MAKE ELECTRICAL CONNECTION – U.S.A. ONLY .......... 10
Power Supply Cord Connection ..................................11
Direct Wire Connection ...............................................13
INSTALLATION NOTES
Date of purchase: _________________________________
Date of installation: _______________________________
Installer: ________________________________________
Model number: ___________________________________
Serial number: ___________________________________
DRYER SAFETY
MAKE GAS CONNECTION – U.S.A. AND CANADA ........ 16
ASSISTANCE OR SERVICE ................................. Back Cover
2
3
INSTALLATION REQUIREMENTS
TOOLS AND PARTS
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed here.
Tools needed for all installations:
Flat-head screwdriver
Level
Utility knife
4
Adjustable wrench that
opens to 1" (25 mm) or
hex-head socket wrench
Vent clamps
Caulking gun and compound
(for installing new exhaust vent)
Tin snips (new vent
installations)
#2 Phillips screwdriver
Tape measure
1/4" (6 mm) nut driver
(recommended)
Wire stripper
(direct wire installations)
Pliers
Tools needed for gas installations:
LOCATION REQUIREMENTS
8" (203 mm) or 10"
(254 mm) pipe wrench
Pipe-joint compound
resistant to LP gas
8" (203 mm) or 10"
(254 mm) adjustable wrench
(for gas connections)
Parts supplied (all models):
or
Leveling legs (4)
(Length and appearance of legs may vary according to model)
Parts package is located in dryer drum. Check that all parts
are included.
If using a power supply cord:
Use a UL listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
■ A UL listed 30-amp power supply cord, rated 120/240 volt
minimum. The cord should be type SRD or SRDT and be
at least 4 ft. (1.22 m) long. The wires that connect to
the dryer must end in ring terminals or spade terminals
with upturned ends.
■ A UL listed strain relief.
You will need:
■ A location allowing for proper exhaust installation. See
“Venting Requirements.”
■ A separate 15 or 20-amp circuit needed for gas dryers and
30-amp circuit needed for electric dryers.
■ If using power supply cord, a grounded electrical outlet located
within 2 ft. (610 mm) of either side of dryer. See “Electrical
Requirements.”
■ Floor must support dryer weight of 200 lbs. (90.7 kg). Also
consider weight of companion appliance.
■ Level oor with maximum slope of 1" (25 mm) under entire
dryer. If slope is greater than 1" (25 mm), clothes may not
tumble properly and automatic sensor cycles may not operate
correctly.
■ For garage installation, place dryer at least 18" (460 mm)
above oor.
IMPORTANT: Do not operate, install, or store dryer where it will
be exposed to water, weather, or at temperatures below 45° F
(7° C). Lower temperatures may cause dryer not to shut o at
end of automatic sensor cycles, resulting in longer drying times.
NOTE: No other fuel-burning appliance can be installed in the
same closet as a dryer.
Parts needed: (Not supplied with dryer)
Check local codes. Check existing electrical supply and venting.
See “Electrical Requirements” and “Venting Requirements” before
purchasing parts.
Mobile home installations require metal exhaust system hardware
available for purchase from the dealer from whom you purchased
your dryer. For further information, call 1-844-553-6667 (U.S.) or
1-800-469-4663 (Canada).
Optional Equipment: (Not supplied with dryer)
Refer to your “Use and Care Guide” for information about
accessories available for your dryer.
5
INSTALLATION CLEARANCES
(13 mm)
29"
(13 mm)
3"/3"
(140 mm/0 mm)
For each arrangement, consider allowing more space for ease of
installation and servicing; spacing for companion appliances and
clearances for walls, doors, and floor moldings. Space must be
large enough to allow door to fully open. Add spacing on all sides
of dryer to reduce noise transfer. If a closet door or louvered door
is installed, top and bottom air openings in door are required.
Check code requirements. Some codes limit, or do not permit,
installation of the dryer in garages, closets, mobile homes, or
sleeping quarters. Contact your local building inspector.
DRYER DIMENSIONS
223/4"
(578 mm)
26"
(660 mm)
29"
(737 mm)
Spacing for recessed area or closet installation
The dimensions shown are for the minimum spacing allowed.
■ Additional spacing should be considered for ease of installation
and servicing.
■ Additional clearances might be required for wall, door, and
oor moldings.
■ Additional spacing of 1" (25 mm) on all sides of the dryer
is recommended to reduce noise transfer.
