Keba Kemro KeTop T10 Project Engineering Manual

Page 1
Kemro
KeTop T10
Project engineering manual V1.02
Translation of the original manual
Page 2
Document : V1.02 / article no.: 1008509 Filename : t10_pjen.pdf Pages : 91
.
All rights reserved.
KEBA AG Headquarters: Gewerbepark Urfahr, 4041 Linz, Austria, Phone: +43 732 7090-0, Fax: +43 732 7309-10,
For information about our subsidiaries please look at www.keba.com.
keba@keba.com
Page 3
KeTop T10 Record of Revision
Record of Revision
Version Date Change in chapter Description changed by
1.00 04-2013 Newly created swb, ekr
1.01 03-2014 Several Several updates swb
1.02 10-2014 Several No enabling control electronics ekr
Project engineering manual V1.02 3
Page 4
Page 5
KeTop T10

Table of Contents

Table of Contents
1 Introduction....................................................................................................................... 9
1.1 Purpose of the document........................................................................................ 9
1.2 Preconditions.......................................................................................................... 9
1.3 Intended Use of the Handheld Terminal............................................................... 10
1.4 Notes on this document........................................................................................ 11
1.4.1 Contents of document............................................................................ 11
1.4.2 Not contained in this document.............................................................. 12
1.5 Documentation for further reading........................................................................ 12
1.6 Information about MD 2006/42/EC........................................................................ 12
1.6.1 Definition of terms.................................................................................. 12
1.6.2 Quantitative safety relevant specifications for emergency stop-
button and enabling control device......................................................... 12
1.6.3 Relationship between Performance Level and Safety Integrity
Level....................................................................................................... 13
1.6.4 Abbreviations.......................................................................................... 13
2 Safety notes.................................................................................................................... 14
2.1 Representation...................................................................................................... 14
2.2 General safety instructions.................................................................................... 14
2.3 Personnel safety instructions................................................................................ 16
2.4 Transport Conditions............................................................................................. 16
3 System overview............................................................................................................. 17
3.1 Functions of KeTop T10........................................................................................ 17
3.2 Integration of the KeTop T10 into robot control..................................................... 18
3.3 Using KeTop T10 for jogging a robot.................................................................... 19
3.3.1 Suggestion for jog functions................................................................... 20
4 Description of the product............................................................................................. 22
4.1 Front view.............................................................................................................. 22
4.2 Rear view.............................................................................................................. 23
4.3 Side view............................................................................................................... 23
4.4 Ergonomic Features.............................................................................................. 23
4.5 Housing................................................................................................................. 24
4.6 Type Plate............................................................................................................. 24
5 Display and operating elements.................................................................................... 25
5.1 Membrane keypad................................................................................................ 25
5.1.1 Key assignment...................................................................................... 25
5.2 Joystick................................................................................................................. 26
5.3 Display.................................................................................................................. 26
6 Connection and wiring................................................................................................... 28
6.1 Power supply......................................................................................................... 28
6.2 Emergency Stop Button and grey Stop Button..................................................... 28
Project engineering manual V1.02 5
Page 6
Table of Contents
KeTop T10
6.3 Enabling Control Device........................................................................................ 29
6.3.1 Functioning............................................................................................. 29
6.3.2 Example of Connection with control relay (PILZ PNOZ)........................ 31
6.4 Foreseeable Misuse of Enabling control device.................................................... 33
6.5 Ethernet................................................................................................................. 33
6.6 Connector plug...................................................................................................... 34
6.6.1 Pin assignment....................................................................................... 34
7 Operating behaviour....................................................................................................... 35
7.1 Start-up................................................................................................................. 35
7.2 Referencing during operation ............................................................................... 36
8 Configuration.................................................................................................................. 37
8.1 Connection KeTop T10 - PC................................................................................. 37
8.2 Configuration of the KeTop T10............................................................................ 38
9 Diagnostics..................................................................................................................... 39
10 Maintenance.................................................................................................................... 41
11 Disposal........................................................................................................................... 42
