![](/html/15/1506/150685a194282f2877f773bd5a47e91381cb3cd008c3b32b4b267d37d3c797c4/bg1.png)
KENCO ENGINEERING COMPANY
P.O. BOX 470426 TULSA, OK 74147-0426
PHONE(918) 663-4406 FAX: (918) 663-4480
www.kenco-eng.com e-mail:info@kenco-eng.com
INSTALLATION INSTRUCTIONS FOR MODEL KLCP OIL LEVEL CONTROLLERS
WITH ADAPTERS (INCLUDING HIGH PRESSURE MODELS)
Note: For fire safe oil level controllers (KLCP-FS) see additional instructions in this work sheet covering installation of fire safe
valves.
PNEUMATIC SWITCH INSTALLATION:
• Connect the supply line of air pressure to the ¼” pipe thread located at the top of the air valve (D)
Note: Acceptable air pressure range is 10 psi to 100 psi. Air pressure greater than 100 psi will prevent the switch from operating.
• The exhaust vent is located at the base of the air valve (E) and is 1/8” pipe thread.
Note: If an exhaust line is used to carry gas away from the pneumatic switch, this line must be short, undamaged and trap free.
COMMON PROBLEMS AND SOLUTIONS
• Leaking switch may caused by dirt. Wash the assembly in solvent to remove any foreign material.
• The switch is not tripping. Check for excessive restriction from a long exhaust line, a damaged line or a line with moisture
traps, or excessive pressure from the supply line.
• The switch is not properly tripping. Check the pressure coming into the switch. The switch may need adjustment. See below:
PNEUMATIC SWITCH ADJUSTMENT: The switch is factory set at 60 psi with a trip point of 5/8” to ¾” oil drop.
• Remove the controller from the housing.
• Connect the supply pressure to the pneumatic valve (D).
• With the switch float arm against the magnet, adjust screw (C) until there is no leakage from the pneumatic valve.
• To adjust for a higher or lower level release lock nut (A) and backing screw (B) out.
• For a lower level, turn screw (B) in and readjust screw (C).
Note: Screw (C) must be adjusted until there is no leakage from the valve with the float assembly resting against the magnet.
:
Figure 1- Pneumatic Switch Adjustment
![](/html/15/1506/150685a194282f2877f773bd5a47e91381cb3cd008c3b32b4b267d37d3c797c4/bg2.png)
II. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR OIL INLET VALVE:
• Connect the oil supply line to the oil inlet on the oil level controller. The minimum recommended supply line is ¾” I.D. The
supply line must be clean and it is recommended that it be flushed with solvent before installation.
• Connect the oil supply line to the oil supply tank. If there is no existing valve at the tank or the existing supply outlet, a shut-off
valve should be placed in the line to prevent oil loss when cleaning the inlet screen or filter.
• For high pressure models HP-A, pressure range must be between 5 psi and 34 psi. For high pressure units HP-B, pressure
range must be between 35 psi and 70 psi.
• The oil inlet valve is adjusted to maintain the oil level at the center of the sight glass. Low or high levels are often caused by
two problems:
1. Excessive oil inlet pressure, which will cause the unit to overfill.
2. Improper equalizing lines between the crankcase and the controller will also result in improper levels.
Note: Low pressure models require a minimum of 2’ of head pressure and a maximum of 15’ of oil inlet head pressure.
III. INSTALLATION INSTRUCTIONS FOR UNITS WITH ADAPTERS:
OIL LEVEL CONTROLLERS WITH –9 (Universal adapter), -10(Slotted universal adapter), -12 (Pole mounted adapter) AND –
FS OPTIONS
• Set the controller so that the centerline of the sight window corresponds to the desired oil level in the crankcase.
• Mount the controller close to the crankcase and connect the hose from the ¾” outlet located on the controller to the crankcase.
NOTE: The outlet port on the oil level controller must be located below the oil level in the crankcase.
• An equalizing line must be used between the controller and crankcase in order to equalize the pressure. The tubing must be a
minimum of 1/2” I.D. and must be kept under 2 feet. DO NOT loop this line. It must be trap free and self draining, with a
downward pitch flow by gravity.
OIL LEVEL CONTROLLER WITH
Figure 3
Figure 2: Typical Mount of –9 Adapter
–11 AND –11-FS OPTION (for Mechanical Lubricators): See Figure 3
Drill holes in the lubricator housing as shown, and mount
the controller with the inlet located on the top side using the
seal washers and mounting bolts provided.
• Place the seal washers between the controller and the
lubricator housing.