Kemper KHS Mini Control System MASTER 2.0, KHS Mini Control System SLAVE Installation And Operating Instructions Manual

Installation and Operating instructions
KHS Mini Control System MASTER 2.0 Figure 686 02 008 KHS Mini Control System SLAVE Figure 686 02 006
K410068602008-00 / 09.2018 2
TABLE OF CONTENTS
INFORMATION ....................................................................................... 3
1.1 Precautions ................................................................................................. 3
1.2 Important advice to the operator ................................................................... 3
1.3 Technical Data............................................................................................. 4
1.4 Scope of delivery | Accessories ...................................................................... 5
INSTALLATION ....................................................................................... 6
2.1 Wall mounting ............................................................................................. 6
2.2 Electrical installation .................................................................................... 7
2.3 Bus system overview .................................................................................. 11
COMMISSIONING ................................................................................. 14
3.1 Menu navigation ......................................................................................... 14
3.1.2.1 System settings ........................................................................................ 16
3.1.2.2 CAN bus setup .......................................................................................... 18
3.1.2.3 Device settings .......................................................................................... 19
3.1.2.4 Operating modes ....................................................................................... 23
3.1.2.5 Logbook ................................................................................................... 27
3.1.2.6 Change Program........................................................................................ 27
3.1.2.7 Valve manual mode ................................................................................... 28
ACKNOWLEDGE ERROR ......................................................................... 30
USB INTERFACE .................................................................................... 30
WEB BROWSER ..................................................................................... 31
6.1 Basic menu operation and functions .............................................................. 31
6.2 System settings .......................................................................................... 33
6.3 Device settings ........................................................................................... 35
6.4 Operating modes ........................................................................................ 50
6.5 Overview ................................................................................................... 60
6.6 Current values ............................................................................................ 61
6.7 Data transfer.............................................................................................. 62
6.8 E-Mail administration .................................................................................. 67
ERROR DESCRIPTION AND ERROR HANDLING ..................................... 69
ACCESSORIES | SPARE PARTS .............................................................. 71
KHS CABLE LIST ................................................................................... 73
APPENDIX ............................................................................................ 74
10.1 Valve technologies ...................................................................................... 74
10.2 Overview for system commissioning .............................................................. 76
K410068602008-00 / 09.2018 3
INFORMATION
For installation, maintenance and operation
Installation and operation
Read the manual and follow the instructions before installation! Installation and maintenance must be carried out by qualified plumbers.
Provide the manual to the plant operator and keep on hand for further reference!
Make sure that the installation location is frost-proof and not prone to flooding.
Priority must be given to the national standards and provisions on sanitary installations and accident prevention.
Warranty
No warranty in case of:
- Non-compliance with the manual.
- Damage due to incorrect installation.
- Unauthorised modification of the product.
Use
Thanks to the MASTER/SLAVE technology, KHS Mini Control System can be used to implement specific water exchanging measures to maintain drinking water hygiene. For each individual water
exchange group, time or temperature­controlled water exchange can be configured individually or according to a specified water volume.
Only skilled professional personnel are permitted to operate electrical systems in accordance with DIN EN 50110-1.
Do not use the device for other purposes than described above in non-freezing interiors. Any other uses constitute misuse.
Warnings used in the manual:
Warning!
Highlights risks that may result in injury, material damage or contamination of drinking water.
Note! Highlights risks that may result in damage to the plant or dysfunction.
The reliability of the supplied unit is
only ensured when used as intended. Never exceed the limits stated in this documentation under any circum­stances
During assembly and maintenance,
make sure that the control is not switched on.
Use only original/approved spare parts
otherwise no warranty claims will be
recognized.
Be sure to comply to local regulations
on waste recycling and disposal.
K410068602008-00 / 09.2018 4
Technical Data
Operating voltage
230V, AC, 50 / 60Hz
Power input for the unit
10 W
Relay flushing valve output
230 V, 2 A
Relay alarm output
max. 230 V, 2 A
CAN bus subscribers
max. 62
Logbook entries
max. 50,000
Datalogging entries
max. 12 million
Ambient temperature range
0 °C to + 50 °C
Degree of protection
IP 54
Dimensions
200 x 130 x 60 [mm]
Integrated user interface (display + 4 keys)
Settings Configuration System overview Data transfer
Network interface for web-based user interface
Settings Configuration System overview Data transfer E-mail management (fault message)
USB interface for USB mass storage
Firmware update Web server update Reading out the flushing log Reading out the logbook Reading the configuration in and out
Language menu
German English Dutch
Operating modes
Time controlled water exchange
Temperature controlled water exchange
Volume controlled water exchange
Routine
Datalogging
Backup
External switch function
Change program System lock / Maintenance operation
K410068602008-00 / 09.2018 5
Art.-No.
H1
[mm]
L1
[mm]
T1
[mm]
6860200800
120
200
58
Fig.
686 04
686 05
688 00
628 0G
138 4G
685 15
689 06 001
689 06 002
K410068602008-00 / 09.2018 6
Installation
Allow only certified electricians to assemble and install electrical equipment. Danger of fatal electric shock.
Rigid leads must form a loop for wiring so that there is no pressure on the terminals and the housing closes without resistance.
Ill. 1 Illustration of the mounting holes for wall installation
Disturbance
space
Please pay attention to the disturbance space when installing the Control System.
Left-hand side: Serial number of the KHS Mini Control System
Right-hand side: USB slot
K410068602008-00 / 09.2018 7
K410068602008-00 / 09.2018 8
2.2.1 Connection of the components
Terminal
characters
Meaning
1
Flushing valve – Switching output 230V
2
L (+)
Flushing valve – Voltage output 230V
3
N (-)
Flushing valve – N
4
L (+)
Power supply – L1 230V
5
N (-)
Power supply – N
6
SW IN
External input - 230V (MASTER only)
7
PE
Protective earth conductor – PE
8
H
A CAN bus – High
9
L
A CAN bus – Low
10
GND
A CAN bus – Ground
11
H
B CAN bus – High
12
L
B CAN bus – Low
13
GND
B CAN bus – Ground
14
+ 5V
Flow measurement valve – Voltage output 5V
15
FLOW
Flow measurement valve – Flow input
17
GND
Flow measurement valve – Ground
18
Input 1 Pt1000
19
Input 1 Pt1000
20
Input 2 Pt1000
21
Input 2 Pt1000
22
IN
Free drain / water sensor (conductors interchangeable)
23
IN
Free drain / water sensor (conductors interchangeable)
24
Alarm relay – External voltage input
25
Monitoring of ext. voltage = Fault
26
Monitoring of ext. voltage = Operation
24
25
26
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17
18
19
20
21
22
23
K410068602008-00 / 09.2018 9
KHS isolating valve + spring reset (Fig. 686 05)
KHS isolating valve (Fig. 686 04) KHS CONTROL-PLUS (Fig. 138 4G)
[4] bn (BN) = L [5] bu (BU) = N [7] ye/gn (YE/GN) = PE L N PE
230V 230V +/- 10% AC 50/60Hz Back-up fuse max. 16A
[6] bn (BN) = L
Switch
230V 230V +/- 10% AC 50/60Hz Back-up fuse max. 16A
[1] bn (BN) [2] [3] bu (BU) bn bu
[1] bn (BN) [2] bl (BK) [3] bu (BU)
bn bl bu
[14] bn (BN) Pt 1000 (optional) [15] bu (BU) [17] bl (BK) [18] bn bu bl gy wh [19] gy (GY) = Pt 1000 (optional) [20] wh (WH) = Pt 1000 (optional) [21]
If the temperature is measured using the CONTROL-PLUS, the jumper on the board must be changed from 4-wire to 2-wire.
