KEBCO COMBIVERT F4-S Instruction Manual

COMBIVERT
INSTRUCTION MANUAL SIMPLE CONTROL
Important Note: The user should read this manual
completely prior to operating the inverter
POWER TRANSMISSION
01/00
This instruction manual must be made available to all users. Before working with this unit the user must be familiar with it. This is especially true for the attention, safety and warning guides. The meaning of the icons used in this manual are:
Danger Attention, Information Warning observe at Help Caution all costs Tip
© KEBCO 0S.F4.0EB-K120 01/00
Table of Contents
Instruction Manual
1. Installation and connection....................................... 2
1.1 Definition of terminal strip X1 ........................................2
1.2 Connection of the control signals ................................................2
1.2.1 Digital inputs ....................................................................2
1.2.2 Analog inputs ...................................................................2
1.2.3 Outputs ................................................................3
2. Operation of the inverter.........................................3
2.1 Digital operator ........................................................................3
2.1.1 Interface operator ................................................................3
2.1.2 Keyboard .................................................................4
2.2 Parameter summary .................................................5
2.3 Password input ......................................................5
2.4 Operating display ..................................................6
2.5 Basic adjustment of the drive ....................................7
2.6 Special adjustments ..................................................9
2.7 The "Drive Mode" ....................................................14
2.7.1 Start / Stop "Drive Mode" ....................................14
2.7.2 Changing direction of rotation ..........................14
2.7.3 Speed setting .........................................................14
2.7.4 Leaving "Drive Mode" .............................................14
POWER TRANSMISSION
F4-S
Table of Contents
3. Error diagnosis ......................................................15
4. Glossary ...................................................17
5. Index .....................................................................18
6. Quick reference ..............................................19
7. Passwords ...........................................................20
1F4-S Instuction Manual
Installation and Connection
GND
98
1. Installation and connection
123456789101112
Size 05...15
13 14
1.1 Definition of terminal strip X1
PIN Function Description 1 NO contact Relay output
2 NC contact Function see parameter CP.22 3 Switch contact ( factory setting: fault indication)
4 Fixed frequency 1 A signal at 4 and 5 give fixed frequency 3, 5 Fixed frequency 2 no signal and the speed reference becomes the analog input
6 Digital common Common terminal for digital inputs and outputs 7 +10V Supply voltage for speed reference potentiometer (max. 4mA)
8 Speed reference 0...10VDC for analog speed setting 9 Analog common Common for analog inputs and outputs
10 Analog output Analog output of actual frequency 0...10VDC = 0...102.4Hz 11 15V Voltage supply for digital inputs and outputs (max. 100mA)
12 Reverse Rotation direction; forward has priority 13 Forward
14 Control release Output voltage enabled; drive faults reset when signal removed
1.2 Connection of the control signals
In order to prevent a malfunction caused by interference voltages on the control inputs, the following steps should be observed:
- Use shielded/twisted cables
- Connect shields to earth ground only at the inverter
- Lay control and power wires separately (about 8 inches apart)
1.2.1 Digital input
EMC Internal voltage supply
5 141312114
- Control and power wires should cross at a right angle External voltage supply
GND
5 1413124
6
+
13...30VDC
1.2.2 Analog input
Analog speed reference
using potentiometer
987
GND
Analog speed
setting using 0...10V
GND
3...10 kW / 0.5 W
+
Ri = 4 kW
0...10 VDC
-
PLC
2 F4-S Instuction Manual
Installation and Connection
1.2.3Outputs
POWER TRANSMISSION
2. Operation of the inverter
2.1 Digital operator
Part Number 00.F4.010-2009
321
109
GND
Analog output:
+
max. 5mA
0...10VDC at R
0...1mADC at R
Load
Load
56 k
5 k
When running the inverter without an operator, it runs with the last stored values or factory setting. The red LED remains on constantly when the unit is connected to supply voltage and functioning nor­mally. The LED will begin to flash in the event of an error condition. To facilitate parameter adjustment and inverter monitoring, a keypad/ display operator is required. To prevent malfunctions, the inverter must be brought into
nOP
status before connecting/disconnecting the operator (remove the signal at the control release terminal 14). The operator is available in different versions:
5-digit LED Display with double function keypad
Interface control Transmit LED flickers during active serial communication
Operating-/Error display Normal - "LED on" Error - "LED blinks"
2.1.1 Interface operator
Part Number 00.F4.010-1009
12345
6789
The Interface operator contains an additional isolated RS232/RS485­communication port for serial communication to and from the inverter.
