The following pages contain the complete specifications for the 2002.
Every effort has been made to make these specifications complete by characterizing its performance under the variety of conditions often encountered in
production, engineering, and research.
The 2002 provides Transfer, 24-hour, 90-day, 1-year, and 2-year specifications, with full specifications for the 90-day, 1-year, and 2-year intervals. This
allows the operator to utilize 90-day, 1-year, or 2-year recommended calibration intervals, depending upon the level of accuracy desired. As a general rule,
the 2002’s 2-year performance exceeds a 6½-digit DMM’s 90-day, 180-day, or
1-year specifications.
Absolute Accuracy
All DC specifications are given as relative accuracies. To obtain absolute
accuracies, the absolute uncertainties of the calibration sources must be
added to the relative accuracies. The absolute uncertainties for the calibration
sources used during Keithley’s factory calibration are included in the specifications. The uncertainties of the operator’s sources may be different.
All AC specifications are given as absolute accuracies.
Typical Accuracies
Accuracy can be specified as typical or warranted. All specifications
shown are warranted unless specifically noted. Almost 99% of the 2002’s
specifications are warranted specifications. In some cases it is not possible to
obtain sources to maintain traceability on the performance of every unit in
production on some measurements (e.g., high-voltage, high-frequency signal
sources with sufficient accuracy do not exist). These values are listed as
typical.
±(ppm of reading+ppm of range+ppm of range rms noise
Accuracy
1,5
10
)
11
PLC = Power Line Cycles. DFILT = Digital Filter.
Noise Rejection (dB)
SpeedAC and DC CMRR
(Number ofLine Sync On
Power LineLine Sync Internal25 ReadingsOn
Cycles)On
PLC ≥ 1140120908060
PLC < 1906060500
Effective noise is reduced by a factor of 10 for every 20dB of noise rejection (140dB reduces
effective noise by 10,000,000:1).
CMRR is rejection of undesirable AC or DC signal between LO and earth. NMRR is rejection of
undesirable power line related AC signal between HI and LO.
DCV Reading Rates
PLCApertureBits DigitsAutozero Off Autozero OnAutozero Off Autozero OnAutozero Off Autozero On
MeasurementDefaultReadings/Second to Memory Readings/Second to IEEE-488
Factory calibration uncertainty represents traceability to
NIST. This uncertainty is added to relative accuracy
specifications to obtain absolute accuracies. The 200mV and
2V range uncertainties are equal to the uncertainty of the 2V
calibration source. The 20V, 200V, and 1000V range
uncertainties are equal to the uncertainty of the 20V
calibration source.
1000 V2.6
Readings/Second with
15
Time Stamp to IEEE-488
15
SBG 12/20/00
Rev. F
Sheet 2 of 12
2002 Multimeter
DC Volts (cont’d)
Linearity<0.1ppm of range typical,
Zero StabilityTypical maximum variation
200 mV
200 V± 5 counts± 2 counts
1000 V± 2 counts± 1 count
<0.2ppm maximum.
in 1 hour, T
digit resolution, 10-reading
digital filter, synchronous
autozero.
Range1 PLC10 PLC
4
± 60 counts± 40 counts
4
2V
± 6 counts± 4 counts
20 V± 4 counts± 1 count
REF± 0.5°C, 7½-
Polarity Reversal ErrorThis is the portion of the instrument error that is seen when
HI and LO are reversed. This is not an additional error—it is
included in the overall instrument accuracy specification.
Reversal Error: <4 counts at 10V input at 7½ digits, 10 power
line cycles, synchronous autozero, 10-reading repeat digital
filter.
Input Bias Current<100pA at 25°C.
Settling Characteristics<50µs to 10ppm of step size for the 200mV–20V ranges. <1ms
to 10ppm of step size for the 200V and 1000V ranges. Reading
settling times are affected by source impedance and cable
dielectric absorption characteristics.
AutorangingAutoranges up at 105% of range, down at 10% of range.
DC Volts Notes
1 Specifications are for 10 power line cycles, synchronous
autozero, 10-reading repeat digital filter, autorange off,
except as noted.
2 For T
CAL±1°C, following 4-hour warm-up. TCAL is ambient
temperature at calibration (23°C at the factory). Add 0.5
ppm of reading uncertainty if the unit is power cycled
during this interval.
3 For T
CAL±5°C, following 4-hour warm-up.