K410068602008-00 / 09.2018 10
KHS temperature measurement valve
(Fig. 628)
KHS Free Drain (Fig. 688 00) Water sensor for leaks (Fig. 620 00)
Potential-free alarm relay
[22] ws (WH) [23] br (BN)
ws br
In the as-delivered state, a cable bridge is plugged between Terminals 22 and
23. This must be removed before connecting the KHS Free Drain.
[22] wh (WH) [23] bn (BN)
wh bn
In the as-delivered state, a cable bridge is plugged between Terminals 22 and 23. This must be removed before connecting the KHS water sensor.
[24] 230V (2A) / 24V [25] OUT (fault) [26] OUT (operation)
230V (2A)
24V
Monitoring example: Faults and mains voltage failures are reported with external voltage to the network warning lamp, the warning horn or to the BMS.
ws
rt
BMS
Warning lamp
Signal horn
K410068602008-00 / 09.2018 11
2.3.1 CAN bus cable
Bus cables for the wiring of CAN bus systems (controller area network) in accordance with
ISO 11898 must be used for bus systems with 120 Ω nominal impedance. Only when such
cables are used can a high level of data transfer security be guaranteed.
Recommended properties for the CAN bus cable
Cable type
CAN bus cable
Conductor material
Kupfer
Conductor cross-section and number of wires
Cross-section Length
1 x 2 x 0,34 mm² 1 x 2 x 0,50 mm² 1 x 2 x 0,75 mm²
300 m 500 m 1000 m
Shielding
Braiding of tinned copper wires
Impedance at f 1Hz
120 Ω ± 15 %
2.3.2 CAN-Bus-Anschluss
Components
Designation
Number
of subscribers
per component
Max. number of
components per
-MASTER-
Control System SLAVE
1
62
KHS HS2 Hygiene
flushing box with one
connection
+
Can bus connection set
1
60
KHS HS2 Hygiene
flushing box with two
connections
+
Can bus connection set
2
30
The KHS Mini Control System has two integrated CAN bus connections with which up to 62 CAN bus participants can be addressed. A maximum of 31 bus subscribers can be connected to each CAN bus connection.
max. 31 CAN bus subscribers max. 1000 m (in total)
max. 31 CAN bus subscribers max. 1000m (in
CAN bus
Connection B
CAN bus Connection A
2
1
K410068602008-00 / 09.2018 12
KHS HS2
KHS HS2
KHS HS2
2.3.3 CAN bus subscriber arrangement
2.3.4 CAN bus cable connection
Wrong topology! Only line topology allowed!
RIGHT
RIGHT
WRONG
Device 1
Device 2
CAN bus cable 1
CAN bus cable 2
K410068602008-00 / 09.2018 13
2.3.5 Terminal resistor
The 120 Ω terminal resistor may only be installed in the last control component of a CAN bus
cable. The MASTER does not require a terminal resistor.
2.3.6 Connection of terminal resistor
All KHS Mini Controls
-SLAVE- are supplied with a 120 Ω terminal resistor.
For non-terminal SLAVE controls, the resistor must be removed!
K410068602008-00 / 09.2018 14
Commissioning
Before commissioning, make sure the connections have been made properly and professionally and that the system is properly protected. The pertinent regulations (EN, VDE, etc.) and the
regulations of the local energy utility must be complied with. After finishing the wall installation and the electrical installation, apply the mains voltage of 230V.
Allow only certified electricians to assemble and install electrical equipment. Danger of fatal electric shock.
To simplify configuration and to guarantee correct installation, fill in the system commissioning overview of the KHS Mini Control System (see supply pressure, Chapter 10.2) before making the settings.
It is mandatory to fill in the form to be able to take advantage of the optional factory support.
All menus have a "rolling" structure, i.e., pressing the " key" on the last menu item
jumps back to the first menu item.
Keys
Description
Esc
Exit the menu / switch between overview and main menu
Roll backwards
OK
Confirm key
Roll forwards
The menu navigation of the KHS Mini Control System –MASTER 2.0– is divided in two types of windows.
Window types
Description
General plan
The "General plan" window is used only for visualising the current states. Viewing possible without password.
Main menu
Preset parameters can be viewed, changed and saved. Viewing not possible without password.
14
K410068602008-00 / 09.2018 15
3.1.1 General plan
The following illustrations explain the symbols of the "General plan" menu interface of the KHS Mini Control System -MASTER
2.0-.
Symbol
Meaning
MAS
Overview -Master-
SLXX
Overview -SLAVE- with the number XX
HSXX
Overview KHS HS2 with the number XX
KHS VAV maximum flow isolating ball valve with servo drive created
KHS VAV maximum flow isolating ball valve opened
CAN bus of the Control System active
Fault detected
Leakage monitoring of Control System active
Flow sensor created (symbol flashes: flow control is active)
Symbol flashes: Time control activated
Temperature sensor created (symbol flashes: temperature control is active)
P1 / P2
Activated program for the program switchover
1/8
Sheet 1 of 8
Detailed overview
*: A frame appears around the entry of the first controller on the selected sheet (see 1). Pressing the OK key once more opens the "Detailed overview" (see
2) of the selected control. Alternatively, press the or key to select another controller. The following table describes the possible content of the detailed views.
Symbol
Meaning
Safety device
Safety valve closed or open
Temperature
Current value of the connected temperature sensor
Flow
Current value of the connected volume flow sensor
Volume
Volume of the last or current water exchange
Flushing duration
Volume of the forthcoming or current water exchange
SNo:
Serial number of the selected Control System
1x „OK“ Selects control (frame*) 2x "OK" Changes into detailed overview
2
1
K410068602008-00 / 09.2018 16
3.1.2 Main menu
Main menu item
Function
System settings
Basic system settings (language; time; etc.)
CAN bus setup
Assignment of the Control System to the CAN bus network
Device settings
Assignment of the actuators and sensors
Operating modes
Setting the operating modes for each water exchange group
Logbook
Access to the event log
Program switchover
Settings for the program switchover
Manual valve operation
Specific manual operation of certain valves
Network setup
Settings for integration into an existing network
3.1.2.1 System settings
Language
Time
Date
S/W automatic
Alarm buzzer
K410068602008-00 / 09.2018 17
Key press signal
Display contrast
Display illumination
Password
To protect the controller from unauthorised external influences, a password can be configured. If a password has been stored,
the password will be queried before every setting.
