AYUDA O SERVICIO TÉCNICO ..............................BACK COVER
DRYER SAFETY
2
• It is recommended that the owner post, in a prominent location, instructions for the customer’s use in the event the customer smells gas.
This information should be obtained from your local gas supplier.
• Post the following warning in a prominent location.
3
4
INSTALLATION INSTRUCTIONS
Tools and Parts
Gather the required tools and parts before starting installation.
Tools needed for all installations:
Flat-blade screwdriver#2 Phillips screwdriver
1/4" nut driver or 5/16"
socket wrench
(recommended)
Tin snips (new vent
installations)
Tools needed for gas installations:
8" or 10" pipe wrench
Pipe-joint compound
resistant to LP gas
8" or 10" adjustable
wrench (for gas
connections)
Parts supplied:
Tape measure
Level
Adjustable wrench that
opens to 1" (25 mm) or
hex-head socket wrench
Vent clamps
Pliers
Caulking gun and
compound (for installing
new exhaust vent)
Leveling legs (4)
Parts package is located in dryer drum. Check that all parts
are included.
Parts needed:
Check local codes. Check existing gas and electrical supply and
venting. See “Electrical Requirements,” “Gas Supply Requirements,”
and “Venting Requirements” before purchasing parts.
Utility knife
Putty knife
5
Location Requirements
43
3
/
8
"
(1102 mm)
*26"(660 mm)
29"
(737 mm)
A
15
1
/
4
"
(387 mm)
B
*273/4"
(705 mm)
43
3
/
8
"
(1102 mm)
29"
(737 mm)
22¾"
(578 mm)
3
43
/
8
(1102 mm)
22¾"
"
(578 mm)
3
43
/
8
(1102 mm)
"
13¾"
(349 mm)
You will need:
■ A location that allows for proper exhaust installation. A
gas dryer must be exhausted to the outdoors. See “Venting
Requirements.”
■ A grounded electrical outlet located within 2 ft (610 mm)
of either side of the dryer. See “Electrical Requirements.”
■ A sturdy oor to support dryer and a total weight (dryer
and load) of 200 lbs. (90.7 kg). The combined weight of
a companion appliance should also be considered.
■ Level oor with maximum slope of 1" (25 mm) under entire
dryer. If slope is greater than 1" (25 mm), install Extended
Dryer Feet Kit, Part Number 279810. If not level, clothes
may not tumble properly and automatic sensor cycles may
not operate correctly.
Do not operate your dryer at temperatures below 45°F (7°C). At
lower temperatures, the dryer might not shut o at the end of an
automatic cycle. Drying times can be extended.
The dryer must not be installed or stored in an area where it will
be exposed to water and/or weather.
Check code requirements. Some codes limit, or do not permit,
installation of the dryer in garages, closets, mobile homes, or
sleeping quarters. Contact your local building inspector.
NOTE: No other fuel-burning appliance can be installed in the
same closet as a dryer.
Installation clearances:
The location must be large enough to allow the dryer door to
open fully.
Most installations require a minimum 5½" (140 mm) clearance
behind the dryer for the exhaust vent with elbow. See “Venting
Requirements.”
Dryer Dimensions
43
(1102 mm)
3
/
"
8
*26"
(660 mm)
A
29"
(737 mm)
1
15
(387 mm)
/
"
4
3
43
/
8
(1102 mm)
*273/4"
(705 mm)
"
B
29"
(737 mm)
22¾"
(578 mm)
*273/4"
(705 mm)
C
29"
(737 mm)
*273/4"
(705 mm)
29"
(737 mm)
D
C. Wide opening side-swing door
D. Wide opening hamper door
Installation Spacing
3"*
(76 mm)
18"*
14" max.*
(356 mm)
2
48 in.
(310 cm )
*
2
(457 mm)
2
1"
(25 mm)
29"
(737 mm)
A
1"*
1"
(25 mm)
(25 mm)
27¾"
(705 mm)
B
24 in.
(155 cm )
*
2
C
3"*
(76 mm)
A. Recessed area
B. Side view - closet or confined area
C. Closet door with vents
*Required spacing
Installation spacing for recessed area or closet
The dimensions shown are for the minimum spacing allowed.
■ Additional spacing should be considered for ease of
installation and servicing.
■ Additional clearances might be required for wall, door, and
oor moldings.
■ Additional spacing of 1" (25 mm) on all sides of the dryer is
recommended to reduce noise transfer.