Ground-Connection
RS232/RS485
PIN RS485 Signal Meaning
1 reserved 2 TxD Transmit signal/RS232 3 RxD Receive signal/RS232 4 A' RxD-A Receive signal A/RS485 5 B' RxD-B Receive signal B/RS485 6 VP Voltage supply-Plus +5V (I
= 10 mA)
max
7 C/C' 0V Data reference potential 8 A TxD-A Transmit signal A/RS485 9 B TxD-B Transmit signal B/RS485
For information about other operator versions contact KEBCO!
3F4-S Instuction Manual
Operation of the Unit
2.1.2 Keypad
When switching on the inverter, the value of parameter CP.1 appears. (See Drive mode to switch the keyboard function)
The function key (FUNC) changes between the parameter value and
FUNC.
SPEED
parameter number.
With UP ( ) and DOWN ( ) the value of the parameter number is increased / decreased .
START
STOP
STOP
START
Generally, when a value is changed, parameter values are immediately accepted and stored nonvolatile. With some parameters it is necessary to press ENTER after changing the value in order for the new value to be stored nonvolatile. When this type of parameter is changed, a decimal point appears behind the last digit.
ENTER
F/R
If a drive fault occurs during operation, the current display changes to the fault message, E.XXX. The faultmessage in the display is reset by pressing ENTER.
error
ENTER
F/R
Pressing ENTER only resets the error message in the display. In order to reset the fault itself, the cause must be identified and removed and a reset signal given on terminal 14 or a power-on reset (cycle supply voltage off and then on) must occur. In the Inverter status display (CP.
2) the fault is still displayed until the inverter has been reset through the steps listed above.
4 F4-S Instuction Manual
Operation of the Unit
2.2 Parameter summary
POWER TRANSMISSION
Display Parameter Adjust. range Resolution
Factory setting
CP. 0 Password input 0...9999 1 ­CP. 1 Actual frequency display read only 0.1 Hz ­CP. 2 Inverter status display read only - ­CP. 3 Actual load read only 1 % ­CP. 4 Peak load read only 1 % ­CP. 5 Rated frequency 0...409.58 Hz 0.0125 Hz 50.0 Hz CP. 6 Boost 0...25.5 % 0.1 % 2 % CP. 7 Acceleration time 0.01...300 s 0.01 s 10 s CP. 8 Deceleration time 0.01...300 s 0.01 s 10 s CP. 9 Minimum frequency 0...409.58 Hz 0.0125 Hz 0 Hz CP.10 Maximum frequency 0...409.58 Hz 0.0125 Hz 70 Hz CP.11 Fixed frequency 1 0...409.58 Hz 0.0125 Hz 5 Hz CP.12 Fixed frequency 2 0...409.58 Hz 0.0125 Hz 50 Hz CP.13 Fixed frequency 3 0...409.58 Hz 0.0125 Hz 70 Hz CP.14 Max. ramp current 10...200 % 1 % 140 % CP.15 Max. constant current 10...200 % 1 % 200 % CP.16 Speed search 0...7 1 0 CP.17 Voltage stabilization 150...649 V,oFF 1 V oFF CP.18 Slip compensation -2.50...2.50 0.01 0=oFF CP.19 Autoboost -2.50...2.50 0.01 0=oFF CP.20 DC-braking 0...9 1 0 CP.21 Braking time 0...100 s 0.01 s 10 s CP.22 Relay output 0...25 1 2 CP.23 Frequency level 0...409.58 Hz 0.0125 Hz 4 Hz
2.3 Password input
From the factory, the frequency inverter is supplied without password protection, this means that all parameters can be adjusted. After programming, the unit can be protected against unauthorized access thus preventing the values from being changed.
Locking the CP-Parameters (Read only)
See the last page for the
actual password values.
Releasing the CP-Parameters
FUNC. SPEED
START
ENTER
F/R
FUNC. SPEED
FUNC.
SPEED
START
ENTER
F/R
FUNC.
SPEED
5F4-S Instuction Manual
Operation of the Unit
2.4 Operating display
Actual frequency display
Inverter status display
The 4 parameters below can be used to monitor the frequency inverter's operation.
Display of the actual output frequency with a resolution of 0.0125 Hz. The rotation of the inverter is indicated by the sign.