Factory settings
Reboot the MASTER
All previous confi­gurations will be lost!
The password "0000" is the factory default setting.
K410068602008-00 / 09.2018 18
3.1.2.2 CAN bus setup
Before device settings can be made, the Control System or KHS HS2 hygiene flushing boxes, which are connected to the -MASTER 2.0- by the CAN bus cable, must be added to the CAN bus
network using the menu item "CAN Bus Setup". The serial numbers of connected devices are automatically listed, and are assigned to a SLAVE in the system.
Adding devices
Term
Meaning
SL XXXXXX
KHS Mini Control System -SLAVE- including serial number
HS XXXXXX V1 / V2
KHS HS2 hygiene flushing box including serial number
HS XXXXXX V1 / V2
Valve of the KHS HS2 hygiene flushing box (V2 = left; V1 = right)
Deactivated
No device is added to the selected SLAVE
Serial number
Serial number KHS Mini Control System -SLAVE-
Serial number KHS HS2 Hygiene flushing box
Even if the KHS HS2 has two valves, it only has one serial number.
Ser.Nr.: XXXXXX
S/N: XXXXXX
K410068602008-00 / 09.2018 19
Main view
When all the devices have been added, they are displayed in the main view, as
shown below. The individual devices can then be configured in Device settings.
3.1.2.3 Device settings
In the "Device settings" submenu, the individual Control System are logically assigned to the integrated actuators
and sensors. The valve control type is also determined.
Control type
Description
B valve
Terminal flushing valve, with several A valves hydraulically preconnected.
A valve
Flushing valve which switches the water exchange for one line.
C valve
Terminal flushing valve for one line.
Safety device
Valve which protects a distribution line.
Only measurement
Slave for the acquisition and long-term monitoring of sensor values.
Configuration of the B Valve
Device selection Control type
Valve
See Miscellaneous settings
Check to see if the antenna icon can always be seen and if the LEDs light up green on all KHS Mini Control System. Only then has a proper connection been established.
When using A/B valve technology, always make sure that the B valve is configured first. A valves can then be assigned to the B valve. The assignment of the A valves is shown in the following. For information on valve technology, please see Chapter 10.1.
K410068602008-00 / 09.2018 20
See Miscellaneous settings
Configuration of the A Valve
Device selection Control type
B valve
See Miscellaneous settings
Configuration of the C Valve
Device selection Control type
Valve
See Miscellaneous settings
Configuration of the safety device
Device selction Control type
Valve
You are recommended not to link more than 5 A valves to one B valve.
K410068602008-00 / 09.2018 21
Configuration of flow measurement
Device selection Control type
Select sensor
Select sensor
See Miscellaneous settings
Configuration of volume flow sensor
Select sensor
Configuration of temperature sensor
Select sensor
Medium Frsot protection limit Target temperature
see Configuration of volume flow sensor
See Configuration of temperature sensor
The measuring range of the sensor can be determined by means of a sticker on the installed flow measurement valve.
K410068602008-00 / 09.2018 22
Miscellaneous settings
Alarm relay setting
Operating cylce reset
Software version
HS2 Simultaneous opening of V1/V2
Alarm in the event of the Control System own faults, or in the event of system faults.
After 20,000 operating cycles of a flushing valve, a maintenance request is generated. After maintenance, the operating cycles of the actuator should be reset.
Overview of the software version of the selected Control System.
Setting for the simultaneous opening of two valves in a KHS HS2. Depending on the flow rate, the following instructions apply with regard to sound protection and free discharge.
V1 V2 V1 V2
OK OK OK
OK OK OK OK
OK OK OK OK
4 l/min
> 15 l/min
15 l/min
10 l/min
K410068602008-00 / 09.2018 23
3.1.2.4 Operating modes
In the "Operating modes" submenu, programs and times are added to the actuators and sensors.
Mode
Description
Time Control
Triggers a water exchange of defined duration at a certain point in time.
Temperature control
Triggers a water exchange when a predefined start temperature is reached, until a predefined stop temperature is reached.
Volume control
Triggers a water exchange with a defined flush volume at a certain point in time.
Backup
Backs up a distribution line by means of a water sensor in a predefined time window.
Datalogging
Acquires sensor values in a predefined time window with a predefined sampling rate.
Routine
Triggers a water exchange for a predefined duration or quantity if a temperature control has not actuated for a certain time.
If two or more valves are simultaneously opened in a drinking water system, under certain circumstances pressure fluctuations or a large pressure drop can occur in the system. For that reason, make sure beforehand that the required flow pressure is continuously guaranteed at all tapping points. You are recommended not to perform simultaneous water exchanging measures.
If the program switch is "Activated" (see Chapter
3.1.2.6), a query is presented during the operating modes configuration to determine the program this applies to (see right). The two mentioned flushing programs can be switched using an external manual switch. The electrical connection is shown in Chapter 2.2.
Configuration of time control
K410068602008-00 / 09.2018 24
Configuration of volume control
Configuration of temperature control
Configuration of the safety device
K410068602008-00 / 09.2018 25
Configuration of datalogging
The following shows an exemplary extract from a CSV log file. In the written log file you can find a detailed listing of the entire measured data. They are
sorted by date, time, index, name and the measured data of the connected measurement valve. Up to 12 million lines can be saved.
Routines
If temperature flushing is configured, a routine duration is automatically activated. Generally speaking, it is
possible to choose between the following routines:
Routine time
K410068602008-00 / 09.2018 26
Routine Duration
Routine Volume
After your Control System have been successfully configured, you are recommended to save the configuration as a backup file. If the KHS Mini Control System -MASTER 2.0- is defective it can be quickly replaced and the configuration can be read in. This saves having to configure everything again.
K410068602008-00 / 09.2018 27
The two mentioned flushing programs can be switched using an external manual switch. The electrical connection is shown in Chapter 2.2.
3.1.2.5 Logbook
The "Logbook" submenu provides a facility for opening event logging. Press the "" and "" keys to change between the individual logbook entries. The event log documents the water exchange operations, error messages
and configuration changes made by the Kemper KHS Mini Control System (see the following illustration). Up to 50,000 logbook entries can be saved.
... ....
Ill: Illustration of a logbook entry index 9-10, configuration change
3.1.2.6 Change Program
With the KHS Mini Control System ­MASTER 2.0- it is possible to switch between two flushing programs or to block them using an external switch. The programs can also be activated or
deactivated in the "Switch program" submenu. The "External input" or "External switch" can be assigned to a program switch in this submenu.
Progr. Switchover Progr. Deactivate switchover
Block system/select program
Select external input action
The stored logbook entries can be saved through the USB interface on a USB memory stick. This function is explained in detail in Chapter 5.
