(waiting 10 minutes before attempting to relight the pilot).
If the status light does not start blinking after three
lighting attempts, turn the gas control/temperature knob
to "OFF" and call a qualified service technician or your
gas supplier.
DANGER: Hotter water increases the risk of scald
FIGURE 'C'
120°F
120°F
Mark
Mark
MAIN BURNER
THERMOPILE
"ON" POSITION
PILOT
FIGURE 'D'
injury. Consult the instruction manual before
changing temperature.
Refer to the Lighting Instructions in the Installation
Manual for more detailed troubleshooting
information.
TO TURN OFF GAS TO APPLIANCE
1. Turn the gas control/temperature knob counterclockwise to the "OFF" setting. The status light will stop blinking and stay
on for a short time after the water heater is turned off. See Figure ‘A’.
25
Checking the Draft
M
G
WARNING
Emergency Shut Down
IMPORTANT: Should overheating occur or the gas supply fails
to shut off, turn off the water heater’s manual gas control valve
and call a qualified technician.
Burn Hazard
Water Temperature Regulation
Do not touch vent.
Water temperature over 125°F (52°C)
Doing so can result in burns.
After successfully lighting the water heater, allow the unit to operate
for 15 minutes and check the draft hood relief opening for proper
draft (Figure 22). Make sure all other appliances in the area are
operating and all doors are closed when performing the draft test.
Pass a match flame around the relief opening of the draft hood. A
steady flame drawn into the opening indicates proper draft.
DRAFT HOOD
RELIEF
OPENIN
ATCH
FIGURE 22.
If the flame flutters or is blown out, combustion products are
escaping from the relief opening. If this occurs, do not operate the
water heater until proper adjustments or repairs are made to the
vent pipe system and/or air supply requirements.
Burner Flames
Inspect the burner flames through the viewport and compare them
to the drawing in Figure 23. A properly operating burner should
produce a soft blue flame. Blue tips with yellow inner cones are
satisfactory. The tips of the flame may have a slight yellow tint.
The flame should not be all yellow or have a sharp blue-orange
color. Contaminated air may cause an orange colored flame.
Contact a qualified technician if the flame is not satisfactory.
FIGURE 23.
Due to the nature of the typical gas water heater, the water
temperature in certain situations may vary up to 30°F
(16.7 °C) higher or lower at the point of use such as, bathtubs,
showers, sink, etc.
HOTTER WATER CAN SCALD: Water heaters are intended to
produce hot water. Water heated to a temperature which will
satisfy space heating, clothes washing, dish washing, and other
sanitizing needs can scald and permanently injure you upon
contact. Some people are more likely to be permanently injured
by hot water than others. These include the elderly, children, the
infirm, or physically/mentally handicapped. If anyone using hot
water in your home fits into one of these groups or if there is
a local code or state law requiring a certain temperature water
at the hot water tap, then you must take special precautions.
In addition to using the lowest possible temperature setting
that satisfies your hot water needs, a means such as a mixing
valve should be used at the hot water taps used by these
people or at the water heater. Mixing valves are available at
plumbing supply or hardware stores. See Figure 18. Follow
manufacturer’s instructions for installation of the valves. Before
changing the factory setting on the thermostat, see Figure 24A.
Using the lowest hot water temperature that meets your needs
will also provide the most energy efficient operation of the water
heater.
Never allow small children to use a hot water tap, or to draw
their own bath water. Never leave a child or handicapped
person unattended in a bathtub or shower.
NOTE: A water temperature range of 120°F-140°F (49°C-60°C)
is recommended by most dishwasher manufacturers.
The thermostat is adjusted to the pilot position when it is shipped
from the factory. Water temperature can be regulated by moving
the temperature dial to the preferred setting. The preferred
starting point is 120°F at the “HOT” setting. Align the knob with
the desired water temperature as shown in Figure 24A. There is
a hot water scald potential if the thermostat is set too high.
NOTE: Temperatures shown on the gas control valve/thermostat
are approximates. The actual temperature of the heated water
may vary.
can cause servere burns instantly
resulting in severe injury or death.
Children, the elderly, and the
physically or mentally disabled are at
highest risk for scald injury.
Feel water before bathing or
showering.
Temperature limiting valves are
available.
Read instruction manual for safe
temperature setting.
26
IMPORTANT: Adjusting the thermostat past the 120°F mark
on the temperature dial will increase the risk of scald injury. Hot
water can produce first degree burns within:
Operating the Temperature Control System
Water
Temperature °F
110
116
116
122
131
140
149
154
(U.S. Government Memorandum, C.P.S.C., Peter L. Armstrong, Sept. 15,1978)
GAS CONTROL VALVE/THERMOSTAT
SETTINGS
GAS CONTROL/TEMPERATURE KNOB
VAC
IGNITER
Time for 1st
Degree Burn
(Less Severe Burns)
(normal shower temp.)
(pain threshold)
35 minutes
1 minute
5 seconds
2 seconds
1 second
Instantaneous
120°F
MARK
STATUS
LIGHT
FIGURE 24A.
Time for
Permanent Burns
2nd & 3rd Degree
(Most Severe Burns)
45 minutes
5 minutes
25 seconds
5 seconds
2 seconds
1 second
VAC
FIGURE 24B.
Water Temperature Adjustment
The water temperature setting can be adjusted from 55°F to
155°F. Turn the Gas Control/Temperature Knob to the desired
setting/temperature.
NOTE:
The temperatures indicated are approximates. The actual
temperature of the heated water may vary.
Operating Modes and Settings
• Standard Mode - The controller adjusts the water heater to
maintain the temperature set by the user.
• Vacation Setting - The Vacation setting (VAC) sets
the controller at approximately 55°F. This setting is
recommended when the water heater is not in use for a
long period of time. This effectively turns the controller
temperature setting down to a temperature that prevents
the water in the water heater from freezing while still
conserving energy.
Should overheating occur or the gas supply fail to shut off, turn
off the manual gas control valve to the appliance.
NOTE: During low demand periods when hot water is not being
used, a lower thermostat setting will reduce energy losses
and may satisfy your normal hot water needs. If hot water
use is expected to be more than normal, a higher thermostat
setting may be required to meet the increased demand. When
leaving your home for extended periods (vacations, etc.), turn
the temperature dial to its lowest setting. This will maintain the
water at low temperatures with minimum energy losses and
prevent the tank from freezing during cold weather.
Status Light Code
Normal Flashes:
• 0 Flashes Indicates Control Off/Pilot Out.
• 1 Flash Indicates Normal Operation.
• A solid red light indicates that the gas control
valve/thermostat is shutting down.
Diagnostic Flashes:
If the water heater is not working, look for the following diagnostic
flashes after lighting the pilot. For more details, see “
and Diagnostic Code Troubleshooting Chart
2 Flashes Indicates Thermopile Voltage Low
4 Flashes Indicates Overheat Failure
5 Flashes Indicates Sensor Failure
7 Flashes Indicates Electronic Control Failure
8 Flashes See “Status Light and Diagnostic Code
Status Light
.”
Troubleshooting Chart.”
27
SERVICE AND ADJUSTMENT
Vent System Inspection
At least once a year, a visual inspection should be made of the
venting system. You should look for:
pilot, follow the instructions in “Maintenance of Your Water Heater.”