4 Care must be taken to minimize thermal offsets due to
operator cables.
CAL±5°C, normal autozero. 1-year or 2-year accuracy
5 For T
can be found by applying the same speed accuracy ppm
changes to the 1-year or 2-year base accuracy.
6 Applies for 1kΩ imbalance in the LO lead. For 400Hz
operation, subtract 10dB. For the 200V and 1000V ranges,
subtract 20dB.
7 For noise synchronous to the line frequency.
8 For line frequency ±0.1%.
9 For on-scale readings, no trigger delays, internal trigger,
digital filter off, normal autozero, display off, SREAL
format. These rates are for 60Hz and (50Hz). Rates for
400Hz equal those for 50Hz.
10 Typical values. Peak-to-peak noise equals 6 times rms
noise.
11 In burst mode, display off. Burst mode requires autozero
refresh (by changing resolution or measurement function)
once every 24 hours.
12 Specifications apply for 20-reading repeat digital filter,
T
REF± 0.5°C (TREF is the initial ambient temperature), and
for measurements within 10% of the initial measurement
value and within 10 minutes of the initial measurement
time.
13 Add 20ppm × (V
inputs above 200V, except in transfer accuracy
specifications.
14 Specifications are for 1 power line cycle, normal autozero,
positive peak spikes and highest spike since reset. Second
option presents negative spikes and lowest spike. Highest
and lowest spike can be reset by pressing DCV function button.
Third option displays the maximum and minimum levels of
the input signal. Spikes displays are also available through
CONFIG-ACV-ACTYPE as primary displays.
1 Specifications apply for 10-reading digital filter. If no
filter is used, add 0.25% of range typical uncertainty.
2 Typical values.
3 Add 0.001% of reading ×(V
for inputs above 100V.
4 Specifications assume AC+DC coupling for frequencies
below 200Hz. Below 20Hz add 0.1% of reading additional
uncertainty.
2
IN/100V)
additional uncertainty
0.004+0.03
0.01 +0.02
SBG 12/20/00
Rev. F
Sheet 3 of 12
2002 Multimeter
AC Volts
AC magnitude: rms or Average. Peak and Crest Factor measurements also available.
ACV Input Characteristics
rmsPeakFull Scale±(% of reading + % of range) / °C
RangeInputrmsResolutionInput ImpedanceOutside T
200 mV1 V210.0000100 nV1MΩ ±2% with <140pF0.004 + 0.001
2 V8 V2.1000001 µV1MΩ ±2% with <140pF0.004 + 0.001
20 V100 V21.0000010 µV1MΩ ±2% with <140pF0.006 + 0.001
200 V800 V210.0000100 µV1MΩ ±2% with <140pF0.006 + 0.001
750 V1100 V775.0001 mV1MΩ ±2% with <140pF0.012 + 0.001
AC Voltage Uncertainty= ±[ (% of reading) × (measured value) + (% of range ) × (range used) ] / 100.
PPM Accuracy= (% accuracy) × 10,000.
0.015% of Range= 30 counts for ranges up to 200V and 113 counts on 750V range at 5½ digits.
dB Accuracy rms±dB, 90 Days, 1 Year or 2 Years, TCAL±5°C, Reference=1V, Autoranging, Low Frequency Mode, AC+DC Coupling
–54 to–40 dB (2 mV to 10 mV)0.2300.2250.2360.355
–40 to–34 dB (10 mV to 20 mV)0.0360.0310.0410.088
–34 to 6 dB (20 mV to 2 V)0.0230.0180.0280.0660.2650.630
6 to 26 dB (2 V to 20 V)0.0240.0240.0280.0660.5380.820
26 to 46 dB (20 V to 200 V)0.0240.0240.0280.066
46 to 57.8 dB (200 V to 775 V)0.0180.0210.049
Normal Mode (rms, average)——0.410.070.015
Low Frequency Mode (rms)0.10.01000
For low frequency mode below 200Hz, specifications apply for sine wave inputs only.
AC+DC Coupling
Range% of Reading% of Range
200mV, 20V0.050.1
2V, 200V, 750V0.070.01
For AC only coupling, add the following % of reading:
1–10Hz 10–20Hz 20–50Hz 50–100Hz 100–200Hz
For DC >20% of AC rms voltage, apply the following additional
uncertainty, multiplied by the ratio (DC/total rms). Applies to
rms and average measurements.