K410068602008-00 / 09.2018 28
3.1.2.7 Valve manual mode
With the KHS Mini Control System ­MASTER 2.0-, it is possible to run a function test of the valves using the "Valve manual mode" submenu. Furthermore, the valves can be
individually addressed during maintenance. The functions are shown in the following illustration.
Maintenance:
A function test is recommended after configuring the "Device settings" submenu to rule out possible errors immediately.
Valve manual mode Select system crtl. Automatic mode
Open
Closed
3.1.2.8 Network setup
To establish a connection between the PC and the KHS Mini Control System ­MASTER 2.0-, the required network
configurations can be set up in the "Network setup" submenu.
Connection
Description
PC MASTER
The IP addresses of the two devices should not differ greatly from each other.
PC LAN MASTER
You can obtain the appropriate parameters for integration into your network from your system administrator
The following parameters are configured as factory defaults:
IP-Adresse: 10.1.23.150 Subnet: 255.255.255.0 Gateway: 10.1.23.1
K410068602008-00 / 09.2018 29
Nework setup Setting the IP address
Setting the gateway
Setting the network mask
Prim. DNS Server einstellen
Setting the sec. DNS server
Setting the http user name
Tiggering a test email
K410068602008-00 / 09.2018 30
Acknowledge error
All the errors that occur in the system are sent to the KHS Mini Control System ­MASTER 2.0- and are signalled acoustically by means of a buzzer. It is possible to integrate an alarm relay (see Chapter 2.2). In normal operation, the alarm relay is energized ("pulled") with voltage. If there is an error, the voltage
drops and an acoustic signal reports the error. Here it does not matter what different effect the error has on the system. The control goes into alarm latching and has to be acknowledged by the user after the malfunction has been repaired.
USB interface
Data can be transmitted comfortably with the USB interface of the KHS Mini Control System MASTER 2.0-. Data can be imported by the device and also exported from the device. It is also possible to use the USB stick to install updates not only for the Control System but also for the web browser.
The USB menu is not visible in normal mode. The menu is automatically activated when a USB memory stick is connected to the KHS Mini Control System
-MASTER 2.0-.
Max. storage capacity of the USB stick
16 GB
File system FAT32
1
2
3
A detailed list of possible errors and their corrections is given in chapter 7.
K410068602008-00 / 09.2018 31
USB menu
Meaning
Copy logbook to USB stick
All saved events are stored on the USB stick in the form of a CSV file.
Copy flushing log to USB stick
All saved flushing processes are stored on the USB stick in the form of a CSV file.
Copy configuration to USB stick
All settings are stored on the USB stick in the form of a CFG file.
Read configuration from USB stick
A saved configuration can be written from the USB stick into the controls.
Copy data log to USB stick
When the "Datalogging" mode is activated, the measured values recorded can be copied onto the USB stick.
Software update from USB stick
Control System software update by means of a UPE file, using the USB stick.
Copy web server from USB stick
Web browser update using the USB stick.
Web browser
The KHS Mini Control System -MASTER
2.0- is a web-based Control System. Using a web browser, basic settings,
configurations and changes can be carried out easily.
Chapter 6 concerns only the web browser interface. You can find the complete operating instructions on the web browser with the button and Downloads, or through the Service/ Download section of our website,
www.kemper-olpe.de.
To use the web browser, the following minimum system requirements must be met:
Java script must be activated Mozilla Firefox Version 22.0.1 or higher Google Chrome Version 31.0 or higher Windows Explorer Version 10.0 or higher or an alternative browser Safari, etc.
Please note Chapter 3.1.2.8 and make sure you know which network settings of the Control System are stored.
K410068602008-00 / 09.2018 32
The WEB browser is subdivided into seven menu interfaces. They can be selected through the web browser tabs shown in Fig. 6.1.1. In the individual menu interfaces, you can make the basic
settings, the configurations and changes. Use the WRITE TO CONTROL button to save your parameters. If you do not want to store the changes in the system, use the
DISCARD CHANGES
button.
Ill. 6.1.1 Menu tab of the web browser
The web browser interface can also be used with a tablet PC or a mobile phone. Here, the input interfaces are changed slightly. When using with a mobile phone, the menu tabs can be seen over the button (see below). The modes of functioning of the individual menu interfaces remain unchanged; merely the graphics of the components are not displayed.
The username “KHS” and password "0000" is the factory default.
K410068602008-00 / 09.2018 33
In the "SYSTEM SETTINGS" menu interface you can make settings for user
data, date / time, network, external switch function and other settings.
User data
To
create a user for the web browser of your KHS Mini Control System, choose a user name and a suitable password. To save the settings, click the WRITE TO CONTROL button. After the settings have been saved, you must identify yourself every time the web browser is started. To do this, enter the user name you have just chosen and the relevant password in the input dialogue that then opens, as shown in Fig. 6.2.1. Use by several users is not possible.
Ill. 6.2.1 Input dialogue Identification
The username “KHS” and password "0000" is the factory default.
K410068602008-00 / 09.2018 34
Date / Time
The
current time and current date of the KHS Mini Control System
-MASTER 2.0- are displayed in the grey boxes. To set the Control System time, click the APPLY DATE/TIME button. This causes the Control System to apply the date and time settings of your PC, for example. The KHS Mini Control System -MASTER 2.0- can switch automatically between daylight saving and standard time. If you do not want this setting, click the button. If the button is showing
, the switchover between daylight savings and standard time is
not automatic
Netzwork
To
establish a connection between the PC and the KHS Mini Control System -MASTER 2.0- using a web browser, the required network configurations can be entered in the boxes IP address, Subnet, Gateway, prim. DNS and sec. DNS.
You can obtain the appropriate parameters for integration into your network from your system administrator.
The following parameters are configured as factory defaults:
IP address: 10.1.23.150 Subnet: 255.255.255.0 Gateway: 10.1.23.254
The network settings can only be loaded when the configuration is loaded using a USB stick. They are not imported when the configuration is loaded using the web server.
Program switch
With the KHS Mini Control System -MASTER 2.0- it is possible to switch between two flushing programs. The programs can be configured in the Operating modes menu interface and the individual Control System can be added (see Chapter 6.2). If the button for the program switchover is set to , the external program switching is deactivated. If the button for the program switchover is set to , the external program switching is active. The names of the flushing programs can be changed with an entry in the related box. Use the "Current operating mode" drop-down list to manually switch the flushing programs in the web server and to block them for maintenance purposes. Use the "External input" drop-down list to set the operating mode of the external input.
Maintenance:
The two flushing programs mentioned above can be switched using the web browser and can be blocked for maintenance purposes.
K410068602008-00 / 09.2018 35
Other settings
The
KHS Mini Control System -MASTER 2.0- can activate an internal buzzer in case of faults. If the related button displays , the alarm buzzer is activated. If the related button displays , the alarm buzzer is not activated. Using the drop-down menu you can also customise the language setting of the control.
