Kelvinator KSV25HRF Installation Guide

Page 1
Inverter Air Conditioner
Installation Manual
KSV25CRF, KSV35CRF, KSV70CRF,
KSV25HRF, KSV35HRF, KSV52HRF,
KSV70HRF, KSV80HRF
Refrigerant R32
Page 2
WARNING
WARNING
TIPS & INFORMATION
ENVIRONMENTAL TIPS
Congratulations Contents
Congratulations and thank you for choosing our Inverter air conditioner. We are sure you will find your new air conditioner a pleasure to use. Before you use the air conditioner, we recommend that you read through the entire user manual, which provides the description of the air conditioner and its functions.
To avoid the risks that are always present when you use an electrical appliance, it is important that the air conditioner is installed correctly and that you read the safety instructions carefully to avoid misuse and hazards.
We recommend that you keep this instruction booklet for future reference and pass it on to any future owners.
After unpacking the air conditioner please check it is not damaged. If in doubt, do not use the air conditioner but contact your local Electrolux Customer Care Centre.
Meanings of symbols used in this manual are shown below:
warning
This symbol indicates information concerning your personal safety
caution
This symbol indicates information on how to avoid damaging the appliance
Important safety instructions ....................................... 3
Notice for installation .................................................. 3
Minimum floor areas .................................................... 4
Components ................................................................ 4
Product description .....................................................5
Installation site instructions ......................................... 6
Rooftop installation ..................................................... 7
Outdoor unit installation .............................................. 8
Indoor unit installation ................................................. 9
Installation ................................................................. 19
Testing the air conditioner ......................................... 23
Installation checklist ................................................... 24
Post installation checks .............................................. 25
Warranty .................................................................... 27
important
This symbol indicates tips and information about use of the appliance
environment
This symbol indicates tips and information about economical and ecological use of the appliance
This symbol indicates never to do this
This symbol indicates always do this
2 Contents
Page 3
WARNING
WARNING
R300 refrigerant warning
ENVIRONMENTAL TIPS
Important safety instructions Notice for installation
Please read this installation manual and the user manual before installation and carefully store in a handy place for later reference. Inside you will find many helpful hints on how to install and test the air conditioner properly.
Electrical work must be installed by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model to be installed.
Incorrect installation due to ignoring this instruction may cause harm or damage, which may not be covered by warranty.
R32 REFRIGERANT WARNING
Warning Refrigerant R32, mildly flammable. This product uses Refrigerant R32, Difluoromethane which is a mildly flammable gas class 2.2, based on AS1677 and must be handled by a Refrigeration Mechanic with an appropriate Australian Refrigerant Gas handling license
environment
Information on disposal for users
• Most of the packing materials are recyclable. Please dispose of those materials through your local recycling depot or by placing them in appropriate collection containers.
• If you wish to discard this air conditioner, please contact your local authorities and ask for the correct method of disposal.
caution
1. The unit must only be installed by a qualified refrigeration mechanic and electrical work carried out by a qualified electrician according to AS/NZS3000 electrical installation standard and all local and national regulations, and in compliance with this manual..
2. Before installation, please contact a qualified air conditioner installer. If the unit is not installed by a qualified air conditioner installer, the malfunction may not be solved due to faulty installation.
3. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
4. The appliance must be positioned so that the plug is accessible.
5. The temperature of the refrigerant circuit will be high, please keep the interconnection cable away from the copper tube.
6. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.
7. Children should be supervised to ensure that they do not play with the appliance.
warning
Before obtaining access to terminals, all supply circuits must be disconnected.
3Safety
Page 4
Minimum floor areas
Components
Your air conditioner is designed to condition the air for a certain range of room sizes, please ensure the selection of your air conditioner complies with the Kelvinator selection tool available from www.kelvinator.com.au
This product uses refrigerant R32. Certain levels of refrigerant require minimum room sizes. Please ensure that these minimum room sizes are adhered to for standard installations (7.5m pipe length). If larger refrigerant charges than standard are used then please consult AS60335.2.40 to determine the safe minimum floor area for the installation.
Model no. Charge of R32 (g) Minimum floor area (m2)
KSV25CRF 710 n/a* KSV25HRF 710 n/a* KSV35CRF 970 n/a* KSV35HRF 970 n/a* KSV52HRF 900 n/a* KSV70CRF 1300 1.87 KSV70HRF 1400 1.87 KSV80HRF 1700 2.76
*no minimum floor area required for this product
Items required for installation
Level gauge
Screw driver
Electric drill
Hole core drill ( 55mm / 70mm)
Flaring tool specifically designed for R32 or R410a refrigerant
Specified torque wrenches
Spanner (half union)
A glass of water
Hexagonal wrench (6mm)
Gas-leak detector
2 stage vacuum pump
Gauge manifold
Users manual
• Thermometer
• Multimeter
Pipe cutter
Measuring tape
Number Description Quantity
1 Indoor unit mounting plate 1 2 Clip anchor not supplied
Self-tapping screw ST4 x 25
3
4 Remote control 1 5 Remote control holder 1 6 Screw for remote holder 2 7 Battery (AAA 1.5V) 2 8 Insulation material not supplied
9
10 Insulation hose for refrigerant piping not supplied 11 Wall clamp not supplied 12 Drain hose not supplied 13 Connection power cable not supplied
14
15
16
17 Flare nut 2
NOTE: Other parts necessary for installation besides those mentioned above must be supplied by the customer/installer.
