KELD KLT11 series, KLT11-D Specification And Operating Instructions

Specification and Operating Instructions
KLT11-D Temperature Digital Controller
Description
Installation
NOTE: Unit must be mounted away from vibration, impacts, water and corrosive gases.
Cut hole in panel 2.80 x 1.14 inches)
the hole to prevent leakage.
Insert unit into hole of panel. Slide removable fitting clips onto unit from the back until
secure to panel.
Wiring diagram is displayed on the top of the unit
NOTE: DO NOT INSTALL PROBE CABLE NEAR POWER CABLES.
The KLT11 is designed for many heating and cooling applications. It has an input for temperature probe type PTC or NTC The probe temperature is displayed on the bright 3-digit display. The user is able to program 16 different parameters including set point, hysteresis, cycle time and ambient probe adjustment using the silicone front keypad. The KLKey input allows an easy programming of the parameters. The unit features error warning and password protection. Select between red, green or blue display color, temperature display in ºC or ºF and 115Vac, 230Vac, 24Vac/dc or 12Vac/dc power supplies.
The model reference is given by: KLT11 - DWXYZ Where each sufix can take the following values:
== X Display Color R=Red, G=Green, B=Blue Y Supply Voltage 110=115Vac, 230=230Vac
24=24Vac/dc, 12=12Vac/dc
Z Units C=ºC, F=ºF
(selectable by parameter).
Model references
W Output Null 16A(1HP), 2 20A(2HP)
71 x 29 mm (
Technical Data
Supply voltages
115Vac±10%, 230Vac±10%, 24Vac/dc±10%, 12Vac/dc±10%
Supply powers
4VA (230V/115V) 1,5VA(24V /12V)
1% of full scale
0,1º (3 digits)
Display
3-digit and sign (red, green or blue)
Output
1HP Model SPDT Relay Resistive load 16A
1HP 240Vac -- 10FLA, 60LRA 240Vac
2HP Model SPST Relay Resistive load 20A
2HP 240Vac -- 12FLA, 72LRA 240Vac
Dimensions
Front 77 x 36 mm Depth 62 mm (3.03 x 1.42 x 2.44 inch)
Front Protection IP64
Storage temperature
-20ºC to 80ºC (-4 to 176ºF)
Operating temperature
0ºC to 70ºC (32 to 158ºF)
Probe range
PTC -50ºC to 150ºC (-58 to 302ºF) NTC -50ºC to 110ºC (-58 to 230ºF)
Accuracy
Better than
Resolution
Probe Input (Selectable by parameter)
PTC1000 probes (25ºC - 1000 Ohm) / NTC
KLKey Input
For an quick programming of all parameters
Wiring Diagram
1 2
7 8 9 1011
SUPPLY
POWER
Probe input
OUTPUT
NC COM NO
1 2
7 8 9 10
SUPPLY
POWER
Probe input
OUTPUT
NO COM
1HP Model
2HP Model
ELECTRONICAELECTRONICA
ETDT1700I_110207
Electrónica Keld, S.L. Phone: +34 976 429 099 Pol.Ind. Empresarium. C/Lentisco, 15 Fax:+34 976 593 532 50720 - La Cartuja Baja, ZARAGOZA E-mail: keld@keld.es Spain Web: http://www.keld.es
List of p
Degrees 1 to 20 r1 Degrees -58 to r2 r2 Higher value for SP Degrees r1 to 302 d0 Cooling or heating control Option Ht/Co d2 Defrosting duration Minutes 0 to 59 d8 Defrosting interval time Hours 0 to 24 c0 Minimum stopping time Minutes 0 to 59 c1 Cool cycle duration Hours 0 to 24 c2 ON time of fault cycle Minutes 0 to 999 c3 OFF time of fault cycle Minutes 0 to 999 P1 Ambient probe adjustment Degrees -10 to 10 P4 Decimal point Option no/yes H5 Access code to parameters Numeric 0 to 255 H6 Probe type Option Ptc/ntc t0 Maximum displayed temp. Degrees -58 to 302
r1 = r2 = Higher value for SP
Cooling or heating control
d2 = Defrosting duration (if d2=0 no defrosting is performed) d8 = A defrosting cycle is performed every d8 hours (if d8=0
no periodic defrosting is performed)
c0 = Minimum stopping time of the load c1 = Cool cycle duration c2 = ON time of fault cycle, when ambient probe is broken c3 = OFF time of fault cycle, when ambient probe is broken P1= Ambient probe adjustment. If the probe is not placed in
the exact point to control use a standard thermometer to offset the measured temperature. P4= Decimal point only in visualization of the probe. The parameters are always decimal.
H5 = Access code to parameters (it is set to 00 from factory) H6 = Probe Model Ptc or Ntc t0 = Maximum temperature displayed during defrosting and
during the next hour to defrosting.
Parameter programming
arameters
Description Units Range
SP Set Point Degrees r1 to r2 r0
Parameter descriptions
Differential or hysteresis Lower value for SP
SP = Set point. Temperature we wish to regulate the machine (variable from r1 to r2) r0 = Differential or hysteresis
Lower value for SP
d0 = If d0 = Ht and TS is the temperature of ambient probe:
If TS >= SP the load is disconnected If TS <= SP-r0 the load is connected
if d0=Co then:
If TS <= SP the load is disconnected If TS >= SP+r0 the load is connected
Set Point (SP) is the only parameter the user can access without code protection.
•Press SET. SP text will appear on the display.
•Press SET again. The real value is shown on the display.
•The value can be modified with the UP and DOWN arrows.
•Press SET to enter any new values.
•Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit programming mode.
Access to all code protected parameters.
•Press SET for 8 seconds. The access code value 0 is shown on the display (unit comes with code set at 0 from factory).
• With the UP and DOWN arrows, code can be set to user needs.
•Press SET to enter the code. If code correct, the first parameter label is shown on the display (SP).
• Move to the desired parameter with the UP and DOWN Keys.
•Press SET to view the value on the display.
• The value can be modified with the UP and DOWN arrows.
•Press SET to enter the value and exit.
• Repeat until all necessary parameters are modified.
•Press SET and DOWN at the same time to quit programming or wait one minute and the display will automatically exit programming mode.
* The keyboard code can be reset to ZERO by turning off the controller and turning it on again while keeping the SET pressed.
Holding the UP arrow pressed for 8 seconds the defrosting is activated. Repeating this operation the defrosting is stopped. If a cool cycle is activated the defrosting is disabled.
Holding the DOWN arrow pressed for 8 seconds a continuous cool cycle is activated. Repeating this operation the cool cycle is stopped. If defrosting is activated cool cycle is disabled.
The led OUT indicates if the load is connected or not. If a continuos cool cycle is being performed the led flashes (90% ON 10% OFF). If the control is waiting the stopping time c0 to start a cool cycle the led flashes (10% ON 90% OFF). The led DEF indicates if the control is performing defrosting. In normal operation, the probe temperature will be shown on the display. In case of alarm or error, the following messages can be shown:
Er = Memory Error
oo = Open Probe Error
• -- = Short Circuit Probe Error
Clean the surface of the display controller with a soft and damp cloth. Never use abrasive detergents, petrol, alcohol or solvents. All repairs must be made by authorised personnel.
Activating/deactivating defrosting
Activating/deactivating cool cycle
Default working
In case of probe error, the control performs a continuous regulation, c2 minutes load connected - c3 minutes load disconnected. In case of memory error, the control performs a continuous regulation, 5 minutes load connected - 5 minutes load disconnected.
Led indication and display messages
Maintenance, cleaning and repair
After final installation of the unit, no routine maintenance is required.