■ For closet installation, with a door, minimum ventilation
openings in the top and bottom of the door are required.
Louvered doors with equivalent ventilitation openings are
acceptable.
■ Companion appliance spacing should also be considered.
Installation Spacing
421/2"
(1080 mm)
1
/2"
A
3
13
/4"
(349 mm)
26"
(660 mm)
421/2"
(1080 mm)
1
/2"
(737 mm)
B
A. Wide opening side-swing door
B. Wide opening hamper door
NOTE: Minimum height of leveling legs should be 1/2" (13 mm),
or to match the height of the accompanying washer.
Back View
1
/4"
1
(32 mm)
18"/18"
(457 mm/
457 mm)
1"/1"
(25 mm/
25 mm)
(76 mm/76 mm)
48 in.2/48 in.
24 in.
3"/3"
(76 mm/76 mm)
(310 cm2/
310 cm
2
/24 in.
(155 cm2/
155 cm
2
2
)
2
2
)
14" max.
(356 mm)
51/2"/0"
(25 mm/0 mm)
1"/0"
Recommended/Minimum spacing
Mobile home - Additional installation requirements:
This dryer is suitable for mobile home installations. The installation
must conform to the Manufactured Home Construction and Safety
Standard, Title 24 CFR, Part 3280 (formerly the Federal Standard
for Mobile home construction and Safety, Title 24, HUD Part 280)
or Standard CAN/CSA-Z240 MH.
Mobile home installations require:
All dryers:
■ Metal exhaust system hardware, available for purchase
from your dealer. For further information, call 1-844-553-6667
(U.S.) or 1-800-469-4663 (Canada).
■ Special provisions must be made in mobile homes to
introduce outside air into dryer. Openings (such as a
nearby window) should be at least twice as large as
dryer exhaust opening.
For gas dryers mobile home installations:
■ Mobile Home Installation Hold-down Kit Part Number
W10432680 is available to order. For further information,
call 1-844-553-6667 (U.S.) or 1-800-469-4663 (Canada).
NOTE: Most installations require a minimum 51/2" (140 mm)
clearance behind the dryer for the exhaust vent with elbow.
See “Venting Requirements”.
6
43/4"
(121 mm)
141/2"
(368 mm)
91/4"
(235 mm)
ELECTRICAL REQUIREMENTS –
U.S.A. ONLY (SPÉCIFICATIONS
ÉLECTRIQUES – ÉTATS-UNIS
SEULEMENT)
ELECTRICAL REQUIREMENTS
It is your responsibility:
■ To contact a qualied electrical installer.
■ To be sure that the electrical connection is adequate and in
conformance with the National Electrical Code, ANSI/NFPA
70 - latest edition and all local codes and ordinances.
The National Electrical Code requires a 4-wire power supply
connection for homes built after 1996, dryer circuits involved
in remodeling after 1996, and all mobile home installations.
A copy of the above code standards can be obtained from:
National Fire Protection Association, One Batterymarch Park,
Quincy, MA 02269.
■ To supply the required 3 or 4 wire, single phase, 120/240
volt, 60 Hz, AC only electrical supply (or 3 or 4 wire, 120/208
volt electrical supply, if specied on the serial/rating plate)
on a separate 30-amp circuit, fused on both sides of the line.
Connect to an individual branch circuit. Do not have a fuse in
the neutral or grounding circuit.
■ Do not use an extension cord.
■ If codes permit and a separate ground wire is used, it is
recommended that a qualied electrician determine that
the ground path is adequate.
Electrical Connection
To properly install your dryer, you must determine the type of
electrical connection you will be using and follow the instructions
provided for it here.
■ This dryer is manufactured ready to install with a 3-wire
electrical supply connection. The neutral ground conductor
is permanently connected to the neutral conductor (white
wire) within the dryer. If the dryer is installed with a 4-wire
electrical supply connection, the neutral ground conductor
must be removed from the external ground connector (green
screw), and secured under the neutral terminal (center or
white wire) of the terminal block. When the neutral ground
conductor is secured under the neutral terminal (center or
white wire) of the terminal block, the dryer cabinet is
isolated from the neutral conductor.
■ If local codes do not permit the connection of a neutral
ground wire to the neutral wire, see “Optional 3-wire
connection” section.