You should check for sooting. Soot is not normal and will impair
proper combustion.
Soot build-up indicates a problem that requires correction before
further use. Turn “OFF” gas to water heater and leave off until repairs
are made, because failure to correct the cause of the sooting can
result in a fi re causing death, serious injury, or property damage.
FIGURE 25.
Burner Cleaning
• Obstructions which could cause improper venting. The
combustion and ventilation air fl ow must not be obstructed.
• Damage or deterioration which could cause improper venting
or leakage of combustion products.
• Rusted fl akes around top of water heater.
Be sure the vent piping is properly connected to prevent escape of
dangerous fl ue gasses which could cause deadly asphyxiation.
Obstructions and deteriorated vent systems may present serious
health risk or asphyxiation.
Chemical vapor corrosion of the fl ue and vent system may occur
if air for combustion contains certain chemical vapors. Spray can
propellants, cleaning solvents, refrigerator and air conditioner
refrigerants, swimming pool chemicals, calcium and sodium chloride,
waxes, bleach and process chemicals are typical compounds which
are potentially corrosive.
If when inspecting the vent system you fi nd sooting or deterioration,
something is wrong. Call the local gas supplier to correct the problem
and clean or replace the fl ue and venting before resuming operation
of the water heater.
Burner Inspection
The burner must be removed for cleaning. If inspection of the burner
shows that cleaning is required, call the Sears Service Center to
remove and clean the burner and correct the problem that required
the burner to be cleaned.
Flood damage to a water heater may not be readily visible or
immediately detectable. However, over a period of time a fl ooded
water heater will create dangerous conditions which can cause
DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE.
Contact a Sears Service Center to replace a fl ooded water heater.
Do not attempt to repair the unit! It must be replaced!
At least once a year, a visual inspection should be made of the main
burner and pilot burner. See Figure 25. To access the burner and
28
Housekeeping
Fire and Explosion Hazard
Do not obstruct combustion air
openings at the bottom of the
water heater.
Do not use or store flammable
vapor products such as gasoline,
solvents or adhesives in the
same room or area near water
heater or other appliance.
At least annually, check the
base-ring filter and flame arrester
for any dust, lint, or debris that
may have accumulated. Clean
as necessary.
Can cause serious injury or death.
Vacuum around base of water heater for dust, dirt, and lint on
a regular basis.
The anode rod should be inspected after a maximum of three
years and annually thereafter until the condition of the anode
rod dictates its replacement. NOTE: Artificially softened water
requires the anode rod to be inspected annually.
Anode Rod Depletion
AT LEAST ANNUALLY, A VISUAL INSPECTION SHOULD BE
MADE OF THE BASE-RING FILTER AND FLAME ARRESTER.
CLEAN IF LINT ACCUMULATIONS ARE NOTICED.
INSTALLED IN SUITABLE AREA: To ensure sufficient ventilation
and combustion air supply, proper clearances from the water
heater must be maintained. See “Installation Instructions.”
Combustible materials such as clothing, cleaning materials, or
flammable liquids, etc. must not be placed against or adjacent
to the water heater because they could catch on fire.
Anode Rod Inspection
The anode rod is used to protect the tank from corrosion.
Most hot water tanks are equipped with an anode rod. The
submerged rod deteriorates to protect the tank. Instead of
corroding the tank, water ions attack and eat away the anode
rod. This does not affect the water’s taste or color. The rod
must be maintained to keep the tank in operating condition.
Anode deterioration depends on water conductivity, not
necessarily water condition. A corroded or pitted anode rod
indicates high water conductivity and should be checked and/
or replaced more often than an anode rod that appears to be
intact. Replacement of a depleted anode rod can extend the
life of your water heater. Inspection should be conducted by
calling the Sears Service Center for an authorized contractor.
FIGURE 26.
Temperature-Pressure Relief Valve Operation
The temperature-pressure relief valve must be manually
operated at least once a year.
Burn hazard
Hot water discharge.
Keep clear of relief valve
discharge outlet.
When checking the temperature-pressure relief valve operation,
make sure that (1) no one is in front of or around the outlet of
the temperature-pressure relief valve discharge line, and (2)
that the water discharge will not cause any property damage, as
the water may be extremely hot. See Figure 27.
FIGURE 27.
29
If after manually operating the valve, it fails to completely reset
and continues to release water, immediately turn off the gas
supply and drain the water heater (see Draining and Flushing).
Once the water heater is completely drained, replace the
temperature-pressure relief valve with a new one.
If the temperature-pressure relief valve on the appliance
weeps or discharges periodically, this may be due to thermal
expansion. You may have a check valve installed in the water
line or a water meter with a check valve. Consult the Sears
Service Center for further information.
Draining and Flushing
It is recommended that the tank be drained and flushed
every 6 months to remove sediment which may build up during
operation. The water heater should be drained if being shut
down during freezing temperatures. To drain the tank, perform
the following steps:
1. Turn off the gas to the water heater at the manual gas shutoff valve.
2. Open a nearby hot water faucet until the water is no longer
hot.
3. Close the cold water inlet valve.
4. Connect a hose to the drain valve and terminate it to an
adequate drain or external to the building.
5. Open the water heater drain valve and allow all of the water
to drain from the tank. Flush the tank with water as needed
to remove sediment.
6. Close the drain valve, refill the tank, and restart the heater
as directed in this manual. If the water heater is going to
be shut down for an extended period, the drain valve should
be left open.
IMPORTANT: Condensation may occur when refilling the tank
and should not be confused with a tank leak.
Service
Before calling for repair service, please read the Troubleshooting
Guide in this manual.
If a condition persists or you are uncertain about the operation
of the water heater, let the Sears Service Center check it out.
Contact Sears Service Center at:
1-800-4-MY-HOME® (1-800-469-4663).
30
MAINTENANCE OF YOUR WATER HEATER
Replacement Parts
IMPORTANT: The following maintenance procedures are for the
FVIR System components and should be performed by a qualified
technician.
Replacement parts may be ordered from Sears Parts and Service
Centers or by calling 1-800-4-MY-HOME (1-800-469-4663). When
ordering replacement parts, always have the following information
ready:
1. model, serial, and product number
2. type of gas
3. item number
4. parts description
See the Parts Order List section for a list of available repair parts.
Removing the Manifold/Burner Assembly
1. Turn the gas control/temperature knob to the “OFF”
position (Figure 28).
2. Before performing any maintenance, it is important to turn off
the gas supply to the water heater at the manual gas shut-off
valve. This valve is typically located beside the water heater.
Note the position of the shut-off valve in the open/on position,
then proceed to turn it off (Figure 2).
3. With the unit shut-off, allow sufficient time for the water heater
to cool before performing any maintenance.
GAS CONTROL/
TEMPERATURE KNOB
GAS CONTROL VALVE/THERMOSTAT
GAS CONTROL/
TEMPERATURE KNOB
PIEZO IGNITER BUTTON
PILOT TUBE
VIEWPORT
OUTER DOOR
NOT SHOWN
MANIFOLD SCREW (2)
VAC
MANIFOLD COMPONENT BLOCK
THERMOPILE AND
SWITCH WIRE
CONNECTIONS
MANIFOLD TUBE
THERMAL SWITCH
MANIFOLD DOOR
FIGURE 29.