- for KSV70CRF, KSV70HRF & KSV80HRF 10
- for all other models 5
Connection piping assembly (refer to page 8)
Drain connector (heat pump model only)
Drain plug (reverse cycle models with capacity of over 4500W)
Thermal insulating pipe for extending drain hose
varies by country
1
3
1
4 Minimum floor areas / components
Page 5
Product description
Indoor unit
4
space to the ceiling
15cm or more
space to the wall
Light
Mode
Healthy
Turbo
Fan
Temp
Timer-On
Timer-Off
Clock
Eco
I feel
Swing
15cm or more
250cm or more
air outlet side
200cm or more
space to the floor
2 3
1
space to the wall
15cm or more
8
9
10
11
Outdoor unit
5
6
7
17
space to obstruction
50cm or more
space to the wall
30cm or more
150cm or more
air outlet side
16
14
air inlet side
20cm or more
50cm or more
space to the wall
12
13
15
5Product description
Page 6
Installation site instructions
A proper installation site is vital for correct and efficient operation of the unit.
Avoid the following sites where:
strong heat sources, vapour, flammable gas or volatile liquids are emitted.
high-frequency electro-magnetic waves are generated by radio equipment, welders or medical equipment.
salt-laden air prevails (such as close to coastal areas).
the air is contaminated with industrial vapours and oils.
the air contains sulphurous gas such as in hot spring zones.
corrosive or poor air quality exists.
Indoor unit
1. The air inlet and outlet should be kept clear of obstructions. Ensure the air can be blown through the whole room.
2. Select a site where the condensing water can be easily drained out, and where it is easily connected to the outdoor unit.
3. Select a place where it is out of reach of children.
4. Select the place where the wall is strong enough to withstand the full weight and vibration of the unit.
5. Be sure to leave enough space to allow access for routine maintenance.
6. For optimum performance, the indoor unit should be installed on the wall at a height of 2 metres or more above the floor and at least 2.5 metres from the opposing wall.
7. Make sure that the indoor unit is installed in accordance with installation dimension as below:
more than 15cm from
the ceiling
refrigerant charge.
14. Do not install near a doorway.
15. Note low temperature soldering alloys are not acceptable.
16. Minimum room space requirements as advised on the rating plate must be complied with.
17. Reusable mechanical connectors may not be used within indoors or within wall or ceiling cavities where a refrigerant leak can gather.
18. All refrigerant tubing shall be protected or enclosed to prevent damage.
Outdoor unit
1. Select a site where noise and outflow air emitted by unit will not annoy neighbours.
2. Select a site where there is sufficient ventilation.
3. Select a site where there is no obstruction blocking the inlet and outlet.
4 The site should be able to withstand the full weight and
vibration of the unit.
5. Select a dry place, but do not expose the unit to direct sunlight or strong wind.
6. Make sure that the outdoor unit is installed in accordance with the installation instructions, and is convenient for maintenance and repair.
7. Select a place where it is out of reach of children and far from animals or plants.
8. Select a place where the unit keeps the horizontal and aligned position.
9. Select at a place that respects the minimum distances around the outdoor unit as below:
more than 20cm
more than
30cm
more than
15c m
more than 2m from the floor
more than 2.5m from the opposing wall
8. Select place about 1m or more away from a TV set or any other electric appliance.
9. Select a place where the filter can be easily taken out.
10. Do not use the unit in wet areas such as the laundry or by a swimming pool.
11. A minimum pipe run of 3 metres is required to minimise vibration and noise.
12. Use a stud finder to locate studs to prevent unnecessary damage to the wall.
13. Any variations in pipe length may require adjustment to
6 Installation site instructions
more than
15c m
more than
50cm
more than 1.5m
10. Note low temperature soldering alloys are not acceptable.
11. Reusable mechanical connectors may not be used within indoors or within wall or ceiling cavities where a refrigerant leak can gather.
Page 7
Rooftop installation
WARNING
If the outdoor unit is installed on a roof structure, be sure to level the unit.
Ensure the roof structure and anchoring method are adequate for the unit location.
If the outdoor unit is installed on roof structures or external walls, this may result in excessive noise and vibration, and may also be classed as non-serviceable installation.
Pipe Length Elevation and Additional Quantity of Gas
Model Number
Discharge Pipe Diameter
Suction Pipe Diameter
Standard Length (m)
Maximum Length (m)
Maximum Height (m)
KSV25HRF Ø6.35 mm (1/4”) Ø9.52 mm (3/8”) 7.5 15 10 16
KSV35HRF Ø6.35 mm (1/4”) Ø9.52 mm (3/8”) 7.5 20 10 16
KSV52HRF Ø6.35 mm (1/4”) Ø12.70 mm (1/2”) 7.5 25 10 16
KSV70HRF Ø6.35 mm (1/4”) Ø15.88mm (5/8”) 7.5 25 10 40
KSV80HRF Ø6.35 mm (1/4”) Ø15.88mm (5/8”) 7.5 30 10 40
KSV25CRF Ø6.35 mm (1/4”) Ø9.52 mm (3/8”) 7.5 15 10 12
KSV35CRF Ø6.35 mm (1/4”) Ø9.52 mm (3/8”) 7.5 20 10 12
KSV70CRF Ø6.35 mm (1/4”) Ø15.88 mm (5/8”) 7.5 25 10 12
caution
The outdoor unit is charged with the refrigerant for standard pipe length of 7.5m.
When the connecting pipe length is longer than the standard length, additional refrigerant should be added into the unit according to the above table through the service port on 3-way service valve on the outdoor unit.
PLEASE MAINTAIN THE SHORTEST DISTANCE (3 TO 5 METRES) AND SHORTEST MISALIGNMENT POSSIBLE BETWEEN THE INDOOR AND OUTDOOR UNITS.
The maximum allowance length and height is based on reliability. Exceeding the maximum may cause poor performance or malfunction.