11.1 Disposal of the module.......................................................................................... 42
12 Technical Data................................................................................................................ 43
12.1 In general.............................................................................................................. 43
12.2 Environmental conditions...................................................................................... 43
12.3 Interface................................................................................................................ 43
12.4 Mechanical properties........................................................................................... 43
12.5 E-Stop ratings (respective grey halt-button).......................................................... 44
12.6 Enabling control device......................................................................................... 44
13 Options............................................................................................................................ 45
13.1 Grey stop switch.................................................................................................... 45
14 Accessories..................................................................................................................... 46
14.1 Wall bracket KeTop T10........................................................................................ 46
14.1.1 Dimensions............................................................................................. 46
14.2 Junction Box JB 001............................................................................................. 46
14.2.1 Views and basic dimensions.................................................................. 47
14.2.2 Connectors............................................................................................. 48
14.2.3 Connection diagram............................................................................... 48
14.2.4 Shielding inside the Control Cabinet...................................................... 49
14.2.5 Mounting Instructions............................................................................. 50
14.2.6 Technical data of Junction Box JB 001.................................................. 51
14.3 KeTop CB211 Connection Box............................................................................. 51
14.3.1 Views and basic dimensions.................................................................. 52
14.3.2 Interior view............................................................................................ 53
14.3.3 Technical data of the connection terminals............................................ 53
14.3.4 Drilling template for wall mounting......................................................... 54
14.3.5 DIN Rail Holder Mounting Set KeTop DR200........................................ 55
14.3.6 Use of Connection Box........................................................................... 56
14.3.7 Minimum Bending Radius of Cable........................................................ 56
Project engineering manual V1.026
Page 7
KeTop T10 Table of Contents
14.3.8 Accessories............................................................................................ 57
14.3.9 Technical Data of Connection Box KeTop CB211................................. 57
15 EC directives and standards......................................................................................... 58
15.1 EC directives......................................................................................................... 58
15.2 Standards.............................................................................................................. 58
16 Declaration of conformity.............................................................................................. 60
16.1 EC Declaration of Conformity................................................................................ 60
17 Appendix: Machinery Safety.......................................................................................... 61
17.1 "Hazard and Risk Analysis"................................................................................... 62
17.2 "Principles for the Integration of Safety"................................................................ 62
17.3 "Technical Construction File"................................................................................ 63
17.4 "State of the Art".................................................................................................... 63
17.5 "Recognition of Conformity by means of Harmonised Standards"........................ 64
17.6 Selection of Performance Level and Safety Categories in accordance
with EN ISO 13849-1............................................................................................ 64
17.7 Application of Handheld Terminals in Special Operating Modes.......................... 65
17.8 Information about the Emergency Stop Button..................................................... 66
17.9 Application of Emergency Stop Button and Stop Button on the Handheld
Terminal................................................................................................................ 67
17.10 Information about enabling control devices........................................................... 70
18 Appendix: Electromagnetic Compatibility................................................................... 72
18.1 The electromagnetic environment – interference sources, interference
sinks and coupling paths....................................................................................... 72
18.2 EMC measures on KeTop..................................................................................... 75
19 Appendix: Icon sets........................................................................................................ 78
19.1 Predefined internal icons....................................................................................... 78
19.2 Icons with 64 x 64 pixels for the application (Icon set 2)....................................... 79
19.3 Symbols with 32 x 32 pixels for the application (Icon set 3).................................. 81
20 Appendix: Status and error codes................................................................................ 85
20.1 Status codes......................................................................................................... 85
20.2 Codes for errors or warnings................................................................................. 86
21 Appendix: KVC telegrams on KeTop T10..................................................................... 90
Project engineering manual V1.02 7
Page 8
Page 9
KeTop T10 Introduction

1 Introduction

1.1 Purpose of the document

This document describes the hand-held terminal KeTop T10. This document contains all specifications required by machinery directive
2006/42/EC.
Information
This manual is not adressed to end costumers! Necessary safety notes for the end costumer have to be taken into the costumer manual in the respective national language by the machine builders and system providers.