Removing the Burner from the Manifold/
Burner Assembly
Natural Gas (Low Nox) & L.P. Gas Burner
1. Take off the burner by removing the two (2) screws located
underneath the burner.
2. Check the burner to see if it is dirty or clogged. The burner
may be cleaned with soap and hot water (Figure 30).
IMPORTANT: DO NOT remove the orifice.
PILOT ASSEMBLY
(BOTTOM VIEW)
SCREWS
VAC
IGNITER
BUTTON
IGNITER
LEAD
WIRE
IGNITER
WIRE
PILOT
TUBE
WHITE
WIRE
(RIGHT
SIDE)
RED WIRE
(LEFT SIDE)
MANIFOLD TUBE
FIGURE 28.
4. Remove the outer door.
5. Disconnect the following from the gas control valve/thermostat:
pilot tube (7/16” wrench), igniter wire (from the igniter lead
wire), and manifold tube (3/4” wrench). See Figure 28.
6.
Disconnect the white and red wires from the gas control
valve/thermostat (Figure 28). Use needle nose pliers to
grip the connector(s). IMPORTANT: Grip the connector
carefully to prevent damage. Do not grip or pull the
wires themselves.
7. Grasp the manifold tube and push down slightly to free the
manifold tube and pilot tube.
8. Remove the screws (1/4” nut driver) securing the
manifold/burner assembly to the combustion chamber.
See Figure 29.
9. Carefully remove the manifold/burner assembly from the
combustion chamber. BE SURE NOT TO DAMAGE ANY
INTERNAL PARTS.
BURNER
(BOTTOM VIEW)
FIGURE 30.
Replacing the Pilot/ Thermopile Assembly
1. Remove the manifold door assembly as described in
“Removing the Manifold/Burner Assembly” section.
2. Remove the burner to access the pilot/thermopile assembly.
Remove and keep the screws securing the burner to the
manifold (Figure 30). IMPORTANT: DO NOT remove the
orifice.
3. Remove the screw securing the pilot/thermopile assembly to
the pilot bracket and keep for reuse later (Figure 31).
4. Lift the retainer clip straight up from the back of the
manifold component block (using a flat-blade screwdriver),
then remove the manifold component block from the
manifold door (Figure 31). IMPORTANT: Be careful not to
bend or alter the position of the pilot tube. It will be used
as a bending template for the new pilot assembly. Note the
placement/order of the wires in the manifold component block.
5. Lift the pilot/thermopile assembly (including the igniter wire)
from the manifold assembly.
31
IGNITER
WIRE
CONNECTORS
RETAINER
CLIP
PILOT / THERMOPILE
ASSEMBLY SCREW
BURNER AND OTHER
FITTINGS NOT SHOW
FOR CLARITY.
RED (+) THERMAL SWITCH WIRE
CONNECTS TO THE GAS CONTROL
VALVE\THERMOSTAT.
WHITE (-) THERMOPILE WIRE
CONNECTS TO THE GAS CONTROL
VALVE\THERMOSTAT.
MANIFOLD COMPONENT
BLOCK
PILOT TUBE
MANIFOLD DOOR
RED WIRES TO
THERMAL SWITCH (2)
FIGURE 31.
6. Read this step carefully before proceeding. Using the old
pilot/pilot tube assembly as a guide, bend the new pilot tube
to match the old one. Make only the bends closest to the
pilot before going to the next step.
PILOT/THERMOPILE ASSEMBLY
THERMOPILE
PILOT/THERMOPILE
ASSEMBLY
THERMAL
SWITCH
CONNECTORS
(RED WIRES)
FOR CLARITY, PILOT
TUBE NOT SHOWN .
IGNITER
CONNECTOR
PILOT
CONNECTORS
(CONNECT AT
GAS CONTROL VALVE/
THERMOSTAT)
FIGURE 32.
7. Route the new pilot tube and wires through the opening in the
manifold door. See Figure 31.
8. Using the pilot screw removed earlier, attach the new pilot/
thermopile assembly. Reattach the burner to the manifold
using the screws removed earlier. NOTE: Make sure the
burner scoop is oriented to the pilot side of the manifold tube
(Figure 30).
9. Reinstall the manifold component block in the manifold door.
Ensure that the pilot tube and wires are positioned as shown
in Figure 33.
10. Carefully bend the new pilot tube to match the bend of the
manifold tube. NOTE: When bending, DO NOT crimp or
crease the pilot tube.
11. Before you proceed to the next step, install the new brass
ferrule nut in the gas control valve/thermostat’s pilot tube
opening, HAND TIGHT ONLY.
12. Install the manifold/burner assembly. Refer to the “Replacing
the Manifold/Burner Assembly” section for instructions.
MANIFOLD
COMPONENT
BLOCK
IGNITER WIRE PASSES
THROUGH CENTER OF
MANIFOLD COMPONENT
BLOCK (SMALLEST HOLE)
PILOT TUBE PASSES
THROUGH BOTTOM HOLE
OF MANIFOLD COMPONENT
BLOCK (LARGEST HOLE)
RED THERMAL SWITCH WIRE
CONNECTIONS AT MANIFOLD DOOR
THERMOPILE WIRES PASS
THROUGH TOP HOLE OF
MANIFOLD COMPONENT
BLOCK
FIGURE 33.
External Inspection & Cleaning of the
Base-Ring Filter
1. At least annually, check the base-ring filter (Figure 34) for
any dust or debris that may have accumulated on the filter
screen. NOTE: If the water heater is located in an area that
is subjected to lint and dirt, it may be necessary to check
the base-ring filter more frequently.
2. Follow the Lighting Instructions to turn off the water heater
and allow it to cool for 10 minutes before attempting to clean
the base-ring filter.
3. Use a vacuum cleaner with a hose attachment to remove
any dust or debris that may have accumulated on the filter.
NOTE: If unable to inspect or clean the base-ring filter, follow
the “Cleaning the Combustion Chamber and Flame-arrestor”
instructions.
4. After the base-ring filter has been cleaned, follow the
Lighting Instructions to return the water heater to service.
32
Cleaning the Combustion Chamber and
Flame-arrestor
1. Follow procedure outlined in “Removing the Manifold/
Burner Assembly”.
2. Use a vacuum cleaner/shop vac to remove all loose debris
in the combustion chamber (Figure 34). Use compressed
air to clear any dust or debris that may have accumulated
in the flame-arrestor.
COMBUSTION CHAMBER
DOOR GASKET
BASE-RING
FILTER
FLAME ARRESTOR
FIGURE 34.
3. Reassemble following the procedure under “Replacing the
Manifold/Burner Assembly.”
Replacing the Manifold/Burner Assembly
WARNING
Explosion Hazard
Tighten both manifold door screws securely.
tube engages the slot of the bracket inside the combustion
chamber (Figure 35).
4. Inspect the door gasket and make sure there is no
fiberglass insulation between the gasket and the
combustion chamber (Figure 34).
5. Tighten the two screws that secure the manifold/burner
assembly to the combustion chamber. (Use a
1/4” nut
driver.) There should be no space between the gasket
part of the manifold door and combustion chamber
IMPORTANT: Do not operate the water heater if the door
gasket does not create a seal between the manifold door
and the combustion chamber.