In the "DEVICE SETTINGS" menu interface, the individual KHS Mini Control
System with integrated actuators and sensors are logically linked to each other.
Selection interface
The "DEVICE SETTINGS" menu interface is a dynamic interface. The selection interface of the installed KHS Mini Control System are shown on the left-hand side. Click on the desired KHS Mini Control System to open the relevant input box.
The changes must be written into the control after every change in the input box. If another KHS Mini Control System is selected immediately after a change in the selection interface, the changes are automatically discarded.
K410068602008-00 / 09.2018 36
Input box
If a KHS Mini Control System is selected in the selection interface, the input box appears on the right-hand side. Use this box to allocate the related actuators and sensors to the KHS Mini-Control System. If an error occurs in the Control System, it can be reported across the entire system. To do this, set the button to . The remaining input options of the input box are explained in the following.
Adding devices
Configuration (B valve)
Select control type
Choose the available control types that can be used by the selected KHS Mini Control System from a drop-down list. The KHS Mini Control System ­MASTER 2.0 - should control a B valve in this sample project.
Select valve
The possible valves are selected from a drop-down list. In this sample project, the KHS Mini Control System
-MASTER 2.0- should actuate a KHS VAV maximum flow isolating ball valve with spring reset and servo drive.
Alarm relay reports system-wide error
K410068602008-00 / 09.2018 37
Select sensor
The possible sensors are selected from a drop-down list. In this sample project, the KHS Mini Control System ­MASTER 2.0- should actuate a KHS CONTROL PLUS
Save settings
To
allow the new parameters of the input box to become effective, the settings must by saved by clicking the
WRITE TO CONTROL button.
K410068602008-00 / 09.2018 38
Configuration of the A valve
Select control type
Choose the available control types that can be used by the selected KHS Mini Control System from a drop-down list. The KHS Mini Control System should actuate an A valve in this sample project.
Select the relevant B valve
Each A valve must be assigned to a B valve. The available KHS Mini Control System that are linked to a B valve can be selected from a drop-down list. The KHS Mini Control System in this sample project should be assigned to the B valve of the KHS Mini Control System -MASTER 2.0-.
K410068602008-00 / 09.2018 39
Select valve
The possible valves are selected from a drop-down list. In this sample project, the KHS Mini Control System should actuate a KHS VAV maximum flow isolating ball valve with servo drive.
Select sensor
The possible sensors are selected from a drop-down list. The KHS Mini Control System in this sample project should actuate a KHS temperature sensor Pt
1000.
K410068602008-00 / 09.2018 40
Select the medium to be monitores
Select the medium to be monitored from a drop-down list. In this sample project, it is cold water.
The temperature ranges are then configured.
Save settings
For
the new parameters of the input box to become effective, the settings must be saved by clicking WRITE TO
CONTROL.
K410068602008-00 / 09.2018 41
Configuration oft he C valve
Select control type
Choose the available control types that can be used by the selected KHS Mini Control System from a drop-down list. The KHS Mini Control System should actuate a C valve in this sample project.
Select valve
Die möglichen Ventile werden mittels einer Dropdownliste gewählt. Die KHS Mini System­steuerung soll im gegebenen Musterprojekt ein KHS VAV­Vollstromabsperrventil mit Feder­rückzug und Stellantrieb an­steuern.
K410068602008-00 / 09.2018 42
Select sensor
The possible sensors are selected from a drop-down list. The KHS Mini Control System in this sample project should actuate a KHS temperature sensor Pt
1000.
K410068602008-00 / 09.2018 43
Select the medium to be monitored
Select the medium to be monitored from a drop-down list. In this sample project, it is cold water.
The temperature ranges must then be configured.
Select sensor
The possible sensors are selected from a drop-down list. In this sample project, the KHS Mini Control System should actuate a KHS CONTROL PLUS
K410068602008-00 / 09.2018 44
Save settings
For
the new parameters of the input box to become effective, the settings must be saved by clicking WRITE TO
CONTROL
Configuration of the safety device
Select control type
Choose the available control types that can be used by the selected KHS Mini Control System from a drop-down list. In this sample project, the KHS Mini Control System should function as a safety valve
K410068602008-00 / 09.2018 45
Select valve
The possible valves are selected from a drop-down list. In this sample project, the KHS Mini Control System should actuate a KHS VAV maximum flow isolating ball valve with servo drive.
Save settings
For
the new parameters of the input box to become effective, the settings must be saved by clicking WRITE TO
CONTROL.
K410068602008-00 / 09.2018 46
Configuration of measurement
Select control type
Choose
the available control types that can be used by the selected KHS Mini Control System from a drop-down list. The KHS Mini Control System -SLAVE­in this example should act as a measurement SLAVE.
Select sensor
The
possible sensors are selected from a drop-down list. The KHS Mini Control System - SLAVE - should be assigned to a KHS CONTROL PLUS.
K410068602008-00 / 09.2018 47
Save settings
For
the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE
TO CONTROL button.
Configuration of the KHS HS2 Hygiene flushing box V1
Change Name
…V1  Connection right …V2  Connection left
Use the APPLY NAME button to transmit the selected system name
.
The KHS HS2 hygiene flushing box is displayed visually
.
K410068602008-00 / 09.2018 48
Select control type
A control type (C valve) is assigned to the KHS HS2 hygiene flushing box by means of a drop-down list.
Select sensor
The
possible sensors are selected from a drop-down list. A KHS temperature sensor Pt 1000 can be assigned to the KHS HS2 hygiene flushing box.
Select the medium to be monitores
Select
the medium to be monitored from a drop-down list. In this sample project, it is cold water. The temperature ranges are then configured.
K410068602008-00 / 09.2018 49
Select valve
An internal volume flow sensor can be added to the KHS HS2 hygiene flushing box by means of a drop-down list.
Save settings
For
the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE
TO CONTROL button.
K410068602008-00 / 09.2018 50
In the "OPERATING MODES" menu interface, the control-specific TIMERS are configured for the KHS Mini Control System. Depending on the control type, a TIMER
defines flushing times, measurement intervals, backup times, routine intervals, temperature flushing etc.
Selection interface
In the "OPERATING MODES" menu interface, you will find the selection interface of the added KHS Mini Control System on the left-hand side. Click the desired KHS Mini Control System to open the input box.
1
2
The changes must be written into the control after every change in the input box. If another KHS Mini Control System is selected immediately after a change in the selection interface, the changes are discarded.
1
K410068602008-00 / 09.2018 51
Input box
If a KHS Mini Control System is selected in the selection interface, the relevant input box appears on the right-hand side. Click the ADD LINE button to add up to 16 lines to the TIMER. Press the button to
delete the line in question from the TIMER. Click the RESORT TIMER button to delete all deactivated lines and to push empty lines to the back. The remaining input options in the lines are explained below.
Ill. 6.3.1 Overview of system commissioning for the sample project
The
selected times and temperatures serve as examples. The values must always be set for each building and for each type of use and medium so that representative measurement values are generated and intended use is maintained for the system.