■ A 4-wire power supply connection must be used when the
appliance is installed in a location where grounding through
the neutral conductor is prohibited. Grounding through the
neutral is prohibited for (1) new branch-circuit installations,
(2) mobile homes, (3) recreational vehicles, and (4) areas
where local codes prohibit grounding through the neutral
conductors.
If using a power supply cord:
Use a UL listed power supply cord kit marked for use with
clothes dryers. The kit should contain:
■ A UL listed 30-amp power supply cord, rated 120/240
volt minimum. The cord should be type SRD or SRDT and
be at least 4 ft. (1.22 m) long. The wires that connect to
the dryer must end in ring terminals or spade terminals
with upturned ends.
■ A UL listed strain relief.
If your outlet looks like this:
Then choose a 4-wire power supply cord with
ring or spade terminals and UL listed strain
relief. The 4-wire power supply cord, at least
4 ft. (1.22 m) long, must have 4 10-gauge solid
copper wires and match a 4-wire receptacle
4-wire
receptacle
(14-30R)
of NEMA Type 14-30 R. The ground wire
(ground conductor) may be either green or
bare. The neutral conductor must be identied
by a white cover.
If your outlet looks like this:
Then choose a 3-wire power supply cord with
ring or spade terminals and UL listed strain
relief. The 3-wire power supply cord, at least
4 ft. (1.22 m) long, must have 3 10-gauge solid
copper wires and match a 3-wire receptacle of
3-wire
receptacle
(10-30R)
NEMA Type 10-30R.
If connecting by direct wire:
Power supply cable must match power supply (4-wire or 3-wire)
and be:
■ Flexible armored cable or nonmetallic sheathed copper cable
(with ground wire), covered with exible metallic conduit. All
current-carrying wires must be insulated.
■ 10-gauge solid copper wire (do not use aluminum) at least
5 ft. (1.52 m) long.
7
ELECTRIC DRYER POWER
GAS DRYER POWER HOOKUP –
HOOKUP – CANADA ONLY
ELECTRICAL REQUIREMENTS
It is your responsibility:
■ To contact a qualied electrical installer.
■ To be sure that the electrical connection is adequate and in
conformance with Canadian Electrical Code, C22.1-latest
edition and all local codes. A copy of above codes standard
may be obtained from: Canadian Standards Association,
178 Rexdale Blvd., Toronto, ON M9W 1R3 CANADA.
■ To supply the required 4 wire, single phase, 120/240 volt,
60 Hz, AC only electrical supply on a separate 30-amp circuit,
fused on both sides of the line. A time-delay fuse or circuit
breaker is recommended. Connect to an individual branch
circuit.
■ This dryer is equipped with a CSA
International Certied Power Cord
intended to be plugged into a standard
14-30R wall receptacle. The cord is
5 ft. (1.52 m) long. Be sure wall receptacle
is within reach of dryer’s nal location.
4-wire receptacle
(14-30R)
U.S.A. AND CANADA
ELECTRICAL REQUIREMENTS
■ 120 Volt, 60 Hz, AC only, 15- or 20- amp fused electrical
supply is required. A time-delay fuse or circuit breaker is
recommended. It is also recommended that a separate circuit
serving only this dryer be provided.
GAS SUPPLY REQUIREMENTS
If using a replacement power supply cord, it is recommended that
you use Power Supply Cord Replacement Part Number 9831317.
For further information, call 1-800-469-4663.
GROUNDING INSTRUCTIONS
■
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipmentgrounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
WARNING:Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualied electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with
the dryer: if it will not t the outlet, have a proper outlet
installed by a qualied electrician.
SAVE THESE INSTRUCTIONS
GAS TYPE
Natural Gas:
This dryer is equipped for use with Natural gas. It is design-
certied by CSA International for LP (propane or butane) gases
with appropriate conversion.
■ Your dryer must have the correct burner for the type of gas in
your home. Burner information is located on the rating plate in
the door well of your dryer. If this information does not agree
with the type of gas available, contact your dealer or call
1-844-553-6667 (U.S.) or 1-800-469-4663 (Canada).
8
LP Gas Conversion:
IMPORTANT: Conversion must be made by a quali ed technician.
No attempt shall be made to convert the dryer from the gas
speci ed on the model/serial rating plate for use with a di erent
gas without consulting your gas company.
IMPORTANT: The gas installation must conform with local codes,
or in the absence of local codes, with the Nationl Fuel Gas Code,
ANSI Z223.1/NFPA 54 or the Canadian Natural Gas and Propane
Installation Code, CSA B149.1.
