Keiki MRG-10 User Manual

Document No.: KF05-001G
MRG-10
User’s Guide
User’s GuideUser’s Guide
User’s Guide
( i )
Safety Cautions
The caution message shown in the User’s Guide is defined as follows:
!!!!
CAUTION
Indicates that incorrect usage may result in death or serious injury to the operator.
!!!!
CAUTION
Indicates that incorrect usage may result in injury to the operator or damage to the equipment
.
Warning
Caution
Warning label
Warning label
WARNING
!
Don't open lower nut if tank is pressurised or contains hazardaous product.
( ii )
Introduction
This User’s Guide includes detailed explanations of MRG-10 safety cautions, installation, configuration, and troubleshooting. Users should carefully read this manual before operation to ensure an adequate understanding of the equipment.
Proper use of the User’s Guide
The following points must be observed:
(1) Carefully read the User’s Guide
The contents of the User’s Guide are very important. Carefully read the entire
manual.
(2) Store the User’s Guide in safe location.
The User’s Guide is very important for the operation of the equipment. Store the manual in a safe and accessible location. The storage location and person responsible for maintaining the Guide should be considered carefully.
(3) Ensure that the User’s Guide is supplied to the operator of the equipment.
The representative or dealer of this equipment must supply this User’s Guide to the user who will actually operate the equipment.
(4) The User’s Guide should be replaced if it is lost.
If the User’s Guide is lost, contact the representative listed on the back cover. A new manual may be purchased.
Restrictions and cautions necessary to maintain the equipment
The following items must be observed to ensure that the equipment is maintained properly. Refer to the pages corresponding to each topic for details. The corresponding pages are shown in ( ) brackets.
(1) Do not drop unit or subject unit to impact. (2) Use the unit in appropriate temperature environments. (Refer: p.6-2 Operating condition) (3) Use the unit under appropriate process temperature and pressure. (Refer: p.6-2 Operating condition) (4) Always use an appropriate power supply. (Refer: p.6-1 Power Supply voltage) (5) Do not loosen union nut when tank is pressured. (Refer: p.2-5 Mounting the cone antenna)
( iii )
Contents
About this manual
1.Product Description 1-1
1.1 Features 1-1
1.2 Measuring principle 1-1
1.3 MRG-10 measuring system 1-2
2.Mechanical Installation 2-1
2.1 Requirements 2-1
2.2 Dimensions 2-4
2.3 Tools 2-5
2.4 Mounting Cone Antenna 2-6
2.5 Mounting Rod Antenna 2-8
2.6 Installation Hints 2-10
3.Electrical Installation 3-1
3.1 Connection of MRG-10 3-1
3.2 Cables 3-2
3.3 Load 3-2
3.4 Power Supply 3-2
3.5 Grounding 3-2
3.6 Arrester replacement 3-3
4.Configuration method 4-1
4.1 Display Panel & Key SW 4-1
5.Configuration 5-1
5.1 Basic Settings 5-1
5.2 Negative level point measurement 5-3
5.3 Avoiding Disturbance Echoes 5-3
5.4 Volume calculation 5-7
5.5 Analog value compensation 5-8
5.6 Measuring value compensation 5-8
5.7 Bottom recognition 5-9
5.8 Other 5-9
5.9 Pipe antenna setting 5-9
5.10 Key Parameter List 5-11
6.Technical Information 6-1
7.Troubleshooting 7-1
Appendix
Control Drawing for ATEX
Safety Manual
( iv )
About this manual
This User’s Guide provides information about mechanical and electrical
installation of the MRG-10. It also describes how to configure the unit.
The main purpose of the book is to serve as a guide to installing and operating the MRG-10. It is not intended to cover service tasks such as changing circuit boards or internal software.
Chapter 1 reviews some basic concepts of radar based level gauging.
Chapter 2 describes how to assemble a gauge and how to mount it onto a tank.
Chapter 3 describes electrical installation.
Chapter 4 describes configuration method by key SW.
Chapter 5 describes how to configure for tank conditions.
Chapter 6 provides technical information.
Chapter 7 lists some typical problems that might occur and suggestions on how
to solve them.
MRG
MRGMRG
MRG----10
1010
10
Product Description
Product DescriptionProduct Description
Product Description
1-1
1 1 Product Description
The MRG-10 is a loop-powered radar level gauge, which can be installed easily in a variety of applications. The MRG-10 employs a non-contact radar level gauging principle based on pulsed microwave signals and is suitable for level measurement in applications such as liquids, pastes and slurries.
MRG-10 uses 5.8GHz low power pulsed microwave. It provides good measurement stability, because propagation of microwaves is not affected by temperature, pressure or gas conditions in tank.
1.1 Features
MRG-10
MRG-10 needs only a two-wire cable for power supply and output signal.
Communication
MRG-10 incorporates HART
®
protocol function which superimposes a digital output signal on the
4-20mA current output signal. Settings can be made by a HART
®
communicator or PC-based setup
software.
Volume calculation function
Volume calculation function is based level measurement of the remaining liquid in the tank and the formula takes into consideration three tank configurations - spherical, vertical cylinder and horizontal cylinder. There is also an applicable user-defined 20-step table.
1.2 Measuring principle
The MRG-10 level gauge utilizes the time-of-flight measurement principle involving short microwave pulses. Installed at the top of tanks, it emits short microwave pulses toward liquids or pastes in the tank. Reflected microwave signals from the surface are received by the antenna, and processed by electronics. The time from transmission to reception is determined by the microprocessor and converted as distance from the transmitter to the liquid surface (ullage) with output of the calculated level from the measured ullage (Level = Tank Height – Ullage).
Ullage
Level
Liquid Surface
Bottom
Tank
Height
MRG
MRGMRG
MRG----10
1010
10
Product Description
Product DescriptionProduct Description
Product Description
1-2
1.3 MRG-10 measuring system
MRG-10 can be configured with its onboard 4 key switches, a handheld terminal or remotely from a personal computer via a modem.
The MRG-10 is connected to a PLC or power supply unit.
Example Connection from power supply unit to MRG-10 mounted in non-hazardous area
HART
modem
MRG-10
Voltage
source
Load
>250
4...20mA
2
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-1
2 Mechanical Installation
2.1 Requirements
2.1.1 Cone antenna
Mounting position
Do not mount the transmitter at the center of the tank or close to the tank wall as this may reduce the measuring range or accuracy and make the transmitter more sensitive to echo disturbances. We recommend that the transmitter be mounted so that the antenna tip is located at least 0.6 m from the tank wall.
Socket requirements
The antenna tip should extend past the nozzle (10 mm or more).
If the antenna tip is located inside the nozzle, echo disturbances may be generated which will negatively affect measurement performance.
Free space requirements
The transmitter should be mounted so that no obstacles are present in the radar beam.