2
2
K410068602008-00 / 09.2018 52
Configuration of time control (A valve)
Select type
After
a line has been added using ADD
LINE, the line type is selected. The KHS
Mini Control System in this sample project is connected to an A valve. To time control the water exchange, the "Time flushing" line type must be selected from a drop-down list.
Define times
Af
ter a line type has been selected, define the times. In the "Time control" line type, a starting time and the duration of the water exchange must be stated. Furthermore, the desired weekday can be selected from a drop­down list. Click the box of the weekday in question to activate it with a check mark.
K410068602008-00 / 09.2018 53
Save settings
the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE TO
CONTROL button.
Configuration of volume flushing (A valve)
Select type
After
a line has been added using ADD
LINE, the line type is selected. To volume
control the water exchange, the "Volume flushing" line type has to be selected from a drop-down list.
K410068602008-00 / 09.2018 54
Define times
Ist
er a line type has been selected, define the times. In the "Volume control" line type, a starting time, the duration and the volume of the water exchange must be specified. Furthermore, the desired weekday can be selected from a drop-down list. Click in the box of the weekday in question to activate it with a check mark.
Save setting
For
the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE TO
CONTROL button.
K410068602008-00 / 09.2018 55
Configuration of temperature flushing (A valve)
Select type (Temperature flushing)
After
a line has been added using ADD
LINE, the line type is selected. The KHS
Mini Control System in the sample project is linked to a temperature measurement valve. To temperature control the water exchange, the "Temperature control" line type has to be selected from a drop-down list.
Define times
I
a line type has been selected, define the times. A starting and stopping time has to be specified for the "Temperature flushing" line type. Furthermore, the desired weekday can be selected from a drop-down list. Click in the box of the weekday in question to activate it with a check mark.
K410068602008-00 / 09.2018 56
Routine time
In
this sample project, it is cold water. The cold water temperature in winter could always be below the starting temperature. Nevertheless, to prevent stagnation, routine water exchanges can simulate operation for the intended purpose. The "Routine" line type can be selected from the drop-down list.
The desired weekday can also be selected from a drop-down list. Click in the box of the weekday in question to activate it with a check mark.
Routine time
If there is no temperature flushing within 7 days, water exchange is guaranteed through the "Routine time" operating mode. In the "Routine time" operating mode, the
starting time, the duration and the weekdays of the water exchange can be defined.
Routine duration
If there is no temperature flushing within the configured interval, the water exchange is guaranteed through the "Routine duration" operating mode. To accomplish
that, the decisive interval (max. 168 h) and the duration of the water exchange can be stored in the "Routine duration" operating mode.
Routine volume
If there is no temperature flushing within the configured interval, the water exchange is guaranteed through the "Routine volume" operating mode. To accomplish this, the
decisive interval (max. 168 h), the volume and the maximum flushing time of the water exchange can be assigned to the "Routine volume" operating mode.
Save settings
For the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE
TO CONTROL button.
K410068602008-00 / 09.2018 57
Configuration of a KHS HS2 Hygiene flushing box V1 (interval flushing)
Select interval
After
a line has been added using ADD
LINE, the line type is selected. The
"Routine duration" line type is selected from the drop-down list. Here, the "Routine duration" line type corresponds to one interval flushing operation.
Define times
After
a line type has been selected, define the times. In the "Routine duration" line type, the duration and the interval of the water exchange must be specified.
Save settings
Fo
r the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE
TO CONTROL button.
K410068602008-00 / 09.2018 58
Configuration of the safety device
Select type
After a line has been added using ADD
LINE, the line type is selected. The
"Release" line type is selected from the drop-down list.
Define time
Af
ter a line type has been selected, define the times. A starting and stopping time has to be specified for the "Release" line type. Furthermore, the desired weekdays can be selected from a drop­down list. Click in the box of the weekday in question to activate it with a check mark.
Configuration of measurement (datalogging)
Select type
Na
er a line has been added using ADD
LINE, the line type is selected. The KHS
Mini Control System in this sample project is connected to a KHS Control Plus flow measurement valve. To record the flow measurement valve measurement data at the same time, the "Datalogging" line type must be selected from a drop-down list.
K410068602008-00 / 09.2018 59
Define times
After a line type has been selected, define the times. A starting and stopping time has to be stated for the "Datalogging" line type. Furthermore, the desired weekdays can be selected from a drop-down list. Click in the box of the respective weekday to activate it with a check mark. The interval time states the storage rate of the measurement values
.
Save settings
For the new parameters of the input box to become effective, the settings must by saved by clicking the WRITE
TO CONTROL button.
K410068602008-00 / 09.2018 60
In the OVERVIEWmenu interface, the configured valves and the linked sensors are shown in an overview. Pure
measurement valves are not listed in the “OVERVIEW”.
Overview
The overview merely shows the current states. No configurations can be carried out on this interface. Click a valve to open the input box of the "SYSTEM SETTINGS" menu interface of the selected component.
If a valve is highlighted in black, this means it is closed. If the valve is highlighted in grey, it is open. If the valve is highlighted in red, there is a fault.
Manual mode / Automatic
The actuators can be triggered manually. Click the button to open a
selection window. Use the selection window to choose between three settings (C valve) or five settings (A/B valve) from a drop-down list. The button indicates a fault in the system.
Automatic = Standard setting Manual OPEN = Opens valve Manual CLOSE = Closes valve Group OPEN = With the A valve, the B
valve also opens
Group CLOSE = both close again
After
a setting has been selected, the duration of the setting can be defined. Use the APPLY button to apply the setting. Press the CANCEL button to cancel the action.
60
K410068602008-00 / 09.2018 61
The CURRENT VALUESmenu interface shows the current values oft he connected KHS Mini Control System and their sensors.
Click
the button to open the input box of the "DEVICE SETTINGS" menu interface of the selected KHS Mini Control System.
K410068602008-00 / 09.2018 62
You can use the "DATA TRANSFER" menu interface to load configurations, software updates,
logbook entries and the created datalogging files.
K410068602008-00 / 09.2018 63
Software update
The "Software update" function can be used to install a software update on the connected KHS Mini Control System. To do this, click the Search button. The UPE files open in the window that then opens, see Fig. 6.7.1. After the LOAD
UPDATE button has been pressed, a
confirmation appears as shown in Fig.
6.6.2. Click the OK button to load the selected setup into the Control System.
Ill. 6.7.1 Selection dialogue Upload setup file
Ill. 6.7.2 „Delete software update“ confirmation
As a precautionary measure, please backup your configuration before making an update.
K410068602008-00 / 09.2018 64
Configuration
Loading a configuration from a file
The "Configuration" function can be used to install an existing configuration in the connected KHS Mini Control System. To do this, click the Search button. The CFG file opens in the window that then opens, see Fig. 6.7.3. After the LOAD CONFIGURATION FROM
FILE button has been clicked, the
selected configuration is then loaded into the Control System.