■ For closet installation, with a door, minimum ventilation
openings in the top and bottom of the door are required.
Louvered doors with equivalent ventilation openings are
acceptable.
■ Companion appliance spacing should also be considered.
Mobile home - Additional installation requirements
This dryer is suitable for mobile home installations. The installation
must conform to the Manufactured Home Construction and Safety
Standard, Title 24 CFR, Part 3280 (formerly the Federal Standard for
Mobile Home Construction and Safety, Title 24, HUD Part 280) or
the Canadian Manufactured Home Standard CAN/CSA-Z240 MH.
■ Metal exhaust system hardware, available for purchase.
For further information, please reference the “Assistance
or Service” section of the “Dryer User Instructions.”
■ Special provisions must be made in mobile homes to
introduce outside air into the dryer. The opening (such as
a nearby window) should be at least twice as large as the
dryer exhaust opening.
A. Small opening side-swing door
B. Large opening side-swing door
6
GAS DRYER POWER HOOKUP
Gas Supply Requirements
Gas type
Natural gas:
This dryer is equipped for use with Natural Gas. It is designcertied by CSA International for LP (propane or butane) gases
with appropriate conversion.
■ Your dryer must have the correct burner for the type of gas
at your location. Burner information is located on the rating
plate in the door well of your dryer. If this information does
not agree with the type of gas available, please contact your
local Sears store or Sears Service Center.
LP gas conversion:
Conversion must be made by a qualified technician.
No attempt should be made to convert the dryer from the gas
specied on the model/serial rating plate for use with a dierent
gas without consulting the serving gas supplier.
Gas supply connection requirements
There are many methods by which your gas dryer can be
connected to the gas supply. Listed here are some guidelines
for two dierent methods of connection.
Option 1 (Recommended Method)
Flexible stainless steel gas connector:
■ If local codes permit, use a new exible stainless steel
gas connector (Design Certied by the American Gas
Association or CSA International) to connect your dryer
to the rigid gas supply line. Use an elbow and a 3/8" are
x 3/8" NPT adapter tting between the stainless steel gas
connector and the dryer gas pipe, as needed to prevent
kinking.
Option 2 (Alternate Method)
Approved aluminum or copper tubing:
■ Lengths over 20 ft. (6.1 m) can use 3/8" approved tubing
(if codes and gas supplier permit).
■ If you are using Natural Gas, do not use copper tubing.
■ 3/8" are x 3/8" NPT adapter tting between dryer pipe
and 3/8" approved tubing.
■ Lengths over 20 ft. (6.1 m) should use larger tubing and a
dierent size adapter tting.
■ If your dryer has been converted to use LP gas, 3/8" LP
compatible copper tubing can be used. If the total length
of the supply line is more than 20 ft. (6.1 m), use larger pipe.
NOTE: Pipe joint compounds that resist the action of LP
gas must be used. Do not use TEFLON®† tape.
Dryer gas pipe
■ The gas pipe that comes out through the rear of your dryer has
a 3/8" male pipe thread.
1¼"
(32 mm)
A
A. 3/8" NPT dryer pipe
9¼"
(235 mm)
Gas supply line
■ 1/2" NPT pipe is recommended.
■ 3/8" approved tubing is acceptable for lengths under
20 ft. (6.1 m) if local codes and gas supplier permit.
■ Must include 1/8" NPT minimum plugged tapping accessible
for test gauge connection, immediately upstream of the gas
connection to the dryer (see illustration).
■ Must include a shuto valve:
An individual manual shuto valve must be installed within
six (6) feet (1.8 m) of the dryer in accordance with the National
Fuel Gas Code, ANSI Z223.1. The shut o valve location should
be easy to reach for opening and closing.
A
A. 3/8" flexible gas connector
B. 3/8" pipe to flare adapter fitting
C. 1/8" NPT minimum plugged tapping
C
B
E
D
D. 1/2" NPT gas supply line
E. Gas shutoff valve
Burner input requirements
Elevations up to 10,000 ft. (3,048 m):
■ The design of this dryer is certied by CSA International for use
at altitudes up to 10,000 ft. (3,048 m), above sea level at the
B.T.U. rating indicated on the model/serial number plate. Burner
input adjustments are not required when the dryer is operated
up to this elevation.