Average ACV Measurement
Normal mode rms specifications apply from 10% to 100% of
range, for 20Hz–1MHz. Add 0.025% of range uncertainty for
50kHz–100kHz, 0.05% of range uncertainty for 100kHz–
200kHz, and 0.5% of range uncertainty for 200kHz–1MHz.
ACV Peak Value Measurement
20Hz–1kHz–10kHz–30kHz– 50kHz–100kHz–300kHz– 500kHz– 750kHz–% of range)/
Settling CharacteristicsNormal Mode (rms, avg.)<300ms to 1% of step change
Common Mode RejectionFor 1kΩ imbalance in either lead: >60dB for line frequency ±0.1%.
Maximum Volt·Hz Product2 × 10
1 Specifications apply for sinewave input, AC + DC coupling,
1 power line cycle, autozero on, digital filter off, following
55-minute warm-up.
2 Temperature coefficient applies to rms and average
readings. For frequencies above 100kHz, add 0.01% of
reading/°C to temperature coefficient.
3 For 1% to 5% of range below 750V range, and for 1% to 7%
of 750V range, add 0.01% of range uncertainty. For inputs
from 200kHz to 2MHz, specifications apply above 10% of
range.
4 Add 0.001% of reading ×(V
above 100V rms.
5 Typical values.
6 For on-scale readings, no trigger delays, internal trigger,
digital filter off, normal autozero, display off, SREAL
format. These rates are for 60Hz and (50Hz). Rates for
Resolution4 digits.
Non-Repetitive Peak10% of range per µs typical slew rate for single spikes.
Peak WidthSpecifications apply for all peaks ≥1µs.
Maximum Input±1100V peak, 2×10
AutorangingAutoranges up at 105% of range, down at 10% of range.
High Crest Factor Additional Error ±(% of reading)
Applies to rms measurements.
Low Frequency Mode (rms) <5s to 0.1% of final value
IN/100V)
Crest Factor1 – 22 – 33 – 44 – 5
Additional Error00.10.20.4
5
7
V·Hz (for inputs above 20V).
<450ms to 0.1% of step change
<500ms to 0.01% of step change
7
V·Hz (for inputs above 20V).
400Hz equal those for 50Hz. Applies for normal rms and
average mode. Low frequency rms mode rate is typically
0.2 readings per second.
7 For overrange readings 200–300% of range, add 0.1% of
reading uncertainty. For 300–400% of range, add 0.2% of
reading uncertainty.
8 In burst mode, display off. Burst mode requires autozero
refresh (by changing resolution or measurement function)
once every 24 hours.
2
additional uncertainty
9 AC peak specifications assume AC + DC coupling for fre-
quencies below 200Hz.
10 Specifications apply for 10-reading digital filter. If no
filter is used, add 0.25% of range typical uncertainty.
11 Subject to peak input voltage specification.
12 Using Internal Buffer.
Temperature Coefficient
±(% of reading +
5
0.004 + 0.03
0.01 + 0.02
°C
SBG 12/20/00
Rev. F
Sheet 5 of 12
2002 Multimeter
Ohms
Two-Wire and Four-Wire Ohms
RangeScaleResolutionSource
20 Ω21.0000000100 nΩ7.2 mA 5 V50Ω10Ω±0.2 V
200 Ω210.0000001 µΩ960µA 5 V200Ω100 Ω±0.2 V
2kΩ2100.0000010 µΩ960µA 5 V200Ω150Ω–0.2 V to +2 V
20 kΩ21.0000000100 µΩ96µA 5 V1.5 kΩ1.5 kΩ–0.2 V to +2 V
200 kΩ210.0000001 mΩ9.6 µA 5 V1.5 kΩ1.5 kΩ
2MΩ2.1000000010 mΩ1.9 µA 6 V1.5 kΩ1.5 kΩ
4
20 MΩ
4
200 MΩ
4
1GΩ
FullCurrentOpenHI LeadLO LeadOffset
21.0000000100 mΩ1.4 µA
210.0000001 Ω1.4 µA
1.0500000010 Ω1.4 µA
1
Circuit12Resistance
13
14 V
13
14 V
13
14 V
MaximumMaximumMaximum
2
Resistance
2
Compensation
3
Keithley Factory Calibration Uncertainty
Enhanced Accuracy5 10PLC, Offset comp. on, DFILT 10
Rangeppm of reading
20 Ω29.5
200 Ω7.7
2kΩ6.4
20 kΩ7.8
200 kΩ7.3
2MΩ14.9
20MΩ14.9
200MΩ14.9
1GΩ14.9
Factory calibration uncertainty represents traceability to
NIST. This uncertainty is added to relative accuracy
specifications to obtain absolute accuracies.