Output frequency 18.3 Hz, rotation forward
Examples:
Output frequency 18.3 Hz, rotation reverse
The status display shows the actual working conditions of the inverter. Possible displays and their meanings are:
" no Operation " control release (terminal 14) not con­nected, modulation switched off, output voltage = 0 V, drive is disabled.
" Low Speed " no rotation signal F or R ( terminal 12 or 13), modulation switched off, output voltage = 0 V.
" Forward Acceleration " drive accelerates with a forward direction of rotation.
" Forward Deceleration " drive decelerates with a forward direction of rotation.
Actual load
Peak load
" Reverse Acceleration " drives accelerates with a re­verse direction of rotation.
" Reverse Deceleration " drive decelerates with a reverse direction of rotation.
" Forward Constant " drive runs with a constant speed and a forward direction of rotation.
" Reverse Constant " drive runs with constant speed and a reverse direction of rotation.
Other status messages are described with the parameters which are related to them.
Display of the actual inverter loading in percent. 100% load is equal to the inverter rated current. Only positive values are displayed, meaning there is no differentiation between motor and regenerative operation.
This display makes it possible to recognize instantaneous load levels by storing the highest value that occurred. The display occurs in percent (100% = inverter rated current).
With the UP or DOWN key the peak value can be reset. Switching off the unit deletes the peak value.
6 F4-S Instuction Manual
Operation of the Unit
2.5 Basic adjustment of the drive
POWER TRANSMISSION
The following parameters determine the fundamental operating data of the drive. They should be checked and/or adjusted for the application.
Rated frequency
Boost
The inverter produces maximum voltage to the motor at the frequency set in this parameter. This parameter is typically adjusted for the motor rated frequency. Note: Motors can overheat when the rated frequency is incorrectly adjusted!
V
U
A
Adjustment range: 0...409.58 Hz Resolution: 0.0125 Hz
Out
100%
Factory setting: 50.0 Hz
Customer adjustment:_______ Hz
CP. 5
f
In the lower speed range losses in the motor become greater. This parameter can be used to boost the voltage in order to over come these losses. With proper adjustment, the torque output of the motor will remain constant even at the lowest speeds.
U
A
V
Out
Adjustment range: 0...25.5 % Resolution: 0.1 % Factory setting: 2.0 % Customer adjustment: _______ %
CP. 6
CP. 5
f
Adjustment: - Using CP.3, determine the load level during no-load
operation at the rated frequency
- Run the motor at 10 Hz and adjust the boost, so that the same load level occurs as at the rated frequency.
- When the motor runs at low speeds continuously with too much boost, overheating of the motor can result.
Acceleration time
This parameter determines the time required to accelerate from 0 to 100 Hz. The actual acceleration time is proportional to the change in frequency. See below.
actual acceleration time =
Adjustment range: 0.01...300 s
change in frequency x CP.7
100 Hz
100 Hz
f
Resolution: 0.01 s Factory setting: 10 s Customer adjustment: _______ s
CP. 7
t
Example: CP. 7 = 10 s ; the drive accelerates from 10 Hz to 60 Hz
change in frequency = 60 Hz - 10 Hz = 50 Hz actual acceleration time = (50 Hz / 100 Hz) x 10s = 5 s
7F4-S Instuction Manual
Operation of the
f
U
REF
CP. 9
CP.10
10 V0 V
Unit
Deceleration time
This parameter determines the time required to decelerate from 100 to 0 Hz. The actual deceleration time is proportional to the frequency change.
Minimum frequency
actual deceleration time =
Adjustment range: 0.01...300 s Resolution: 0.01 s
change in frequency x CP.8
100 Hz
f
100 Hz
Factory setting: 10 s Customer adjustment: _______ s
CP. 8
t
Example: CP. 8 = 10 s ; the drive should decelerate from 60 Hz to 10 Hz
change in frequency = 60 Hz - 10 Hz = 50 Hz actual deceleration time = (50 Hz / 100 Hz) x 10s = 5 s
The frequency the inverter outputs with 0V applied to the analog input or if the activated fixed frequency (CP.11CP.13) is lower than this value.
Adjustment range: 0.0...409.58 Hz Resolution: 0.0125 Hz Factory setting: 0.0 Hz Customer adjustment:_______ Hz
V
ref
Maximum frequency
The frequency the inverter outputs with 10V applied to the analog input or if the activated fixed frequency (CP.11CP.13) is greater than this value.