GAS SUPPLY LINE
Option 1 (Recommended Method)
Flexible stainless steel gas connector:
■ If local codes permit, use a new exible stainless steel gas
connector (Design Certi ed by the American Gas Association
or CSA International) to connect your dryer to the rigid gas
supply line. Use an elbow and a 3/8" are x 3/8" NPT adapter
tting between the stainless steel gas connector and the dryer
gas pipe, as needed to prevent kinking.
Option 2 (Alternate Method)
Approved aluminum or copper tubing
■ Must include 1/8" NPT minimum plugged tapping accessible
for test gauge connection, immediately upstream of the gas
connection to the dryer.
■ 1/2" IPS pipe is recommended.
■ 3/8" approved aluminum or copper tubing is acceptable for
lengths under 20 ft. (6.1 m) if local codes and gas supplier
permit.
■ If you are using Natural gas, do not use copper tubing.
■ Lengths over 20 ft. (6.1 m) should use larger tubing and
a di erent size adapter tting.
■ If your dryer has been converted to use LP gas, 3/8" LP
compatible copper tubing can be used. If the total length of
the supply line is more than 20 ft. (6.1 m), use larger pipe.
NOTE: Pipe-joint compounds that resist the action of LP gas
must be used. Do not use TEFLON
■ Must include shut-o valve.
In the U.S.A.:
An individual manual shut-o valve must be installed within six
(6) ft. (1.8 m) of the dryer in accordance with the National Fuel
Gas Code, ANSI Z223.1. The location should be easy to reach
for opening and closing.
In Canada:
An individual manual shut-o valve must be installed in
accordance with the B149.1, Natural Gas and Propane
Installation Code. It is recommended that an individual manual
shuto valve be installed within six (6) ft. (1.8 m) of the dryer.
The location should be easy to reach for opening and closing.
C
®†
tape.
E
BURNER INPUT REQUIREMENTS
Elevations above 10,000 ft. (3,048 m):
■ When installed above 10,000 ft. (3,048 m), a 4% reduction of
the burner Btu rating shown on the model/serial number plate
is required for each 1,000 ft. (305 m) increase in elevation.
Gas supply pressure testing
■ The dryer must be disconnected from the gas supply piping
system during pressure testing at pressures greater than 1/2 psi.
DRYER GAS PIPE
■ The gas pipe that comes out through the rear of your dryer has
a 3/8" male pipe thread.
1
/4"
1
91/4"
(235 mm)
3/8" NPT dryer pipe
(32 mm)
NOTE: For a garage installation, the gas pipe height must be an
additional 18" (460 mm) from the oor.
INSTALL LEVELING LEGS
1. Prepare dryer for leveling legs
BA
A. 3/8" exible gas connector D. 1/2" NPT gas supply line
B. 3/8" pipe to are adapter tting E. Gas shuto valve
C. 1/8" NPT minimum plugged tapping
GAS SUPPLY CONNECTION REQUIREMENTS
■ Use an elbow and a 3/8" are x 3/8" NPT adapter tting
between the exible gas connector and the dryer gas pipe,
as needed to avoid kinking.
■ Use only pipe-joint compound. Do not use TEFLON
■ This dryer must be connected to the gas supply line with a
listed exible gas connector that complies with the standard
for connectors for gas appliances, ANSI Z21.24 or CSA 6.10.
®†
tape.
D
To avoid damaging oor, use a large at piece of cardboard
from dryer carton; place under entire back edge of dryer.
Firmly grasp dryer body (not console panel) and gently lay
dryer down on cardboard.
†® TEFLON is a registered trademark of Chemours.
9
2. Screw in leveling legs
or
Using a wrench and tape measure, screw leveling legs into leg
holes until bottom of foot is approximately 1/2" (13 mm) from
bottom of dryer (so that the dryer height matches that of the
accompanying washer).
Now stand the dryer on its feet. Slide the dryer until it is
close to its nal location. Leave enough room to connect
the exhaust vent.
MAKE ELECTRICAL CONNECTION – U.S.A. ONLY (EFFECTUER
LE RACCORDEMENT ÉLECTRIQUE – ÉTATS-UNIS SEULEMENT)
Electrical Connection Options
For mobile home use
Gas dryers must be securely fastened to the oor.
Mobile home installations require a Mobile Home Installation
Hold-down Kit. For ordering information, call 1-844-553-6667
(U.S.) or 1-800-469-4663 (Canada).
