Lift Station LeveL tranSmitter
non-fouLing deSign for waStewater appLicationS
Specically designed for extended service in sewage lift station environments, the
LevelRat by Keller America features a wide sensing diaphragm yet small overall size. Unlike similar,
competing models which feature a fragile Teon®-coated rubber diaphragm, the LevelRat incorporates
a monolithic diaphragm which combines the non-stick quality of Teon with superior toughness and
abrasion resistance.
Perfectly suited for pump control applications, the LevelRat is compatible with any standard 2-wire, 4...20
mA current loop or 3-wire voltage systems.
Keller America’s guaranteed lightning protection makes this transmitter ideal for installation in areas
prone to chronic damage due to transients caused by lightning.
For more information on the LevelRat, or any other Keller product, please contact Keller America, or
view the entire Keller catalog at http://www.kelleramerica.com/datasheets.html.
FEATURES
4...20mA models include guaranteed lightning protection at no additional cost.
16-bit internal digital error correction for cost-effective low Total Error Band (TEB)3.
316L SS housing construction.
Non-fouling diaphragm for superior resistance to puncture.
2-year warranty covers defects in materials and workmanship.
User-rangeable analog output ensures compatibility as requirements change.
RS485 modied-MODBUS compatible interface allows up to 128 transmitters on a single bus.
Standard dual (analog & RS485) outputs simplify interface to controls, data collection, and telemetry
systems.
Built in the U.S.A. ARRA Section 1605 Compliant.
Standard 3-day lead time.
LeveLrat
KELLER America Inc.
Newport News, Virginia
www.kelleramerica.com
sales@kelleramerica.com
Output White Black Red Blue Yellow
2-wire
(mA)
3-wire
(VDC)
OUT /
GND
GND +VCC +OUT RS485A RS485B
Braided shield wire connected to transmitter housing
+Vcc N/A RS485A RS485B
Subject to alterations
Edition 11/2017
877-253-5537
757-596-6659
Pressure Ranges
1,2
Relative Innite between 0...5 thru 0...100 ft W.C.
1. The LevelRat can be provided with custom calibration at no extra cost. For uids other than water,
the specic gravity must be given at the time the order is placed.
2. Intermediate ranges are realized by deranging the analog output from the next highest basic range:
1, 3, and 10 bar (relative). Level range may be specied in units of lb/in2(psi), inches WC or feet WC.
Keller America uses the International Standard conversion of 2.3067 feet WC/psi.
Accuracy
3
Static Standard ±0.2% FS
Total Error Band Standard ±0.5% BR
3. Static accuracy includes the combined effects of non-linearity, hysteresis, and non-repeatability
at room temperature (25°C). Total Error Band (TEB) includes the combined effects of non-linearity,
hysteresis, and non-repeatability as well as thermal dependencies, over the compensated temperature
range, expressed as a percentage of the basic range (BR).
The calculation for maximum TEB on intermediate ranges (IR) is: TEB
= (BR/IR) X TEB
IR
BR
Electrical
6
Supply (4-20mA) 11...32 VDC
Supply (0-5VDC) 8...32 VDC
Supply (0-10VDC) 13...32 VDC
Load Resistance (mA) <(Supply-11V)/0.022A
Load Resistance (VDC) >4k ohm
6. Nominal values may be higher depending upon cable length. Internal lightning protection increases
the minimum-required supply voltage from 8VDC to 11VDC, due to internal resistance of the surge
protectors. In addition, cable resistance (~70Ω / 1000ft) adds to the supply requirement. In order to
insure proper system operation, calculate the minimum required supply voltage (at the source) as
follows:
For two-part (internal+external) system (recommended):
MINIMUM SUPPLY VOLTAGE = 11.6 + 0.022 (CABLE LENGTH x 0.07) VDC
For internal only protector (standard with 4-20mA output):
MINIMUM SUPPLY VOLTAGE = 11 + 0.022 (CABLE LENGTH x 0.07) VDC
Output
4
Current 4...20mA + RS485
Voltage 0...5, 0...10VDC + RS485
Resolution 0.002%
4. Other voltage output options available on request.
5. Resolution applies to digital output only. Analog resolution is continuous and limited by the process
meter and not the instrument.
5
Environmental
Protection Rating IP68
Operating Temp. -10...60° C
Compensated Temp. 0...50° C
Wetted Materials 316 L Stainless Steel
Kynar
Fluorocarbon
Certications
CE EN50081-1, EN50082-2
Cable Options Polyethylene for general purpose
Hytrel for hydrocarbon
Tefzel for chemical interaction
Optional Accessories
1/2” NPT Conduit Fitting Drying Tube Assembly Bellows Assembly Cable Hanger Termination Enclosure Pressure Test Adapter
Stabilizing Weight Process Meter Signal Line Surge ProtectorInterface Converter
KELLER America Inc.
Newport News, Virginia
www.kelleramerica.com
sales@kelleramerica.com
Edition 11/2017
Subject to alterations
877-253-5537
757-596-6659