Congratulations on choosing the FreshAir (FA) respiratory protective system.
Used correctly, Kemppi products can signicantly increase the productivity
of your welding, and provide years of economical service.
This operating manual contains important information on the use,
maintenance and safety of your Kemppi product. The technical
specications of the equipment can be found at the end of the manual.
Please read the operating manual and other instructions carefully before
using the equipment for the rst time.
For more information on Kemppi products, contact Kemppi Oy, consult an
authorised Kemppi dealer, or visit the Kemppi web site at www.kemppi.com.
The specications presented in this manual are subject to change without
prior notice.
Important notes
Items in the manual that require particular attention in order to minimise
damage and personal harm are indicated with the ’NOTE!’ notation. Read
these sections carefully and follow their instructions.
1.2 About the product
FreshAir (FA) is a respiratory protective system which is based on the
principle of circulated pressurized air in the hood. A supply of clean, ltered
breathing air creates positive pressure inside the headpiece, which prevents
the external contaminated air from entering the user’s breathing zone.
A suitable compressed air source complying to EN 12 021 standard and
supplying hygienically clean breathing air, can be connected to the FA
Pressure Flow control valve. If the air does not comply with this standard,
install the FA Pressure Conditioner ltration unit before the FreshAir Pressure
Flow Control valve unit.
FA Pressure Flow Control is equipped with a pressure gauge for checking
the input pressure. The air at the outlet of a FA Pressure Conditioner lter
unit complies with EN 12 021 standard, if it is used within the temperature
range 10 – 60 °C and the air from the compressor complies with the
requirements explained later in this manual. Up to two users can be
connected to the FA Pressure Conditioner ltration unit.
NOTE: FreshAir Pressure Conditioner does not remove carbon monoxide (CO)
and carbon dioxide (CO₂).
EN
Disclaimer
While every eort has been made to ensure that the information contained
in this guide is accurate and complete, no liability can be accepted for any
errors or omissions. Kemppi reserves the right to change the specication of
the product described at any time without prior notice. Do not copy, record,
reproduce or transmit the contents of this guide without prior written
permission from Kemppi.
1.3 Requirements for compressed air supplied from
the compressor
• FA Pressure Conditioner can only be connected to a compressor which
supplies air at an oxygen concentration of 20 – 22 % vol.
• The carbon dioxide concentration must not exceed 500 ppm and the
carbon monoxide concentration must not exceed 15 ppm.
• The maximum concentration of water in the air may be 50 mg/m at
the rated pressure of 1 – 20 MPa. The humidity of the supplied air must
be controlled to prevent the unit from freezing.
1.4 Manufactured by
Manufactured for and on behalf of Kemppi Oy by:
CleanAir Ltd.
2. PRECONDITIONS FOR USE
Before you can use the system correctly and safely, you must fully
understand all of the following precautions.
• It is forbidden to use the unit in explosive environments.
• The system may only be used in environments where the probability
of damaging the supply hose is small and the user’s movement is not
limited.
• If the unit is used in environments with high temperatures, the supply
hose must be resistant to such eects.
• During an extreme work load, the pressure in the hood may reach
negative values and the user may feel air deciency. In such case the
protection of air passages is reduced.
• In the FreshAir system it is forbidden to use oxygen-enriched air or
oxygen. There is a risk of explosion.
• If another accessory apart from FreshAir (e.g. a spray gun) is connected
to the compressed air supply, the user must make sure that a sucient
air ow to the hood is secured even at the maximum air consumption
by this accessory.
• Before every use of the unit, check that the air ow is higher than the
minimum value specied in the technical parameters.
• If the unit stops supplying air for any reason, the user must leave the
contaminated area immediately.
• The unit, in a combination with a welding helmet or a hard hat, is
6FreshAir Pressure Flow Control / Conditioner
not recommended for users with beard or long hair extending to the
respiratory zone.
• Beware of a higher CO concentration in the air supply, which may
occur if the compressor does not work properly when lubricating oil
burns due to high temperatures.