1.2 Preconditions

This document contains information for following persons with corresponding preconditions:
Target group Prerequisite knowledge and ability
Technical basic education (advanced technical education, engineering degree or corresponding professional experience),
Project engineer
Electrician
Knowledge about:
the method of operation of a PLC,
safety regulations,
the application.
Specialized training in the electro-technical field (in accordance with industrial training guidelines).
Knowledge in:
safety regulations,
wiring guidelines,
circuit diagrams,
correct installation of electrical connections.
Project engineering manual V1.02 9
Page 10
Introduction
Target group Prerequisite knowledge and ability
Technical basic education (advanced technical education, engineering degree or corresponding professional experience),
Knowledge about:
Start-up technician
Service technician
safety regulations,
the method of operation of the machine or system,
fundamental functions of the application,
system analysis and troubleshooting,
the setting options at the operating devices.
Technical basic education (advanced technical education, engineering degree or corresponding professional experience),
Knowledge about:
the method of operation of a PLC,
safety regulations,
the method of operation of the machine or system,
diagnosis possibilities,
systematic error analysis and troubleshooting
KeTop T10

1.3 Intended Use of the Handheld Terminal

The intended use of the KeTop T10 covers tasks from watching and parame­trizing up to operating of machines e.g.:
Injection moulding machine
Robots
Machine tools
Textile machines
Printing machines
Theater backdrops
and similar
in normal operating modes
Automatic as well as
Setting
Teaching
Testing
and similar
in half automatic or manual mode. Enabling control devices and an optional emergency stop button or halt-button
are available as savety features.
Project engineering manual V1.0210
Page 11
KeTop T10
Handheld terminals which are not connected permanently must not be equip­ped with a red-yellow emergency shutdown button, therefore a gray stop button is available.
All savety function are realized with two circuts in order to meet the require­ments of category 4 PL e in accordance with EN ISO 13849-1 considering m the B
values of the savety elements.
10d
The selection of the Handheld Terminal which is suitable for the machine and the projecting of the additional functions must obey the necessary hazard analyses and risk assessment bounded by law.
For intended use of the Handheld Terminal also please pay attention to the appendices.

1.4 Notes on this document

This manual is integral part of the product. It is to be retained over the entire life cycle of the product and should be forwarded to any subsequent owners or users of the product.
Introduction
Information
This manual also applies to identically constructed and functional identically costumer variants of the KeTop T10.
Because of the fact that costumer variants may differ in their appearance (e.g. with a different front cover) from the KEBA standard variant, the pictured de­vices used in this manual may differ in their appearance from the devices used by you.
Information
Note the datasheet provided in the delivery if there are any differences be­tween the KEBA standard variant and the costumer variant.

1.4.1 Contents of document

Safety notes and transport conditions
General product description
Display, operating elements and keypad
Connection and wiring
Configuration and operating instructions
Options
Accessories
Technical Data
CE Conformity, Directives and Standards
Project engineering manual V1.02 11
Page 12
Introduction

1.4.2 Not contained in this document

Mask description of the application
Software

1.5 Documentation for further reading

If certificates (e.g. UL certificate) are required they can be purchased from KEBA on request.

1.6 Information about MD 2006/42/EC

1.6.1 Definition of terms

This user's manual corresponds to machinery directive 2006/42/EC. To avoid ambiguity for users the following table shows the comparison of the
old terms of MD 98/37/EC and the new ones of MD 2006/42/EC.
KeTop T10
This term replacement is also fulfilled in the corresponding standard EN ISO 13850:2008.
98/37/EC 2006/42/EC
emergency switching off (chap. 1.2.4) emergency stop (chap 1.2.2)
Within standard EN 60204-1 the following term has changed:
EN 60204-1:1997 EN 60204-1:2006
Enabling device Enabling control device (chapter 10.9)
In this manual the new terms of MD 2006/42/EC are used.

1.6.2 Quantitative safety relevant specifications for emergency stop-button and enabling control device

Emergency stop-button and enabling control device (Enabling device)
KEBA specifies a B specified by KEBA.
Explanation: KEBA solely delivers the control element, but no evaluation of the element. The customer has to connect the emergency stop and the enabling control device to his application on his own. Depending on the connection of the emergency stop and the enabling control device to the machine the SIL­or category and PL-value can be determined.
-value. Other values (e.g. SIL, PL, Category) cannot be
10d
The B
-value is declared in the manuals at chapter "Technical Data" ("Emer-
10d
gency stop" respective "Enabling Control Device".
Project engineering manual V1.0212
Page 13
KeTop T10 Introduction