The 20Ω - 2MΩ range uncertainties are equal to the uncertainty
of the respective calibration sources.
The 20MΩ, 200MΩ, and 1GΩ range uncertainties are equal to
the uncertainty of the 2MΩ calibration source.
MeasurementDefaultReadings/Second to Memory Readings/Second to IEEE-488
167 µs (167 µs)194½2000 (2000)2000 (2000)
Readings/Second with
9
Time Stamp to IEEE-488
9
Speed and Accuracy90 Days
±(ppm of reading+ppm of range+ppm of range rms noise
1PLC
Range10 ReadingsDFILT OffDFILT OffDFILT Off
200 µA275+25+0275+25+0.5300+25+50300+200+80
2 mA275+20+0275+20+0.5300+20+50300+200+80
20 mA275+20+0275+20+0.5300+20+50300+200+80
200 mA300+20+0300+20+0.5325+20+50325+200+80
2 A600+20+0600+20+0.5625+20+50625+200+80
PLC = Power Line Cycles. DFILT = Digital Filter.
Settling Characteristics<500µs to 50ppm of step
Maximum Allowable Input2.1A, 250V.
Overload Protection2A fuse (250V), accessible
DFILT On,1PLC0.1PLC0.01PLC
size. Reading settling times
are affected by source
impedance and cable
dielectric absorption
characteristics.
from front (for front input)
AutorangingAutoranges up at 105% of
and rear (for rear input).
range, down at 10% of
range.
ACCURACY
1,8
DC Amps Notes
1 Specifications are for 1 power line cycle, autozero on, 10-reading repeat digital filter.
CAL± 1°C, following 55-minute warm-up. TCAL is ambient temperature at calibration
2 For T
(23°C at the factory).
3 For T
CAL± 5°C, following 55-minute warm-up.
4 Typical values. Peak-to-peak noise equals 6 times rms noise.
5 For on-scale readings, no trigger delays, internal trigger, digital filter off, normal autozero,
display off, SREAL format. These rates are for 60Hz and (50Hz). Rates for 400Hz equal those
for 50Hz.
6 Actual maximum burden voltage = (maximum burden voltage) × (I
7 In burst mode, display off. Burst mode requires autozero refresh (by changing resolution
or measurement function) once every 24 hours.
CAL±5°C, normal autozero. 1-year and 2-year accuracy can be found by applying the
8 For T
same speed accuracy ppm changes to the 1-year or 2-year base accuracy.
9 Using Internal Buffer.
DC In-Circuit Current
Measurement Range Chart
10Ω
1Ω
100mΩ
Specified
Measurement Range
10mΩ
1mΩ
Trace Resistance
1mA 10mA 100mA 1A10A 100A100µA
Measured Current
The DC in-circuit current measurement function allows a user to measure the current through
a wire or a circuit board trace without breaking the circuit.
When the In-Circuit Current Measurement function is selected, the 2002 will first perform a 4wire resistance measurement, then a voltage measurement, and will display the calculated
current.
TYPICAL RANGES
Trace Resistance1mΩ to 10Ω.
Keithley Factory Calibration Uncertainty
4
)
7
Factory calibration uncertainty represents traceability to
NIST. This uncertainty is added to relative accuracy
specifications to obtain absolute accuracies. The
uncertainties for each range are equal to the uncertainty of
the respective calibration sources.
Current100µA to 12A.
Voltage±200mV max. across trace.
Speed4 measurements/second at 1 power line cycle.
Accuracy±(5% + 500µA). For 1 power line cycle, autozero on, 10-
For AC only coupling, add the following % of reading:
rms, Average0.550.090.015
20–50Hz50–100Hz 100–200Hz
AC+DC Coupling
For DC>20% of AC rms voltage, apply the following additional
uncertainty, multiplied by the ratio (DC/total rms).
rms, Average0.050.1
% of Reading% of Range
AC Amps Notes
1 Specifications apply for sinewave input, AC+DC coupling, 1
power line cycle, autozero on, digital filter off, following 55minute warm-up.
2 Add 0.005% of range uncertainty for current above 0.5A
rms for self-heating.