Obstacles in the radar beam may reduce the measuring range.
Half Power Beam Width.
Diameter of radiated area (m).
Antenna
Tip
Half-power
beam width
10mm
or more
600mm or more
Antenna Type
Half Power Beam Width
(Degrees)
4” cone 34
6” cone 22
8” cone 17
Rod 30
Distance
5m
10m
15m
20m
Antenna Type
Distance[m]
4”cone 6”cone 8”cone Rod
5m 2.9 1.9 1.5 2.7
10m 5.8 3.8 3.0 5.4
15m 8.8 5.7 4.4 8.0
20m 11.7 7.6 5.9 10.7
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-2
2.1.2 Rod antenna
Mounting position
Do not mount the transmitter at the center of the tank or too close to the tank wall as this may reduce the measuring range or accuracy and make the transmitter more sensitive to echo disturbances. We recommend that the transmitter be mounted so that the antenna tip is located at least 0.6m from the tank wall.
Socket requirements
There are 2 inactive zone lengths (100mm and 250mm). Noise reflections from the nozzle are avoided in these zones. Nozzle height must be less than the antenna extension.
Free space requirements
The transmitter should be mounted so that no obstacles are present in the radar beam. Obstacles in the radar beam may reduce the measuring range.
2.1.3 Key factors for measurement
1. The strength of the microwave reflection from the liquid surface is proportional to the dielectric constant Er (Epsilon) of the target fluid. The higher the fluid’s dielectric constant, the wider the measurable range.
2. A larger antenna enables more stable measurement and a wider measuring range.
3. Compared to calm fluid surfaces, measuring ranges of turbulent surfaces are reduced due to poorer reflection.
4. Deposit buildup on the antenna, foaming on liquid surfaces, powder granules in air suspension and other interior tank conditions may affect measuring range and performance.
5. Obstructions in the microwave radiating area or target fluid surface areas less than the radiating area will reduce microwave reflection and decrease and narrow the measurable range.
Inactive Zone
NPT 1 1/2
Height of nozzle
10mm or more
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-3
Maximum measuring distance
Maximum measurement distance is determined by antenna type, dielectric constant of the product and product surface conditions. Please refer to the table below. These values are rough estimates, and are strongly influenced by the measuring conditions.
Calm surface
4"Cone 6"Cone 8"Cone
0
10
20
0
10
20
0
10
20
0
10
20
a b c a b c a b c
(m)
Rod
a b c
Turbulent surface
4"Cone 6"Cone 8"Cone
0
10
20
0
10
20
0
10
20
0
10
20
a b c a b c a b c
(m)
Rod
a b c
a) Dielectric constant 1.9 - 4.0 Oil, gasoline and other hydrocarbons,
petrochemicals
b) Dielectric constant 4.0 - 10 Alcohol, concentrated acids, and organic
solvents
c) Dielectric constant >10 Water
-based liquids, dilute acids and acetone
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-4
514
* 250
176
226
148
NPT 1 1/2
176
226
148
NPT 1 1/2
364
*100
148
φ38
Rod Short
Rod Long* : Extended Part
148
238
176
106
226
346
φ215
φ265
φ188
φ140
φ92
φ154
φ52
4" Cone Antenna
6" Cone Antenna
8" Cone Antenna
2.2 Dimensions
Weights
MRG-10(except antenna) 2.5 kg
4” Cone antenna 0.8 kg
6” Cone antenna 1.2 kg
8” Cone antenna 1.8 kg
MRG-10 with rod antenna short 3.4 kg
MRG-10 with rod antenna long 3.7 kg
*: Part extension
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-5
Flange
The MRG-10 gauge is mounted with a flange of the following specifications
:
Cone antenna Rod antenna
Maximum thickness : 29mm (ANSI Class-150 8” ).
2.3 Tools
The following tools are needed for installation of MRG-10:
• Hexagon socket screw keys(-4)
• Adjustable wrench (for locking nut)
• Pipe wrench (for neck of cone antenna)
• Screwdriver (-) width 3mm
NPT 1 ½ Threaded
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-6
2.4 Mounting the cone antenna
!!!!
Warning
Do not damage the PTFE seal and O-ring during mounting. Damaged seals may cause gas leakage when the MRG-10 is installed on pressurized tanks.
1. Check and confirm the parts described below which are required for installation of the cone antenna.
2. Mount the flange on top of the cone plate. Secure the flange with the locking nut.
Make sure that the nut is fitted tightly to the flange.
!!!!
Warning
Make sure that the bottom side of the flange is flat and all parts are clean and dry as problems related to this may result in gas leakage when the MRG-10 is installed on pressurized tanks.
Transmitter
Locking Nut
Cone Antenna
O-ring
Seal
Union Nut
Set Screw(M4)
Flange
Nuts & Bolts
Gasket
65
φ59
Locking Nut
Flange
Cone Antenna
Note! No gasket on top of this plate.
Cone Plate
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-7
Transmitter
Union Nut
Set Screw
O-ring
Sleeve
Antenna Adapter
!!!!
Warning
Make sure that the O-ring inside of the sleeve is clean as improper sealing may lead to gas leakage problems when the MRG-10 is installed on pressurized tanks.
3. Carefully insert the antenna adapter of the transmitter into the sleeve. Secure the antenna adapter with the union nut. Make sure that the antenna adapter fits inside of the cone antenna. Secure the union nut with the set screw.
4. Place the gasket on the tank nozzle. Carefully fit the flange and the cone antenna on the tank nozzle. Tighten the assembly with the screws and nuts.
!!!!
Warning
Do not loosen the union nut when the tank is pressurized.
Gasket
Tank Nozzle
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-8
2.5 Mounting rod antenna
!!!!
Warning
Do not damage antenna. Damaged antenna may cause gas leakage if the MRG-10 is installed on a pressurized tank.
NPT 1 1/2
Flange (NPT 1 1/2
Gasket
Nuts & Bolts
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-9
Fix rod antenna to flange
Place the gasket on the tank nozzle. Carefully fit the flange and the cone antenna on the tank nozzle. Tighten the assembly with the screws and nuts.
NPT 1 1/2
Flange
NPT 1 1/2
Nuts & Bolts
Gasket
Tank nozzle
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-10
2.6 Installation Hints
Obstacles in the radar beam may generate signal reflections (false echoes) which may be larger than the reflected signals from the surface of the liquid. The MRG-10 may erroneously interpret such false echoes as reflections from the liquid surface. To reduce the influence of false echoes, attenuate such signals using the following methods.
1. Thin pipe or ladder
Microwave reflections from elongated metal objects such as thin pipes or ladders rungs are largest when the axis of such objects are in parallel with the electric field. The orientation of the electric field generated by the MRG-10 is as shown in the right figure. Mount the MRG-10 so that the electric field is not in parallel with the axis of the obstacle which reduces the affect of the false echo emitted by it.
