The SmartSonic Acoustic Wave Transmitter is designed for high accuracy level measurement of a variety of liquids. The
SmartSonic Integral can also be used for Open Channel Flow Measurement.
PRINCIPLE OF OPERATION
The SmartSonic Transmitters consist of two main components:
• The Electronics
• The Sensor (Transducer)
The transducer contains a piezoelectric crystal that converts an electrical signal
from the electronics, into acoustic (sound) waves. These acoustic waves are
directed through the air toward the process media surface. They are then
reflected off of this surface and returned to the transducer. The piezoelectric
crystal then converts the received waves into an electrical signal which is
analyzed by the electronics.
The time difference between the transmitted wave and the received wave is
proportional to the distance from the face of the transducer to the process media
surface. This distance is used by the electronics to calculate level or open
channel flow in the units selected by the operator.
Range
Accuracy ±0.2% of max. range
Resolution 0.04” (1 mm)
Enclosure Material ABS + UV
Transducer Housing Material Polypropylene or PVDF
Transducer Material Glass Reinforced Epoxy
Cable Length 328ft. (std.); 656ft. (opt.)
Weight
INSTALLATION
Unpack the transmitter carefully. Inspect all units for damage. Report any damage to carrier immediately. Check the
contents against the packing slip and purchase order. Kenco’s SmartSonic Acoustic Wave Transmitters are
manufactured to the highest quality standards. These instruments use electronic components that can be damaged by
static electricity. Make sure that you are properly grounded before starting installation. Insure that all electrical
connections are properly made, and that there are no “floating” connections.
Analog 4-20mA
Digital RS-422
Discrete (5) SPDT Relays
AC 2A @ 220Vac Relay
DC 2A @ 30Vdc
Display Graphical LCD User
Keypad 4 Button
Ambient -40ºF to 140ºF Temperature
Process -40ºF to 212ºF
Electronics 2.4 lbs
Sensor 1.1 lbs.
Page 2
DIMENSIONS - INCHES
3.15
3.31
9.68
3.26
2.87
2.28
2.75
Transducer
(Sensor)
2.83
0.59
4.88
2.56
0.55
1” NPT
7.87
Mounting Plate
Page 3
MOUNTING GUIDELINES
MOUNTING INSTRUCTIONS
Precautions:
•Ensure that the sensor is mounted in an area that meets the stated temperature, pressure and technical specifications.
The transmitter must
be mounted in such a
way, as to avoid the
process fluid level from
entering the Dead
Zone.
If the level enters the
Dead Zone, an error
will occur, and the
transmitter will not
measure the fluid level
The sensor needs to
be mounted as far
away as possible from
processes that can
interfere with the
Acoustic Wave. This
example shows a fluid
filling inlet.
While the narrow wave
diameter of the Kenco
Acoustic Wave
Transmitters allows
you to mount the
sensor closer to the
vessel wall, than other
Ultrasonic transmitters,
it is recommended to
mount the sensor at
least 1.64 feet away
from the wall.
The sensor must be
mounted perpendicular
with the process fluid
level. Even the
slightest mounting off
perpendicular will affect
the measurement.
Anything over 4º will
usually result in a loss
of echo or at the very
least, an inaccurate
reading
• Ensure that high voltage (ac) sources or cables are at least 1 yard away from the sensor and its cable.
• Installation and Operation of this transmitter must conform to the National Electric Code and any applicable local
codes.
Direct Mounting of the Sensor to the Tank
1.) Open the top of the tank
2.) Feed the free end of the sensor cable from the inside of the tank, through the 1” NPT coupling attached to the top
of the tank (customer supplied).
3.) Keep feeding the cable until the sensor threads are touching the coupling. Screw the sensor threads into the
coupling.
Page 4
Mounting the Sensor to a Flange
2
1
JP1
1.) Feed the free end of the sensor cable through the 1” NPT threaded connection on the flange. Feed the cable from
the process side of the flange
2.) Keep feeding the cable until the sensor threads are touching the inside of the flange. Screw the sensor threads into
the 1” NPT threaded connection on the flange.