1.6.3 Relationship between Performance Level and Safety Integrity Level

When evaluating safety functions by IEC EN 62601 the PL can be transformed into SIL by following the equivalence table of EN ISO 13849-1.
Table 4 (EN ISO 13849-1) - Correlation of Performance Level (PL) and Safety Integrity Level(SIL)
Performance Level (PL) by
Table 3 (EN ISO 13849-1) - Performance Level (PL)
Performance Level (PL)

1.6.4 Abbreviations

Abbreviation Term Meaning
B
10d
MTTF
d
DC Diagnostic Coverage Diagnostic coverage
PL Performance Level
PFH SIL Safety Integrity Level Safety integrity level
Safety Integrity Level (SIL) by
EN ISO 13849-1
a no corresponding value b 1 c 1 d 2 e 3
IEC 61508-1
Average probability of a dangerous
breakdown per hour 1/h
a b c d e
Number of cycles until 10% of the
-
components fail dangerously (per channel)
Mean Time to Dangerous Failure
Mean time to dangerous failure (per channel)
Discrete level that specifies the ca­pacity of safety devices to execute a safety function under foreseeable conditions.
Probability of Failure per Hour Probability of failure per hour
-5
≥ 10
to < 10
3 x 10-6 to < 10
-6
≥ 10
to < 3 x 10
-7
≥ 10
to < 10
-8
≥ 10
to < 10
-4
-5
-6
-6
-7
Project engineering manual V1.02 13
Page 14
Safety notes

2 Safety notes

2.1 Representation

At various points in this manual you will see notes and precautionary warnings regarding possible hazards. The symbols used have the following meaning:
DANGER!
indicates an imminently hazardous situation which will result in death or serious bodily injury if the corresponding precautions are not taken.
WARNING!
indicates a potentially hazardous situation which can result in death or se­rious bodily injury if the corresponding precautions are not taken.
CAUTION!
means that if the corresponding safety measures are not taken, a potentially hazardous situation can occur that may result in property injury or slight bodily injury.
KeTop T10
CAUTION
CAUTION used without the safety alert symbol indicates a potentially haz­ardous situation which, if not avoided, may result in damage to property.
This symbol reminds you of the possible consequences of touching elec­trostatically sensitive components.
Information
Useful practical tips and information on the use of equipment are identified by the “Information” symbol. They do not contain any information that warns about potentially dangerous or harmful functions.

2.2 General safety instructions

The device was developed, manufactured, tested and documented in ac-cord­ance with the applicable safety standards. If you follow the instructions re­garding safety and use as described in this manual, the product will, in the normal case, neither cause personal injury nor damage to machinery and equipment.
The instructions contained in this manual must be precisely followed in all cir­cumstances. Failure to do so could result in the creation of potential sources of danger or the disabling of safety features integrated in the handheld terminal.
Project engineering manual V1.0214
Page 15
KeTop T10 Safety notes
Apart from the safety instructions given in this manual, the safety precautions and accident prevention measures appropriate to the situation in question must also be observed.
Handling of KeTop
You have chosen a high-quality KeTop that is equipped with highly sensitive state-of-the-art electronics. To avoid malfunctions or damage through improp­er handling, follow these instructions during operation.
WARNING!
The following application areas are expressly excluded for the KeTop:
Use in areas prone to explosion or fire
Use in mining
Outdoor use
Other products must be used for these applications!
CAUTION
The KeTop housing must not be opened. Otherwise safety and tightness of the housing can no longer be ensured.
Make sure that nobody can fall over the cable to avoid that the device falls to ground.
Take care not to squeeze and thus damage the cable with any object.
Do not lay the cable over sharp edges to avoid damaging the cable sheath.
If you do not use the device, hang it into the wall bracket provided for stor-
age.
Do not lay down the device with the operating side facing down to avoid damaging the operating elements.
Never lay the device onto unstable surfaces. It could fall to ground and thus be damaged.
Never lay the device close to heat sources or into direct sunlight.
Avoid exposing the device to mechanical vibrations, excessive dust, hu-
midity or to strong magnetic fields.
Never clean the device, operating panel and operating elements with sol­vents, scouring agent or scrubbing sponges. For cleaning the device, use a soft cloth and a bit of water or a mild cleaning agent.
Make sure that no foreign objects or liquids can penetrate into the device. Check at regular intervals and especially after a hard hit (e.g. a fall) the pro­tective covers of the device, if all housing screws are firmly tightened and if the housing or the cable entry is damaged.
If the device shows any defect, please send it, including a detailed error description, to your supplier or the relevant after-sales service office.
Project engineering manual V1.02 15
Page 16
Safety notes