1. Choose electrical connection type
Power supply cord 4-wire receptacle
(NEMA Type 14-30R):
Go to 4-wire Power Supply Cord
Connection.
Power supply cord 3-wire receptacle
(NEMA Type 10-30R):
Go to 3-wire Power Supply Cord
Connection.
4-wire direct connection:
Go to Direct Wire Connection.
3-wire direct connection:
Go to Direct Wire Connection.
NOTE: If local codes do not permit connection of a
cabinet-ground conductor to neutral wire, go to “Optional
3-wire connection.” This connection may be used with
either a power supply cord or a direct wire connection.
2. Remove terminal block cover
E
B
Before you start, disconnect power. Remove hold-down screw
(D) and terminal block cover (A).
C
A
D
F
A. Terminal block cover
B. External ground conductor screw
C. Center terminal block screw
D. Hold-down screw
E. Neutral ground wire
F. Hole below terminal block cover
10
POWER SUPPLY CORD CONNECTION
2. Attach power supply cord to strain relief
Put power supply cord through the strain relief. Be sure that
the wire insulation on the power supply cord is inside the strain
relief. The strain relief should have a tight t with the dryer
cabinet and be in a horizontal position. Do not further tighten
strain relief screws at this point.
If your outlet looks like this:
Power supply cord 4-wire receptacle
(NEMA Type 14-30R):
Go to “4-wire Power Supply Cord
Connection”.
Power Supply Cord Strain Relief
1. Attach power supply cord strain relief
A
B
C
D
Remove the screws from a 3/4" (19 mm) UL listed strain relief
(UL marking on strain relief). Put the tabs of the two clamp
sections (C) into the hole below the terminal block opening
(B) so that one tab is pointing up (A) and the other is pointing
down (D), and hold in place. Tighten strain relief screws just
enough to hold the two clamp sections (C) together.
Power supply cord 3-wire receptacle
(NEMA Type 10-30R):
Go to “3-wire Power Supply Cord
Connection”.
4-wire Power Supply Cord Connection
IMPORTANT: A 4-wire connection is required for mobile homes
and where local codes do not permit the use of 3-wire connections.
Connect remaining wires to outer terminal block screws.
Tighten screws. Finally, reinstall terminal block cover.
Secure cover with hold down screw. Now, go to “Venting
Requirements.”
3-wire Power Supply Cord Connection
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
B
Connect neutral ground wire (E) and neutral wire (white) (C)
of power supply cord under center terminal block screw (B).
Tighten screw.
3. Connect ground wire
F
A
Connect ground wire (F) (green or bare) of power supply cord
to external ground conductor screw (A). Tighten screw.
3-wire receptacle (NEMA
type 10-30R)
Spade terminals with
upturned ends
3-prong plug
Ring terminals
1. Remove center screw
Remove center terminal block screw (B).
B
12
2. Connect neutral wire
BCB
Connect neutral wire (white or center) (C) of power supply cord
to center terminal block screw (B). Tighten screw.
3. Connect remaining wires
DIRECT WIRE CONNECTION
Connect remaining wires to outer terminal block screws. Tighten
screws. Finally, reinstall terminal block cover. Secure cover with
hold down screw. Now, go to “Venting Requirements.”
Direct Wire Strain Relief
1. Attach direct wire strain relief
A
B
C
Unscrew the removable conduit connector (A) and any screws
from a 3/4" (19 mm) UL listed strain relief (UL marking on
strain relief). Put the threaded section of the strain relief (C)
through the hole below the terminal block opening (B). Reaching
inside the terminal block opening, screw the removable conduit
connector (A) onto the strain relief threads.
13
2. Attach direct wire cable to strain relief
Put direct wire cable through the strain relief. The strain
relief should have a tight t with the dryer cabinet and be
in a horizontal position. Tighten strain relief screw against
the direct wire cable.
If your wiring looks like this:
2. Prepare to connect neutral
ground wire and neutral wire
E
A
B
Remove center terminal block screw (B). Remove neutral
ground wire (E) from external ground conductor screw (A).
4-wire direct connection:
Go to “4-wire Direct Connection”
on this page.
3-wire direct connection:
Go to “3-wire Direct Connection”.
4-wire Direct Wire Connection
IMPORTANT: A 4-wire connection is required for mobile homes
and where local codes do not permit 3-wire connections.