3.) Bolt the flange to the top of the tank. Use a soft gasket.
Mounting the Transmitter (Electronics)
1.) Drill (2) holes, 2.75” apart, onto the desired mounting surface. Install (2) screws into these holes.
2.) Attach the mounting plate to the SmartSonic, using the (4) screws provided.
3.) Mount the SmartSonic onto the desired mounting surface, using the slotted holes on the mounting plate and the (2)
screws on the desired mounting surface from Step #1.
WIRING
It is recommended that conduit be installed onto the ½” NPT connections (C1 thru C4) on the electronics
housing. Seal drain fittings should be used to prevent moisture from entering the transmitter. In high humidity
areas, use breather drains to minimize moisture intrusion.
All wiring, conduit, and fittings must conform to local electrical codes for the location selected. If the transmitter is to be
used in a Hazardous Area, the applicable sections of the National Electric Code must be followed as well.
GND
Page 5
Sensor cable side
Wiring Connections
In order to connect the wiring, remove the ribbed faceplate on the front of the electronics, using a 7/64” (3mm) Allen
wrench. Ensure that the cover is reinstalled, with the gasket in place, after completing the wiring. Refer to the drawing on
the previous page for the location of the wiring connections and cable entries.
NOTE: Power must be off when wiring the electronics. Damage and/or injury may occur if power is applied
during wiring.
Wiring the Sensor Connections
The sensor uses a custom 5-conductor cable between the sensor and electronics. The cable comes with a cable
connector, which can be used to extend the length of the cable. Make sure that you use Helukabel p/n 16028. Use of
any other cable may damage the sensor, or interfere with the signal.
If you are only using the standard 16.4 ft. of cable supplied attached to the sensor, or the non-connector end of an
extended cable:
1.) Remove the cable connector from the sensor-side of the cable (the male plug). Skip this step if you are using the
non-connector end of an extended cable.
2.) Thread the cable through aperture (C1 – see wiring drawing on page 5) located on the right side of the SmartSonic
electronics base.
3.) Connect each wire by color, to the appropriate screw terminal on connector JP5. If the cable contains multiple black
wires, connect as follows:
JP5 Post Color
1 Green (Black 1)
2 Brown (Black 2)
3 Blue (Shield)
4 White (Black 3)
5 Yellow
If you are using the cable connector, follow these directions:
Nut
1.) Unscrew the nut holding the cable connector together.
Loose cable side
2.) Disassemble the “loose cable side” of the connector.
3.) Disconnect the “dummy cable” wires from the connector, and connect the wires from the extended cable (supplied
separately). The blue wire is connected to the cable shield. Make sure that the wires match exactly. If you aren’t
sure, disassemble the “Sensor cable side” connector and match up the pins to the wire color. If you have any
questions, please contact Kenco. Do not apply power unless the connector is wired correctly.
Page 6
Wiring the Digital and Analog Communication Cables
SmartSonic data can be monitored on a PC or PLC via RS-485 (MODBUS RTU) digital communications, when connected
to JP22. You can also monitor a 4-20mA output by connecting to JP32 (the 4mA and 20mA settings are discussed in the
CALIBRATION section).
1.) Thread the connection wires through aperture C2.
2.) Connect each wire to the appropriate screw terminal at connection block JP22 (MODBUS) and / or JP32 (4-20mA).
JP22 connections are as follows:
JP22 Post Wire
1 B (TxD)
2 A (RxD)
3 Ground
JP32 connections are as follows: Post 1 (+); Post 2 (-).
JP32 Post Wire
1 +
2 -
Wiring the Power Connections
1.) Thread the power wires through aperture C4
2.) If you have 100-230Vac power, connect each wire to the appropriate screw terminal on JP1 as follows:
JP1 Post Wire
1 Neutral
2 Hot
GND Ground
NOTE: If you are using 100-230Vac leave the red and black wires connected to JP2.
3.) If you have a 24Vdc power source, disconnect the red and black wires from JP2, and connect your power wires:
JP2 Post Wire
1 +
2 -
NOTE: Use either JP1 or JP2. Do not connect external power to both.