6. Reconnect the manifold tube (3/4” wrench) and pilot tube
(7/16” wrench) to the gas control valve/thermostat (Figure 28).
Do not cross-thread or apply any thread sealant to the fittings.
IMPORTANT: If you were supplied with a new ferrule
nut in a parts kit, follow these steps to connect the
pilot tube:
1.) Install the ferrule nut into the gas valve at the pilot tube
location, hand tight only. 2.) Insert the pilot tube into the
ferrule nut until the tube bottoms out, then tighten the nut
with a 7/16” wrench until the crimp connection seals to the
pilot tube. 3.) Continue to tighten until the nut is tight in the
gas valve.
7. Connect the white and red wires to the gas control valve/
thermostat as shown in Figure 28. Also, ensure that the
red thermal switch wires are connected to the thermal
switch on the manifold door (Figure 33).
8. Reconnect the igniter wire (Figure 28).
9. Turn on the gas supply to the water heater at the manual gas
shut-off valve (Figure 2).
10. Follow the lighting instructions on the front of the water
heater. With the main burner lit, check for leaks at
the manifold and pilot connections by brushing on an
approved noncorrosive leak detection solution. If such
a solution is not available, use a mixture of hand dish
washing soap and water (one part soap to 15 parts
water) or childrens’ soap bubble solution. Bubbles forming
indicate a leak. Correct any leak found.
11. Verify proper operation, then replace the outer door.
Remove any fiberglass between gasket and
combustion chamber.
Replace viewport if glass is missing or damaged.
Replace manifold component block if missing or
removed.
Replace door gasket if damaged.
Failure to follow these instructions can result in
death, explosion, or fire.
1. Check the door gasket for damage or imbedded debris
prior to installation (Figure 34).
2. Inspect the viewport for damage and replace as required
(Figure 29).
3. Insert the new manifold/burner assembly into the burner
compartment, making sure that the tab of the manifold
33
MANIFOLD TUBE
FIGURE 35.
CLOSE-UP INSIDE VIEW OF
THE COMBUSTION CHAMBER.
TIP
BRACKET
SLOT
Piezoelectric Igniter System
The piezoelectric igniter system consists of the igniter
button, electrode, and wire. The pilot is ignited by an
electric spark generated when the igniter button is
pressed. (See Figure 36).
THERMOPILE
PILOT
VAC
ELECTRODE
WIRE TO ELECTRODE
IGNITER BUTTON
FIGURE 36.
PILOT/
THERMOPILE
BRACKET
Testing the Igniter System
Turn off the gas to the water heater at the manual gas shut-off
valve. Watch the electrode tip while activating the igniter. A
visible spark should jump from the electrode. To avoid shock,
do not touch the burner or any metal part on the pilot or pilot
assembly. If no spark is visible, check the wire connections
and make sure the electrode is not broken. Replace the igniter
if defective. Dirt and rust on the pilot or electrode tip can
prevent the igniter spark. Wipe clean with a damp cloth and dry
completely. Rust can be removed from the electrode tip and
metal surfaces by lightly sanding with an emery cloth or fine
grit sandpaper.
6. To remove the gas control valve/thermostat, thread
a 4” section of gas pipe into the inlet and use it to turn the
gas control valve/thermostat (counterclockwise.) Do not
use a pipe wrench or equivalent to grip body. Damage may
result, causing leaks. Do not insert any sharp objects into
the inlet or outlet connections. Damage to the gas control
valve/thermostat may result.
Replacing the Gas Control Valve/Thermostat:
To replace the gas control valve/thermostat, reassemble in
reverse order. When replacing the gas control valve/thermostat,
thread a 4” section of gas pipe into the inlet and use it to turn
the gas control valve/thermostat (clockwise). DO NOT OVER
TIGHTEN; damage may result.
• Be sure to use approved Teflon® tape or pipe joint
compound on the gas piping connections and fitting on the
back of the gas control valve that screws into the tank.
• Be sure to remove the pilot ferrule nut from the new gas
control valve/thermostat.
• Turn the main gas supply on and check the gas supply
connections for leaks. Correct any leak found. Next, light
the pilot and main burner, then check the manifold tube and
pilot tube connections for leaks. Correct any leak found.
Use an approved noncorrosive leak detection solution.
If such a solution is not available, use a mixture of hand
dish washing soap and water (one part soap to 15 parts
water) or childrens’ soap bubble solution. Bubbles forming
indicate a leak.
• Be sure tank is completely filled with water before lighting
and activating the water heater. Follow the “Lighting
Instructions” on the front of the water heater.
• If additional information is required, contact Sears Service
at 1-800-4-MY-HOME (1-800-469-4663).
Removing and Replacing the Gas Control
Valve/Thermostat
IMPORTANT: This water heater has a resettable thermal switch
installed. Do not attempt to disable or modify this feature
in any way. Use only factory authorized replacement parts.
IMPORTANT: This gas control valve/thermostat is shipped
from the factory as a natural gas unit. However, it may be
converted to use LP gas. Before installing this gas control valve/
thermostat, make sure that it is configured for the type of gas
that you are using. Refer to the “Gas Conversion” section.
Removing the Gas Control Valve/Thermostat:
1. Turn the gas control/temperature knob to the “OFF” position
(Figure 24B).
2. Turn off the gas at the manual shut-off valve on the gas
supply pipe (Figure 2).
3. Drain the water heater. Refer to the section of “Draining and
Flushing” and follow the procedure.
4. Disconnect the igniter wire from the igniter lead wire. Use
needle nose pliers to disconnect the red (+) and white (-)
thermopile wires. D isconnect the pilot tube (7/16 ” wrench) and
manifold tube (3/4” wrench) at the gas control valve/thermostat
(Figure 28).
5. Refer to “Gas Piping” (Figure 2) and disconnect the ground
joint union in the gas piping. Disconnect the remaining pipe
from the gas control valve/thermostat.
TEFLON® is a registered trademark of E.I. Du Pont De Nemours
and Company
FVIR System Operational Checklist
1. Manifold gasket properly sealed.
2. Viewport not damaged or cracked.
3. Flame-arrestor free of debris and undamaged.
4. Manifold component block properly installed.
5. No leaks at pilot and manifold connection.
6. Manifold door screws securely tightened.
7. Depress the button on the thermal switch
34
TROUBLESHOOTING GUIDE
COLD WATER
IN
PRESSURE
REDUCING
VALVE WITH
BYPASS
PRESSURE
GAUGE
COLD WATER
INLET VALVE
(SHUT-OFF VALVE)
THERMAL
EXPANSION TANK
MASSACHUSETTS: INSTALL
A VACUUM RELIEF IN COLD
WATER LINE PER SECTION
19 MGL 142.
HOT WATER
OUT
COLD WATER
SUPPLY
TO
FIXTURES
Start Up Conditions
Thermal Expansion
As water is heated, it expands (thermal expansion). In a closed
system, the volume of water will grow. As the volume of water
grows, there will be a corresponding increase in water pressure
due to thermal expansion. Thermal expansion can cause
premature tank failure (leakage). This type of failure is not
covered under the limited warranty. Thermal expansion can also
cause intermittent temperature-pressure relief valve operation:
water discharged from the valve due to excessive pressure
build up. The temperature-pressure relief valve is not intended
for the constant relief of thermal expansion. This condition is not
covered under the limited warranty.