Ladder rungs Ladder rungs
Pipe
Pipe
EEEE
A-plane
A-plane
Top view
Pipe
Pipe
EEEE
A-plane
A-plane
Top view
Correct
Wrong
Ladder
EEEE
A-plane
A-plane
Top view
EEEE
A-plane
A-plane
Top view
Correct
Wrong
Ladder Ladder
Ladder
Cone AntennaFront Cover
EEEE
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-11
2. Shoulders and Struts
Install a reflector (flat metal plate) above the obstacle as shown in the figure.
!!!!
Warning
Measuring range may be reduced if there are obstacles in the radar beam.
3. Center of the Tank
When the MRG is installed at the center of the tank, measurement may be adversely affected or become unstable because of microwave side-lobes (non-main beams). Thus center-of-tank installations should be avoided.
4. Narrow Channel
In case of channel applications, install the MRG so the axis of the electric field is at right angle to the channel wall to avoid influences from edge reflections off channel walls and the liquid surface.
Correct Wrong
Shoulder
Correct
Wrong
Shoulder
Reflector
MRG
MRGMRG
MRG----10
10 10
10
Mechanical Installation
Mechanical InstallationMechanical Installation
Mechanical Installation
2-12
5. Tank Installation
For round tank applications, install the MRG so the axis of the electric field is oriented 45 degrees to the tank wall to avoid influences from edge reflections off channel walls and the liquid surface. For flat wall tank applications, install the MRG so the axis of the electric field is perpendicular to the tank wall.
Round wall tank Flat wall tank
6. Open area Installation
This is an example of an open area installation. In these types of applications, install the MRG so the axis of the microwave beam is perpendicular to the liquid surface.
Fixing bracket
Beam area
MRG
MRGMRG
MRG----10
1010
10
Electrical Installation
Electrical InstallationElectrical Installation
Electrical Installation
3-1
3 Electrical Installation
3.1 Connection of MRG-10
!!!!
Caution
Handle the front cover with care as the glass panel and gasket are removable.
The glass panel and gasket are fixed in place when the cover is screwed onto the case and tightened. The gasket provides sealing between the housing and front cover and as such the front cover should be securely and firmly screwed onto the case.
1. Unscrew and remove the front cover.
2. Pass the cable through the entry and connect it to the terminal block.
3. Connect the shield to the ground terminal.
4. Replace the front cover and firmly screw it onto the case.
Ground
Terminal
Terminal block
+ +
-
-
Ground
Terminal
Keys
LCD
+ +
-
-
HART
modem
Power Supply
Unit
Terminal block
250Ω
-
+
MRG-10 Housing
R
MRG
MRGMRG
MRG----10
1010
10
Electrical Installation
Electrical InstallationElectrical Installation
Electrical Installation
3-2
3.2 Cables
Cable Use shielded twisted pair for connection. Cross-sectional area of conductor is 0.2 …2.5mm
2
.
(AWG24 …14)
Cable entry 2×M20×1.5 (cable diameter 10mm max.)
3.3 Load
Minimum load for HART® 250Ω Maximum load (Non-Ex) 900Ω (EX) 540Ω
3.4 Power supply
Power (Non-Ex) 16…36VCD (EX) 16…28VDC
3.5 Grounding
The terminal must be connected to earth ground prior to connection to any other equipment.
MRG
MRGMRG
MRG----10
1010
10
Electrical Installation
Electrical InstallationElectrical Installation
Electrical Installation
3-3
3.6 Arrester replacement
Step 1; Loosen the 4 screws indicated by the arrows in the schematic below and
remove the LCD panel.
Step 2; Loosen the Arrester PWB fixing screw indicated by the arrow.
Step 3; Remove and replace the Arrester PWB.
Step 4; Tighten the Arrester PWB fixing screw.
Step 5; Tighten the LCD panel fixing screw. Please be sure that the LCD panel is positioned correctly.
Arrester PWB
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-1
4 Configuration method
It is a simple task to configure the MRG-10. The MRG-10 can be configured with:
Display Panel & Key SW on MRG-10 PC (Setup Software)
4.1 Display Panel & Key SW
4.1.1 Display
Bar graph, measured data and units are displayed during normal operation. Blinking display of the last measured value indicates that gauge is in search mode.
When the key SW is used in configuration mode, the menu number or registered data is displayed.
4.1.2 Key SW
1: ENT (Enter) key
Changes display from measurement mode to configuration mode. Moves to the lower layer (from main menu to sub menu). Moves the blinking cursor to the target column when changing the registered data. Inputs data.
2: ESC (Escape) key
Changes display from configuration mode to measurement mode. Moves to the upper layer (from sub menu to main menu). Freezes changes to registered data.
3: (Up) key
Increases the main menu number and the sub menu number. Increases the blinking column value.
4: (Down) key.
Decreases the main menu number and the sub menu number. Decreases the flashing column value.
m
Bar graph [%] Measured value
Unit
mA
%
ft
m
ESC ENT
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-2
4.1.3 Examples
Example-1
When R-constant is set to 6.275m from the default value.
Step
Key
Display
1
7.956m
M
easuring level(m) (Normal operation mode)
2 E NT
[1--]
Main menu number (Configuration mode)
3 E NT
[1-1]
4
[1-2]
5
△△△△
[1-3]
6
△△△△
[1-4]
7 E NT
10.000
Default value
8 E NT
10.00 0
0 ”
blinks
9
×
5
10.00 5
×
5 : Push 5 times
10 E NT
10.0 0 5
11
×
3 10.0 7 5
12 E NT
10. 0 75
13
×
2
10. 2 75
14 E NT
1 0
.275
15
▽▽▽▽
×
4
1 6 .275
16 E NT 1
6.275
17
▽▽▽▽
0 6.275
18 E NT
06.275
19 E SC
[1-4]
20 E SC
[1--]
21 E SC
4.231
M
easuring level(m) (Normal operation mode)
Main Menu
Sub Menu
Input Stage
Measuring
Data
ENT
ESC
G
[1-3]
R
[1-4]
CONFIG
[1--]
Output
Parameter
[1-1]
ENT
ESC
ENT
ESC
Registered
data
ESC ESC ESC
Meas.
Unit
[1-2]
Meas. Mode
Config. Mode
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-3
Example-2
When Volume point 2 is set to 2345.67m3.
Volume point can be set from 00000.00 to 99999.99.