Wiring the Relays
1.) Thread the power wires through aperture C2 (DC Power) or C4 (AC Power). C3 may not be available when using
conduit.
2.) Connect each wire to the appropriate screw terminal (see wiring drawing on page 5).
Page 7
CALIBRATION
This section explains how to set up and calibrate the SmartSonic for accurate measurement monitoring using the basic
menu options. SmartSonic is supplied with preprogrammed default settings, making it ready for immediate operation.
Measurement readings are displayed on the default screen as soon as the unit is powered on. It is recommended that
you replace the default tank height value with the actual tank height, as described later in this section.
Display / Keypad
The LCD display screen functioning in “Normal” mode provides continuously updated measurement readings. This
display is also used to view the program menus, options, settings, and data values. These are accessed by using the
keypad. The picture below shows the display of the SmartSonic:
The keypad buttons are used to perform various operations, summarized in the following table
Indication modes
Numerical area
Measurement
units
Relays
Flow
measurements
Application types
Button Uses Include:
or
20 mA/4 mA
levels
Tank graphic
Operation
modes
Scan distance
Tank height
Sensor offset
mode indicator
Clear scan distance
• Accessing the program menu (when pressed simultaneously with “ESC.”
• Accessing a function within a menu, enabling you to make modifications
• Moving from left to right between displayed digits.
• Saving changes to data.
• Accessing the program menu (when pressed simultaneously with “ENT.”
• Moving from right to left between displayed digits.
• Returns you to the previous function (without saving changes), or back to
the default screen
• Moving to the next/previous function within a menu.
• Scrolling through or back data values in programs.
NOTE: Within some programs, the digits in the display can be individually modified. This is indicated by a flashing digit.
In this case the ENT and ESC buttons are used to move between digits. The BACK and NEXT buttons are used to
change the value of the flashing digit.
Page 8
Tank Terminology
Process
Media
r
Tank
Span
Dead Zone
Ai
Dead Zone
SmartSonic Remote
● Minimum 1.3 feet
Tank Height
SmartSonic Remote
● Maximum 39.4 feet
Height
Span Range
(4mA to 20mA)
SmartSonic Remote
● Maximum 38.1 feet
Default Screen
As soon as SmartSonic is fully installed and powered on, the LCD displays the default screen. The default screen
provides continuously updated measurement readings and displays the current settings for some functions (either the
default settings or the settings selected from the main menu). The relay number is displayed for each activated relay. You
can toggle between display indication types, such as: level, distance, volume and others, by using the SmartScan Main
Menu.
The tank graphic in the default screen gives an approximate visual indication of the current level of the tank contents,
while the numerical area gives the exact reading. If the level enters the dead zone, the numerical area displays FF FFF. If
the tank is empty, the numerical area displays the tank height. 000000 may be displayed temporarily while SmartSonic is
taking a reading. You can refresh the reading by pressing the ENT and BACK buttons simultaneously.
NOTE: By default, the displayed value is in meters, and gives the distance measurement, meaning from the sensor face
to the level of the fluid. The measurement indication mode and measurement unit can be changed, as described in Setting
Main Menu Options
Page 9
Accessing the Main Menu
and
This section describes the procedure for accessing the SmartSonic Main Menu. The main screen (see Page #7) is
accessed as follows:
Press / Action Display Description
The SmartSonic takes several seconds to
Connect SmartSonic to power supply See Wiring Section
and simultaneously
Flashes for 5
Flashes for 5
seconds, then is
displayed
seconds
warm-up. During this time various characters
will turn on and off, and the Tank Graphic will
cycle
This is the password display
Use to enter the password (716) in place of
(000). BACK and NEXT will change the vlue of
the digit (0-9). ENT steps to the next digit; ESC
steps to the previous digit.
Single Sensor (only available option).
Press ENT.
The main screen (Page #7) is now displayed.