When the level difference between indoor and outdoor units is greater than the maximum height of 10 metres, or when the outdoor unit is installed above the indoor unit, an oil trap should be installed every 5-7 metres.
maximum length
outdoor unit
A
B
piping length under 7.5m
maximum height
Additional Refrigerant (g/m)
indoor unit
outdoor unit
maximum length
oil trap
piping length 7.5m or more
A
indoor unit
B
maximum height
7Rooftop installation
Page 8
Outdoor unit installation
WARNING
Securing the outdoor unit
Anchor the outdoor unit by fixing the 4 holes existent in its base with 4 bolts and nuts of φ10 mm tightly (not included).
Place the outdoor unit over a horizontal concrete or rigid surface (never directly over grass or earth).
A
air inlet
air inlet
B
air outlet
Model
KSV25HRF/ CRF
Outdoor unit dimensions W x D x H (mm)
776 x 320 x 540 510 286
Dimension A (mm)
Dimension B (mm)
Outdoor condensate drainage
During heating operation, the condensate and defrosting water should be drained out reliably through the drain hose.
The drain-water hole must be plugged. Whether to plug other holes will be determined by the installer according to actual conditions.
Install the outdoor drain connector in the drain-water hole on the chassis of the outdoor unit, and attach the drain hose to the connector so that the waste water formed in the outdoor unit can be drained out.
In case of a drain hose, the unit must be installed on a base more than 3cm in height.
drain-water hole
chassis
drain connector
KSV35HRF/ CRF
842 x 320 x 596 540 286
KSV52HRF, KSV70CRF/
955 x 396 x 700 560 364
HRF KSV80HRF
caution
If a suspended installation is needed, the installation bracket must allow the fixation according to dimensions on the figure above.
The wall where the unit will be installed must be of solid brick, concrete or provided with other reinforcement ways to fix the bracket. The fixation of the bracket to the wall and the bracket to the air conditioner must be firm, steady and levelled.
hose of inner diameter 16mm (not supplied)
8 Outdoor unit installation
Page 9
Indoor unit installation
Installing the mounting plate
1. Fit the mounting plate horizontally on the wall with five or more self-tapping screws (type ST4x25, item 3 on page 3).
2. Be sure that the mounting plate has been fixed firmly enough to withstand about 60kg. The weight should be evenly shared by every screw.
3. If the wall is made of brick, concrete or the like, drill five (5) or more holes of 5mm diameter in the wall. Insert clip anchor (item 2 on page 3) for appropriate mounting screws.
4. The water tray’s outlet for the indoor unit has two-way drainage design. During installation, the indoor unit should slightly slant
to water tray’s outlet for smooth drainage of condensate water.
Mounting plate type A
135
Fit the mounting plate and drill holes in the wall according to the wall structure and corresponding mounting points on the mounting plate. (dimensions are in mm unless otherwise stated)
Model no.
Indoor unit dimension
W x D x H (mm)
Mounting
plate type
KSV25CRF 912 x 188 x 290 A
KSV25HRF 912 x 188 x 290 A
KSV35CRF 912 x 188 x 290 A
KSV35HRF 912 x 188 x 290 A
KSV52HRF 1000 x 219 x 326 B
KSV70CRF 1178 x 253 x 326 C
KSV70HRF
1178 x 253 x 326 C
KSV80HRF 1178 x 253 x 326 C
542
235
Mounting plate type B
256
55
78
55mm 55mm
143
87
1000
694
31
80
219
98
55
78
9Indoor unit installation
Page 10
Indoor unit installation
Mounting plate type C
326
253 179746
65 65
50
163 90
6
74 105
indoor
unit
10 Indoor unit installation
Page 11
Indoor unit installation
Drill piping hole
1. Determine hole positions according to the diagram. Drill one (1) hole (Ф55 or Ф70 mm) in the wall at a slight downward slant to the outdoor side.
Piping hole Model
55
70
2. The inclination must be between 5mm and 10mm in order to ensure a good drain of condensed water generated by the indoor unit.
KSV25CRF, KSV35CRF, KSV25HRF, KSV35HRF, KSV52HRF
KSV70CRF, KSV70HRF, KSV80HRF
indoor
wall pipe
5-10mm
outdoor
seal putty
55mm or 70mm
Installation of drain hose
1. Connect the drain hose to the outlet pipe of the indoor unit. Bind the joint with vinyl tape.
outlet pipe of
outlet pipe of
indoor unit
vinyl tape
2. Put the drain hose into insulating pipe.
outlet pipe of
indoor unit
vinyl tape
indoor unit drain hose
drain hose (narrow)
insulating pipe
3. Insert the wall pipe into the hole to prevent any wiring from being damaged when passing through the hole.
4. Always use a wall hole conduit when drilling metal grids, metal plates or the like.
5. For models with a cooling capacity greater than 4500W, remove and dispose the two polystyrene lateral rear supports from the indoor unit before the installation.
remove both supports
3. Wrap the insulating pipe with wide vinyl tape to prevent the shift of insulating pipe. Slant the drain hose downward slightly for smooth drainage of condensed water.
vinyl tape
outlet pipe of
indoor unit
connected
insulating pipe
11Indoor unit installation
Page 12
WARNING
Indoor unit installation
caution
1. The insulating tube should be connected reliably with the sleeve outside the outlet pipe.
2. The drain hose should be slanted downward slightly, without distortion, bulge or fluctuation.
refrigerant
piping
drain hose (connected at the rear left side)
do not block water flow with a rise
do not put the end of the hose in water
3. Do not put the outlet in the water.
bulge flooded
The piping can be output from right, rear right, left or rear left of the indoor unit body.