Step
Key
Display
1
4.231
Measuring level(m) (Normal operation mode)
2 E NT
[1--]
3
△△△△
× 2
[3--]
Volume(Main menu)
4 E NT
[3-1]
5
△△△△
× 3
[3-4]
Volume point(Sub menu)
6 E NT
[320]
Volume point 1
7
[321]
Volume point 2
8 E NT
000.00
Default value
9 E NT
000.0 0
0 ”
blinks
10
× 7
000.0 7
× 7
: Push 7 times
11 E NT
000. 0 7
12
× 6
000. 6 7
13 E NT
0000 0
14
×
5 0000 5
15 E NT
000 0 5
16
×
4 000 4 5
17 E NT
00 0 45 18
×
3
00 3 45
19 E NT 0 0
345
20
×
2
0 2 345
21 E NT 0
2435
22 E NT
02435
23 E SC
[321]
24 E SC
[3-4]
25 E SC
[3--]
26 E SC
4.231
Measuring level(m) (Normal operation mode)
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-4
4.1.4 Parameter instructions
- shaded areas indicate default settings.
[1--] CONFIGURATION Settings
[1-1] Output Parameter: LCD display
Parameter Value Description
0 Level Level value from target 1 Ullage Distance between measuring reference point and target 2 Volume (%) Volume rate value (%) 3 Current Current value (mA) (4-20 mA) 4 Amplitude Signal strength (dB) 5 Max. Volume Max value of volume settings
When [ft] units are selected for “Level” or “Ullage” display, parameter range is calculated in ‘feet’.
[1-2] Antenna type
Parameter Value
0 4 inch cone 1 6 inch cone 2 8 inch cone 3 Rod antenna (inactive SHORT) 4 Rod antenna (inactive LONG)
[1-3] Measuring Unit
Parameter Value Description
0 m
Sets display in Metric units
1 ft
Sets display in Feet units
Note: When ‘Measuring Unit’ is changed, units of other parameters also change.
[1-4] G parameter distance between flange reference point and measuring reference point
Parameter Default Value Description
-3.000-3.000
0.000
R+C-G 20
(Parameter range in metric [m] units)
If measurement unit is [ft], display will be converted to show ‘feet’ units.
[1-5] R parameter Measurement range
Parameter Default Value Description
0.000-23.000
0.000
R+C-G 20
(Parameter range in metric [m] units)
If measurement unit is [ft], display will be converted to show ‘feet’ units.
[1-6] C parameter Below measurement range
Parameter Default Value Description
0.000-10.000
0.000
R+C-G 20
(Parameter range in metric [m] units)
If measurement unit is [ft], display will be converted to show ‘feet’ units.
[1-7] H parameter Deadband
Parameter Default Value Description
0.000-23.000 0.103 (4 inch cone)
0.223 (6 inch cone)
0.343 (8 inch cone)
0.350 (Rod Long)
0.500 (Rod Short)
Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-5
[1-8] Offset parameter for LCD level values
Parameter Default Value
Description
-99.999-99.999 0.000 Parameter range, in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units
Note: Offset affects LCD display only and does not affect analog output or other values.
[2--] ANALOG Settings
[2-1] Analog output parameter
Parameter Value Description
0 Level Level value
converted
to 4-20 mA
1 Ullage Ullage value
converted
to 4-20 mA
2 Volume Volume value
converted
to 4-20 mA
3 Amplitude Signal strength amplitude value converted to 4-20 mA
[2-2] Minimum output (4 mA)
Parameter Output
Default Value
Description
-3.000-23.000 Level 0.000 Parameter range in metric [m] units
-3.000-23.000 Ullage 0.000 Parameter range in metric [m] units
0.000-100.000 Volume 0.000 [%]
0.000-100.000 Amplitude
0.000 [dB]
When [ft] units are selected for “Level” or “Ullage” display, parameter range is calculated in ‘feet’.
[2-3] Maximum output (20 mA)
Parameter Output
Default Value
Description
-3.000-23.000 Level 20.000 Parameter range in metric [m] units
-3.000-23.000 Ullage 20.000 Parameter range in metric [m] units
0.000-100.000 Volume 100.00 [%]
0.000-100.000 Amplitude
100.00 [dB]
When [ft] units are selected for “Level” or “Ullage” display, parameter range is calculated in ‘feet’.
[2-4] Alarm selection
Parameter Value Description
0 High output 22 mA alarm output 1 Low output 3.9 mA alarm output 2 Hold output Hold last value
[2-5] Fixed current output setting
Parameter Value Description
0 Measuring Value [mA]
3.900-22.000
Fixed current Any current value selectable
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-6
[3--] Volume Setting
[3-1] Linearization Selection
Parameter Value Description
0 Not Calculated 1 Vertical Cylinder 2 Spherical 3 Horizontal Cylinder 4 User Tank Table
Tank Configurations
[3-2] Linearization Point Number
Parameter Default Value Description
0-20 0 Input required
no. of points for table
[3-3] Level point [300] ~ [319]
Parameter Default Value Description
-3.000-23.000
0.000 Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units
[3-4] Volume point [320] ~ [339]
Parameter Default Value
Description
0-99999.99 0.000
Display will be converted to the volumetric unit setting under [3-9].
If you create a volumetric table incorporating settings [3-2] ~ [3-4], you can produce a line chart such as that shown below which enables you to quickly calculate level and volumetric values.
3
2
1
4
19
20
[300] [301] [302] [303] [318] [319]
[320]
[321]
[322]
[323]
[338]
[339]
Volume point Number on [3-2]
Volume table on [3-4]
Volume
Level
Level table on [3-3]
Level and Volume correlation on the user tank table
1: Vertical Cylinder
2: Spherical
3: Horizontal Cylinder
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-7
[3-5] Delete all tables
Parameter Value Description
0
Do not delete
1 Delete all
Setting “1” clears table
[3-6] Diameter of the tank
Parameter Default Value Description
0.000-10.000 1.000 Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units.
[3-7] Length of the tank
Parameter Default Value Description
0.000-20.000 1.000 Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units.
[3-8] Offset level
Parameter Default Value Description
-3.000-23.000
0.000 Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units.
Diameter
1:
Vertical Cylinder
R
G
Offset
Diameter
2:
Spherical
R
G
Offset
Length
Diameter
3:
Horizontal Cylinder
R
G
Offset
[3-9] Volume unit
Parameter Value
0 m3 1 Gallons 2 Barrels 3 Ft3
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-8
[4--] Calibration
[4-1] 4mA Calibration
Parameter Default Value Description
3.50-4.50 4.00
In fixed current output mode with current set at 4mA, input ammeter reading.
[4-2] 20mA Calibration
Parameter Default Value Description
15.00-25.00 20.00
In fixed current output mode with current set at 20mA, input ammeter reading.
[4-3] Offset Calibration
Parameter Default Value Description
-1.00-1.00 0.00 Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units.