1. Prepare your 4-wire cable
for direct connection
1
"
2
⁄
3
(89 mm)
5"
(127 mm)
Direct wire cable must have 5 ft. (1.52 m) of extra length
so dryer may be moved if needed.
Strip 5" (127 mm) of outer covering from end of cable,
leaving bare ground wire at 5" (127 mm). Cut 11/2" (38 mm)
from remaining 3 wires. Strip insulation back 1" (25 mm).
Shape ends of wires into hooks.
1"
(25 mm)
3. Connect neutral ground wire
and neutral wire
EC
B
Connect neutral ground wire (E) and place
hooked end (hook facing right) of neutral
wire (white or center wire) (C) of direct wire
cable under center screw of terminal block
(B). Squeeze hooked ends together and
tighten screw.
4. Connect ground wire
FE
A
14
Connect ground wire (green or bare) (F) of direct wire cable
to external ground conductor screw (A). Tighten screw.
5. Connect remaining wires
3. Connect neutral wire
C
B
Place hooked ends of remaining direct wire cable wires
under outer terminal block screws (hooks facing right).
Squeeze hooked ends together and tighten screws. Finally,
reinstall terminal block cover. Secure cover with hold-down
screw. Now, go to “Venting Requirements.”
3-wire Direct Wire Connection
Use where local codes permit connecting cabinet-ground
conductor to neutral wire.
1. Prepare your 3-wire cable
for direct connection
1"
(25 mm)
3½"
(89 mm)
Direct wire cable must have 5 ft. (1.52 m) of extra length so
dryer may be moved if needed.
Strip 31/2" (89 mm) of outer covering from end of cable. Strip
insulation back 1" (25 mm). If using 3-wire cable with ground
wire, cut bare wire even with outer covering. Shape wire ends
into hooks.
Place hooked end of neutral wire (white
or center) (C) of direct wire cable under
center terminal block screw (B). Squeeze
hooked end together. Tighten screw.
4. Connect remaining wires
Place hooked ends of remaining direct wire cable wires under
outer terminal block screws (hooks facing right). Squeeze
hooked ends together and tighten screws. Finally, reinstall
terminal block cover. Secure cover with hold-down screw.
Now, go to “Venting Requirements.”
Optional 3-wire Connection
with External Grounding
You must verify with a qualified electrician that this
grounding method is acceptable before connecting.
2. Remove center screw
Remove center terminal block screw (B).
1. Prepare to connect neutral
ground wire and neutral wire
E
B
Remove center terminal block screw (B). Remove neutral ground
wire (E) from external ground conductor screw (A).
A
B
15
2. Connect neutral ground wire
A
E
A
B
A
B
A
B
D
C
and neutral wire
MAKE GAS CONNECTION –
U.S.A. AND CANADA
CE
B
Connect neutral ground wire (E) and neutral wire (white or
center wire) (C) of power supply cord or cable under center
terminal block screw (B). Tighten screw.
3. Connect remaining wires
1. Connect gas supply to dryer
Flared
male tting
Remove red cap from gas pipe. Using a wrench to tighten,
connect gas supply to dryer. Use pipe-joint compound
on threads of all non- ared male ttings. If exible metal
tubing is used, be sure there are no kinks.
NOTE: For LP gas connections, you must use pipe-joint
compound resistant to action of LP gas. Do not use
TEFLON®† tape.
Non- ared
male tting
2. Plan pipe fi tting connection
Place hooked ends of remaining wires under outer terminal
block screws (hooks facing right). Tighten screws.
4. Connect external ground wire
Connect a separate copper ground wire (E) from the external
ground conductor screw (A) to an adequate ground. Finally,
reinstall terminal block cover. Secure cover with hold-down
screw. Now, go to “Venting Requirements.”
A. 3/8" exible gas connector
B. 3/8" dryer pipe
A combination of pipe ttings must be used to connect dryer
to existing gas line. A recommended connection is shown. Your
connection may be di erent, according to supply line type,
size, and location.
C. 3/8" to 3/8" pipe elbow
D. 3/8" pipe-to- are adapter tting
3. Open shut-off valve
Closed valve
Open valve
Open shut-o valve in supply line; valve is open when handle
is parallel to gas pipe. Then, test all connections by brushing
on an approved noncorrosive leak-detection solution. Bubbles
will show a leak. Correct any leaks found.