Elevations above 10,000 ft. (3,048 m):
■ When installed above 10,000 ft. (3,048 m) a 4% reduction
of the burner B.T.U. rating shown on the model/serial
number plate is required for each 1,000 ft. (305 m)
increase in elevation.
Gas supply pressure testing
■ The dryer must be disconnected from the gas supply piping
system during pressure testing at pressures greater than 1/2 psi.
†®
TEFLON is a registered trademark of E.I. Du Pont De Nemours and Company.
7
Electrical Requirements
VENTING
Venting Requirements
■ 120 Volt, 60 Hz., AC only, 15- or 20-amp fused electrical
supply is required. A time-delay fuse or circuit breaker is
recommended. It is also recommended that a separate
circuit serving only this dryer be provided.
Electrical Connection
Plug into a grounded 3-prong outlet
1.
GROUNDING INSTRUCTIONS
■
For a grounded, cord-connected dryer:
This dryer must be grounded. In the event of malfunction or
breakdown, grounding will reduce the risk of electric shock
by providing a path of least resistance for electric current.
This dryer is equipped with a cord having an equipmentgrounding conductor and a grounding plug. The plug must
be plugged into an appropriate outlet that is properly
installed and grounded in accordance with all local codes
and ordinances.
WARNING:Improper connection of the equipment-
grounding conductor can result in a risk of electric shock.
Check with a qualied electrician or service representative
or personnel if you are in doubt as to whether the dryer is
properly grounded. Do not modify the plug provided with
the dryer: if it will not t the outlet, have a proper outlet
installed by a qualied electrician.
WARNING:To reduce the risk of re, this dryer MUST BE
EXHAUSTED OUTDOORS.
IMPORTANT: Observe all governing codes and ordinances.
Dryer exhaust must not be connected into any gas vent,
chimney, wall, ceiling, attic, crawlspace, or a concealed
space of a building. Only rigid or exible metal vent shall
be used for exhausting.
■ Only a 4" (102 mm) heavy metal exhaust
Rigid metal vent:
■ Recommended for best drying performance and to avoid
crushing and kinking.
Flexible metal vent: (Acceptable only if accessible to clean)
■ Must be fully extended and supported in nal dryer location.
■ Remove excess to avoid sagging and kinking that may result in
reduced airow and poor performance.
■ Do not install in enclosed walls, ceilings, or oors.
■ The total length should not exceed 7
NOTE: If using an existing vent system, clean lint from entire
length of the system and make sure exhaust hood is not plugged
with lint. Replace plastic or metal foil vents with rigid metal or
exible metal vents. Review Vent System Chart and if necessary,
modify existing vent system to achieve best drying performance.
vent and clamps may be used. DURASAFE™
venting products are recommended and are
available from your local Sears store or Sears
Service Center.
■ DURASAFE™ vent products can be
purchased from your dealer. For further
information, please call 1-800-4-MY-HOME®
(1-800-469-4663) or visit our Internet site at:
www.sears.com.
■ Do not use plastic or metal foil vent.
3
/4 ft. (2.4 m).
SAVE THESE INSTRUCTIONS
8
Elbows:
B
■ 45° elbows provide better airow than 90° elbows.
Good Better
Clamps:
■ Use clamps to seal all joints.
■ Exhaust vent must not be connected or secured with screws
or other fastening devices that extend into interior of duct
and catch lint. Do not use duct tape.
Plan Vent System
Recommended exhaust installations
Typical installations vent the dryer from the rear of the dryer.
Other installations are possible.
B
C
D
E
A
A . Dryer E . Clamps
B . Elbow F . Rigid metal or flexible metal vent
C . Wall G . Vent length necessary to connect elbows
D . Exhaust hood H . Exhaust outlet
F
G
B
H
Exhaust hoods:
■ Must be at least 12" (305 mm) from ground or any object that
may obstruct exhaust (such as owers, rocks, bushes, or snow).
4"
A
4"
(102 mm)
4"
(102 mm)
Recommended styles:
A. Louvered hood
B. Box hood
(102 mm)
2½"
(64 mm)
Acceptable styles:
C. Angled hood
Standard exhaust installation with rigid metal vent
9
Alternate installations for close clearances
Venting systems come in many varieties. Select the type best
for your installation. Two close-clearance installations are shown.
Refer to the manufacturer’s instructions.
Over-The-Top installation (also available with one offset elbow)
Special provisions for mobile home installations:
The exhaust vent must be securely fastened to a noncombustible
portion of the mobile home structure and must not terminate
beneath the mobile home. Terminate the exhaust vent outside.