3 Typical values.
4 For on-scale readings, no trigger delays, digital filter off,
normal autozero, display off, internal trigger, SREAL
High Crest Factor Additional Error ±(% of reading)
Applies to rms measurements.
Crest Factor1 – 2 2 – 3 3 – 4 4 – 5
Additional Error00.10.20.4
Average ACI Measurement
rms specifications apply for 10% to 100% of range.
Settling<300ms to 1% of step change
Characteristics
Autoranging Autoranges up at 105% of range,
format. These rates are for 60Hz and (50Hz). Rates for
400Hz equal those for 50Hz.
5 Actual maximum burden voltage = (maximum burden
voltage) × (I
6 In burst mode, display off. Burst mode requires autozero
refresh (by changing resolution or measurement function)
once every 24 hours.
7 Using Internal Buffer.
MEASURED/IFULL SCALE).
<450ms to 0.1% of step change
<500ms to 0.01% of step change
down at 10% of range.
SBG 12/20/00
Rev. F
Sheet 9 of 12
2002 Multimeter
Frequency Counter
Frequency/Period Input Characteristics and Accuracy90 Days, 1 Year, or 2 Years
FrequencyPeriodMinimum Signal Level
1
AC Voltage Input1Hz–15 MHz67 ns – 1 s5 digits60 mV60 mV350 mV1100 V pk
AC Current Input 1Hz– 1 MHz1 µs – 1 s5 digits150 µA 1 A pk0–600mA0.03
Voltage Input Impedance1MΩ ± 2% with <140pF.
Trigger Level AdjustmentTrigger level is adjustable in 0.5% of range steps to ±60% of
Reading Time420ms maximum.
Frequency RangingAutoranging from Hz to MHz.
Frequency CouplingAC + DC or AC only.
Range
Time Base7.68MHz ± 0.01%, 0°C to 55°C.
RangeResolution1Hz–1MHz 1–5MHz 5–15MHzInputLevel±(% of reading)
range in real-time using the up and down range buttons.
Temperature (RTD)
RangeResolution24 Hours290 Days31 Year32 Years
–100° to +100°C0.001°C±0.016°C±0.020°C ±0.021°C ±0.022°C
–200° to +630°C0.001°C±0.061°C±0.066°C ±0.068°C ±0.070°C
–148° to +212°F0.001°F±0.029°F±0.036°F ±0.038°F ±0.040°F
–328° to +1166°F0.001°F±0.110°F±0.119°F ±0.122°F ±0.126°F
RTD Type100Ω platinum, DIN 43760, 4-wire. ITS-90 (PT100, D100, F100)
Sensor Current960µA (pulsed).
Temperature Coefficient± 0.001°C/°C or ± 0.002°F/°C outside T
Maximum Source
HI Lead Resistance200Ω.
Maximum Source
LO Lead Resistance100Ω.
and IPTS-68 (PT385, PT3916).
4-Wire Accuracy
5
CAL±5°C.
3
2
MaximumTrigger Accuracy
1
0–600V0.03
Frequency Notes
1 Subject to 2 × 107V·Hz product (for inputs above 20V).
2 Valid for the lowest range. For each range increase,
multiply these numbers by 10.
RTD Temperature Reading Rates 1 (2- or 4-Wire)
Readings or Readings with
Time Stamp/Second
PLC Autozero OffAutozero On
103 (2.5)1 (0.8)
212 (10)4 (3.3)
120 (16)17 (13)
0.151 (49)41 (39)
0.0158 (58)46 (46)
to Memory or IEEE-488
Temperature (Thermocouple)
Thermo-
couple
TypeRangeResolutionAccuracy
J–200° to + 760°C0.001°C±0.5°C
K–200° to +1372°C0.001°C±0.5°C
T–200° to + 400°C0.001°C±0.5°C
E–200° to +1000°C0.001°C±0.6°C
R0° to +1768°C0.001°C±3 °C
S0° to +1768°C0.001°C±3 °C
B+350° to +1820°C0.001°C±5 °C
Temperature Notes
1 For on-scale readings, no trigger delays, digital filter off,
display off, normal autozero, internal trigger, SREAL
format. These rates are for 60Hz and (50Hz). Rates for
400Hz equal those for 50Hz. Typical values.
2 For T
CAL± 1°C, following 4-hour warm-up.