1. When routing the piping and wiring from the left or right side of indoor unit, cut off the tailings from the chassis when necessary (see figure below).
tailing 2
tailing 1
Cut off the tailings 1 when routing the wiring only.
Cut off the tailings 1 and tailings 2 when routing both the wiring and piping.
drain hole
drain cap
Follow the instructions below for exchanging the position of the drain cap and drain hose from the left to the right side.
a. Pull out the drain cap at the rear right of the
indoor unit.
drain cap
b. Pull out the drain hose at the rear left of the
indoor unit.
drain hose
indoor unit outline
connection piping
43
2. The drain hose can be connected at two different positions. Use the most convenient position and, if necessary, exchange the position of drain cap and drain hose.
The drain hose is connected at the rear left side of the
indoor unit when you receive the product.
12 Indoor unit installation
c. Put the drain cap into the drain hole at the rear left of the
indoor unit.
drain cap
Page 13
d. Insert the drain hose into the drain hole at the rear right of the
WARNING
indoor unit.
drain hose
3. Arrange the pipe in the most convenient direction and position.
piping on the rear right side
piping on the left rear side
drain hose from the left side
piping on the left side
piping on the rear right side
drain hose from the right side
piping on the right side
drain hose from the left side
drain hose from the left side
drain hose from the left side
caution
When refrigerant pipes and the drain pipe are fitted to the same side, ensure that the bulk does not push the unit away from the wall when in its final position.
drain hose from the right side
Piping and cable from the right side
piping on the right side
drain hose from the right side
13Indoor unit installation
Page 14
4. Take out the piping from body case, wrap the piping, power
WARNING
cords, drain hose with the tape and then make them pass through the piping hose.
Do not put any object in the drain pan located in the rear of
the indoor unit, as the condensed water is gathered there and piped out of the room.
5. Hang the mounting slots of the indoor unit on the upper hooks of the mounting plate and check if it is firm enough .
To ease the piping installation, put a spacer between the
indoor unit and the wall. Remove the spacer once finished.
upper hook
mounting plate
indoor unit
liquid pipe
connecting cable
drain hose
gas pipe
piping insulation
caution
Connect the indoor unit first, then the outdoor unit.
Do not plug the cable to the indoor unit. That must be done at a later stage.
Turn the cable lightly to make the connection easier.
• Be careful not to let the drain hose become slack.
• Heat insulate the connecting pipe.
Be sure that the drain hose is located at the lowest side of the bundle. Locating at the upper side can cause drain pan to overflow inside the unit.
Never cross connect or interwind the power wire with any other wiring.
Do not allow the piping to be exposed out from the back of the indoor unit.
If part of the drain hose is positioned inside the room, wrap it with insulating materials so as to prevent condensed water from dropping.
spacer
6. Press the lower left and right sides of the unit against the mounting plate until the lower hooks engage into their slots. Ensure the unit is firmly fitted.
upper hook
connecting cable
drain hose
mounting plate
fixing lower hook
7. The installation site should be 2 metres or more above the floor.
14 Indoor unit installation
Page 15
WARNING
Indoor unit installation
Refrigerant pipe connection
The main cause of refrigerant leakage is due to defects in the flaring work. Carry out flaring work using the following procedure:
Note: When using refrigerant R32, a reusable flared connection is the only allowed pipework on the outside of any building.
Hence the supplied "once only" flare fitting must be used unless all welded connections are used. If welded connections are used, no low temperature solder is permitted.
a. Cut the pipes and the cable
Use the piping kit accessory (if applicable) or pipes purchased locally. Measure the distance between the indoor and the outdoor unit. Cut the pipes a little longer than the measured distance. Cut the cable 1.5m longer than the pipe length.
pipe
caution
It is not possible to put them on after flaring work.
d. Flaring work
Carry out flaring work using flaring tool as shown below.
handle
bar
Firmly hold copper pipe in a die according to the dimension shown in the table below.
A
copper pipe
clamp handle
bar
yoke
cone
90°
oblique roughness burr
b. Burr removal
Completely remove all burrs from the cut cross section of pipe/ tube. Face the end of the copper pipe/tube in a downward direction as you remove burrs in order to avoid burrs dropping into the tubing.
pipe
reamer
face down
c. Put the flare nut on
Remove flare nuts attached to indoor and outdoor unit, then put them on pipe/tube having completed burr removal.
flare nut
Outer diameter (mm)
6.35 (1/4”)
9.52 (3/8”)
12.70 (1/2”)
15.88 (5/8”)
A (mm)
Max. Min.
1.3 0.7
1.6 1.0
1.8 1.0
2.4 2.2
e. Check
Compare the flare work with the adjacent diagram.
If the pipe has any defect, cut off the enlarged section and redo the work.
smooth all around
incorrect flaring
inclined
damaged
even length all
around
Make an independent covering for each pipe with the appropriate tubular isolation.
surface
cracked
uneven
thickness
copper tube
15Indoor unit installation
Page 16
Piping connection - indoor unit
WARNING
a. Connecting the indoor unit tubing to the connection piping:
Align the centres of the pipes and sufficiently tighten the flare
nut with your hands first.
b. Wrap the insulation material around the connecting portion:
Cover the indoor unit pipe and the connection pipe with the
heat insulation material. Bind them together with vinyl tape so that there is no gap.
insulating material
indoor unit tubing
spanner (fixed)
indoor unit piping
torque wrench
flare nut
flare nut
piping
piping
Isolate the suction pipe from the liquid pipe.
heat insulation
suction line pipe liquid line pipe
Wrap the insulated pipes with vinyl tape in the rear section for pipe housing. Fasten the power cable to the pipes with vinyl tape.
connection pipe
vinyl tape (wide)
wrap with vinyl tape
indoor unit pipe
Then tighten the flare nut with spanner and torque wrench referring to the following:
Outer diameter (mm) Torque (N.m)
6.35 (1/4”)
9.52 (3/8”)
12.70 (1/2”)
15.88 (5/8”)
19.05 (3/4”)
15-20
35-40
50-55
60-65
70-75
caution
Excessive torque can break the nut depending on installation conditions.
