CONTENTS
Pressure switch PA-22 PS / PAA-22 PS
Connector pin assignment M12 3
Connection diagram 3
Programmer dV-22 PP
Overview 4
Programming / Pressure switch conguration 5
Programming with the Programmer dV-22 PP 5
Programming with the PC / Laptop 5
Connections of the dV-22 PP
Power supply connection M12 plug 6
Converter connection connector plug 6
Pressure switch connection M12 socket 6
Display 7
Navigating in the Menu
Functions of the keys 7
Menu structure 8
Programming mode 9
Switching thresholds 9
Switching functions 9
Software “Pressure switch console”
Selection of the serial port 10
Selection of the pressure unit display 10
Read-out and programming of the pressure switch 10
Display of the pressure value and status of the switches 11
- 2 - www.keller-druck.com

Pressure switch PA-22 PS / PAA-22 PS
Connector pin assignment M12
Pin 1: +VCC (8…40 V DC)
Pin 2: Switch output 2
Pin 3: GND
Pin 4: Switch output 1
Pin 5: Analog output
The switch outputs are factory congured as PNP (switch switches load to +VCC) or
NPN (switch switches load to ground) and can be programmed independently. The
following functions can be congured for each switch output: hysteresis / window
function, normally open / normally closed, time delay (0…5 seconds).
If a meter is connected to the analog output, it must have an internal resistance of at
least 30 kΩ. Though the pressure switches are already congured at the factory, the
conguration can be changed via the dV-22 PP programmer. Time delay can only be
changed with a PC / laptop running “Pressure Switch Console” software.
Connection diagram
NPN switch output with
external load (RL)
PNP switch output with
external load (RL)
Switch output
(pin 4 or pin 2)
+V
CC
R
L
R
L
GND
Pressure Switch PA-22 PS / PAA-22 PS - 3 -
Pressure connection Electrical
connection M12
Switch output
(pin 4 or pin 2)
Analog output
GND
Analog output
(pin 5)
V
Voltmeter
(Ri > 30 kΩ)

Programmer dV-22 PP
The conguration of the pressure switch can be changed with the dV-22 PP programmer.
1
5
2
3
6
4
- 4 - www.keller-druck.com
1) M-12 plug Power supply connection (8…40 V DC)
2) 5-pole connector Connection to PC / laptop with a converter (K-107 / K-104B)
3) M-12 socket Connection of the pressure switch
4) LED Indicates the status of the switches (switch 1 and switch 2)
5) LCD Main display
6) Keys SELECT and ENTER