CAL± 5°C, following 4-hour warm-up.
Ratio or Delta
(2 channels)8.2 ms1228.5 ms 118 18.8 ms53
Fast Scan
(using solid state
channels)8.2 ms1226.3 ms 159501 ms2559 ms1.812.8 ms78
Normal Scan14 ms7111.4 ms 88 14.4 ms69506 ms2564 ms1.817.2 ms5843 ms23
per (Chan./per (Chan./per (Chan./ per (Chan./per(Chan./per(Chan./per(Chan./
4
Operating Speed Notes
2WΩ4WΩRTD Temp
Ω)(2kΩ)ACVFreqTC Temp (2-Wire)
1 For display off, 0.01 power line cycles, autorange off,
digital filter off, autozero on, offset compensation off.
Display on may impact time by 3% worst case. To
eliminate this impact, press ENTER (hold) to freeze
display.
2 Using 386/33 computer, average time for 1000 readings,
byte order swapped, display off.
3 For on-scale readings, no trigger delays, display off, 0.01
power line cycles, autorange off, digital filter off, offset
compensation off, autozero off.
4 Ratio and delta functions output one value for each pair
of measurements.
5 Based on 100kHz input frequency.
SBG 12/20/00
Sheet 11 of 12
Rev. F
2002 Multimeter
Maximum Input Levels
RatedRecovery
1
Input
HI to LO±1100V< 900 ms
HI Sense to LO± 350V pk 250V rms < 900 ms
LO Sense to LO± 150V pk 100V rms < 900 ms
I Input to LO 2A, ± 250V(fused) —
HI to Earth±1600V< 900 ms
LO to Earth± 500V
Note 1: For voltages between other terminals, these ratings
can be added.
Overload
Time
IEEE-488 Bus Implementation
ImplementationIEEE-488.2, SCPI-1991.0.
Multiline CommandsDCL, LLO, SDC, GET, GTL,
Uniline CommandsIFC, REN, EOI, SRQ, ATN.
Interface CommandsSH1, AH1, T5, TE0, L4, LE0,
UNT, UNL, SPE, SPD.
SR1, RL1, PP0, DC1, DT1, C0,
E1.
Digital I/O
Connector Type8 pin “D” subminiature.
InputOne pin, TTL compatible.
OutputsFour pins. Open collector,
ControlDirect control by output or
30V maximum pull-up
voltage, 100mA maximum
sink current, 10Ω output
impedance.
set real-time with limits.
Delay and Timer
Time StampResolution: 1µs.
Delay Time(Trigger edge to reading initiation)
Accuracy: ±0.01% of elapsed time ± 1µs.
Maximum: 2,100,000.000000 seconds (24 days, 7 hours).
PowerVoltage: 90–134V and 180–250V, universal self-selecting.
Frequency: 50Hz, 60Hz, or 400Hz, self-identifying at power-
up.
EnvironmentalOperating Temperature: 0°C to 50°C.
CalibrationType: Software. No manual adjustments required.
ProcessMIL-STD 45662A.
PhysicalCase Dimensions: 90mm high × 214mm wide × 369mm deep
StandardsEMI/RFI: Conforms to VDE 0871B (per Vfg 1046/1984), IEC
Accessories SuppliedThe unit is shipped with line cord, high performance modular
Consumption: <55VA.
Storage Temperature: –40°C to 70°C.
Humidity: 80% R.H., 0°C to 35°C, per MIL-T-28800E
4.5.5.1.2.
Sources: 2 DC voltages, 6 resistances, and 5 DC currents. All
other functions calibrated (adjusted) from these sources and
a short circuit. No AC calibrator required for adjustment.
Average Time to Perform: 40 minutes for comprehensive
calibration, 6 minutes for AC-only calibration.
(3½ in. × 8½ in. × 14½ in.).
Working Dimensions: From front of case to rear including
power cord and IEEE-488 connector: 15.0 inches.
Net Weight: <4.2kg (<9.2 lbs.).
Shipping Weight: <9.1kg (<20 lbs.).
801-2. Meets FCC part 15 Class B, CISPR-22 (EN55022).
Safety: Conforms to IEC348, CAN/CSA-C22.2. No. 231, MIL-
1
T-28800E
. Designed to UL1244.
test leads, operator’s manual, option slot cover, and full
calibration data.
1
Para
Note 1For MIL-T-28800E, applies to Type III, Class 5, Style E.