[4-4] Span Calibration
Parameter Default Value
0.90-1.10 1.00
[5--] Advanced Setting
[5-1] Averaging Time
Parameter Default Value Description
1-120 10 Measuring value is averaged in accordance with
[sec] setting
[5-2] Noise Margin
Parameter Default Value Description
0-10000 300 Noise is eliminated in accordance with [1/100dB]
setting
When noise level is high, noise can be masked by attenuating the signal gain.
[5-3] Search Delay
Parameter Default Value Description
1-120 30
Time delay after loss of echo until restart in accordance with [sec] setting.
[5-4] Alarm Delay
Parameter Default Value Description
1-120 30
Time delay after loss of echo until alarm sounds in accordance with [sec] setting.
10
24
Signal Amplitude
[dB]
14
Set noise margin as 10.00dB
Noise
Signal Amplitude
[dB]
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-9
[5-5] Bottom Window
Parameter Default Value Description
0-0.5 0.3 Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units.
Valid only when [5-7] is set at “0".
[5-6] First Echo Flag
Parameter Value Description
0 Max Echo Max strength echo defined as surface echo 1 First Echo First echo defined as surface echo
[5-7] Bottom Visible
Parameter Value Description
0 Bottom Visible When tank bottom echo is larger than surface echo
(such as with oil fluids). Effective against echo misdetection.
1 Bottom Invisible
When tank bottom echo is smaller that surface echo (such as with water). Setting “1”, invalidates this function.
Measurement Range (R)
Peak detectable range
Bottom window
Surface echo Bottom echo
Distance
Detected as Surface echo at First Echo setting
Detected as Surface echo at Max Echo setting
Signal Amplitude
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-10
[6--] Noise
[6-1] Noise table number
Parameter Default Value Description
0-10 0
Input required no. of points for table
[6-2] Noise table [600] ~ [609]
Parameter Default Value Description
0.000-20.000 0.000 Noise position by distance Parameter range in metric [m] units
If measurement unit is [ft], display will be converted to show ‘feet’ units.
[6-3] Amplitude threshold [610] ~ [619]
Parameter Default Value Description
0-10000 0 [1/100dB]
If you create a noise table incorporating settings [6-1] ~ [6-3], you can produce a line chart such as that shown below which enables you to eliminate lower signal strength noises below the line.
Amplitude at distance 0m and 20 m is set at 0 dB as default.
[6-4] Delete All
Parameter Value Description
0
Do not delete
1 Delete All
Setting “1” clears noise table
Distance
[600]
[601]
[602]
[603]
[604] [605]
[610]
[611][614]
[612][613]
[615]
[616]
[606]
Signal Amplitude
Setting amplitude through [6-3]
Setting distance through [6-2]
3
2
1
4
5
6
Noise table points
7
MRG
MRGMRG
MRG----1111000
Configuration method
Configuration methodConfiguration method
Configuration method
4-11
[7--] Other
[7-1] Password: not normally used
[7-2] Re-search
Parameter Value Description
0 1 Research
Mandatory surface echo re-search
[7-3] User Reset
Parameter Value Description
0 1 Initialization Initialized by “1” setting
[7-4] Error Status
Indication Error status
E-00 No error E-01 Internal ROM Error E-02 Internal RAM Error E-03 Transmission error E-04 Amplitude detection malfunction E-05 Volume table error E-99 Echo search status
[7-5] Software Version
[7-6] Hardware Reset
Parameter Value Description
0 1 Reset
Setting “1” executes hardware reset
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-1
5 Configuration
5.1 Basic settings
Set up the following parameters
- Output Parameter Select measurement value displayed on the LCD.
- Meas. Unit Select measurement unit, meter or feet.
- Antenna Type Select type of antenna.
- R Set the distance from ref. point to level zero.
- C Set the distance from level zero to bottom of tank. (‘C’ is normally set to ‘0’. If it is necessary to measure
negative level, please set the distance.)
- H Set the distance from ref. point to measurement range. (see 5.2.1)
Parameters of tank dimensions are optimized for your application.
Ref. Point
R C Level
Ullage
Fluid
surface
Zero Level
Bottom
H
Measuring
Range
- Analog Output Parameter Select measurement value output for analog output.
- Minimum Output Set value corresponding to 4mA.
- Maximum Output Set value corresponding to 20mA.
- Alarm Selection Set value to be output when the gauge misses the echo. Low(3.9mA), High(22mA) or Hold Last Value
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-2
Configuration with PC software
- PC connection
PC configuration software can also be used for commissioning.
1) Connect HART modem to
both ends of resistor as shown below.
2) Open the software. Enter the HART modem port number
and click the “set” button. When communication is completed successfully, ID, Version No and Product Name will appear in the boxes.
3) By selecting other tabs such as the sample below, you can set any parameter. Any action requires “READ” parameters from the main unit, before changing values (pressing the “ENTER” key may be required to set value changes) and clicking “WRITE” to the main unit.
Configuration Setting Tab Analog Setting Tab
+ +
-
-
HART
modem
Power Supply
Unit
Terminal block
250Ω
-
+
MRG-10 Housing
R
Click Here
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-3
5.2 Negative level point measurement
Value ‘C’ defines below zero level. When C values are set, the LCD or PC Hart communication will show negative values.
Note: If 4mA corresponds to LV 0m, Analog output will be maintained at 4mA even if
measurement values fall below LV 0m.
5.3 Avoiding disturbance echoes.
There are two ways to avoid the disturbance echo problem.
5.3.1 Dead Band (=”H”)
When there are disturbance echoes in the near zone such as stairs at the top of the tank, the gauge may capture and interpret these echoes as coming from the liquid surface. Set up “H” to avoid this problem. All echoes within this area would be outside of the measuring range and ignored.
5.3.2 Noise Table
If there are disturbance echoes in the effective measuring range and the gauge tracks such echoes, set up “Noise Table” parameters. You can adjust the threshold level for sections of the measurement range with these parameters. “Noise Table” parameters are comprised of ullage points and threshold values. Up to 10 points of values can be established respectively with linear interpolation between points. (Amplitude at distance 0m and 20 m is set at 0 dB as default.) If disturbance echoes are tracked, you should first check the ullage and the amplitude level with the LCD display or with the configuration software.
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-4
To create a noise table, follow the steps below.
1) Enter Menu code [6-1], then set the noise table number (maximum10 points).
2) Enter Menu code [6-2], and set distance parameters into the data field in accordance with selected numbers. (For example, if “10” is set at [6-1], you will need to set data [600]~[609] for distance values.)
3) Set distance data for [600], and push ENT to complete the entry. Similarly set distance values
for [601]…[609].
4) After completing input of distance values, the next step is entering amplitude values.
5) Return to the sub-menu by clicking the ESC key. Then enter Menu code [6-3] and set threshold level parameters into the data fields in accordance with selected numbers. For example, if “10” is set at [6-1], you will need to set data [610]~[619] for amplitude values.)