16 Indoor unit installation
pipe
vinyl tape (narrow)
connection cable
Wrap the piping, drain hose and power cable tightly with vinyl tape so that they can fit into the rear piping housing section.
pipe
drain hose
connection power cable
vinyl tape (narrow)
wrap with vinyl tape (wide)
Page 17
Indoor unit installation
c. Positioning the indoor unit:
Remove the spacer.
Hook the indoor unit onto the upper portion of the mounting plate (engage the hooks of the mounting plate into the openings at the rear top of the indoor unit). Ensure that the hooks are properly seated on the mounting plate by moving the indoor unit in all directions.
outdoor unit
2-way valve
discharge pipe (suction pipe for KSV52HRF)
suction pipe (discharge pipe for KSV52HRF)
upper hook
mounting plate
spacer
Press the lower left and right sides of the unit against the mounting plate until the hooks engage into their slots (clicking sound).
upper hook
connecting cable
mounting plate
fixing lower hook
Piping connection - outdoor unit
a. Align the centres of the pipes and sufficiently tighten the flare
nut with your hands.
3-way valve
Make sure to follow the torque table value as below:
Outer diameter (mm) Torque (N.m)
6.35 (1/4”)
9.52 (3/8”)
12.70 (1/2”)
15.88 (5/8”)
19.05 (3/4”)
15-20
35-40
50-55
60-65
70-75
Piping formation
a. Form the piping by wrapping the connecting portion of the
indoor unit with insulation material and secure it with narrow vinyl tape and wide vinyl tape.
If you want to connect an additional drain hose, the end of the
drain hose outlet should be routed above the ground. Secure the drain hose appropriately.
b. In cases where the outdoor unit is installed below the indoor
unit level:
Wrap the piping, drain hose and connecting cable from the
bottom to the top. Secure the wrapped piping along the exterior wall using saddle or equivalent.
seal small openings around piping with a gum type sealer
wrapping
b. Then, tighten the flare nut with torque wrench until the
wrench clicks.
pipe
drain hose
connection cable
drain hose
trap is required to prevent water from entering electrical parts
NOTE: all piping must be protected against mechanical damage.
17Indoor unit installationV
Page 18
Safety precautions
c. In cases where the outdoor unit is installed above the indoor
unit level:
Wrap the piping and connecting cable from bottom to top.
Form a trap to prevent water from entering the room.
Secure the wrapped piping along the exterior wall using
saddle or equivalent.
seal small openings around piping with a gum type sealer
trap
trap
drain hose
Note: all refrigerant piping must be protected against mechanical damage
Electrical safety rules before starting the installation:
1. A dedicated power supply circuit and breaker should be provided for the products which are not supplied with a service cord and plug in accordance with local electrical safety regulations.
2. The circuit breaker must have the functions of magnetic tripping and heat tripping to prevent short circuit and overload.
3. The appliance shall be installed in accordance with national wiring regulations.
4. A circuit breaker with proper capacity must be installed according to AS3000 and applicable local electrical safety regulations.
5. In case of problems in power supply, the air conditioner must not be installed before the customer fixes the problem.
6. Be sure the power supply matches the air conditioner.
7. Ensure the live wire, neutral wire and earth wire in the power socket are properly connected.
8. Inadequate or incorrect electrical connections may cause electric shock, fire or some electrical parts to malfunction.
9. Before performing any electrical work, turn off the main power to the system.
Earthing requirements
1. Air conditioners are type 1 electric appliances. The unit must be reliably earthed and connected by a qualified electrician.
2. The yellow-green wire in the air conditioner is the earthing wire which cannot be used for any other purposes. Improper earthing may cause electric shock.
3. The earth resistance must comply to national wiring regulations.
4. The user’s power must have reliable earthing terminal. Do not connect the earthing wire with the following:
Water pipe
Gas pipe
Contamination pipe
18 Safety precautions
Page 19
N(1) 2 4 5
N(1) 2 3
Installation
WARNING
Indoor electric wiring
Note: for correct operation of the air conditioner and standby power modes the mains power should be supplied to the indoor unit.
1. Open the front panel and remove the wiring cover by loosening the screw.
wiring cover
2. Route the power connection cable from back of the indoor unit and pull it toward the front through the wiring hole for connection.
3. Connect and screw the wires onto the terminal block as identified by their colours.
warning
All wires between indoor and outdoor units must be connected by a qualified electric contractor.
If the length of the power cord is not enough, please contact your installer for new a power cord. Lengthening the power cord by yourself is dangerous and illegal.
NOTE: Powered accessories cannot be connected to these wiring points
After tightening the screws, pull the wire slightly to confirm whether it’s firm or not.
Do not connect two power cables together to supply power to the air conditioner.
Do not extend the power cable conductor by cutting or splicing.
blue
black
brown
4. Wrap wires that are not connected with insulating tape so that they do not touch any electrical or metal parts.
5. Secure the wires firmly with the cable clamp.
6. Put the wiring cover back and screw it.
7. Reinstall the front panel.
earthing wire (green and yellow)
19Installation
Page 20
N(1) 2
N(1) 2 3
WARNING
Installation
Outdoor electric wires
1. When required, remove the handle on the right side plate of outdoor unit by loosening the screw.
handle
terminal block
2. Take off wire cable clamp. Connect and screw the power connection cable and signal control wire (for reverse cycle models only) onto the terminal block following corresponding identification numbers and colours on the terminal blocks of indoor and outdoor units.