Adjustment range: 0.0...409.58 Hz Resolution: 0.0125 Hz Factory setting: 70 Hz Customer adjustment:_______ Hz
Fixed frequency 1...3
Three fixed frequencies can be adjusted. The selection of the fixed frequencies is made with the terminals 4 and 5.
terminal 4
Adjustment range: 0.0...409.58 Hz Resolution: 0.0125 Hz
terminal 5
Factory setting: 5/50/70 Hz Customer adjustment 1:______ Hz Customer adjustment 2:______ Hz Customer adjustment 3:______ Hz
terminals 4 + 5
If the adjusted values are outside of the fixed limits of CP.9 and CP.10, then the actual run frequency will be either CP.9 or CP.10.
8 F4-S Instuction Manual
Operation of the Unit
t
POWER TRANSMISSION
2.6 Special adjustments
Max. ramp current
Max. constant current
The following parameters serve to optimize the inverter for the application. These adjustments can be ignored at initial start-up.
This function acts as an adjustable current limit during acceleration or deceleration. It can be used to prevent the load current from exceeding the inverters peak current rating, thereby preventing shut down of the inverter with an E.OC fault. When the load level reaches the adjusted value , the acceleration or deceleration is stopped until the load drops below the adjusted value. CP.2 displays "LAS" when the function is active.
Adjustment range: 10...200%, 200% = off Resolution: 1 % Factory setting: 140 % Customer adjustment: _______ %
This function acts as an adjustable current limit when operating at a constant speed. It can be used to prevent the load current from exceeding the inverters over current level, thereby preventing shut down of the inverter with an E.OC fault. When the load level reaches the adjusted value , the output frequency is reduced until the load drops below the adjusted value, after which the frequency is increased again to the previous value. CP. 2 displays "SLL" when the function is active.
CP.14
CP.15
on off
on
off
Adjustment range: 10...200%, 200% = off Resolution: 1 % Factory Setting: 200 % Customer adjustment: _______ %
t
LAD-stop
t
Current limit
f
actual
f
set
t
9F4-S Instuction Manual
Operation of the Unit
Speed search
Voltage stabilization
When starting the frequency inverter into a spinning motor, an E.OC fault can be triggered because of the difference between the actual motor speed and the inverter set speed. By activating speed search, the inverter searches for the actual motor speed, adjusts its output frequency to match. It will then accelerate with the adjusted ramp time to the given set value. During speed search CP.2 displays "SSF". This parameter deter­mines under which conditions the function will operate.
Adjustment range: 0...7 Resolution: 1 Factory setting: 0 Customer adjustment: _______
Value Condition
0 function off 1 control release turned on 2 power on 3 control release & power on 4 after fault reset 5 after reset & control release 6 after reset & power on 7 all the above
This parameter can be used to regulate the output voltage in relation to the rated frequency. Voltage variations at the input as well as in the DC bus will have only a small influence on the output voltage (V/Hz­characteristic). The function can be used to adapt the output voltage for special motors. In the example below the output voltage is stabilized at 230 V (The graph shows 0% boost).
Adjustment range: 150...649 V, off Resolution: 1 V Factory setting: off Customer adjustment: _______ V
U
VI , V
N/UA
O
250 V
CP.17 = 230 V
190 V
CP.5 = 50 Hz
VO at VI = 250V unstabilized
VO at VI = 250V stabilized
VO at VI = 190V stabilized
VO at VI = 190V unstabilized
VI = input voltage VO= output voltage
f
10 F4-S Instuction Manual
Operation of the Unit
POWER TRANSMISSION
Slip compensation
Autoboost
Slip compensation reduces speed variations caused by changes in the load. The function will increase the output frequency, as the load current of the motor increases, to maintain the same motor speed. To activate the function, set the value at 1.00 and optimize as directed in the diagram below
Adjustment range: -2.50...2.50 Resolution: 0.01 Factory setting: 0.00 (= off) Customer adjustment: _______
Autoboost gives automatic I*R-compensation. When the load torque increases, the additional resistive losses reduce the magnetizing current in the motor, leading to a reduction in motor speed. To compensate, auto boost can be used to automatically increase the applied motor voltage as the motor load increases. To activate the function set the value to 1.00 and optimize as directed below. After making an adjustment, check the response by monitoring the motor voltage. When the load is removed, the voltage should drop to a lower level. If it does not, reduce the value of CP.19.
Adjustment range: -2.50...2.50 Resolution: 0.01 Factory setting: 0.00 (= off) Customer adjustment: _______
Slip compensation and autoboost functions use a model of a standard motor equal in power to the inverter rating. When using a special motor or in case of inverter oversizing, both functions should be deactivated.