The Vent System Chart provides venting requirements that will
help achieve best drying performance.
Periscope installation
NOTE: The following kits for close clearance alternate installations
are available for purchase. For further information, please call
1-800-4-MY-HOME® (1-800-469-4663).
■ Over-the-Top Installation:
Part Number 26-49900
■ Periscope Installation (For use with dryer vent to wall vent
mismatch):
Part Number 26-49901 - Less than 5" (127 mm) mismatch
Part Number 26-49908 - 5" (127 mm) to 18" (457 mm)
mismatch
Part Number 26-49904 - 18" (457 mm) to 29" (737 mm)
mismatch
Part Number 26-49905 - 29" (737 mm) to 50" (1270 mm)
mismatch
Vent System Chart
Number of
90° turns
Type
of vent
or elbows
0
1
2
3
4
Rigid metal
Rigid metal
Rigid metal
Rigid metal
Rigid metal
Determine vent length
■ Select route that will provide straightest and most direct path
outdoors.
■ Plan installation to use fewest number of elbows and turns.
■ When using elbows or making turns, allow as much room
as possible.
■ Bend vent gradually to avoid kinking.
■ Use as few 90° turns as possible.
Box/Louvered
hoods
64 ft. (20 m)
54 ft. (16.5 m)
44 ft. (13.4 m)
35 ft. (10.7 m)
27 ft. (8.2 m)
Angled
hoods
58 ft. (17.7 m)
48 ft. (14.6 m)
38 ft. (11.6 m)
29 ft. (8.8 m)
21 ft. (6.4 m)
10
Determine vent length and elbows needed for best drying
performance:
■ Use following Vent System Chart to determine type of vent
material and hood combinations acceptable to use.
NOTE: Do not use vent runs longer than those specied
in Vent System Chart. Exhaust systems longer than those
specied will:
■ Shorten life of dryer.
■ Reduce performance, resulting in longer drying times and
increased energy usage.
If an Exhaust Hood Cannot be Used:
The outside end of main vent should have a sweep elbow directed
downward.
Each exhaust vent should enter the main vent at an angle
pointing in the direction of the airow. Vents entering from
the opposite side should be staggered to reduce the exhaust
air from interfering with the other vents.
dryer exhaust vent
air flow
dryer exhaust vent
30° max.
main collector vent
dryer exhaust vent
30° max.30° max.
dryer exhaust vent
A
A. Main collector vent (vertical)
B. 180° sweep elbow
C. 2 ft (610 mm) minimum above highest point of building
D. Roof
B
C
D
If the main vent travels vertically through the roof, rather than
through the wall, install a 180° sweep elbow on the end of the
vent at least 2 ft (610 mm) above the highest part of the building.
B
C
A
A. Exhaust hood or sweep elbow
B. Wall
C. Main exhaust vent
D. Horizontal vent
2 ft (610 mm)
D
The maximum angle of each vent entering the main vent should
be no more than 30°.
Keep air openings free of dry cleaning uid fumes. Fumes
create acids which, when drawn through the dryer heating units,
can damage dryers and loads being dried.
A clean-out cover should be located on the main exhaust vent
for periodic cleaning of the exhaust system.
An exhaust hood should cap the outside end of the main vent to
keep exhausted air from returning to the dryers. If an exhaust
hood cannot be used, the outside end of the main vent should
have a sweep elbow directed downward.
Install Leveling Legs
Prepare dryer for leveling legs
1.
The opening in the wall or roof shall have a diameter 1/2" (13 mm)
larger than the exhaust vent diameter. The exhaust vent should be
centered in the opening. Do not install screening or cap over the
end of the vent.
Multiple Dryer Venting:
NOTE: For more information on installing multiple vents or for
local code requirements, contact a mechanical contractor.
A main exhaust vent can be used for exhausting a group of dryers.
Main exhaust vent should be sized to remove 200 CFM of air per
dryer. Large capacity lint screens of proper design may be used
in the main exhaust vent if checked and cleaned frequently. The
room where the dryers are located should have makeup air equal
to or greater than the CFM of all the dryers in the room.
Backdraft Damper Kits, Part No. 3391910, are available from
your Sears Service Center and should be installed in each dryer’s
exhaust vent to keep exhausted air from returning into the dryers
and to keep the exhaust in balance within the main exhaust vent.