3. To prevent water from entering, make a trap (“U”) in the connection wires (see page 16).
4. Wrap wires that are not connected with insulating tape so that they do not touch any electrical or metal parts.
5. Fix the power connection wires with wire clamps.
6. Reinstall the handle.
caution
After confirming the above conditions, prepare the wiring as follows:
• The screws which fasten the wiring to the terminal block may come loose from vibrations during transportation.
• Check and make sure all screws are well fixed. Otherwise, it could cause burn-out of the wires.
• Be sure the circuit capacity is sufficient.
• Ensure the starting voltage is maintained at over 90% of the rated voltage marked on the nameplate.
• Confirm that the cable thickness is as specified in the power source specification.
• Always install a Residual Current Device (RCD).
• The following may be caused by voltage drop: vibration of a contactor, which will damage the contact point, fuse blowing, disturbance of the normal function of the overload.
• The means for disconnection from a power supply shall be incorporated in the fixed wiring and have an air gap contact separation of at least 3mm in each active (phase) conductor.
NOTE: Powered accessories cannot be connected to these wiring points.
blue black brown
earthing wire
(green & yellow)
cable clamp
to outdoor unit
20 Installation
Page 21
Checking the drainage
WARNING
Do not place drain piping as indicated below:
1. Open and lift the indoor unit front panel.
Hold the lower part of the left and right sides of the panel, pull it against you and lift it stops with a full support from the bracket.
panel bracket
2. Check the drainage
Carefully pour a glass of water on the evaporator.
Ensure the water flows through the drain hose of the indoor unit without any leakage and goes out the drain exit.
do not rise
water leakage
accumulated drain water
water leakage
water leakage
tip of drain hose dipped in water
space less than 50mm
Air purging and leakage test
Note: Any brazed connections must be completed before evacuation and prior to the release of any refrigerant into the refrigerating components.
Air and moisture in the refrigeration system have undesirable effects as indicated below:
• System pressure increase
• Rise of the operating current.
Cooling or heating efficiency drops.
Moisture in the refrigeration circuit may freeze and block the capillary tubing.
Water may lead to corrosion of parts in the refrigeration system.
Therefore, the indoor unit and tubing between the indoor and outdoor units must be tested for leakage and evacuated to remove any non-condensables and moisture from the system.
drain hose
c. Drain piping
The drain hose should point downward for easy drain flow.
downward slope
Air purging with a vacuum pump
Preparation
Check that each tube (both liquid and gas side tubes) between the indoor and outdoor units have been properly connected and all wiring for the test has been completed. Remove the service valve caps from both gas and liquid sides on the outdoor unit.
For detailed data of pipe length and refrigerant amount, please refer to page 6.
caution
Both liquid and gas side service valves on the outdoor unit are kept closed at this stage.
When relocating the unit, perform evacuation using a vacuum pump. Make sure the refrigerant added into the air conditioner is in liquid form.
Handling the stop valve
Opening the stop valve:
Open the valve stem until it hits against the stopper. Do not try to open it further.
Closing the stop valve:
Securely tighten the valve stem with a special tool. Then securely tighten the valve stem cap with a spanner or the like.
21Installation
Page 22
outdoor unit
WARNING
B
D
C
A
hi stop valve (2-way valve)
gas side
liquid side
indoor unit
half union
caution
A: Low pressure valve (3-way) - gas side.
B: High pressure valve (2-way) - liquid side.
C and D: they are the ends of indoor unit connection
valve body
charge port
valve stem
stopper
flare nut
cap
5 Keep vacuuming for more than 15 minutes and make sure
the reading of multimeter is -1.0 x 10 Pa (-76cmHg). Then fully close the low handle of manifold valve and stop the operation of the vacuum pump.
6 Turn the stem of the stop valve B (2-way valve) about 45
counterclockwise for 6~7 seconds after the gas coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a little higher than the atmosphere pressure.
7 Remove the charge hose from the low pressure charge port.
8 Fully open the valve stems of A (3-way valve) and B (2-way
valve).
9 Securely tighten the stem cap.
outdoor unit
low handle
changing hose
low pressure valve
multimeter
-76cmHg
vacuum pump
manifold valve
high handle
charging hose
Make sure to follow the torque table value as below:
Outer diameter (mm) Torque (N.m)
6.35 (1/4”)
9.52 (3/8”)
12.70 (1/2”)
15.88 (5/8”)
19.05 (3/4”
15-20
35-40
50-55
60-65
70-75
Using the vacuum pump
1 Completely tighten the flare nuts on A, B, C and D, connect
the manifold valve charge hose (blue) to the charge port of the low pressure valve (3-way valve) on the gas pipe side.
2 Connect the other charge hose (yellow) of the manifold to the
vacuum pump.
3 Fully open the low handle of the manifold valve.
4 Open the vacuum pump for vacuumisation. At the beginning,
slightly loosen the flare nut of the low pressure valve to check if there is air coming inside (if operation noise of the vacuum pump has been changed, the reading of multimeter is 0 instead of minus). Then tighten the flare nut.
22 Installation
Page 23
Testing the air conditioner
Soapy water method
Apply soapy water or liquid neutral detergent on all valves and pipe connections (A, B, C and D, refer to the figure below) involved in installation by a soft brush to check for leakage. If bubbles come out, the pipes have leakage.
indoor check points
D
discharge pipe (suction pipe for KSV52HRF)
C
suction pipe (discharge pipe for KSV52HRF)
B
outdoor
unit
2-way
valve
3-way
valve
A
outdoor check points
Leak detector
Use the leak detector to check for leakage.