A properly sized thermal expansion tank should be installed
on all closed systems to control the harmful effects of thermal
expansion. Thermal expansion tanks are available from Sears
stores and through the Sears Service Centers. Contact the local
plumbing inspector, water supplier and/or the Sears Service
Center for assistance in controlling these situations. See
Figure 37.
NOTE: Expansion tanks are pre-charged with a 40 psi air
charge. If the inlet water pressure is higher than 40 psi, the
expansion tank’s air pressure must be adjusted to match
that pressure, but must not be higher than 80 psi.
FIGURE 37.
Strange Sounds
Possible noises due to expansion and contraction of some
metal parts during periods of heat-up and cool-down do not
represent harmful or dangerous conditions.
Condensation causes sizzling and popping within the burner
area during heating and cooling periods and should be
considered normal. See “Condensation” section.
Thermal Expansion Tank Specifi cations
Tank Dimensions Pipe
Model Capacity in Inches Fitting
Number In Gallons Diameter Length On Tank
153.331020 2 8 (203 mm) 12-3/4 (323 mm) 3/4” Male
153.331050 5 11 (279 mm) 14-3/4 (375 mm) 3/4” Male
Expansion Tank Sizing Chart
Inlet* Water Heater Capacity (Gallons)
Water
Pressure 30 40 50 66 82
Expansion 40psi 2 2 2 5 5
Tan k 50psi 2 2 2 5 5
Capacity 60psi 2 2 5 5 5
Needed 70psi 2 2 5 5 5
80psi 2 5 5 5 5
*Highest recorded inlet water pressure in a 24 hour period or regulated
water pressure.
Draft Hood Operation
Check draft hood operation by performing a worst case
depressurization of the building. With all doors and windows
closed, and with all air handling equipment and exhaust fans
operating such as furnaces, clothes dryers, range hoods and
bathroom fans, a match flame should still be drawn into the draft
hood of the water heater with its burner firing. If the flame is not
drawn toward the draft hood, shut off water heater and make
necessary air supply changes to correct.
Condensation
Whenever the water heater is filled with cold water, some
condensate will form while the burner is on. A water heater may
appear to be leaking when in fact the water is condensation.
This usually happens when:
• A new water heater is filled with cold water for the first
time.
• Burning gas produces water vapor in water heaters,
particularly high efficiency models where flue temperatures
are lower.
• Large amounts of hot water are used in a short time and the
refill water in the tank is very cold.
35
Moisture from the products of combustion condense on the
cooler tank surfaces and form drops of water which may fall
onto the burner or other hot surfaces to produce a “sizzling” or
“frying” noise.
Excessive condensation can cause pilot outage due to water
running down the flue tube onto the main burner and putting
out the pilot.
Because of the suddenness and amount of water, condensation
water may be diagnosed as a “tank leak”. After the water in
the tank warms up (about 1-2 hours), the condition should
disappear.
Do not assume the water heater is leaking until there has been
enough time for the water in the tank to warm up.
An undersized water heater will cause more condensation.
The water heater must be sized properly to meet the family’s
demands for hot water including dishwashers, washing machines
and shower heads.
Excessive condensation may be noticed during the winter and
early spring months when incoming water temperatures are at
their lowest.
Good venting is essential for a gas fired water heater to operate
properly as well as to carry away products of combustion and
water vapor.
Smoke Odor
It is not uncommon to experience a small amount of smoke and
odor during the initial start-up. This is due to burning off of oil
from metal parts, and will disappear in a short while.
Operational Conditions
Smelly Odor
In each water heater there is installed at least one anode rod
(see parts section) for corrosion protection of the tank. Certain
water conditions will cause a reaction between this rod and the
water. The most common complaint associated with the anode
rod is one of a “rotten egg smell”. This odor is derived from
hydrogen sulfide gas dissolved in the water. The smell is the
result of four factors which must all be present for the odor to
develop:
• a concentration of sulfate in the supply water.
• little or no dissolved oxygen in the water.
• a sulfate reducing bacteria within the water heater. (This
harmless bacteria is non-toxic to humans.)
• an excess of active hydrogen in the tank. This is caused by
the corrosion protective action of the anode.
Smelly water may be eliminated or reduced in some water
heater models by replacing the anode(s) with one of less active
material, and then chlorinating the water heater tank and all
hot water lines. Contact Sears Service for further information
concerning this chlorination treatment and an anode replacement
kit #9001453005. (For short heaters, use anode replacement
kit #9006299005.) Anode replacement and chlorination of the
tank are not covered by the water heater’s limited warranty.
If the smelly water persists after the anode replacement and
chlorination treatment, it may be necessary to chlorinate or
aerate your water supply to eliminate the problem.
Do not remove the anode, leaving the tank unprotected. By
doing so, all warranty on the water heater tank is voided.
“AIR” In Hot Water Faucets
HYDROGEN GAS: Hydrogen gas can be produced in a hot water
system that has not been used for a long period of time (generally
two weeks or more). Hydrogen gas is extremely fl ammable and
explosive. To prevent the possibility of injury under these conditions,
we recommend the hot water faucet, located farthest away, be
opened for several minutes before any electrical appliances which are
connected to the hot water system are used (such as a dishwasher
or washing machine). If hydrogen gas is present, there will probably
be an unusual sound similar to air escaping through the pipe as the
hot water faucet is opened. There must be no smoking or open fl ame
near the faucet at the time it is open.
Safety Shut-off and Thermal Switch
This water heater is designed to automatically shut-off in
the event of the following:
1. The pilot flame is extinguished for any reason.
2. The water temperature exceeds 189°F (87°C) for 155°F
models or 199°F (93°C) for 180°F models. See the data
plate for your model.
3. Excessive combustion chamber temperatures.
4. The ignition of flammable vapors.
A thermopile is used to determine if a pilot flame is present,
and will shut off the gas supply to the main burner and the
pilot if the flame is absent. This unit is also equipped with a
thermal switch, designed to shut off the gas supply in the event
the heater has been exposed to flammable vapors (spilled
gasoline or paint fumes, for example), poor combustion caused
by insufficient combustion air, or improper venting. If the switch
opens, check the flame arrestor for signs of high temperature
(blue or black discoloration), and inspect your installation for
any problems with venting or combustion air. (See Pilot Light
Troubleshooting Flowchart). Reset the switch by depressing
the small button in the center of the switch.
IMPORTANT: Correct any issues prior to resetting the switch.
Contact Sears at 1-800-4-MY-HOME (1-800-469-4663) to
request service.
The gas control valve\thermostat includes a temperature
limiting ECO (Energy Cut Off) system that will shut off the water
heater if the water temperature exceeds 189°F (87°C) for 155°F
models or 199°F (93°C) for 180°F models. See the data plate
for your model.
Should the water temperature get too high, the diagnostic
36
status light will flash a code (4 flashes), indicating an over-
AC
B
D
E
F
G
H
I
temperature condition and the main burner will be shut off.
If a high temperature condition occurs, turn the main gas
supply OFF and have the water heater repaired by a qualified
service technician.
(1-800-469-4663) to request service.
Contact Sears at 1-800-4-MY-HOME
Leakage Checkpoints
Read this manual first. Then, before checking the water heater,
make sure the gas supply has been turned “OFF”, and never
turn the gas “ON” before the tank is completely full of water.