Unobstructed air openings are required.
To avoid damaging oor, use a large at piece of cardboard
from dryer carton; place under entire back edge of dryer.
Firmly grasp dryer body (not console panel) and gently lay
dryer down on cardboard.
11
A
B
C
D
12" min.
(305 mm)
12" min.
(305 mm)
A
B
Screw in leveling legs
2.
diamond
diamond
marking
marking
Connect vent to exhaust hood
2.
Examine leveling legs, nd diamond marking. Screw legs into
leg holes by hand, use a wrench to nish turning legs until
diamond marking is no longer visible.
Now stand the dryer on its feet. Slide the dryer until it is close
to its nal location. Leave enough room to connect the exhaust
vent.
For mobile home use
Gas dryers must be securely fastened to the oor.
Mobile home installations require a Mobile Home Installation
Hold-down Kit. For ordering information please reference the
“Dryer User Instructions.”
Install Vent System
Install exhaust hood
1.
12" min
(305 mm)
Vent must t over the exhaust hood. Secure vent to exhaust
hood with 4" (102 mm) clamp. Run vent to dryer location
using straightest path possible. Avoid 90° turns. Use clamps
to seal all joints. Do not use duct tape, screws, or other
fastening devices that extend into interior of vent to secure
vent, because they can catch lint.
Make Gas Connection
Connect gas supply to dryer
1.
Flared
male fitting
Remove red cap from gas pipe. Using a wrench to tighten,
connect gas supply to dryer. Use pipe-joint compound
on threads of all non-ared male ttings. If exible metal
tubing is used, be sure there are no kinks.
NOTE: For LP gas connections, you must use pipe-joint
compound resistant to action of LP gas. Do not use
TEFLON®† tape.
Non-flared
male fitting
12" min
(305 mm)
Install exhaust hood and use caulking compound to seal
exterior wall opening around exhaust hood.
12
Plan pipe tting connection
2.
A. 3/8" flexible gas connector
B. 3/8" dryer pipe
A combination of pipe ttings must be used to connect dryer
to existing gas line. A recommended connection is shown. Your
connection may be dierent, according to supply line type,
size, and location.
†®
TEFLON is a registered trademark of E.I. Dupont De Nemours and Company.
C. 3/8" to 3/8" pipe elbow
D. 3/8" pipe-to-flare adapter fitting
A
B
Open shut-o valve
3.
Closed valve
Open valve
Open shut-o valve in supply line; valve is open when handle
is parallel to gas pipe. Then, test all connections by brushing
on an approved noncorrosive leak-detection solution. Bubbles
will show a leak. Correct any leaks found.
Connect Vent
Connect vent to exhaust outlet
1.
Level Dryer
Level dryer
1.
Check levelness of dryer from side to side. Repeat from
front to back.
NOTE: The dryer must be level for the moisture sensing system
to operate correctly.
Using a 4" (102 mm) clamp, connect vent to exhaust outlet
in dryer. If connecting to existing vent, make sure vent is
clean. Dryer vent must t over dryer exhaust outlet and inside
exhaust hood. Check that vent is secured to exhaust hood with
a 4" (102 mm) clamp.
Move dryer to nal location
2.
Not Level LEVEL Not Level
Tighten and adjust leveling legs
2.
If dryer is not level, prop up using a wood block, use wrench
to adjust legs up or down, and check again for levelness.
Once legs are level, make sure all four legs are snug against
the ground before tightening them.
Move dryer to nal location. Avoid crushing or kinking vent.
After dryer is in place, remove corner posts and cardboard
from under the dryer.
13
Complete Installation Checklist
■ Check that all parts are now installed. If there is an extra
part, go back through steps to see what was skipped.
■ Check that you have all of your tools.
■ Dispose of/recycle all packaging materials.
■ Check dryer’s nal location. Be sure vent is not crushed
or kinked.
■ Check that dryer is level. See “Level Dryer”.
Reverse Door Swing (Optional)
If your door is the Large Side-Swing Door, follow
steps 1-6.
If your door is the Super Wide Side-Swing Door,
follow steps 1-13.
NOTE: Magnetized screw driver is helpful.
Wide Model Large Side-Swing Door
Place towel on dryer
1.
■ Plug into a grounded 3 prong outlet. Turn power on.
■ Remove lm on console and any tape remaining on dryer.
■ Wipe dryer drum interior thoroughly with a damp cloth to
remove any dust.