Electrical safety check
Perform the electric safety check after completing the installation:
1. Earthing work
After finishing earthing work, measure the earthing
resistance by visual detection and earthing resistance tester.
2. Electrical leakage check (perform while the test is running)
During test operation after finishing the installation, the service
person can use the electric probe and multimeter to perform the electrical leakage check. Turn off the unit immediately if refrigerant leakage happens. Check and find out the solution ways until the unit operates properly.
Operation test
1. Before operation test
Do not switch on power before installation is finished completely.
Electric wiring must be connected correctly and securely.
Stop valves of the connection pipes should be fully opened.
All the impurities such as scraps and waste must be cleared from the unit.
Operation test method
Switch on power and press “ON/OFF” button on the remote controller to start the operation. Press MODE button to select the COOL, HEAT (if applicable), FAN to check if all the functions work well.
When the ambient temperature is lower than 16°C), the unit can not be set on the remote control to work in COOL mode. Please use the Emergency Operation mode which is used only when the remote is unavailable or in case of maintenance.
manual control button
manual control button
Pump down
When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is released into the atmosphere.
Connect the hose of manifold valve to the charge port of stop valve on the gas pipe side of the outdoor unit.
Close the stop valve on the gas pipe side almost completely.
Fully close the stop valve on the liquid pipe side.
Turn on the unit in COOL mode.
Fully close the stop valve on the gas pipe side when the pressure gauge shows 1 - 0.5 kgf/cm (100 ~ 50 kPa).
Stop the test run operation by turning the unit off and all the refrigerant gases have been collected in the outdoor unit.
23Testing the conditioner
Page 24
Installation checklist
TIPS & INFORMATION
important
• If your appliance is damaged due to improper installation your warranty may be void.
• Proper installation requires the use of a licensed installer.
• You must keep full details of the installer including the license number and provide those details whenever you request a service for your appliance.
Question
Does the unit have adequate clearance from walls and ceiling in accordance to installation instructions?
Is the unit mounted to allow condensate to flow freely toward the outside?
Does outdoor section have adequate clearance in accordance to installation instructions?
Is the unit securely mounted?
Is the unit readily accessible without special equipment?
Has the appropriate size circuit and fuse/circuit breaker been fitted?
Has the unit been tested and confirmed to operate correctly?
Has the user of the air conditioner been shown how to use the air conditioner?
CUSTOMER: PLEASE RETAIN WITH YOUR PURCHASE DOCUMENTS IN A SAFE PLACE
Model Number ________________________________________________
Serial Number ___________________________________________________________________________________________________________
Installers name ________________________________________________ Refrigerant handling license no. ______________________________
Installers address ______________________________________________ Phone
Installers signature _____________________________________________ Date of installation
24 Checklist
Page 25
Post installation checks
Items to be checked Possible malfunction
Has the unit been fixed firmly?
Have you done the refrigerant leakage test?
Is thermal insulation sufficient?
Is water drainage satisfactory?
Is the voltage in accordance with the rated voltage marked on the nameplate?
Is the electric wiring or piping connection installed correctly and securely?
Has the unit been securely earthed?
Is the power cord specified?
Is the inlet or outlet blocked?
Is the length of connection pipes and refrigerant capacity recorded?
The unit may drop, shake or emit noise
It may cause insufficient cooling (heating)
It may cause condensation
It may cause water leakage
It may cause electric malfunction or damage the unit
It may cause electric malfunction or damage the parts
It may cause electrical leakage
It may cause electric malfunction or damage the parts
It may cause insufficient cooling (heating)
The refrigerant capacity is not accurate
25Post installation checks
Page 26
Notes
26 Notes
Page 27
Warranty
FOR SALES IN AUSTRALIA AND NEW ZEALAND
APPLIANCE: KELVINATOR SPLIT SYSTEM AIR CONDITIONER
This document sets out the terms and conditions of the product warranties for Electrolux Appliances. It is an important document. Please keep it with your proof of purchase documents in a safe place for future reference should you require service for your Appliance.
1. In this warranty:
(a) ‘acceptable quality’ as referred to in clause 10 of this warranty has the
same meaning referred to in the ACL;
(b) ‘ACL’ means Schedule 2 to the Competition and Consumer
Act 2010;
(c) ‘Appliance’ means any Electrolux product purchased by you and
accompanied by this document;
(d) ‘ASC’ means Electrolux authorised service centres;
(e) ‘Electrolux’ means Electrolux Home Products Pty Ltd of 163
O’Riordan Street, Mascot NSW 2020, ABN 51 004 762 341 in respect of Appliances purchased in Australia and Electrolux (NZ) Limited (collectively ‘Electrolux’) of 3-5 Niall Burgess Road, Mount Wellington, in respect of Appliances purchased in New Zealand;
(f) ‘major failure’ as referred to in clause 10 of this warranty has the same
meaning referred to in the ACL and includes a situation when an Appliance cannot be repaired or it is uneconomic for Electrolux, at its discretion, to repair an Appliance during the Warranty Period;
(g) ‘Warranty Period’ means the Appliance is warranted against
manufacturing defects in Australia and New Zealand for the period of 60 months, subject to this warranty and to the customer meeting the Warranty Condition.
(h) ‘Warranty Condition’ means:
(i) evidence by the customer that the Appliance was installed by a licensed air conditioner installer in Australia and in accordance with Electrolux installation guidelines as set out in the installation manual;
(ii) the Appliance rating is correct for the size and thermal characteristics of the room;
(iii) the Appliance has been regularly maintained in accordance with Electrolux guidelines set out in the user manual;
(iv) the Appliance is designed for providing human comfort and should be used under ambient conditions as set out in the
productspecicationsandgeneralairqualityconditions.