The network and e-mail settings can only be loaded when the configuration is loaded using a USB stick. They are not imported when the configuration is loaded using the web server.
Backing up the configuration
You can use the "Configuration" function to backup parameterised configurations of the connected KHS Mini Control System to your PC. To do this, click the WRITE CONFIGURATION
TO FILE button. In this window, see Fig.
6.7.4, you can back up the CFG file to the desired folder on your PC.
Ill. 6.7.4 Selection dialogue Back up configuration file
After successfully configuring your Control System, you are recommended to save the configuration as a backup file. If the KHS Mini Control System -MASTER 2.0- is defective, it can be quickly replaced and the configuration can be read in. This saves having to configure everything again.
Ill. 6.7.3 Selection dialogue „Upload configuration file“
K410068602008-00 / 09.2018 65
Logbook
You can use the "Logbook" function to open and save the event log as a CSV file. The event log documents the water exchange operations, error messages and configuration changes made by the Kemper KHS Mini Control System.
Based on the documentation about the location, duration of the water exchange and the temperatures, recordings can be made across a defined time period to verify the state of hygiene of the drinking water system. To open the CSV file, click
OPEN LOGBOOK AS CSV. A dialogue
window then opens, where you can select whether the flushing log should be saved or if it should be immediately opened (see Fig. 6.7.5).
The KHS Mini Control System have a facility to be used as measuring instruments. To do this, the Control System that are connected to a sensor, as described in Chapter 6.3, are configured. Use the "Datalogging" function to generate, delete and save the recorded measurement data records in the form of a CSV file on the PC. Up to 12 million lines can be backed up. Click the
CREATE LOGFILE button to generate the
current CSV file, which is not yet completely full. Click the CSV file to open a dialogue as shown in Fig. 6.7.6. Here you can select whether the flushing log should be saved or immediately opened. Use the button to open a query as shown in Fig. 6.7.7. Click OK to delete the selected file.
Ill. 6.7.5 Opening the CSV log file dialogue
K410068602008-00 / 09.2018 66
Ill. 6.7.6 Openeing the CSV data log file dialogue
Ill. 6.7.7 „Delete file“ confirmation
Ill. 6.7.8 shows an extract of a CSV log file. In the log file you will find a detailed list of the entire measured data; sorted by date,
time, index, name and the measured data of the connected measuring valve.
Ill. 6.7.8 Illustration of an extract of a CSV log file
As described in Chapter 6.3, the sampling interval of the measured values can be set using the "OPERATING MODES" menu interface.
K410068602008-00 / 09.2018 67
If errors or warning messages occur, the KHS Mini Control System -MASTER 2.0- can send them directly to the plant operating organisation by e-mail. In the "EMAIL ADMINISTRATION" menu
interface, a selection of error and warning messages can be individually configured. Furthermore, the e-mail configuration is set with the user, server and login information functions.
K410068602008-00 / 09.2018 68
User information | Server information | Login information
To enable the KHS Mini Control System ­MASTER 2.0- to send error and warning messages to the plant operating organisation, the e-mail settings have to be configured. Here, an internal company e-
mail account can be created, or an independent provider can be used if he works without encryption. The control name can be used to allocate a location, e.g. Cologne Gymnastics Hall.
Select error messages for notification per email
If the button is set to , the relevant notification about a possible error is activated. If an error occurs, an error message is sent to the plant operator by e­mail.
Select warning messages for notification per email
If the button is set to , the relevant notification about a possible warning is activated. If a warning occurs, an error message is sent to the plant operating organisation by e-mail.
K410068602008-00 / 09.2018 69
Error description and error handling
Error description / Error handling
Status
LED
Status LED
Status LED
Status LED
Status LED
General error
Flashes red
Backwater in drain
Drain is clogged or cannot accept
the flushing volume.
Check the drain
channel, channel
acceptance capacity.
Error message!
Defective control will be
completely blocked
Backwater in drain
Float switch on the drain has a
cable break
Replace cable / switch
Error message!
Defective control will be
completely blocked
Temperature flushing
switched off during
runtime
Medium did not reach the switch-
off temperature in the set time
Check the installation
setup and the
maximum flushing
time.
Error message!
Temperature operating
mode is blocked in the
defective control.
Volume flushing
switched off during
runtime
Set volume not reached
Check the installation
setup and the
maximum flushing
time.
Error message!
Volume operating mode is
blocked in the defective
control.
PT1000 value too
high
Sensor defective / No sensor
available
Replace sensor / Check
inputs on the MASTER
Error message!
Temperature flushing
operating mode is blocked
in the defective control.
PT1000 value too low
Sensor defective / No sensor
available
Replace sensor / Check
inputs on the MASTER
Error message!
Temperature flushing
operating mode is blocked
in the defective control.
Leak on sensor
Pipe failure, moisture on the
sensor
Check the local area
and remove the
moisture
The safety valve is
blocking the system.
Real-time clock data
inconsistent
Data in the clock are not
consistent
Check the time & date
and adjust if necessary.
Check battery/replace
if applicable
All time-based services
are running on incorrect
time/date.
Flow detected with
valve closed"
Flow is detected by the flow
measurement valve when the
valve is closed
Check the function of
the flushing valve
Error message! The
involved valve will be
blocked.
"No flow detected
despite open valve"
No flow is detected during a
flushing process.
Check the flushing line
and the flushing valve
Error message! The
involved valve will be
blocked.
K410068602008-00 / 09.2018 70
Error description / Error handling
Status
LED
Status LED
Status LED
Status LED
Auswirkung
Bus error
Flashes orange
No response from the
SLAVE
Cable break, incorrect installation,
interference fields
Check CAN bus cables
and installation
Faulty SLAVE does not
function
No response from the
SLAVE
SLAVE does not have voltage
Restore SLAVE power
supply
Faulty SLAVE does not
function
No response from the
SLAVE
SLAVE with its corresponding
serial number no longer part of
the plant (e.g., after a
replacement)
Assign the correct
serial number to the
SLAVE or delete the
device from the system
Faulty SLAVE does not
function
CAN bus line fault
Cable break, incorrect installation,
interference fields
Check CAN bus cables
and installation
CAN bus and all SLAVEs
do not function.
Too many bus
subscribers
CAN bus A
More than 31 SLAVEs are
connected to
CAN bus A
Rewire the BUS
subscribers or change
the position of the
MASTER in the bus
system.
CAN bus A faulty.
Communication and
functions can be impaired.
Too many bus
subscribers
CAN bus B
More than 31 SLAVEs are
connected to
CAN bus B
Rewire the BUS
subscribers or change
the position of the
MASTER in the bus
system.
CAN bus B faulty.
Communication and
functions can be impaired.