6) Amplitude points must
correlate to the distances defined under
[6-2]. Select table addressex.
[610] and enter amplitude data, then click ENT to complete the entry. Similarly, set amplitude data for [611]…[619].
7) After setting all data, return to the Sub-Menu by clicking the ESC key of the LCD panel. When
returning to the main menu, click ESC again. Click ESC again to go to the measurement mode.
Note: When using PC configuration software, enter all data into the following menu then click “WRITE”.
Setting of distance data must be in ascending order, that is, from shortest to longest distance. Noise table error and noise table malfunction will occur if settings are mis-ordered. Error status will appear under [7-3]
Example of a noise table is shown above. All noise lower than the noise threshold line will be ignored.
1
2 3
4 5
6 7
8
[60 0]
[601]
[602]
[603]
[604]
[605]
[606]
[607]
[610]
[611][612]
[613][614]
[615][616]
[6167
Signal Amplitude
Distance
Noise Table
Surface Echo
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-5
5.3.3 One point advice regarding noise table input procedure
It is necessary to provide some allowance around the echo peak and a margin of threshold for noise amplitude. These are +-0.3m and +5dB respectively. Noise Table point “n” must also be nearer than next Noise Table point “n+1”. If this rule is not maintained, noise table errors will occur and this function will become invalid.
Also by using the PC configuration software, you can add or change the position of the noise table with a right click.
1) On the “Tank Spectrum” tab, when the “START” button is clicked, you may view the red line wave form data from the main unit as shown below.
2) If you would like to set the noise table manually, right click and select “ADD” at designated points for the new table. Also the table (points) can be moved by a left-click and dragging.
3) After the noise table is set, click the “Noise Write” button to complete.
5 dB
- 0.3m +0.3m
Signal
Amplitude
Distance
Peak Point
Peak Position
Right Click Option
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-6
5.3.4 Noise Margin
When noise level is high over the whole range, the threshold level over the entire range can be set by the “noise margin” parameter as shown below.
Noise margin is set at 13dB
(10dB above 3dB default value)
From the LCD menu, select [5-2].
With the PC configuration software, please refer to [5-2] under the “5. Advance” tab.
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-7
5.4 Volume calculation
There are 4 types of volume calculations which are set up by the Linearization Selection parameter.
- Spherical Tank
Volume is calculated from diameter, offset level and measured level. Diameter is the diameter of the sphere and offset level is the measurement level compensation factor.
- Vertical Cylinder Tank
Volume is calculated from diameter, offset level and measured level. Diameter is the diameter of the tank and offset level is the measurement level compensation factor. .
- Horizontal Cylinder Tank
Volume is calculated from diameter, length, offset level and measured level. Diameter is the diameter of the tank and offset level is the measurement level compensation factor. Length is the horizontal length of tank as shown.
- Tank Table
Set up Linearization Point Number. It is possible to set up 20 points each for level and volume respectively in the Tank Table which are linearly interpolated between points. More than two points must be input to set up the Tank Table. (Tank Table Error) Four volume units can be selected - cubic meter, gallons, barrels and cubic feet.
To create the volume table, follow the steps below.
1) Select “4” for menu code [3-1].
2) Set the required number of point settings for menu code [3-2]. (Max 20 points.)
3) Enter menu code [3-3]. Select point and set level parameters into the data field in accordance
with the selected numbers. (e.g. when setting 20 points at [3-2], [300]~[319] can be set.)
4) Input Level data then click ENT to enter values for [300] ~ [319].
5) After completing input of Level data, the next step is entering the Volume data.
6) Return to the sub-menu by clicking the ESC key. Then enter Menu code [3-3], and set the
volume parameters into the data fields in accordance with the selected numbers. (e.g. when setting 20 points” at [3-2], [320]~[329] can be set.)
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-8
7) Volume point must
correlate to the level data defined under
[3-2]. Select table address(ex. [320]),
enter amplitude data and click ENT to complete entry. Similarly, enter data for [321]…[329].
8) After setting all data, return to the Sub-Menu by clicking the ESC key on the LCD panel. To return to the main menu, click ESC again. Click ESC once more to go to the measurement mode.
Note: When using PC configuration software, enter all data in the following menu then click
“WRITE”.
Setting of distance data must be in ascending order, that is, from shortest to longest distance. Volume table error and volume table malfunction will occur if settings are mis-ordered. Error status will appear under [7-3]
3
2
1
4
19
20
[300][301] [302] [303] [318] [319]
[320]
[321]
[322]
[ 323]
[338]
[339]
Volume table points
Level
Volume
Level table points on [3-3]
Volume data on [3-4]
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-9
5.5 Analog value compensation
When analog output current is not correct, revise the value in the following manner. Input “4.000mA” under “Fixed Current Output” [2-5], then input the measured current value under “4mA Calibration” [4-1]. Input “20.000mA” under “Fixed Current Output” [2-5], then input the measured current value under “20mA Calibration” [4-2].
5.6 Measuring value compensation
Offset level from reference point and scale factor are adjusted under [4-3] (offset) and [4-4] (scale factor). If there is a difference between the Tank ref. point and the MRG-10 ref. point, you can input “G” for calibration [1-4].
5.7 Bottom recognition
Tank bottom recognition is necessary for measurement of low reflection targets such as oil surfaces. In such cases, the smaller amplitude echo from liquid surface reflections is concealed in the larger echo from the tank bottom and the gauge can not distinguish the surface reflection echo from the bottom echo. “Bottom Visible Flag” and “Bottom Window” parameters of the gauge function to avoid the tracking of bottom echoes. Initial settings of these parameters are “On” and “0.3m”. The gauge outputs level value as the bottom level, when the surface echo is in the bottom window. However when the level is higher and the surface echo is not in the bottom window, the gauge can distinguish surface echoes from bottom echoes. On the other hand, if bottom echoes cannot be discerned in high reflection targets such as water, the “Bottom Visible Flag” parameter should be set at “Off” to eliminate any bottom deadband.
5.8 Other
5.8.1 Echo search methods
Two echo search methods are available - one based on recognizing the echo of maximum signal strength (Max. Echo Flag) and the other where the first echo in the measurement range
is captured (First Echo Flag). The “First Echo Flag” provides a means to recognize the surface echo from other echoes in the measuring range.
5.8.2 Reset
Initializes all setting values.
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-10
5.9 Pipe antenna setting
5.9.1 Overview
The following instructions are applicable when the MRG-10 is used in the pipe mode (hence referred to as “pipe antenna”).
Advantages
and disadvantages of the pipe antenna are as follows.
1) Advantages
Existing pipe can be used as the pipe antenna. Even if obstacles are located near to the beam area, measurement will not be affected. Measuring coverage can be extended to low dielectric constant liquids.