A
B
C
Torque
Motor Speed
Motor Speed
Motor Speed
Motor load
t
t
t
t
Example
Torque
1) No compensation Standard motor
1
2
3
Speed
curve,speed decreases with increasing torque
2) Good compensation speed remains stable with increasing torque
3) Over compensation speed is increased too much
Slip compensation and autoboost adjustment steps see curves A,B,C above.
1. Measure "no load" speed with tachometer. Apply the load to the motor and the speed will drop as in curve A.
2. To begin compensation, set CP.18 and CP.19 to 1.00. Motor speed should increase.
3. If speed is still below "no load" value, increase CP.19. until speed does not change with further increase in CP.19. See curve B.
4. Increase CP.18 to compensate for the remaining speed difference. See curve C.
5. Verify output voltage drops when load is removed.
11F4-S Instuction Manual
Operation of the Unit
DC-braking
During DC-braking, the motor is not decelerated by a controlled ramp. Quick braking without regen voltage can be achieved by applying a DC voltage to the motor winding. This parameter determines how the DC­braking is triggered.
Value Mode of Activation 0 DC-braking deactivated 1 DC-braking activates when direction signal is removed and
the output frequency has reached 0Hz. Braking time is dependent on CP.21 or until a direction of rotation signal is given.
2 DC-braking activates as soon as the direction signal is
removed. Braking time dependent on the actual frequency.
3 DC-braking, activates as soon as the direction of rotation
changes. Braking time dependent on the actual frequency.
4 DC-braking activates when rotation signals are removed and
the actual frequency goes below 4 Hz. 5 DC-braking, when the actual frequency goes below 4 Hz. 6 DC-braking, activates when the set value goes below 4 Hz. 7 DC-braking deactivated 8 DC-braking deactivated 9 DC-braking before the acceleration ramp when a direction
signal is given. The time is dependent on CP.21.
Braking time
Factory setting: 0 Note: Enter-Parameter Customer adjustment: _______
The actual braking time is calculated using one of the two methods listed below. The value of CP.20 determines which one is used.
- entered time = braking time
- entered time relates to 100 Hz and increases/decreases proportionally to the actual frequency.
Adjustment range: 0.00...100 s
f
100Hz
Resolution: 0.01 s
f
Factory setting: 10 s
actual
Customer adjustment: _______
Calculation of the braking time:
tbrake
actual
CP.21 x f
=
actual
time brake actual
CP.21
100 Hz
12 F4-S Instuction Manual
Operation of the Unit
POWER TRANSMISSION
Relay output
The relay output (terminals 1,2,3) is adjusted as a fault relay at the factory. This parameter can adjust the function of the output to any function listed in the table below.
Value Function
0 No function 1 On when unit has voltage applied to it 2 Fault relay 3 No function 4 Overload alert signal (10s before inverter switch off) 5 Over temperature inverter alert signal 6 Over temperature motor alert signal (10s before switch off) 7 No function 8 Stall load level (CP.15) exceeded
9 LA-/LD-Stop load level (CP.14) exceeded 10 DC-braking active 11 No function 12 Load level (CP.3) > 100% 13 No function 14 Actual value=set value (CP.2 = Fcon or rcon only;
not during noP, LS, error, SSF) 15 Acceleration (CP.2 = FAcc, rAcc, LAS) 16 Deceleration (CP.2 = FdEc, rdEc, LdS) 17 Forward rotation (not during noP, LS error) 18 Reverse rotation (not during noP, LS error) 19 Actual direction of rotation = set direction of rotation 20 Actual frequency > frequency level CP.23 21 Set frequency > frequency level CP.23 22 No function 23 Operating signal (active after initialization; off when fault occurs) 24 Run signal 25 No function
Frequency level
Factory setting: 2 Note: Enter-Parameter Customer adjustment: _______
This parameter determines the switching point for the relay output terminals 1,2,3 when CP.22 = "20 or 21
After the switching of the relay, the frequency can move within a 0.5 Hz window, without the relay changing states.
Adjustment range: 0.0...409.58 Hz Resolution: 0.0125 Hz Factory setting: 4 Hz Customer adjustment: _______
13F4-S Instuction Manual
Drive mode
2.7 The "Drive Mode"
2.7.1 Start / Stop "Drive Mode"
The drive mode is an operating mode of the F4-S inverter used to start the drive manually through the digital operator. After applying a signal to the control release terminal 14, the set frequency and rotation direction can be adjusted by the buttons on the digital operator. In order to activate the drive mode, a password in CP.0 must be entered. Refer to page 20 for password information. The display changes as follows.
