List of p
Degrees 1 to 20
r1 Degrees -58 to r2
r2 Higher value for SP Degrees r1 to 302
d0 Cooling or heating control Option Ht/Co
d2 Defrosting duration Minutes 0 to 59
d8 Defrosting interval time Hours 0 to 24
c0 Minimum stopping time Minutes 0 to 59
c1 Cool cycle duration Hours 0 to 24
c2 ON time of fault cycle Minutes 0 to 999
c3 OFF time of fault cycle Minutes 0 to 999
P1 Ambient probe adjustment Degrees -10 to 10
P4 Decimal point Option no/yes
H5 Access code to parameters Numeric 0 to 255
H6 Probe type Option Ptc/ntc
t0 Maximum displayed temp. Degrees -58 to 302
r1 =
r2 = Higher value for SP
Cooling or heating control
d2 = Defrosting duration (if d2=0 no defrosting is performed)
d8 = A defrosting cycle is performed every d8 hours (if d8=0
no periodic defrosting is performed)
c0 = Minimum stopping time of the load
c1 = Cool cycle duration
c2 = ON time of fault cycle, when ambient probe is broken
c3 = OFF time of fault cycle, when ambient probe is broken
P1= Ambient probe adjustment. If the probe is not placed in
the exact point to control use a standard thermometer to
offset the measured temperature.
P4= Decimal point only in visualization of the probe.
The parameters are always decimal.
H5 = Access code to parameters (it is set to 00 from factory)
H6 = Probe Model Ptc or Ntc
t0 = Maximum temperature displayed during defrosting and
during the next hour to defrosting.
Parameter programming
arameters
Description Units Range
SP Set Point Degrees r1 to r2
r0
Parameter descriptions
Differential or hysteresis
Lower value for SP
SP = Set point. Temperature we wish to regulate the machine
(variable from r1 to r2)
r0 = Differential or hysteresis
Lower value for SP
d0 =
If d0 = Ht and TS is the temperature of ambient probe:
If TS >= SP the load is disconnected
If TS <= SP-r0 the load is connected
if d0=Co then:
If TS <= SP the load is disconnected
If TS >= SP+r0 the load is connected
Set Point (SP) is the only parameter the user can
access without code protection.
•Press SET. SP text will appear on the display.
•Press SET again. The real value is shown on the display.
•The value can be modified with the UP and DOWN arrows.
•Press SET to enter any new values.
•Press SET and DOWN at the same time to quit
programming or wait one minute and the display will
automatically exit programming mode.
Access to all code protected parameters.
•Press SET for 8 seconds. The access code value 0 is shown
on the display (unit comes with code set at 0 from factory).
• With the UP and DOWN arrows, code can be set to user
needs.
•Press SET to enter the code. If code correct, the first
parameter label is shown on the display (SP).
• Move to the desired parameter with the UP and DOWN
Keys.
•Press SET to view the value on the display.
• The value can be modified with the UP and DOWN arrows.
•Press SET to enter the value and exit.
• Repeat until all necessary parameters are modified.
•Press SET and DOWN at the same time to quit
programming or wait one minute and the display will
automatically exit programming mode.
* The keyboard code can be reset to ZERO by turning off the
controller and turning it on again while keeping the SET
pressed.
Holding the UP arrow pressed for 8 seconds the defrosting is
activated. Repeating this operation the defrosting is
stopped. If a cool cycle is activated the defrosting is disabled.
Holding the DOWN arrow pressed for 8 seconds a
continuous cool cycle is activated. Repeating this operation
the cool cycle is stopped. If defrosting is activated cool cycle
is disabled.
The led OUT indicates if the load is connected or not. If a
continuos cool cycle is being performed the led flashes
(90% ON 10% OFF). If the control is waiting the stopping
time c0 to start a cool cycle the led flashes (10% ON 90%
OFF).
The led DEF indicates if the control is performing defrosting.
In normal operation, the probe temperature will be shown on
the display. In case of alarm or error, the following messages
can be shown:
• Er = Memory Error
• oo = Open Probe Error
• -- = Short Circuit Probe Error
Clean the surface of the display controller with a soft and
damp cloth. Never use abrasive detergents, petrol, alcohol
or solvents.
All repairs must be made by authorised personnel.
Activating/deactivating defrosting
Activating/deactivating cool cycle
Default working
In case of probe error, the control performs a continuous
regulation, c2 minutes load connected - c3 minutes load
disconnected.
In case of memory error, the control performs a continuous
regulation, 5 minutes load connected - 5 minutes load
disconnected.
Led indication and display messages
Maintenance, cleaning and repair
After final installation of the unit, no routine maintenance is
required.