• The supply air pressure must be within the range 300 – 1000 kPa.
• The supply pressure hoses may only be located in such places of the
workplace where they cannot be damaged.
• The maximum working pressure of the hose supplied to the
conditioner is 1000 kPa.
• Before connecting the unit to the air distribution, it is necessary to
check what medium is in the line and what is its quality. For the FA
Pressure units, it is necessary to provide breathable air according to
EN 12 021 standard.
• The FA Pressure unit can be combined with Beta 90 FreshAir or Delta
90 FreshAir head tops.
• Information on head parts are provided in the instructions for use of
the FreshAir head parts.
FA Pressure Conditioner
• Pressure hose for FA Pressure Conditioner is not antistatic and the
maximum temperature to which they are resistant without damage is
70 °C.
• The maximum length of the hose from the compressed air distribution
or FA Pressure Conditioner to the head unit must not exceed 10 m.
• The recommended temperature range of use ideally is 10 – 40 °C. At
lower temperatures, the use of the protective hood with air supply
may be unpleasant. The lowest allowable temperature for use of FA
Pressure is 10 °C.
NOTE! If the recommendations stated in this manual are ignored, the warranty
is automatically invalidated and the level of personal protection may not meet
the designated standards.
EN
3. UNPACKING AND ASSEMBLY
3.1 Unpacking FA Pressure Flow Control
Check that the delivery is complete and no damage occurred during
transport.
We recommend using the FA Pressure Conditioner together with the FA
Pressure Flow Control in order to guarantee the supplied breathing air
quality. The supplied compressed air in the breathing air distribution system
must meet EN 12 021 standard.
Content of the FA Pressure Conditioner assembly
FA Pressure Conditioner unit1 pc
Unit stand1 pc
Screws for connecting the unit to the stand2 pcs
Washer4 pcs
Operating manual1 pc
3.2 Assembly
FA Pressure Flow Control + FA Pressure Conditioner
1. Check that all components are in good condition with no visible
damage.
2. Connect FA Pressure Conditioner to a suitable breathing air
distribution system. The air source must be equipped with safety
valve. If the FA Pressure Conditioner is not used, the air supply must
comply with EN 12 021 standard.
3. Attach the enclosed hose connector and screw it in.
4. It is recommended to use only original hoses supplied by the
manufacturer and certied according to the applicable standard.
5. Check that the air pressure in the distribution system corresponds to
the range 300 – 1000 kPa.
6. Attach the unit onto your belt and t the connecting hose to it.
7. Using the quick coupling, connect the pressure hose from the
compressed air source to the FA Pressure unit. The hose from FA
Pressure Conditioner to FA Pressure Flow Control must not be longer
than 10 metres.
8. Check the air ow as explained in section 4.2: "Air ow test". The lowest
allowable ow rate is 170 l/min.
8FreshAir Pressure Flow Control / Conditioner
4. USAGE
4.1 Inspection before every use
Do the following checks always before you start using the equipment:
• Visually check individual parts, particularly the air hose and sealing
elements for damages.
• Check that the hose is tted correctly to the air unit and to the head
part connector.
• The air pressure in the distribution system must be in the range
300 – 1000 kPa.
• Check that the air ow in the hose is sucient.
• Ensure that air is supplied into the head part breathing zone.
4.2 Air ow test
When measuring the air ow, follow the instructions delivered with the ow
indicator. If the ow rate is dierent, proceed as follows.
EN
1. Pull plastic screw cap out to the adjustment position and turn counterclockwise by hand until it stops.
2. Lever the cap o from the regulation valve with a at screwdriver.
3. Let the noise silencer stay in place and connect the ow meter to the
regulation valve. Turn on the air supply and adjust the ow rate to
170 l/min using a at screwdriver.
4. Air ow is sucient, if the top of the cone is placed in the green area. Read
the ow meter manual.