Status
Direction of rotation
F=forward / r=reverse
At first the inverter is in standby mode
By pressing the motor accelerates to and runs at the adjusted value
START
noP = no control release signal /
LS = neutral position /
50.0 = actual frequency
STOP
By pressing the motor decelerates to 0 rpm and returns to standby mode.
2.7.2Changing Direction of Rotation
2.7.3 Speed Setting
2.7.4Leaving "Drive Mode"
ENTER
Pressing changes direction of rotation
The set frequency can be changed by pressing or while holding the key down.
To exit the drive mode the inverter must be in standby (display shows noP or LS). Press the FUNC and ENTER keys simultaneously for about 3 seconds in order to leave the drive mode. The CP-parameters appear in the display.
F/R
FUNC.
SPEED
FUNC.
The display changes when is pressed. The set frequency is displayed.
START
SPEED
STOP
FUNC.
SPEED
14 F4-S Instuction Manual
+
ENTER
F/R
for 3 seconds
Error Diagnosis
POWER TRANSMISSION
3. Error diagnosis
Error messages are represented with an "E. " followed by a code that defines the type of error. When an error occurs, inverter operation stops and the motor is no longer controlled by the inverter. The errors and their causes are described below.
Undervoltage
Occurs, when the DC bus voltage falls below the permissible value. (for 230V units 255VDC, for 460V units 425VDC)
Possible Causes
- input voltage too low or unstable
- inverter sized too small for given load
- missing input phase or input not connected properly
- connection to an unbalanced supply (i.e. corner ground delta)
Overvoltage
Occurs, when the DC bus voltage rises above the permissible value. (for 230V units 400VDC, for 460V units 800VDC)
Possible Causes
- input voltage too high
- voltage spikes on supply voltage
- PF correction capacitor switching at sub-station
- deceleration time too short and or braking resistor not connected.
Possible solutions
- install boosting transformer to increase voltage
- step up to next larger sized inverter
- check protective fusing for blown fuses, verify connections
- install to Y isolation transformer between inverter and main supply voltage
Possible solutions
- install buck transformer to decrease voltage
- install line choke on input to inverter
- install buck transformer or choke on inverter input
- lengthen decel time or add/connect braking resistor
Overcurrent
Occurs, when the peak current level of the inverter has been exceeded or during a ground fault condition. For specific current levels consult the power stage instruction manual and refer to the technical data section.
Possible causes
- motor larger than recommended for inverter size
- acceleration or deceleration times too short
- voltage boost (CP.6) set too high
- rated frequency (CP.5) of inverter is not adjusted correctly
- 50 Hz 400V motor running on inverter connected to 480V
Overload
Occurs when inverter load is greater than 105% for longer than the allowable time. Consult inverter specifications. See also E.nOL .
Possible causes
- motor larger than recommended for inverter size
- increased friction or jam in the mechanical system
- motor incorrectly wired
- rated frequency (CP.5) of inverter is not adjusted correctly
- 50 Hz 400V motor running on inverter connected to 480V
Possible solutions
- increase size of inverter, consult inverter specifications
- lengthen times and/or activate LAD stop function (CP.14)
- lower adjusted value
- check motor rated frequency and adjust inverter rated frequency the same except in case listed below
- change rated frequency from 50Hz to 60 Hz when input voltage is 460V or greater
Possible solutions
- increase size of inverter, consult inverter specifications
- check machine for wear, clear obstructions
- verify motor connection
- check motor rated frequency and adjust inverter rated frequency the same except in case listed below
- change rated frequency from 50Hz to 60 Hz when input voltage is 460V or greater
15F4-S Instuction Manual
Error Diagnosis
Cooling down phase completed
After an E.OL error you must wait for the inverter to cool down. This message appears after the cooling down phase is completed. The E.OL error can only be reset after this message is displayed. Removing the supply voltage will not defeat the cool down period; leave supply voltage on until message is displayed.
Overheat
Possible Causes
- insufficient cooling
- insufficient cooling
- ambient temperature too high
- cooling fan (when installed) not functioning
External Overheat
Occurs, when the inverter heat sink temperature is greater than 158°F.
Occurs when resistance between "OH terminals becomes greater than 1650 ohms.