Main Screen Functions
Indication modes
Numerical area
Measurement
units
Relays
Flow
measurements
Application types
20 mA/4 mA
levels
Tank graphic
Operation
modes
Scan distance
mode indicator
Tank height
Sensor offset
Clear scan distance
Page 10
SETTING MAIN MENU OPTIONS
The following functions are available in the SmartSonic Main Menu:
Functions Page
Setting the Indication Mode 11
Setting the Measurement Units 12
Setting the Relay Values 12
Setting The 20mA and 4mA Values 17
Setting the Open Channel Flow Measurements 17
Setting the Tank Height 17
Setting the Application Type 18
Setting the Operation Modes 18
Setting the Sensor Offset 19
Setting the Scan Distance Values 20
Clearing the Scan Distance Values 21
NOTES: After you select any option the “Tank Graphic” will cycle a few times. Wait until one of the options starts to blink before proceeding to the next step.
When you change an option, a flashing “Ar. 5” may appear. This is just to remind you that the option
you just selected may affect the Relay or 4-20mA Settings, and that you need to review these settings.
Setting the Indication Mode
The first function in the Main Menu is the Indication Mode. This sets the type of measurement. The options are:
• DIST: The displayed reading represents the distance from the sensor face to the process media.
• LEVEL: The displayed reading represents the level of the process media measured from the bottom of the vessel.
• FLOW: The displayed reading represents the flow rate through the configured Flume or Weir.
• DIA: DO NOT USE
Setting an Indication Mode enables you to toggle between other indication types as well, using the BACK and NEXT
buttons as described in the table below: For example, if the unit is configured for Level, the BACK and NEXT buttons will
toggle between Level and Distance.
Indication Toggle Selections (BACK / NEXT Buttons)
Totalization indicates the total accumulative flow. It is expressed in 10 digits. The first 5 digits (High) are shown as
H00000, and the second 5 digits (Low) are shown as L00000. This function will be described later in this manual
(Additional Features).
Press / Action Display Description
and
Move between the available options. DIA
(Diameter) is no longer available.
For Example
Select the desired option. This will show on the
display for a few moments, then return to the
Main Menu
Go to the next function (Measurement Mode)
Page 11
Setting the Measurement Mode
This function is used to select the units used for the display. The following measurement options are available:
• METER (default), INCH, or FEET: Select one of these options for Level or Distance measurements
• M3/HR or G.P.M.: Select one of these for Flow measurements
After setting the measurement unit, the selected unit flashes on the display whenever you enter numerical values during
the setup procedure. The values for functions, such as Relay, will be displayed in the selected measurement unit.
Press / Action Display Description
Move between the available options.
and
For Example
Select the desired option. This will show on the
display for a few moments, then return to the
Main Menu
Go to the next function (Relay Values)
NOTE: If you select METER any relevant flow measurement will be in metric units (M3/HR). The opposite also applies,
so that if you select M3/HR, any relevant distance or level measurements will be in meters. If you select INCH or FEET,
the flow measurements will be in G.P.M.. If you select G.P.M., any relevant distance or level measurements will be in
inches.
If you select METER when using a FLOW unit configured to show G.P.M., the METER sign will flash rapidly for a few
seconds. If you approve the selection by pressing ENT, the flow unit will change to M3/HR.
Setting the Relay Values
The relays in the SmartSonic Remote are SPDT (Single Pole, Double-throw). This means that each relay has (3)
connections:
• Normally Closed (NC)
• Common (C)
• Normally Open (NO)
In the SmartSonic, the term CLOSED means that the relay is de-energized. In this state the NC and C terminals are
closed (connected), and the NO and C terminals are open (disconnected).
The term OPEN means that the relay is energized. In this state the NC and C terminals are open (disconnected), and the
NO and C terminals are closed (connected).
In the event of power loss to the SmartSonic, the relays automatically go to the CLOSED state (NC & C are connected;
NO & C are disconnected). Make sure that any auxiliary equipment connected to the SmartSonic relays, will be in a safe
condition upon loss of power to the SmartSonic.
You can set the relays to (5) different indication modes:
• Level
• Distance
• Flow
• Volume
• Totalization
Page 12
Loading...
+ 25 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.