Never use this water heater unless it is completely filled with
water. To prevent damage to the tank, the tank must be filled
with water. Water must flow from the hot water faucet before
turning “ON” gas to the water heater.
A. Water at the draft hood is water vapor which has condensed
out of the combustion products. This is caused by a
problem in the vent. Contact a qualified technician.
B. *Condensation may be seen on pipes in humid weather or
pipe connections may be leaking.
C. *The anode rod fitting may be leaking.
D. Small amounts of water from temperature-pressure relief
valve may be due to thermal expansion or high water
pressure in your area.
E. *The temperature-pressure relief valve may be leaking at
the tank fitting.
F. Water from a drain valve may be due to the valve being
slightly opened.
FIGURE 38.
G. *The drain valve may be leaking at the tank fitting.
H. Combustion products contain water vapor which can
condense on the cooler surfaces of the tank. Droplets form
and drip onto the burner or run on the floor. This is common
at the time of start-up after installation and when incoming
water is cold.
I. Water in the water heater bottom or on the floor may be
from condensation, loose connections, or the relief valve.
DO NOT replace the water heater until a full inspection
of all possible water sources is made and necessary
corrective steps taken.
Leakage from other appliances, water lines, or ground seepage
should also be checked.
* To check where threaded portion enters tank, insert cotton
swab between jacket opening and fitting. If cotton is wet, follow
draining instructions in the “Draining and Flushing” section and
37
then remove fitting. Put pipe dope or teflon tape on the threads
and replace. When you are finished, follow the steps in “Filling
the Water Heater” in the Installation Instructions earlier in this
manual.
TROUBLESHOOTING CHECKLIST
PROBLEMPOSSIBLE CAUSE(S)CORRECTIVE ACTION
BURNER WILL NOT IGNITE1. Pilot not lit
SMELLY WATER1. Sulfides in the water1. Replace the anode with a special anode
BURNER FLAME YELLOWLAZY
PILOT WILL NOT LIGHT OR
REMAIN LIT
HIGH OPERATION COSTS1. Thermostat set too high
INSUFFICIENT HOT WATER 1. Thermostat set too low
2. Thermostat set too low
3. Main burner line clogged
4. Non-functioning thermostat
5. Base-Ring Filter blocked with lint/dust
6. Heater installed in a confined area
7. FVIR Flame Arrestor blocked with lint/
dust.
1. Insufficient combustion air
2. Low gas pressure
3. Water heater flue or vent system
blocked
4. Main burner line clogged
5. Base-Ring Filter blocked with lint/ dust
6. Heater installed in a confined area
7. FVIR Flame Arrestor blocked with lint/
dust.
8. Obstruction in main burner orifice
9. Incorrect gas conversion (if unit was
converted to use a different type of gas)
1. Non-functioning igniter
2. The thermal switch tripped
3. Wire lead connection at thermal switch
loose
4. Thermopile connection loose
5. Air in gas line
6. Low gas pressure
7. N o gas
8. Dirt in gas lines
9. Cold drafts
10. Thermostat temperature limit was
exceeded. Status light will blink 4 flashes.
11. Pilot line or orifice clogged
12. Non-functioning thermopile
13. Air for combustion obstructed
14. FVIR Flame Arrestor blocked with lint/
dust
15. Flammable vapors incident, FVIR
function actuated
16. Base-Ring Filter blocked with lint/dust
2. Sediment or lime in tank
3. Water heater too small for job
4. Wrong piping connections
5. Leaking faucets
6. Gas leaks
7. Wasted hot water
8. Long runs of exposed piping
9. Hot water piping in exposed wall
2. Sediment or lime in tank
3. Water heater too small
4. Wrong piping connections
5. Leaking faucets
6. Wasted hot water
7. Long runs of exposed piping
8. Hot water piping in outside wall
9. Low gas pressure
10. Incorrect gas conversion (if unit was
converted to use a different type of gas)
1. Light pilot
2. Turn temp. dial to desired temperature
3. Clean, locate source and correct
4. Test Gas Control Valve/Thermostat
5. Clean filter, See “External Inspection &
Cleaning of the Base-Ring Filter” section.
6. Provide fresh air ventilation
7. Clean filter, See “Cleaning the Combustion
Chamber and Flame-Arrestor” section.
1. Provide ventilation to water heater
2. Check with gas utility company
3. Clean, locate source and correct
4. Clean, locate source and correct
5. Clean filter, See “External Inspection &
Cleaning of the Base-Ring Filter” section.
6. Proper fresh air ventilation
7. Clean filter, See “Cleaning the Combustion
Chamber and Flame-Arrestor” section.
8. Clean or replace orifice
9. Contact a qualified technician
1. Replace igniter pilot assembly
2. See Pilot Light Troubleshooting Flowchart section
3. Remove and reconnect the wire leads at
thermal switch, confirm connections are tight
and not loose
4. Seat connector firmly in socket
5. Bleed the air from the gas line
6. Check with gas utility company
7. Check with gas utility company
8. Notify utility-install dirt trap in gas line
9. Locate source and correct
10. Replace thermostat
11. Clean, locate source and correct
12. Replace thermopile
13. See maintenance section for inspection and
cleaning of flame arrester
14. Clean filter, See “Cleaning the Combustion
Chamber and Flame-Arrestor” section.
16. Clean filter, See “External Inspection &
Cleaning of the Base-Ring Filter” section.
1. Set temperature dial to lower setting
2. Drain/flush-provide water treatment if needed
3. Install adequate heater
4. Correct piping-inlet tube must be in cold inlet
5. Repair faucets
6. Check with utility-repair at once
7. A d v is e cus t o mer
8. Insulate piping
9. Insulate piping
1. Turn temperature dial to desired setting
2. Drain/flush-provide water treatment if needed
3. Install adequate heater
4. Correct piping-inlet tube must be in cold inlet
5 Repair faucets
6. Advise customer
7. Insulate piping
8. Insulate piping
9. Check with gas utility company
10. Contact a qualified technician
38
TROUBLESHOOTING CHECKLIST (CONTINUED)
PROBLEMPOSSIBLE CAUSE(S)CORRECTIVE ACTION
SLOW HOT WATER
RECOVERY
DRIP FROM RELIEF VALVE1. Excessive water pressure
THERMOSTAT FAILS TO
SHUT-OFF
COMBUSTION ODORS1. Insufficient combustion air
SMOKING AND CARBON
FORMATION (SOOTING)
CONDENSATION1. Temperature setting too low1. Increase the temperature setting. Refer to the
BURNER FLAME FLOATS
AND LIFTS OFF PORTS
BURNER FLAME TOO HIGH 1. Orifice too large
FLAME BURNS AT ORIFICE1. Thermostat not functioning properly
PILOT FLAME
TOO SMALL
1. Insufficient combustion air
2. Water heater flue or vent system
blocked
3. Low gas pressure
4. Improper calibration
5. Base-Ring Filter blocked with lint/dust
6. FVIR Flame Arrestor blocked with lint/
dust.
7. Incorrect gas conversion (if unit was
converted to use a different type of gas)
2. Heater stacking
3. Closed water system
1. Thermostat not functioning properly
2. Improper calibration
2. Water heater flue or vent system
blocked
3. Heater installed in a confined area
4. Base-Ring Filter blocked with lint/dust
5. FVIR Flame Arrestor blocked with lint/
dust.