Communication error
CAN bus A
Cable break, incorrect installation,
interference fields
Check CAN Bus A
cables and installation
Affected SLAVEs do not
function
Communication error
CAN bus B
Cable break, incorrect installation,
interference fields
Check CAN Bus B
cables and installation
Affected SLAVEs do not
function
K410068602008-00 / 09.2018 71
Description of warnings / notices
Status
LED
Status LED
Status LED
Status LED
Status LED
Warnings
flashes
red
Operating cycles
exceed 20,000
The VAV on the defective SLAVE
has performed more than 20,000
operating cycles
Replace VAV bonnet in
accordance with the
maintenance manual
and reset the operating
cycles.
The warning message
cannot be confirmed.
SLAVE continues to
operate normally.
No influence
Thermal disinfection
limit exceeded
The monitored temperature has
exceeded the set limit value.
Check to see if it needs
to be set otherwise.
Entry in logbook and
optional message via
email.
Set-point max. limit
exceeded
The monitored temperature has
exceeded the set limit value.
Check to see if it needs
to be set otherwise.
Entry in logbook and
optional message via
email.
Set-point min. limit
undercut
The monitored temperature has
undercut the set limit value.
Check to see if it needs
to be set otherwise.
Entry in logbook and
optional message via
email.
Frost protection limit
undercut
The monitored temperature has
undercut the set limit value.
Prevent danger of
valves freezing up.
Entry in logbook and
optional message via
email.
Notes
No
influen
ce
Set-point OK
Notice that the monitored
temperature is in the target
range.
No action needed!
Entry in logbook and
optional message via
email.
Lights
up
green
Control in standby
No flushing pending. Control in
standby
No action needed!
No influence
Flash
es
gree
n
Flushing is running
The valve on the involved control
is flushing / is open.
No action needed!
Entry in logbook.
Accessories | Spare parts
Optionally available accessories
FIGURE
KHS VAV with servo drive 230 V
686 04
KHS VAV plus with spring-reset servo drive (230 V)
686 05
KHS drain with overflow monitor
688 00
KHS temperature sensor fitting Pt 1000
628 0G / 629 0G
KHS flow measurement valve
638 4G / 138 4G
Leakage water sensor
620 00 001
K410068602008-00 / 09.2018 72
Spare parts
Pos.
Art.-No.
Designation
Note
Installation advice
(1)
6260201900
Network cable for KHS Mini Control System MASTER 2.0; hardware stand 2.0
For Master hardware stand
2.0
(2)
6860202000
Network cable for KHS Mini Control System MASTER 2.0; hardware stand 2.01
For Master hardware stand
2.01
(3)
6860202100
Network cable for KHS Mini Control System MASTER 2.0;
For hardware stand 2.0 additionally cable 6860202000 is required.
Service department ­application technology
Tel. +49 2761 891-0
(4)
6860202200
Micro SD card for network module in KHS Mini Control System MASTER 2.0
---
Service department ­application technology
Tel. +49 2761 891-0
1 2 3
4
K410068602008-00 / 09.2018 73
KHS cable list
This list of cables only shows examples of applications. The exact design of the cables in questions must be carried out on site by the planner on the basis of
Designation Art.-No.
[-] [-] [mm²] [mm] [m] [-]
KHS quarter turn stop
valve PLUS with spring
reset servo drive (24 V)
KHS quarter turn stop valve with servo drive
(24 V)
KHS quarter turn stop
valve PLUS with spring
reset servo drive (230V)
KHS quarter turn stop valve with servo drive
(230 V)
KHS free drain with
overflow sensor
686 01 015…032
686 00 015…032
686 05 015…032
685 15 032…050
686 04 015…032 5 x 1.50 mm² 1000 NYM-J
688 00 020...032 2 x 2 x 0.80 mm **
the ambient conditions (temperature, frequency, routing type, mechanical load).
Cable cross-section /
diameter
3 x X mm²
(power supply)
+
2 x 2 x 0.80 mm **
(position feedback)
5 x X mm²
(power supply)
+
2 x 2 x 0.80 mm **
(position feedback)
3 x 1.50 mm² 1000 NYM-J
Max. cable
length
700 (X=1,50)
10
00 (X=2,50)
250 (X=1,50) 450 (X=2,50)
1000
Cable type*
NYM-J
+
J-Y(ST)Y
NYM-J
+
J-Y(ST)Y
J-Y(ST)Y
Kemper CONTROL PLUS
flow measurement valve
Vortex principle
Kemper CONTROL PLUS
flow measurement valve
Vortex principle
KHS flow and
temperature sensor
Pt 1000
Leakage water sensor 620 00 00100 2 x 2 x 0.80 mm ** 500 J-Y(ST)Y
CAN bus cable
The application is based on
the ISO 11898 international
standard.
138 4G 015…050
138 6G 015…050 4 x 2 x 0.80 mm ** 300 J-Y(ST)Y
628 0G 015...050 629 0G 015...050
4 x 2 x 0.80 mm **
2 x 2 x 0.80 mm ** 1000 J-Y(ST)Y
1 x 2 x 0.34 mm² ** 1 x 2 x 0.50 mm² ** 1 x 2 x 0.75 mm² **
300 J-Y(ST)Y
300 500
1000
CAN bus cable
* Possible cable type for fixed routing, without mechanical load ** Shielded cable lead
According to VDE 0815: The specification of signal transmission cables with
respect to the diameter is specified in mm.
K410068602008-00 / 09.2018 74
Appendix
The following chapter shows the various valve technologies based on exemplary
illustrations.
10.1.1 A-/B Valve technology
In A/B valve technology, several riser branches or distribution lines are connected to a common flushing line. Here, one A valve and the B valve are successively opened and closed together. This guarantees that there is no idling in the flushing lines and there is no water exchange between the pipelines to be flushed.
Example of a flushing process:
A1 and B1 open in accordance with the specifications, A1 and B1 close
A2 and B1 open in accordance with the specifications, A2 and B1 close
A3 and B1 open in accordance with the specifications, A3 and B1 close
A4 and B1 open in accordance with the specifications, A4 and B1 close
Please note:
If valve A1 is flushing, the pending flushing processes of other valves are blocked. With temperature flushing, these are then carried out successively by the system.
A Valve
B Valve
KHS maximum flow isolation ball valve with servo drive Figure 686 04 230 V AC
KHS PLUS maximum flow isolation ball valve with servo drive and spring reset Figure 686 05 230 V AC
K410068602008-00 / 09.2018 75
10.1.2 C valve technology
KHS PLUS maximum flow isolation ball valve with servo drive and spring reset Figure 686 05 230 V AC
C valve technology makes it possible to exchange the water of an individual riser branch or of one individual distribution line independent of the other water exchanging valves.
K410068602008-00 / 09.2018 76
You can find the write-in form at: www.kemper-olpe.de at "Building Technology" in the service download area.
K410068602008-00 / 09.2018 77
K410068602008-00 / 09.2018 78
K410068602008-00 / 09.2018
Gebr. Kemper GmbH & Co. KG
Harkortstraße 5
D-57462 Olpe
Service-Hotline +49 2761 891-800
info@kemper-olpe.de
www.kemper-olpe.de
Loading...