■ Read “Dryer Use” in your Use and Care Guide.
■ Set the dryer on a full heat cycle (not an air cycle) for
20 minutes and start the dryer.
If the dryer will not start, check the following:
■ Dryer is plugged into a grounded 3 prong outlet.
■ Electrical supply is connected.
■ Household fuse is intact and tight, or circuit breaker has
not tripped.
■ Dryer door is closed.
■ When the dryer has been running for 5 minutes, open the dryer
door and feel for heat. If you feel heat, cancel cycle and close
the door.
If you do not feel heat, turn the dryer o and check to see whether
gas supply line shuto valve is open.
If the gas supply line shuto valve is closed, open it, then repeat
the 5-minute test as outlined above.
■ If the gas supply line shuto valve is open, contact a
qualied technician.
NOTE: You may notice an odor when the dryer is rst heated. This
odor is common when the heating element is rst used. The odor
will go away.
Place towel on top of dryer to avoid damaging the surface.
Remove bottom screws
2.
14
Open dryer door. Remove bottom screws from dryer cabinet
side of hinges. Loosen (do not remove) top screws from dryer
cabinet side of hinges.
Lift door o top screws
3.
Check door strike alignment
6.
Lift door until top screws in cabinet are in large part of hinge
slot. Pull door forward o screws. Set door on top of dryer.
Remove top screws from dryer cabinet.
Remove and transfer hinge hole
4.
plugs
Use a small, at-blade screwdriver to gently remove 4 hinge
hole plugs on left side of dryer cabinet. Insert plugs into hinge
holes on opposite side of dryer cabinet.
Insert screws in hinge holes on
5.
dryer cabinet
Close door and check that door strike aligns with door
catch. If needed, slide door catch left or right within slot
to adjust alignment.
Super Wide Side-Swing Door
Place towel on dryer
1.
Place towel on top of dryer to avoid damaging the surface.
Remove bottom screws
2.
NOTE: Two people maybe needed to reinstall door.
Insert screws into bottom holes on left side of dryer cabinet.
Tighten screws halfway. Position door so large end of door
hinge slot is over screws. Slide door up so screws are in bottom
of slots. Tighten screws. Insert and tighten top screws in hinges.
Open dryer door. Remove bottom screws from dryer cabinet
side of hinges. Loosen (do not remove) top screws from dryer
cabinet side of hinges.
15
Lift door o top screws
3.
Rotate outer door
6.
Take outer door and rotate in 180º and set it back down on
inner door. Be certain to keep cardboard spacer centered
between doors. Reattach outer door panel to inner door panel
so handle is on the side where hinges were just removed. Insert
4 door screws.
Lift door until top screws in dryer cabinet are in large part of
hinge slot. Pull door forward o screws. Set door (handle side
up) on top of dryer. Remove top screws from dryer cabinet.
Remove screws from hinges
4.
Remove screws attaching hinges to door.
Remove screws from door
5.
Flip door over
7.
Flip door over so handle side is down.
Attach door hinges
8.
Remove screws at top, bottom, and side of door (4 screws).
Keep door screws separate from hinge screws as they are
diferent sizes. Holding door over towel on dryer, grasp sides
of outer door and lift to separate it from inner door.
NOTE: Do not pry apart with putty knife or screwdriver.
Do not pull on door seal or plastic door catches.
16
Reattach door hinges to dryer door so that the larger hole is at
the bottom of the hinge.
Remove door strike
9.
Remove door strike plug
12.
Remove door strike from dryer cabinet and set aside.
Remove and transfer
10.
hinge hole plugs
Use a small, at-blade screwdriver to gently remove 4 hinge
hole plugs on left side of dryer cabinet. Transfer plugs into
hinge holes on opposite side of dryer cabinet.
Insert screws in hinge holes on
11.
dryer cabinet
Remove door strike plug. Insert the door strike removed in Step
9 into hole and secure with screw. Insert door strike plug into
original door strike hole and secure with screw.
13.
Close door and check that door strike aligns with door
catch. If it is needed, slide door catch left or right within slot
to adjust alignment.
Check door strike alignment
NOTE: Two people maybe needed to reinstall door.
Insert screws into the bottom holes on left side of dryer
cabinet. Tighten screws halfway. Position door so large
end of door hinge slot is over screws. Slide door up so
screws are in bottom of slots. Tighten screws. Insert and
tighten top screws in hinges.
17
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.