1. Insufficient combustion air
2. Low gas pressure
3. Water heater flue or vent system
blocked
4. Thermostat not functioning properly
5. Heater installed in a confined area
6. Burner flame yellow-lazy
7. Base-Ring Filter blocked with lint/dust
8. FVIR Flame Arrestor blocked with lint/
dust.
9. Incorrect gas conversion (if unit was
converted to use a different type of gas)
1. Orifice too large
2. High gas pressure
3. Water heater flue or vent system
blocked
4. Cold drafts
5. Incorrect gas conversion (if unit was
converted to use a different type of gas)
2. Incorrect gas conversion (if unit was
converted to use a different type of gas)
2. Low gas pressure
3. Incorrect gas conversion (if unit was
converted to use a different type of gas)
1. Pilot line or orifice clogged
2. Low gas pressure
1. Provide ventilation to water heater. Check flue
way, flue baffle, and burner
2. Clean flue, locate source and correct
3. Check with gas utility company
4. Replace thermostat
5. Clean filter, See “External Inspection &
Cleaning of the Base-Ring Filter” section.
6. Clean filter, See “Cleaning the Combustion
Chamber and Flame-Arrestor” section.
7. Contact a qualified technician
1. Use a pressure reducing valve and relief valve
2. Lower the thermostat setting
3. See “Closed System/Thermal Expansion”
1. Replace thermostat
2. Replace thermostat
1. Provide ventilation to water heater. Check flue
way, flue baffle, and burner
2. Clean, locate source and correct
3. Provide fresh air ventilation
4. Clean filter, See “External Inspection &
Cleaning of the Base-Ring Filter” section.
5. Clean filter, See “Cleaning the Combustion
Chamber and Flame-Arrestor” section.
1. Provide ventilation to water heater. Check flue
way, flue baffle, burner
2. Check with gas utility company
3. Clean, locate source and correct
4. Replace thermostat
5. Provide fresh air ventilation
6. See “Burner Flame Yellow-Lazy”
7. Clean filter, See “External Inspection &
Cleaning of the Base-Ring Filter” section.
8. Clean filter, See “Cleaning the Combustion
Chamber and Flame-Arrestor” section.
9. Contact a qualified technician
“Condensation” sub-section of this manual’s
Troubleshooting Guide.
1. Replace with correct orifice
2. Check with gas utility company
3. Clean flue and burner-locate source and correct
4. Locate source and correct
5. Contact a qualified technician
1. Replace with correct orifice
2. Contact a qualified technician
1. Replace thermostat
2. Check with gas utility company
3. Contact a qualified technician
1. Clean, locate source and correct
2. Check with gas utility company
39
PILOT LIGHT TROUBLESHOOTING FLOWCHART
Section A: Pilot light will not light (new installation).
Is the manual gas shut-off valve,
located in the supply line to the
water heater, in the on position?
YES
Have you bled all the air
from the pilot tube and
gas supply line?
YES
Is the igniter producing a
spark?
NO
Follow the “Testing the Igniter
System” section in this manual.
NO
YES
Turn the manual gas shut-off valve to
the on position and follow the lighting
NO
instructions on the front of the water heater.
While repeatedly depressing the igniter
button, push in and hold the gas control/
temperature knob until the pilot is lit and
maintains a stable flame (status light will
blink). It may take up to 90 seconds of
pilot operation before status light blinks.
Once status light blinks, release the gas
control/temperature knob.
Set thermostat to desired temperature.
Section B: Pilot light repeatedly goes out.
Check the Base-Ring Filter and
Flame Arrestor for blockage due
to lint or dust. Are both the Air
Filter and Flame Arrestor clean?
YES
Refer to the “Maintenance of
your Water Heater” section of this
NO
manual for information on cleaning
the flame arrestor and burner.
Section C: Pilot light will not remain lit.
Co mplete this sect ion after comp leting S ectio n B.
Check for insufficient combustion air.
YES
Are the combustion air supply and ventilation
openings of sufficient size? See “Combustion Air
Supply and Ventilation” section in this manual for
requirements.
YES
Does the return air duct
for the furnace/air handler/
air conditioner draw its air
from the same location as
the water heater? See the
“Location Requirements”
section and the “Combustion
Air Supply” section.
YES
Contact a Heating and Air
Conditioning service technician
to relocate the return air duct.
The water heater’s pilot can be
extinguished when the heating
or cooling system is turned on
if the return air duct is in the
same location.
NO
Correct size of
NO
openings to allow
sufficient air.
Is there proper
drafting at the
drafthood? See
“Checking the Draft”
section in this manual.
YES
Check the vent system for
restrictions/obstructions and
check the vent termination
height. Refer to the “Installation
Instructions” section of this
manual for specific requirements.
NO
Does the flame
arrestor show signs
of discoloration?
YES
Shut-off the gas supply to the water heater at the
manual gas shut-off valve. Contact Sears Service at
1-800-4-MY-HOME (1-800-469-4663).
NO
Go to section C.
Reassemble the water heater, press the
NO
thermal switch, and attempt to return the
water heater to service. Does the pilot
remain lit?
Set to desired temperature.
Does the diagnostic status light on the
gas control valve/thermostat give
a two flash error code?
Refer to the “Replacing the Pilot
Assembly” instructions in the manual.
Reassemble and restore to service.
YES
NO
YES
If you are still having difficulty keeping the pilot
lit, contact Sears Service at 1-800-4-MY-HOME
(1-800-469-4663).
NOTE: If you are still experiencing diffi culties after following
the steps in sections A, B, and C, please contact Sears
Service at 1-800-4-MY-HOME (1-800-469-4663).
THERMAL SWITCH LOCATION
THERMAL
SWITCH
40
FIGURE 39.
STATUS LIGHT AND DIAGNOSTIC CODE TROUBLESHOOTING CHART
LED STATUSPROBLEMCORRECTIVE ACTION
0 FLASHES (LED NOT LIT)Pilot light is not lit or Thermopile
has not yet reached normal
operating temperature.
RED LIGHT ON (SOLID)Pilot light was recently extinguished
Turn Gas Control Valve/Thermostat knob to OFF.
Wait 10 minutes, then attempt to relight Pilot by
following the lighting instructions on the water
heater’s label. Until the Thermopile reaches its
normal operating temperature, the Status Light will
not blink, even if the Pilot is lit. It may take up to 90
seconds of continuous Pilot operation before the
Thermopile reaches normal operating temperature
and the Status Light starts to blink.
If the Status Light does not blink after three lighting
attempts, check to make sure unit is getting gas.
Remove the outer door. Press reset button. Replace
outer door. Turn Gas Control Valve/Thermostat
knob to OFF. Wait 10 minutes, then attempt to light
Pilot by following the lighting instructions on the
water heater’s label. Look through the view port for
the Pilot flame. If Pilot is not visible, the spark igniter
or gas supply to the Pilot should be checked.
If the Pilot is visible and the Status Light does not
blink after 90 seconds of continuous Pilot operation,
the Pilot flame may not be heating the Thermopile
sufficiently (weak Pilot), the Thermopile may be
defective, or wiring connectors may be loose.