Possible Causes
- factory jumper loose (not using this function)
- ambient temperature around motor too high
- motor overload, see E.OC and E.OL causes
- Motor temperature sensor cable broken
Possible solutions
- observe proper mounting clearances
- clear heatsink of all dirt and debris
- install cooling device to reduce air temp below 113°F
- check for fan obstructions, blades should spin freely.
Possible solutions
- tighten black jumper wire between OH terminals
- install cooling device to reduce air temp
- see E.OC and E.OL solutions
- repair cable
Overheat cleared
Internal or external temperature has dropped to a safe level. Error "E. OH" can be reset.
Charging relay error
Occurs when the charging relay does not close after the DC bus voltage reaches its normal operating level.
Possible Causes
- see causes listed under E.UP
- charge relay or charge resistor has failed
Possible solutions
- see solutions listed under E.UP
- replace unit with new unit and return old unit for repair
16 F4-S Instuction Manual
Glossary
4. Glossary
POWER TRANSMISSION
Analog/Digital Common
EMC
Energy-Saving Function
Frequency-dependent Switch
Actual Value
The F4-S inverter has potential separated (galvanically isolated) digital inputs and power supply. With this design, electrical noise and leakage currents are greatly reduced. As a result, the digital common (6) serves as a reference for the power supply and all digital inputs. The analog common (9) serves only as a common for the analog signals. For best results, it is important to avoid connecting these two commons together.
Electro- magnetic compatibility, guidelines for reducing high frequency interference caused by the inverter.
When motors are running under "no-load" conditions, the voltage can be reduced, and as a result energy can be saved.
Relay or transistor output that activates at a preset frequency.
A value that is measured by sensors in the inverter or a value that is calculated from a measured value and a preexisting condition.
LA-Stop
RS232/485
Set Value
Speed Search
Stall
Acceleration stop, prevents over current errors during acceleration by stopping the ramp. The current level is specified by the max. ramp current (CP.14).
RS232, is the standard serial interface for connection between an inverter and computer or PLC with a cable length of 45 feet maximum . RS485, is the standard serial interface for multiple inverters connected to a computer or PLC . Maximum cable length is 3000 feet.
The preset analog or digital value with which the frequency inverter shall operate.
Speed search prevents an over current error when starting the inverter into a running motor. The motor speed is determined and the inverter begins to accelerate the motor at this frequency.
The Stall-function protects the inverter against an E.OC error while running at a constant speed. When exceeding the level adjusted with CP.15, the output frequency is reduced until the load level drops below the level in CP.15.
17F4-S Instuction Manual
Index
5. Index
A
Acceleration stop 17 Acceleration time 5, 7, 19 Actual frequency display 5, 6, 19 Actual load 5, 6, 19 Actual V alue 17 Analog inputs 2 Analog output 2 Autoboost 5, 11, 19
B
Basic adjustment 7 Boost 5, 7, 19 Braking time 5, 19
C
Change direction 14 Common 2 Control release 2 Cooling down phase 16 Current limit 9 Current limit resistor error 16
D
DC-braking 5, 12, 19 Deceleration time 5, 8, 19 Digital inputs 2 Digital common 2 Drive Mode 14
K
Keyboard 3, 4
L
LAD -stop 9, 17 LED 3
M
Max. constant current 5, 9, 19 Max. r amp current 5, 9, 19 Maximum frequency 5, 8, 19 Minimum frequency 5, 8, 19 Modulation 6, 14
O
Operating Display 6 Optimize 11 Overcurrent 15 Overheat 16 Overload 15 Overvoltage 15
P
Pass word input 5, 19, 20 Peak load 5, 6, 19 Peak value 6
R
V
V oltage stabilization 5, 10, 19
X
X1 2
E
EMC 17 Energy-Saving Function 17 Error diagnosis 15
F
Fixed frequency 2, 5, 8, 19 Forward 2 Frequency v alue 5, 13, 19 Frequency-dependent s witch 17
I
I*R - compensation 11 Interface operator 3 Interference voltage 2 Inverter status display 5, 6, 19
Rated frequency 5, 7, 19 Relay output 2, 5, 13, 19 Releasing 5 RS232/485 3, 17
S
Set value input 2 Set-point value 17 Slip compensation 5, 11, 19 Special adjustments 9 Speed search 5, 10, 17, 19 Stall-function 17 Start / Stop 14
