Kenco Engineering KLCP User Manual

KENCO ENGINEERING COMPANY
P.O. BOX 470426 TULSA, OK 74147-0426
PHONE(918) 663-4406 FAX: (918) 663-4480
www.kenco-eng.com e-mail:info@kenco-eng.com
INSTALLATION INSTRUCTIONS FOR MODEL KLCP OIL LEVEL CONTROLLERS
WITH ADAPTERS (INCLUDING HIGH PRESSURE MODELS)
Note: For fire safe oil level controllers (KLCP-FS) see additional instructions in this work sheet covering installation of fire safe valves.
PNEUMATIC SWITCH INSTALLATION:
Connect the supply line of air pressure to the ¼” pipe thread located at the top of the air valve (D) Note: Acceptable air pressure range is 10 psi to 100 psi. Air pressure greater than 100 psi will prevent the switch from operating.
The exhaust vent is located at the base of the air valve (E) and is 1/8” pipe thread. Note: If an exhaust line is used to carry gas away from the pneumatic switch, this line must be short, undamaged and trap free.
COMMON PROBLEMS AND SOLUTIONS
Leaking switch may caused by dirt. Wash the assembly in solvent to remove any foreign material.
The switch is not tripping. Check for excessive restriction from a long exhaust line, a damaged line or a line with moisture
traps, or excessive pressure from the supply line.
The switch is not properly tripping. Check the pressure coming into the switch. The switch may need adjustment. See below:
PNEUMATIC SWITCH ADJUSTMENT: The switch is factory set at 60 psi with a trip point of 5/8” to ¾” oil drop.
Remove the controller from the housing.
Connect the supply pressure to the pneumatic valve (D).
With the switch float arm against the magnet, adjust screw (C) until there is no leakage from the pneumatic valve.
To adjust for a higher or lower level release lock nut (A) and backing screw (B) out.
For a lower level, turn screw (B) in and readjust screw (C).
Note: Screw (C) must be adjusted until there is no leakage from the valve with the float assembly resting against the magnet.
:
Figure 1- Pneumatic Switch Adjustment
II. INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR OIL INLET VALVE:
Connect the oil supply line to the oil inlet on the oil level controller. The minimum recommended supply line is ¾” I.D. The
supply line must be clean and it is recommended that it be flushed with solvent before installation.
Connect the oil supply line to the oil supply tank. If there is no existing valve at the tank or the existing supply outlet, a shut-off valve should be placed in the line to prevent oil loss when cleaning the inlet screen or filter.
For high pressure models HP-A, pressure range must be between 5 psi and 34 psi. For high pressure units HP-B, pressure range must be between 35 psi and 70 psi.
The oil inlet valve is adjusted to maintain the oil level at the center of the sight glass. Low or high levels are often caused by two problems:
1. Excessive oil inlet pressure, which will cause the unit to overfill.
2. Improper equalizing lines between the crankcase and the controller will also result in improper levels.
Note: Low pressure models require a minimum of 2’ of head pressure and a maximum of 15’ of oil inlet head pressure.
III. INSTALLATION INSTRUCTIONS FOR UNITS WITH ADAPTERS:
OIL LEVEL CONTROLLERS WITH –9 (Universal adapter), -10(Slotted universal adapter), -12 (Pole mounted adapter) AND – FS OPTIONS
Set the controller so that the centerline of the sight window corresponds to the desired oil level in the crankcase.
Mount the controller close to the crankcase and connect the hose from the ¾” outlet located on the controller to the crankcase.
NOTE: The outlet port on the oil level controller must be located below the oil level in the crankcase.
An equalizing line must be used between the controller and crankcase in order to equalize the pressure. The tubing must be a minimum of 1/2” I.D. and must be kept under 2 feet. DO NOT loop this line. It must be trap free and self draining, with a downward pitch flow by gravity.
OIL LEVEL CONTROLLER WITH
Figure 3
Figure 2: Typical Mount of –9 Adapter
–11 AND –11-FS OPTION (for Mechanical Lubricators): See Figure 3
Drill holes in the lubricator housing as shown, and mount
the controller with the inlet located on the top side using the seal washers and mounting bolts provided.
Place the seal washers between the controller and the lubricator housing.
Loading...
+ 2 hidden pages