5. Close the air supply. Remember that there is still some pressure in the
conditioner for a few seconds after the air supply is closed.
6. Firmly replace the plastic cap to the regulation valve body with a rm
pressing action.
WARNING: This test is an indication of mechanical lter state. However, the
absorption capacity of the activated carbon lter in the FA Pressure Conditioner
may already be exhausted, even at a sucient ow rate. The lter should be
replaced when you smell a noticeable odour, but at least every 3 months.
10FreshAir Pressure Flow Control / Conditioner
5. MAINTENANCE AND CLEANING
FA Pressure Flow Control unit
Every time you nish work, it is recommended to clean the FA Pressure Flow
Control unit, to check individual parts and to replace the damaged ones.
• Cleaning must be carried out in a well ventilated room. Avoid
inhaling the harmful dust settled on individual parts of the unit and
accessories.
• It is forbidden to use cleaning agents containing solvents or abrasives.
Mild soap detergent and warm water is recommended.
• The air hose can be rinsed with clean water.
• Use a damp cloth for cleaning. Each part must be wiped dry after
cleaning.
FA Pressure Conditioner
• Once a week, drain the condensate from the bottom of the unit, using
the drain cock located at the base of the unit. Before completing
this operation, it is recommended to disconnect the unit from the
compressed air supply.
• Replace the lter at least once every three months. After this period,
viruses and bacteria may proliferate in the units lter and if it is used
regularly, the absorption capacity of the activated carbon to eliminate
odour may be exhausted. If the air leaving FA Pressure Conditioner
smells in any way, replace the lter immediately. When replacing the
lter, clean the inner part of the container with a dry cloth.
EN
6. SPARE PARTS
6.1 Assembling FA Pressure Conditioner
Screw the pressure conditioner body onto the stand.
The FA Pressure Conditioner contains a combined lter which removes oil
mist, smells and avours from industrially produced compressed air.
NOTE: The lter does not remove CO and CO₂.
Read the instructions for use and replacement.
Replacing FA Pressure Conditioner lters:
EN
1.
2.
x 6
3.
1. Unscrew the top part of the lter pressure container (6 screws).
2. Remove the contaminated lter, wipe the inside of the container.
3. Check the condition of the rubber seal in the top cover. If the seal is
damaged, replace it.
4. Install a new lter on the container cover and screw it back.
5. Check the container for leakage. If the container is not absolutely tight,
tighten all screws that fasten the top cover.
4.
12FreshAir Pressure Flow Control / Conditioner
7. TROUBLESHOOTING
FaultProbable causeRecommendation
The unit does not work
at all.
The unit does not supply
the sucient amount of air.
During the use, if there is a sudden decrease or increase in air supply and the
user is located in a contaminated area, it is necessary to leave the workplace
immediately and check the following:
• The unit is assembled correctly.
• The lter condition in FA Pressure Conditioner is in good condition.
• The air hose is not damaged during the use.
• The noise damper in FA Pressure FC is not clogged.
• The seal on the safety hood is in good condition.
Compressed air supply failure. Check the compressed air source.
Hose damage.Check that connecting hoses are
Air hose or air channel blocked.Check and remove the possible
Air escapes through leakages.Check all sealing elements and
The bae is clogged.Replace the bae in FA Pressure
The lter in FA Pressure
Conditioner is clogged.
not damaged.
obstacle.
connections, check that the hose
is not damaged and without
leaks.
Flow Control.
Replace the lter.
EN
8. STORAGE
All parts of a FreshAir system must be stored in an environment with
temperature between 0 – 40 °C and humidity between 20 – 80 % Rh. The
storage life is 2 years for the product if stored in its original unopened
package. Temporary transportation to and from site is permitted, providing
the units are stored in a dry container.
NOTE! Batteries get discharged even if not in use. Therefore for long-term
storage it is highly recommended to charge the NiMH batteries every
12 months.
There is a 12 month warranty covering production defects and a 6 month
warranty for batteries.