16
VENTING
Venting Requirements
Exhaust hoods:
■ Must be at least 12" (305 mm) from ground or any object
that may obstruct exhaust (such as owers, rocks, bushes,
or snow).
Recommended Styles:
WARNING:To reduce the risk of re, this dryer MUST BE
EXHAUSTED OUTDOORS.
IMPORTANT: Observe all governing codes and ordinances.
Dryer exhaust must not be connected into any gas vent, chimney,
wall, ceiling, attic, crawlspace, or a concealed space of a
building. Only rigid or exible metal vent shall be used for
exhausting.
4"
(102 mm)
4" (102 mm) heavy metal exhaust vent
■ Only a 4" (102 mm) heavy metal exhaust vent and clamps
may be used.
■ Do not use plastic or metal foil vent.
Rigid metal vent:
■ Recommended for best drying performance and to avoid
crushing and kinking.
Flexible metal vent: (Acceptable only if accessible to clean)
■ Must be fully extended and supported in nal dryer location.
■ Remove excess to avoid sagging and kinking that may
result in reduced airow and poor performance.
■ Do not install in enclosed walls, ceilings, or oors.
■ The total length should not exceed 7
■ The length of exible metal vent used must be included in
the overall vent system design as shown in the “Vent System
Charts.”
NOTE: If using an existing vent system, clean lint from entire length
of the system and make sure exhaust hood is not plugged with
lint. Replace plastic or metal foil vents with rigid metal or exible
metal vents. Review Vent System Chart and, if necessary, modify
existing vent system to achieve best drying performance.
3
/4 ft. (2.4 m).
Louvered Hood
Box Hood
Acceptable Style:
Angled Hood
Elbows:
■ 45° elbows provide better airow than 90° elbows.
Recommended Styles:
Good
Better
Clamps:
■ Use clamps to seal all joints.
■ Exhaust vent must not be connected or secured with screws
or other fastening devices that extend into interior of duct
and catch lint. Do not use duct tape.
Vent products can be purchased from your dealer or by calling
1-844-553-6667 (U.S.) or 1-800-469-4663 (Canada).
17
Plan Vent System
A
Recommended exhaust installations
Typical installations vent the dryer from the rear of the dryer.
Other installations are possible.
B
C
D
E
F
G
B
E
H
Alternate installations for close clearances
Venting systems come in many varieties. Select the type best
for your installation. Two close-clearance installations are shown.
Refer to the manufacturer’s instructions.
Over-The-Top installation (also available with one oset elbow)
A. Dryer
B. Elbow
C. Wall
D. Exhaust hood
E. Clamps
F. Rigid metal or exible metal vent
G. Vent length necessary to connect elbows
H. Exhaust outlet
Optional exhaust installations
Each kit includes step-by-step instructions. For ordering
information, see “Venting Kits.”
Periscope installation
NOTE: The following kits for close clearance alternate installations
are available for purchase.
Venting Kits
For more information, call 1-844-553-6667, or visit us at
www.kenmore.com. In Canada, call 1-800-469-4663 or visit us at www.sears.ca.
Part NumberDescriptions
8171587RP0–5" Metal vent periscope
4396037RP0"–18" Metal vent periscope
4396011RP18"–29" Metal vent periscope
439601429"–50" Metal vent periscope
4392892In-Wall metal DuraVent
4396028Sure Connect
close elbow
4396007RWThrough-the-wall vent cap
4396008RP4" steel dryer venting clamps – 2 pack
8212662Flush mounting louvered vent hood 4"
™
Periscope
™
vent, exible dryer venting
18
Special provisions for mobile homes:
12" min.
(305 mm)
12" min.
(305 mm)
Exhaust vent must be securely fastened to a noncombustible
portion of mobile home and must not terminate beneath the
mobile home. Terminate exhaust vent outside.
Vent System Chart
(29" Wide Long Vent 65212610
and 75212610 Models Only)
Mobile home exhaust installation
Determine vent path:
■ Select route that will provide straightest and most direct
path outdoors.
■ Plan installation to use fewest number of elbows and turns.
■ When using elbows or making turns, allow as much room
as possible.
■ Bend vent gradually to avoid kinking.
■ Use as few 90° turns as possible.
