INSTALLATION INSTRUCTIONS
Install in compliance with Class I, Division 2 wiring methods in the National Electrical Code, any applicable local codes and any specic instructions given on the luminaire labels. If installing in conjunction with any additional options and/or accessories, also refer to the respective instruction sheets. Installation required by a qualied electrician only.
1
NOTE: To maintain the ratings and approvals noted on the xture nameplate, any ttings or mounting hardware supplied with this xture, must be used with this xture. If lag screws are provided and the mounting surface does not facilitate the use of the lag screws, alternate hardware can be used, provided the enclosed nylon washer is used under the head of the fastener. The conduit hub shipped with the xture must also be used with the wiring method selected to maintain the integrity of the xture.
Read all xture markings and labels to insure correct installation of the xture. Additional information may be located on the xture, separate from this instruction sheet, regarding orientation and mounting restrictions.
www.kenall.com | P: 800-4-Kenall | F: 262-891-9701 | 10200 55th Street Kenosha, Wisconsin 53144, USA
This product complies with the Buy American Act: manufactured in the United State swith more than 50% of the component cost of US origin It may be covered by patents found at www.kenall.com/patents. Content of specication sheets is subject to change; please consult www.kenall.com for current product details. ©2019 Kenall Mfg.Co.
HES_F-2589-091118
INSTALLATION INSTRUCTIONS
SURFACE MOUNTED FIXTURES
1. Use mounting hardware to secure the xture (see diagram). Install lens to housing, adjust so that lens is centered. To prevent lens from shifting install screw to housing with washer, through hole in lens. Note-mount screw with washer in the down position. For Peace of Mind Guarantee with at least 4 fasteners (4 point mounting) Exception is HES3 series (2 point mounting). Attachment to the electrical box only will not insure proper xture performance. (When wall mount: Mount with lens fastener down and lamp in horizontal position).
1/4 - 20 × 1/2 Screw Rubber Washer
Nylon Washer
Lens Retention Screw with Washer (mounting position screw down)
®
, xture must be mounted to building
2
2. Disconnect power to the circuit before wiring xture.
3. Remove 6 screws to remove reector.
4. Remove lens by pulling up on end of lens that is not under base end cap.
5. IP65: Remove four screws and washers to remove two end caps and pull out lens.
6. Place xture over an installed electrical junction box. Locate and drill 4 pilot holes in mounting surface. Use xture base as template. Using 1/4-20 fasteners and anchors appropriate for the mounting surface, (not supplied), mount xture base to building (HES3 series requires 1/2" NPT watertight tting directly to back 7/8" hole for wiring).
7. Connect xture leads to power supply leads using connectors suitable for the gauge and number of wires being used (not included). Connections are to be made in the junction box, not the xture. Black xture lead connects to the supply conductor, white xture lead connects to the neutral supply conductor, and the grounding wire must be connected to a suitable ground.
8. As applicable, reassemble reector to the base. Install lamps. Place one end of lens in end of base at an angle into lens channel. Press lens down completely into lens channel. Squeeze lens in middle slide lens over and center in xture. Install lens retention screw with washer.
IP65 reassembly: Reassemble reector to the base. Install lamps. Install lens in lens channels with edge of lens even with edge of base (lens centered). Install end caps with bottom end cap ange under base. Push down on lens and rotate end cap over lens. Install 4 screws and washers to secure end caps. Install end caps on loosely. Tighten each end cap equally rotating from one end cap to the other till end caps tightened equally to Max. of 8 lbf.
www.kenall.com | P: 800-4-Kenall | F: 262-891-9701 | 10200 55th Street Kenosha, Wisconsin 53144, USA
This product complies with the Buy American Act: manufactured in the United State swith more than 50% of the component cost of US origin It may be covered by patents found at www.kenall.com/patents. Content of specication sheets is subject to change; please consult www.kenall.com for current product details. ©2019 Kenall Mfg.Co.
HES_F-2589-091118
INSTALLATION INSTRUCTIONS
PENDANT MOUNTED FIXTURES
1. Install in accordance with all local codes. No counterbalancing required.
2. Kenall xture is supplied with two 1/2" NPT threaded entries for attachment to conduit.
3. Connect conduit suitable for the area to all hubs and terminate the conduit in an approved junction box. (Note: HES3 and HES5 series pendant mount only)
EMERGENCY LIGHTING (-EL) OPTION
Install per above and enclosed supplementary instruction (included with product upon shipment).
CUSTOMER SERVICE
For technical assistance, call 1-800-4KENALL (1-800-453-6255).
WARRANTY
For warranty information visit www.kenall.com/Resources/Certied-Performance-Warranties
3
www.kenall.com | P: 800-4-Kenall | F: 262-891-9701 | 10200 55th Street Kenosha, Wisconsin 53144, USA
This product complies with the Buy American Act: manufactured in the United State swith more than 50% of the component cost of US origin It may be covered by patents found at www.kenall.com/patents. Content of specication sheets is subject to change; please consult www.kenall.com for current product details. ©2019 Kenall Mfg.Co.