2) Disadvantages
Material of the pipe (metal, etc.) must be that which can contain and channel microwaves. Dirty, dusty conditions inside of the pipe may cause noise disturbance echoes which decrease accuracy.
5.9.2 Pipe antenna specifications
Specifications Antenna size 4B Cone antenna Measurable Range 10 m Accuracy
±10 mm (< 5 m) ±20 mm (< 10 m)
Pipe specification (metal pipe only) ID over 100mm Max hole for air ventper 1 m φ5 mm / 2pcs
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-11
5.9.3 Parameter setting
5.9.3.1 Antenna Type Menu code:[1-1]
Use actual antenna type. (ex. 4inch cone antenna)
5.9.3.2 Span calibration
• As the speed of microwaves propagated inside of pipes differ from the speed of microwaves when propagated in free spaces, a compensating coefficient must be input in the “Span Calibration” parameter (Menu code, [4-4]).
• “Span Calibration” values are
derived from the inner diameter of the pipe.
The following table is one example.
Inner Pipe Dia [mm] Span Calibration
107 0.9507
• When span calibration value (‘F’) is unknown, ‘F’ can be calculated from two points ­reference level value (X) and measured level value (Y) - using the following equation.
F =Y
High
- Y
Low
/X
High
- X
Low
F : Span calibration value X
High
: High reference level value
X
Low
: Low reference level value
Y
High
: High measured level value
Y
Low
: Low measured level value
5.9.3.3 Offset compensation
Offset setting may be required using Menu code: [4-3]. Offset value is
derived from the difference in measured level and reference level at 1 point.
5.9.4
Considerations
• Pipe material should be metal. In cases of existing pipes of concrete or PVC material instead of metal, span calibration may not be required as their low dielectric constants allow transmission of microwaves. However when wet, such pipe materials exhibit high reflectivity characteristics from wetted surfaces. This affects accuracy and span calibration becomes necessary. Because of such changes in characteristics under wet conditions, non-metal pipe applications are not recommended.
• Air vents (10mm dia.) for pressure release should be incorporated and located above the tip of the antenna.
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-12
5.10 Key Parameter List
Antenna Type [1-2]
0: 4inch Horn Antenna 1: 6inch Horn Antenna 2: 8inch Horn Antenna 3: Rod Antenna Short 4: Rod Antenna Long
Meas. Unit [1-3]
0: meter 1: feet
G [1-4]
-3 to +3m, (R+C-G) <=20m
R [1-5]
-3 to +23m, (R+C-G) <=20m
C [1-6]
0 to +3m, (R+C-G) <=20m
H [1-7]
0 to +23m
Offset of level value on LCD [1-8]
-99.999 ~ 99.999 m
Analog Output Parameter [2-1]
0: Level 1: Ullage 2: Volume(%) 3: Amplitude(dB)
Minimum Output [2-2]
-3 to +23m (level, Ullage) 0 to 100 (Vol., Amp.)
Maximum Output [2-3]
-3 to +23m (level, Ullage) 0 to 100 (Vol., Amp.)
Alarm Se lection [2-4]
0: High(22mA) 1: Low(3.9mA) 2: Hold last value
CONFIGUR ATION
[1--]
[2--]ANALOG
Title
Menu
Code
Input Value
Output Parameter [1-1]
0: Level 1: Ullage 2: Volume(%) 3: Current 4: Amplitude 5: Max. Volume
Parameters
Sub Menu
Code
Sub Parameter
Lowest Menu
Code
MRG
MRGMRG
MRG----10
10 10
10
Configuration
ConfigurationConfiguration
Configuration
5-13
Linearisation Selection
[3-1]
0: Not Calculate 1: Horizontal Cylinder 2: Spherical 3: Vertical Cylinder 4: User Tank Table
Linearisation Point Number [3-2]
2
to 20
Input
[3-3]
Level Point
[300]~[319] -3 to +23m
[3-4]
Volume Point [320]~[339] 0 to 99999.99
Delete All
[3-5]
E
xecute by 1
Diameter
[3-6]
0 to +10m
Length
[3-7]
0 to +20m
Offset Level
[3-8]
-3 to +23m
Volume Unit
[3-9]
0: m3 1: gal
l
ons 2: barrels 3: ft3
4mA Calibration
[4-1]
3.9 to 2 2 mA
20mA Calibration
[4-2]
3.9 to 2
2
mA
Offset Calibration
[4-3]
-1 to 1m
Span Calibration
[4-4]
0
.9 to 1.1
Averaging Times
[5-1]
1 to 120sec
Noise Margin
[5-2]
0 ~ 10000 [1/100] dB
Research Delay
[5-3]
1 to 120sec
Alarm Delay
[5-4]
1 to 120sec
Bottom Window
[5-5]
0
to 0.5m
First Echo Flag
[5-6]
0: Max echo 1: First echo
Bottom Visible
[5-7]
0: Bottom Visible 1: Bottom invisible
Noise Table Number
[6-1]
0 to 10
Input
[6-2]
Noise Table
[600]~[609] -3 to +23m
[6-3]
Amplitude Threshold
[610]~[619] 0 to 100.00dB
Delete All
[6-4]
Execute by "1"
Password
[7-1]
t
o service mode
Re-Search
[7-2]
User Reset
[7-3]
E
xecute by 1
Error Status
[7-4]
Software Revision
[7-5]
Input Value
Title
Menu Code
Parameters
Sub Menu
Code
VOLUME [3--]
Sub Parameter
Lowest Menu
Code
CALIBRATI ON
[4--]
ADVANCE [5--]
NOISE
[6--]
ELSE
[7--]
Hardware Reset
[7-6]
MRG
MRGMRG
MRG----10
10 10
10
Technical Information
Technical InformationTechnical Information
Technical Information
6-1
6 Technical Information
System
Operating frequency • 5.8 GHz
Half-power beam width • 4 " Cone antenna: 34 deg
• 6 " Cone antenna: 22 deg
• 8 " Cone antenna: 17 deg
• Rod antenna : 30 deg
Measuring range Max. 20 m (65 ')
Serial communication HART communication
Key switch 4 keys for configuration
Display 5-digit LCD and bar graph
Power
Supply voltage 16..28 VDC(Ex) / 16..36 VDC(Non-Ex)
Specification for HART • Ripple: 47..125 Hz
• Vpp=200 mV (measured at 500 ohms)
• Max. noise: 500 Hz..10 kHz
• Vrms=2.2 mV (measured at 500 ohms)
Output
Variable Ullage / Level / Volume / Current /
Signal amplitude/Volume Max
Unit Level, Ullage : m/ft
Volume : % Current : mA
Amplitude : dB
Signal type Analog 4..20 mA, HART
Resolution • Analog: 4 μA
• Digital: 1 mm (0.04")
Update time 1 s
MRG
MRGMRG
MRG----10
10 10
10
Technical Information
Technical InformationTechnical Information
Technical Information
6-2
Averaging time 1..120 s
Signal on alarm Hold/Low(3.9mA)/High(22 mA)
Load Minimum load for HART communication 250
ohms.