Determine vent length and elbows needed for best drying
performance:
■ Use following Vent System Chart to determine type of vent
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those speci ed
in Vent System Chart. Exhaust systems longer than those
speci ed will:
Number of
90° turns
or elbows
0Rigid metal160 ft. (48.8 m)
1Rigid metal150 ft. (45.7 m)
2Rigid metal140 ft. (42.7 m)
3Rigid metal130 ft. (39.6 m)
4Rigid metal120 ft. (36.6 m)
5Rigid metal110 ft. (33.5 m)
Type
of vent
Box/louvered
or angled hoods
INSTALL VENT SYSTEM
1. Install exhaust hood
Install exhaust hood and use caulking compound to seal
exterior wall opening around exhaust hood.
■ Shorten life of dryer.
■ Reduce performance, resulting in longer drying times
and increased energy usage.
Vent System Chart
Number of
90° turns
or elbows
0Rigid metal64 ft. (20 m)58 ft. (17.7 m)
1Rigid metal54 ft. (16.5 m)48 ft. (14.6 m)
2Rigid metal44 ft. (13.4 m)38 ft. (11.6 m)
3Rigid metal35 ft. (10.7 m)29 ft. (8.8 m)
4Rigid metal27 ft. (8.2 m)21 ft. (6.4 m)
Type
of vent
Box/louvered
hoods
2. Connect vent to exhaust hood
Angled
hoods
Vent must t over the exhaust hood. Secure vent to exhaust
hood with 4" (102 mm) clamp. Run vent to dryer location using
straightest path possible. Avoid 90° turns. Use clamps to seal
all joints. Do not use duct tape, screws, or other fastening
devices that extend into interior of vent to secure vent,
because they can catch lint.
19
CONNECT VENT
LEVEL DRYER
1. Connect vent to exhaust outlet
Using a 4" (102 mm) clamp, connect vent to exhaust outlet
in dryer. If connecting to existing vent, make sure vent is clean.
Vent must t over dryer exhaust outlet and inside exhaust
hood. Check that vent is secured to exhaust hood with a
4" (102 mm) clamp.
2. Move dryer to fi nal location
1. Level dryer
Check levelness of dryer from side to side. Repeat from
front to back.
NOTE: The dryer must be level for the moisture sensing
system to operate correctly.
Not Level LEVEL Not Level
Move dryer to nal location. Avoid crushing or kinking vent.
2. Adjust leveling legs
If dryer is not level, prop up using a wood block. Use wrench
to adjust legs up or down, and check again for levelness.
20
COMPLETE INSTALLATION
CHECKLIST
■ Check that all parts are now installed. If there is an extra
part, go back through steps to see what was skipped.
■ Check that you have all of your tools.
■ Dispose of/recycle all packaging materials.
■ Check dryer’s nal location. Be sure vent is not crushed
or kinked.
■ Check that dryer is level. See “Level Dryer.”
■ Remove lm on console and any tape remaining on dryer.
■ Wipe dryer drum interior thoroughly with a damp cloth to
remove any dust.
■ Read “Dryer Use” in your “Use and Care Guide.”
All Models:
■ Select a Timed Dry heated cycle, and start dryer.
Do not select Air Only Temperature setting.
If dryer will not start, check the following:
• Controls are set in a running or “On” position.
• Start button has been touched and held for 3 seconds.
• Dryer is plugged into an outlet and/or electrical supply
is connected.
• Household fuse is intact and tight, or circuit breaker has
not tripped.
• Dryer door is closed.
Electric Models:
■ For power supply cord installation, plug into a grounded
outlet. For direct wire installation, turn on power.
■ When the dryer has been running for 5 minutes, open the dryer
door and feel for heat. If you feel heat, cancel the cycle and
close the door.
If you do not feel heat, turn the dryer o and check
the following:
• There may be 2 household fuses or circuit breakers for the
dryer. Check that both fuses are intact and tight, or that
both circuit breakers have not tripped. If there is still no
heat, contact a qualied technician.
Gas Models:
■ Check that gas supply is on.
■ Check for leaks.
■ When the dryer has been running for 5 minutes, open the dryer
door and feel for heat. If you feel heat, cancel the cycle and
close the door.
If you do not feel heat, turn the dryer o and check to see
whether gas supply line shut-o valve is open.
• If the gas supply shut-o valve is closed, open it,
then repeat the 5-minute test as outlined above.
• If the gas supply shut-o valve is open, contact a qualied
technician.
All Models:
NOTE: You may notice an odor when dryer is rst heated. This
odor is common when heating element is rst used. The odor will
go away.
21
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.