(i) ‘you’ means the purchaser of the Appliance not having purchased the Appliance for re-sale, and ‘your’ has a corresponding meaning.
2. This warranty only applies to Appliances purchased and used in Australia or New Zealand in normal domestic appliactions and is in addition to (and does not exclude, restrict, or modify in any way) any non-excludable statutory warranties in Australia or New Zealand.
3. During the Warranty Period Electrolux or its ASC will, at no extra charge if your Appliance is readily accessible for service, without special equipment and subject to these terms and conditions, repair or replace any parts which it considers to be defective. Electrolux or its ASC may use remanufactured parts to repair your Appliance. You agree that any replaced Appliances or parts become the property of Electrolux. This warranty does not apply to
lightglobes,batteries,ltersorsimilarperishableparts.
4. Parts and Appliances not supplied by Electrolux are not covered by this warranty.
5. To the extent permitted by law, you will bear the cost of transportation, travel and delivery of the Appliance to and from Electrolux or its ASC. If you reside outside of the service area, you will bear the cost of:
(a) travel of an authorised representative;
(b) transportation and delivery of the Appliance to and from Electrolux
or its ASC.
Important Notice
Before calling for service, please ensure that the steps listed in clause 13 above have been followed.
In all instances, unless the Appliance is transported by Electrolux or an Electrolux authorised representative, the Appliance is transported at the owner’s cost and risk while in transit to and from Electrolux or its ASC.
6. Proof of purchase is required before you can make a claim under this warranty.
7. You may not make a claim under this warranty unless the defect claimed is due to faulty or defective parts or workmanship. Electrolux is not liable in the following situations (which are not exhaustive):
(a) the Appliance is damaged by:
(i) accident
(ii) misuse or abuse, including failure to properly maintain or service
(iii) normal wear and tear
(iv) power surges, electrical storm damage or incorrect power supply
(v) incomplete or improper installation
(vi) incorrect, improper or inappropriate operation
(vii) insect or vermin infestation
(viii) failure to comply with any additional instructions supplied with the
Appliance;
(b) theApplianceismodiedwithoutauthorityfromElectroluxinwriting;
(c) the Appliance’s serial number or warranty seal has been removed
or defaced;
(d) the Appliance was serviced or repaired by anyone other than Electrolux,
an authorised repairer or ASC.
8. This warranty, the contract to which it relates and the relationship between you and Electrolux are governed by the law applicable where the Appliance was purchased. Where the Appliance was purchased in New Zealand for commercial purposes the Consumer Guarantee Act does not apply.
9. To the extent permitted by law and subject to your non-excludable statutory rights and warranties, Electrolux excludes all warranties and liabilities (other than as contained in this document) including liability for any loss or damage whether direct or indirect arising from your purchase, use or non use of the Appliance.
10. For Appliances and services provided by Electrolux in Australia, the Appliances come with a guarantee by Electrolux that cannot be excluded under the ACL. You are entitled to a replacement or refund for a major failure and for compensation for any other reasonably foreseeable loss or damage. You are also entitled to have the Appliance repaired or replaced if the Appliance fails to be of acceptable quality and the failure does not amount
toamajorfailure.Thebenetstoyougivenbythiswarrantyareinaddition
to your other rights and remedies under a law in relation to the Appliances or services to which the warranty relates.
11. At all times during the Warranty Period, Electrolux shall, at its discretion, determine whether repair, replacement or refund will apply if an Appliance has a valid warranty claim applicable to it.
12. For Appliances and services provided by Electrolux in New Zealand, the Appliances come with a guarantee by Electrolux pursuant to the provisions of the Consumer Guarantees Act, the Sale of Goods Act and the Fair Trading Act.
13. To enquire about claiming under this warranty, please follow these steps:
(a) carefully check the operating instructions, user manual and the terms of
this warranty; (b) have the model and serial number of the Appliance available; (c) have the proof of purchase (e.g. an invoice) available; (d) telephone the numbers shown below.
14. You accept that if you make a warranty claim, Electrolux and its ASC may exchange information in relation to you to enable Electrolux to meet its obligations under this warranty.
ortondtheaddressofyournearest
FOR SERVICE
state service centre in Australia
PLEASE CALL 13 13 49
For the cost of a local call (Australia only)
FOR SERVICE
ortondtheaddressofyournearest
authorised service centre in New Zealand
FREE CALL 0800 10 66 10
(New Zealand only)
KSSAC_Warr_Aug13
SERVICE AUSTRALIA
ELECTROLUX HOME PRODUCTS
www.electrolux.com.au
SERVICE NEW ZEALAND
ELECTROLUX (NZ) Limited
www.electrolux.co.nz
FOR SPARE PARTS
ortondtheaddressofyournearest
state spare parts centre in Australia
PLEASE CALL 13 13 50
For the cost of a local call (Australia only)
FOR SPARE PARTS
ortondtheaddressofyournearest
state spare parts centre in New Zealand
FREE CALL 0800 10 66 20
(New Zealand only)
27Warranty
Page 28
For more information on all Kelvinator appliances, or for dimension and installation information, call into your retailer, phone or email our customer care team or visit our website:
AUSTRALIA
phone: 1300 363 640 fax: 1800 350 067 email: customercare@electrolux.com.au web: kelvinator.com.au
NEW ZEALAND
phone: 0800 436 245 fax: 0800 225 088 email: customercare@electrolux.co.nz web: kelvinator.co.nz
Kelvinator. We are part of the Electrolux family. Share more of our thinking at electrolux.com.au
Part No. 66129913263 © 2015 Electrolux Home Products Pty Ltd. ABN 51 004 762 341 KMAN_KAIRINV2_IM_Jun15
Loading...