The warranty begins from the date of purchase. The claim must be lodged
with the dealer. The paid invoice or receipt must be produced if claiming on
the warranty.
Warranty is void if there is evidence of mechanical intervention or abuse of
the unit(s). Warranty does not cover, in particular, defects caused by a late
replacement of the lter or by using a lter damaged by attempted cleaning
with compressed air.
10. TECHNICAL DATA
FreshAir Pressure Flow Control
Minimum air ow170 l/min-1
Maximum air ow> 400 l/min-1
Weight of unit 250 g
Inlet connection
Outlet connectionMINI DN 5
Noise level of unit61 dB
Belt size60 – 150 cm
Supply pressure range300 – 1000 kPa
Recommended temperature range at work 10 – 60 °C
Recommended air humidity range at
workplace
CerticationClass 2A
20 – 80 % Rh
FreshAir Pressure Conditioner
Maximum air ow500 l/min
Weight without lter6300 g
Weight including lter6800 g
Inlet connectionCompatible with RECTUS series 25,26 a CEYN320
Outlet connectionCompatible with RECTUS series 25,26 a CEYN320
Recommended temperature range at work 10 – 60 °C
Recommended air humidity range at
workplace
14FreshAir Pressure Flow Control / Conditioner
20 – 80 % Rh
CerticationIf the requirements of TP-610050-1 are met, it
Notied body for CE testing:
Výzkumný ústav bezpečnosti práce, v.v.i. – ZL
Testing Laboratory No. 1024
Jeruzalémská 9, 116 52 Praha 1
Authorized Body 235
Notied Body 1024
11. ORDERING CODES
Packages
FA PRESSURE FLOW PACK
FA PRESSURE FLOW SPIRAL HOSE
FA PRESSURE CONDITIONER UNIT
complies with EN 12 021
includes:
FA Pressure ow control set (W007496)
and
FA Pressure ow hose (W007501)
Box 717
S-194 27 UPPLANDS VÄSBY
SVERIGE
Tel +46 8 590 783 00
Telefax +46 8 590 823 94
sales.se@kemppi.com
KEMPPI NORGE A/S
Postboks 2151, Postterminalen
N-3103 TØNSBERG
NORGE
Tel +47 33 346000
Telefax +47 33 346010
sales.no@kemppi.com
KEMPPI DANMARK A/S
Literbuen 11
DK-2740 SKOVLUNDE
DANMARK
Tel +45 4494 1677
Telefax +45 4494 1536
sales.dk@kemppi.com
KEMPPI BENELUX B.V.
Postbus 5603
NL-4801 EA BREDA
NEDERLAND
Tel +31 765717750
Telefax +31 765716345
sales.nl@kemppi.com
KEMPPI (UK) Ltd
Martti Kemppi Building
Fraser Road
Priory Business Park
BEDFORD, MK44 3WH
UNITED KINGDOM
Tel +44 (0)845 6444201
Telefax +44 (0)845 6444202
sales.uk@kemppi.com
KEMPPI FRANCE S.A.S.
65 Avenue de la Couronne des Prés
78681 EPONE CEDEX
FRANCE
Tel +33 1 30 90 04 40
Telefax +33 1 30 90 04 45
sales.fr@kemppi.com
KEMPPI GmbH
Perchstetten 10
D-35428 Langgöns
DEUTSCHLAND
Tel +49 6 403 7792 0
Telefax +49 6 403 779 79 74
sales.de@kemppi.com
KEMPPI SPÓŁKA Z O.O.
Ul. Borzymowska 32
03-565 WARSZAWA
POLAND
Tel +48 22 7816162
Telefax +48 22 7816505
info.pl@kemppi.com
LAKSHMI TOWERS
New No. 2/770,
First Main Road,
Kazura Garden,
Neelankarai,
CHENNAI - 600 041
TAMIL NADU
Tel +91-44-4567 1200
Telefax +91-44-4567 1234
sales.india@kemppi.com
www.kemppi.com
1918830
1309
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.