NOTE: If the water heater has been operating but
has stopped and will not re-light, check the flamearrestor for signs of high temperature (blue or black)
discoloration indicating a flammable vapor incident.
If you suspect a flammable vapor incident has
occurred, do not use this appliance. Immediately
call a qualified technician to inspect the appliance.
Water heaters subjected to a flammable vapors
ignition will require replacement of the entire water
heater.
Turn Gas Control Valve/Thermostat knob to OFF.
Wait 10 minutes for the Thermopile to cool, then
attempt to relight Pilot by following the lighting
instructions on the water heater’s label. NOTE: This
gas control valve/thermostat has built-in circuitry
that requires waiting 10 minutes between lighting
attempts.
Until the Thermopile reaches its normal operating
temperature, the Status Light will not blink, even
if the Pilot is lit. It may take up to 90 seconds of
continuous Pilot operation before the Thermopile
reaches normal operating temperature and the
Status Light starts to blink.
Turn Gas Control Valve/Thermostat knob to OFF.
The Thermopile is probably defective, but loose
wiring connections or a weak Pilot flame can also
cause this symptom.
41
STATUS LIGHT AND DIAGNOSTIC CODE TROUBLESHOOTING CHART (Continued)
LED STATUSPROBLEMCORRECTIVE ACTION
4 FLASHESThe Gas Control Valve’s
temperature sensor has detected
that the water temperature was too
high. Once this condition occurs,
the Main Burner and the Pilot Light
will be shut off. Since the Pilot light
will be off, should this condition
occur, this Flash Code will only
be displayed immediately after
the Pilot has been relit. Turn Gas
Control Valve/Thermostat knob to
OFF.
5 FLASHESThe temperature sensor
(thermistor) is defective.
7 FLASHESGas Control Valve failure.Turn Gas Control Valve/Thermostat knob to OFF.
Relight pilot and verify 4 flashes. If 4 flashes are
observed, turn Gas Control Valve/Thermostat knob
to OFF. Turn Main Gas Supply OFF. Replace the
Gas Control Valve/Thermostat. See “Removing
and Replacing the Gas Control Valve/Thermostat.”
Turn Gas Control Valve/Thermostat knob to OFF.
Replace the temperature sensor (thermistor).
Turn Main Gas Supply OFF. Replace the Gas
Control Valve/Thermostat. See “Removing and
Replacing the Gas Control Valve/Thermostat.”
8 FLASHESThis condition only appears if the
gas control/temperature knob has
been turned off and the thermopile
continued to produce electric
power. This condition can occur
if the thermopile does not cool
down as quickly as expected when
the unit is shut off. This condition
can also occur if the gas control/
temperature knob has been turned
off and the pilot continues to
operate because the pilot valve is
stuck in the open position.
Make sure that the gas control valve/thermostat
knob is set to OFF. Wait one minute. Remove
the outer door. Look through the sight glass for
a pilot flame. If a pilot flame is observed with the
gas control valve/thermostat knob set to the OFF
position, the pilot valve is stuck open. Turn the main
gas supply OFF. Replace the gas control valve/
thermostat. For instructions, see “Removing and
Replacing the Gas Control Valve/Thermostat.”
If the pilot flame is not observed when the gas
control valve/thermostat knob is set to the OFF
position, wait 10 minutes for the thermopile to cool,
then attempt to relight the pilot by following the
lighting instructions on the water heater’s label. If
this condition returns, replace the gas control valve/
thermostat. See “Removing and Replacing the Gas
Control Valve/Thermostat” for instructions.
42
PARTS ORDER LIST
KENMORE MOBILE HOME
GAS WATER HEATER
5
13
MODEL NUMBERS
1
153.33693030 Gallon Tall
153.33694040 Gallon Tall
3
15
17
9
18
11
4
VAC
2
14
Key No. Part Description153.336930153.336940
1Anode Rod90039449003944
2Base-Ring Filter90066169006616
3Burner Head - Natural Gas90061369006136
3Burner Head - LP Gas90066519006603
4Burner Orifi ce - Natural Gas90018869001886
4Burner Orifice - LP Gas186056-0529006700
5Draft Hood90066479006647
6Drain Valve90000589000058
7Gas Control Valve/Thermostat90081019008101
8Inlet Tube90082329008233
9Inner Door Gasket90061419006141
10Instruction Manual *321634-001321634-001
11Manifold Door Assembly - Natural Gas**
11Manifold Door Assembly - LP Gas**
12Mounting Bracket Kit *
13Nipple w/Heat Trap90037199003719
14Outer Door90066489006648
15Pilot Assembly w/ Tubing and
Fittings - Natural Gas
15Pilot Assembly w/ Tubing and
Fittings - LP Gas
16T & P Relief Valve90007289000728
17Thermopile90078729007872
18Manifold Component Block w/ Clip90064499006449
* Not Shown.
** Contains: Manifold Tube, Gasket, Door, Pilot Tube,
Thermopile, Manifold Component Block w/ Clip, Thermal
Switch, Burner Head, Burner Orifi ce, and Pilot Assembly.
90081059008108
90081069008107
90063889006388
90078769007876
90078779007877
16
8
7
6
Now that you have purchased your gas water
heater, should a need ever exist for repair
parts or service, simply contact any Sears
Service Center or call 1-800-4-MY-HOME
®
(1-800- 469-4663). Be sure to provide all pertinent
facts when you call or visit.
WHEN ORDERING REPAIR PARTS, ALWAYS GIVE THE
FOLLOWING INFORMATION:
• MODEL NUMBER
• SERIAL NUMBER
• TYPE GAS - NATURAL OR PROPANE (L.P.)
• PART DESCRIPTION
THIS IS A REPAIR PARTS LIST, NOT A PACKING LIST.
43
Get it fixed, at your home or ours!
Your Home
For troubleshooting, product manuals and expert advice:
www.managemylife.com
For repair – in your home – of all major brand appliances,
lawn and garden equipment, or heating and cooling systems,
no matter who made it, no matter who sold it!
For the replacement parts, accessories and
owner’s manuals that you need to do-it-yourself.
For Sears professional installation of home appliances
and items like garage door openers and water heaters.
1-800-4-MY-HOME
Call anytime, day or night (U.S.A. and Canada)
www.sears.com www.sears.ca
®
(1-800-469-4663)
Our Home
For repair of carry-in items like vacuums, lawn equipment,
and electronics, call anytime for the location of your nearest
Sears Parts & Repair Service Center
1-800-488-1222 (U.S.A.) 1-800-469-4663 (Canada)
www.sears.com www.sears.ca
To purchase a protection agreement on a product serviced by Sears:
1-800-827-6655 (U.S.A.) 1-800-361-6665 (Canada)
Para pedir servicio de reparación
a domicilio, y para ordenar piezas:
1-888-SU-HOGAR
(1-888-784-6427)
www.sears.com
®
Au Canada pour service en français:
1-800-LE-FOYER
(1-800-533-6937)
www.sears.ca
MC
® Registered Trademark / TM Trademark of KCD IP, LLC in the United States, or Sears Brands, LLC in other countries
® Marca Registrada /
MC
Marque de commerce / MD Marque déposée de Sears Brands, LLC
TM
Marca de Fábrica de KCD IP, LLC en Estados Unidos, o Sears Brands, LLC in otros países
44
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.