U
Undervoltage 15
18 F4-S Instuction Manual
Quick Reference
POWER TRANSMISSION
6. Quick reference
Display Parameter Adjust. range Resolution Customer setting
CP. 0 Password input 0...9999 1 ­CP. 1 Actual frequency display Read only 0.1 Hz ­CP. 2 Inverter status display Read only - ­CP. 3 Actual load Read only 1 % ­CP. 4 Peak load Read only 1 % ­CP. 5 Rated frequency 0...409.58 Hz 0.0125 Hz ____________ CP. 6 Boost 0...25.5 % 0.1 % ____________ CP. 7 Acceleration time 0.01...300 s 0.01 s ____________ CP. 8 Deceleration time 0.01...300 s 0.01 s ____________ CP. 9 Minimum frequency 0...409.58 Hz 0.0125 Hz ____________ CP.10 Maximum frequency 0...409.58 Hz 0.0125 Hz ____________ CP.11 Fixed frequency 1 0...409.58 Hz 0.0125 Hz ____________ CP.12 Fixed frequency 2 0...409.58 Hz 0.0125 Hz ____________ CP.13 Fixed frequency 3 0...409.58 Hz 0.0125 Hz ____________ CP.14 Max. ramp current 10...200 % 1 % ____________ CP.15 Max. constant current 10...200 % 1 % ____________ CP.16 Speed search 0...7 1 ____________ CP.17 Voltage stabilization 150...649 V,oFF 1 V ____________ CP.18 Slip compensation -2.50...2.50 0.01 ____________ CP.19 Autoboost -2.50...2.50 0.01 ____________ CP.20 DC-braking 0...9 1 ____________ CP.21 Braking time 0...100 s 0.01 s ____________ CP.22 Relay output 0...25 1 ____________ CP.23 Frequency level 0...409.58 Hz 0.0125 Hz ____________
The function key (FUNC) changes between the parameter value and parameter name.
With UP ( ) and DOWN ( ), the value of the parameter or the parameter number is increased/ decreased. The values of "Read Only Parameters" can not be changed.
START
Value Name
FUNC.
SPEED
STOP
START
STOP
19F4-S Instuction Manual
Passwords
7. Passwords
A - Locking the
CP-Parameters from change (read only)
B - Releasing the CP-Parameters, allowing changes
FUNC. SPEED
START
ENTER
F/R
FUNC.
SPEED
FUNC. SPEED
START
ENTER
F/R
C - Activating "Drive Mode"
D - Leaving "Drive Mode"
FUNC. SPEED
FUNC. SPEED
+
ENTER
F/R
FUNC.
SPEED
XX
START
ENTER
F/R
FUNC.
SPEED
for 3 seconds
20 F4-S Instuction Manual
POWER TRANSMISSION
Special Notice to Customer
Prior to delivery all products pass several quality and performance inspections in order to guarantee the product is free from defects in manufacturing. When used in accordance with the operating instructions, failure of the unit is not likely. However, if you have reason for concern please contact KEBCO at 800-899-3226 and ask for inverter technical support. From this point our technical support engineers can help you determine the cause of the problems and also the proper solution.
Listed values in this manual are standard values only and do not pertain to special units. We reserve the right to make technical changes without notification.
KEBCO Limited Warranty
KEBCO will repair or replace, at KEBCO's discretion, any inverter which shows signs of defect in material, workmanship or fails to meet factory specifications with in one year from original date of shipment from KEBCO in St. Paul. The serial number will be used to track the shipping date. Operation of the inverter outside the rated specifications printed in the instruction manuals will void the warranty.
KEBCO does not assume any liability ( cost of removal, cost of installation, down time, production delays, or damage to other items associated with the inverter) for failures which occur during or after the warranty period.
To make a warranty claim contact the Electronic repair department at the number listed above, and request a Return Goods Authorization (RGA) number. The inverter is to be shipped prepaid to the address listed below. Suitable packaging must be provided to prevent the inverter from incurring damages during shipping as damages of this nature will void the warranty.
KEBCO will inspect the inverter to determine the cause of the problems in the inverter and will repair or replace the inverter at its discretion.
KEBCO Inc. Attn. ELECTRONIC REPAIR (RGA#) 1335 Mendota Heights Road St. Paul, MN 55120
POWER TRANSMISSION
KEBCO Inc. • USA Headquarters 1335 Mendota Heights Road St. Paul, MN 55120 PH:800-899-3226 / 651-454-6162 FAX:651-454-6198 WEB:www.kebco.com
With Sales Offices in: Atlanta, Georgia Columbus, Ohio Dallas, Texas
KEBCO 0S.F4.0EB-K120 01/00
Loading...