Accuracy
Measured error *) ±10 mm (0.4")
Linearity *) ±10 mm (0.4")
Repeatability *) ±1 mm (0.4")
Ambient temperature effect ±0.01% / 10 K
*): Free-space reflection from flat metal surface, ambient temperature 25 °C (77 °F), atmospheric pressure.
Environment resistance
Ambient temperature -20..70 °C (-40..158 °F)
Storage temperature -40..80 °C (-40..176 °F)
Tank temperature -20..150 °C (-4..302 °F)
Tank pressure -0.1..1.0 MPa (-14..145 Psi)
Degree of protection IP65
Vibration resistance IEC 68-2-6 /1G
EU directive compliance
CE mark / EMC 2004/108/EC/ EN 61326-1(2006)/
EN 61326-1(1997)+A1(1998)+A2(2001)+A3(2003)
ATEX 94/9/EC
Input Voltage [V]
16
21.5
36
0 250 900
Load[Ohm]
R0≦(Vin-16)/0.022
MRG
MRGMRG
MRG----10
10 10
10
Technical Information
Technical InformationTechnical Information
Technical Information
6-3
Harmonized standard EN
61000-4-2 (1995)+A1(1998)+A2(2001)
EN 61000-4-3(2006)
EN 61000-4-4(2004)
EN 61000-4-5 (1995)+A1(2001)
EN 61000-4-6 (1996)+A1(2001)
EN 61000-4-8(1993)+A1(2001)
EN 60079-0(2006)
EN 60079-11(2007)
EN 60079-26(2004)
Cable Connection
Cable type Shielded twisted pair
Cross-section area of cable: 0.2..2.5 mm2, (AWG24..14)
Cable entry 2-M20X1.5, NPT 1/2" (cable dia. 6.5..9 mm)
Ground cable Max. 4 mm
2
Material
Transmitter Case Aluminum
Cone antenna 316L stainless steel
Rod antenna PFA (Thread part: 316 stainless steel)
Sealing parts PTFE, Viton O-ring
Certificate and Approvals
Hazardous area certification ATEX: Ex ia IIC T4Ⅱ Ⅱ1/2GD(Cone Antenna)
2GRod Antenna
TIIS: Ex ia IIC T4
MRG
MRGMRG
MRG----10
10 10
10
Troubleshooting
TroubleshootingTroubleshooting
Troubleshooting
7-1
7 Troubleshooting
SYMPTOM ACTION No level reading Check the power supply.
Incorrect level reading Check the gauge calibration. Check that gauge has not locked on an
interfering object.
Check for correct mechanical installation.
Serial Communication failure Check the COM port setting in the LR setup
program. Check the serial communication address. Check the cable and HART modem
connections and make sure that correct cable
and resistor are used.
Display Panel window is blank Check the power supply.
Check the status of the gauge in the LCD display. Status descriptions are as follows.
[E00] Normal Operation ­[E01] Internal Error Critical Error. Please contact service [E02] Memory Error Critical Error. Please contact service [E03] Receive Error No measured data. Please contact service [E04] Tank Table Error Incorrect setting on tank table. Set up correctly. [E05] Noise Table Error Incorrect setting on noise table. Set up correctly. [E99] Searching Echo Conducting echo search.
BARRIER
ASSOCIATED
APPARATUS
POWER
SUPPLY
HAZARDOUS
LOCATION
NON-HAZARDOUS
LOCATION
MRG-10
Intrinsic Safety Parameters ( Ex ia IIC T4 )
Parameters Ui <= 28V, Ii <= 93mA, Pi <= 0.65W, Ci = 0, Li = 0
Ambient Temperature Limits
-20 <= Ta <= 60 deg C
CONTROL DRAWING
2008-2-8
5198 5640
1
1
1
T.Kinoshita T.Kinoshita S.Takatsuka S.Takatsuka
 
Safety Instructions
Microwave Radar Gauge
MRG-10
IMQ 08 ATEX 003
II 1/2 GD II 2 G Ex ia IIC T4
1. Category
This equipment is certified for installation in category 1/2GD. And it has various antennas. For use rod
antenna covered by Teflon, category is limited only in 2G.
2. Gas group and Temperature class
This equipment may be used with flammable gases and vapours with apparatus groups IIA, IIB & IIC, and
with temperature classes T1, T2, T3, & T4.
3. Mounting and wiring
Mounting and wiring operations in classified areas for explosive gas atmospheres, must be executed
accordingly to the current procedures and to the national and international standards (e.g. EN 60079-14)
only by qualified personnel specifically and completely trained.
4. Inspection and Maintenance
Inspection and maintenance of this equipment must be carried out according to the EN60079-17. Only
approved spares supplied by the manufacturer or approved agent should be used.
5. Ambient temperature range
This equipment is certified for use in ambient temperature range of -20°C to +60°C.
6. Contact with aggressive substances
If the equipment is likely to come into contact with aggressive substances, it is the responsibility of the
user to take suitable precautions that prevent it from being adversely affected, thus ensuring that the type of
protection is not compromised.
Aggressive substances: - e.g. acidic liquids or gases that may attack metals, or solvents that may affect
polymeric materials
Suitable precautions: - e.g. regular checks as part of routine inspections or establishing from the material’s
data sheet that it is resistant to specific chemicals
7. Technical data
Ratings
Power supply : 16 to 30VDC
Output : 4 to 20mA
Ambient Temp. : -20°C to +60°C
Microwave output : within 1000uV/m
Intrinsically safe parameters
Ui : 28V
Ii : 93mA
Pi : 650mW
CI : negligible uF
Li : negligible mH
8. Installation conditions
The associated apparatus shall be linear type, with an internal limiting resistor of 300 ohm minimum.
This equipment is not insulated from earth due to the use of surge/light protection provided by installation.
9. Degree of Protection
This equipment, if correctly installed, have an ingress protection rating IP65.
10. Marking
This equipment with following label attached has been certified to comply with Directive 94/9/EC.
Document No.

Microwave Radar Gauge MRG-10 Safety Instructions May 2009 1st Edition
Control Division I 2-16-46, Minami-Kamata, Ohta-ku, Tokyo 144-8551, Japan TEL: +81-3-3737-8621 FAX: +81-3-3737-8665 Web: http://www.tokyo-keiki.co.jp/
Copyright 2009 by TOKYO KEIKI INC. All rights reserved.
(Specifications are subject to change without notice.)
Loading...