General PurPose submersible level TransmiTTer
cusTom ranGe analoG level TransmiTTer
The Levelgage by Keller America provides standard features that far exceed those of comparably priced
instruments, including standard ±1% FS Total Error Band (TEB)3 or optional ±0.5% FS TEB3 accuracy.
This level transmitter is approved to NSF 61 and NSF 3726 standards for water quality and includes
Keller America’s guaranteed lightning protection, making the Levelgage an outstanding value for liquid
level measurement.
The ability of the Levelgage to provide this level of sustained performance over a wide range of operat-
ing conditions makes it ideally suited to an equally wide range of applications, including drinking water,
stream and reservoir level, environmental monitoring, tank level, wastewater, and for installations in
areas prone to chronic damage due to transients caused by lightning.
For more information on the Levelgage, or any other Keller product, please contact Keller America, or
view the entire Keller catalog at http://www.kelleramerica.com/datasheets.html.
FEATURES
NSF 61 / NSF 372 approved construction for use in drinking water applications
4...20mA models include guaranteed lightning protection at no additional cost
16-bit internal digital error correction for cost-effective low Total Error Band (TEB)
316L stainless steel construction
2-year warranty covers defects in materials and workmanship
Industry standard analog outputs simplify interface to controls, data collection, and telemetry systems
Built in the U.S.A. ARRA Section 1605 Compliant
Standard 3-day lead time
6
3
levelGaGe
KELLER America Inc.
Newport News, Virginia
www.kelleramerica.com
sales@kelleramerica.com
Output White Black Red
2-wire (mA) OUT / GND +Vcc N/A
3-wire (VDC) GND +VCC +OUT
Braided shield wire connected to transmitter housing
Min. pipe bend radius 1” IPS 1.5” IPS 2” IPS
Schedule 40 22” 4” 3”
Schedule 80 22” 6” 4”
Edition 07/2019
Subject to alterations
877-253-5537
757-596-6659

Pressure Ranges
1,2
Relative Innite between 0...3 thru 0...900 ft W.C
Absolute Innite between 0...2 thru 0...11 bar
1.The Levelgage can be provided with custom calibration at no extra cost. For uids other than water,
the specic gravity must be given at the time the order is placed.
2. Intermediate ranges are realized by deranging the analog output from the next highest basic range:
1, 3, 10, and 30 bar (relative) 2, 4, and 11 bar (absolute). Level range may be specied in units of lb/
in2(psi), inches WC or feet WC. Keller America uses the International Standard conversion of 2.3067
feet WC/psi.
Accuracy
3
Static Standard ±0.25% FS
Total Error Band Standard ±1% BR, Optional ±0.5% BR
3.Static accuracy includes the combined effects of non-linearity, hysteresis, and non-repeatability
at room temperature (25°C). Total Error Band (TEB) includes the combined effects of non-linearity,
hysteresis, and non-repeatability as well as thermal dependencies, over the compensated temperature
range, expressed as a percentage of the basic range (BR).
The calculation for maximum TEB on intermediate ranges (IR) is:
TEBIR = (BR/IR) X TEB
BR
Output
Current 4...20mA
Voltage 0...5, 0...10VDC
4
4. Other voltage output options available on request.
Certications
CE EN50081-1, EN50082-2
NSF / ANSI
6
61, 372
Electrical
5
Supply (4-20mA) 11...28 VDC
Supply (0-5VDC) 8...28 VDC
Supply (0-10VDC) 13...28 VDC
Load Resistance (mA) <(Supply-11V)/0.022A
Load Resistance (VDC) >4k ohm
5. Nominal values may be higher depending upon cable length. Internal lightning protection increases
the minimum-required supply voltage from 8VDC to 11VDC, due to internal resistance of the surge
protectors. In addition, cable resistance (~70Ω / 1000ft) adds to the supply requirement. In order to
insure proper system operation, calculate the minimum required supply voltage (at the source) as
follows:
For two-part (internal+external) system (recommended):
MINIMUM SUPPLY VOLTAGE = 11.6 + 0.022 (CABLE LENGTH x 0.07) VDC
For internal only protector (standard with 4-20mA output):
MINIMUM SUPPLY VOLTAGE = 11 + 0.022 (CABLE LENGTH x 0.07) VDC
Environmental
Protection Rating IP68
Operating Temp. -10...60° C
Compensated Temp. -10...80° C
Wetted Materials 316 L Stainless Steel
Polyamide
Cable & Sealing PE & EPDM for water / wastewater
6
Hytrel & Viton for hydrocarbons
Tefzel & Viton or EPDM as required for
chemical interaction
6. NSF 61 and NSF 372 approval applies only to PE & EPDM contruction material option, which is
standard on this instrument unless otherwise specied.
Optional Accessories
1/2” NPT Conduit Fitting Drying Tube Assembly Bellows Assembly Cable Hanger Termination Enclosure
Pressure Test AdapterStabilizing Weight Process Meter Open-faced Nose Cap Signal Line Surge Protector
KELLER America Inc.
Newport News, Virginia
www.kelleramerica.com
sales@kelleramerica.com
Edition 07/2019
Subject to alterations
877-253-5537