2.3 Personnel safety instructions

WARNING!
Danger of personal injury due to electric shock!
Supply the device exclusively from power sources that have an extra low voltage (e.g. SELV or PELV according to EN 61131-2)
When using a SELV power source it can become PELV by reason of the module construction and the connectors (grounding!).
Protective low voltage circuits must always be installed safely insulated separated from circuits with dangerous voltage.
CAUTION!
Danger of fire in case of component failure!
In final application, make sure that the 24 V DC power supply to the operator panel is adequately fused! Therefore a fuse that complies with UL 248 and is rated max. 0,5 A must be used.
KeTop T10
WARNING!
For the right projecting of the Handheld Terminal the manufactorer must enforce a hazard and risk analysis. The following safety aspects must be considered:
Right cable length for limitation of workspace.
Is an emergency stop button necessary and permissible?
Is the safety category for the application sufficient?
From the operating place the operator must have a good view at the hazard
area.
The device may be operated in faultless condition only and the operating instructions must be observed.
The operator must have a sufficient educational level and must know details of intended use described in the user’s manual.
The safety advices in the following chapters must be considered absolutely.
Further informations to safety and EMC are included in the appendices.

2.4 Transport Conditions

To avoid damaging the KeTop during further or return transport, the following transport conditions must be fulfilled:
Always use the original packaging for the transport.
The environmental conditions for the KeTop (see chapter "Technical Da-
ta") must also be fulfilled during transport.
Project engineering manual V1.0216
Page 17
KeTop T10

3 System overview

The following chapters provide a brief overview of the functions, integration and use of the KeTop T10.
In general
The KeTop T10 is a machine operating device that is intended for jogging ro­bots in an intuitive way with "DirectMove". DirectMove is the name for operating a robot or a machine on the basis of position detection in or parallel to the pointing direction.
Compared to a conventional KeTop the KeTop T10 is equipped with a firmware for calculation the orientation of the device and for communication with the control, since it has a limited graphical interface.
The key benefit of the KeTop T10 is the knowledge about it’s own orientation in space. This way the KeTop T10 can be used for selecting desired directions of movements. Similar to show a direction to a human operator using ones finger. Although the KeTop T10 is designed for jogging robots, it can be used for any application, where it is useful to show directions or orientation in space by using the device itself.
System overview
An integrated emergency stop and an enabling control switch make it the per­fect operating device for any machine requiring save manual operation. The new, intuitive way of operation together with its compact size allows the oper­ator to concentrate on the operated machine instead of paying attention to the operating device.
The display of the KeTop T10 is used to display the status and shows the icons setted by the application on the control. An exception are the error codes or internal icons (e.g. compass for referencing) which are displayed directly by the KeTop T10.
The following chapters offer an overview of the following topics:
KeTop T10 functions
Connecting the KeTop T10 to an OEM control
Using the KeTop T10 for robot jogging

3.1 Functions of KeTop T10

In principle the KeTop T10 is a operating device with keyboard, joystick and a small color LCD display for showing operating modes and status. But in addi­tion to that the device has knowledge about its own orientation in space. This information is used by the robot control to handle the robot. The KeTop T10 itself has no built-in logic for robot jogging and no specific information about it. This way it is up to the controller to implement the best way of using the device in a special context.
Project engineering manual V1.02 17
Page 18
System overview
KeTop T10
The display is quite reduced in function: It only allows the selection of prede­fined icons representing mode and state information. There are several icon sets available which are stored in the KeTop T10 itself.
The KeTop T10 has an Ethernet interface which allows exchanging information with the control. The following information is exchanged between controller and the device:
state of keyboard and joystick
current orientation of the device
current selected icons for display
As a communication protocol KVC (KEBA Virtual Channel) based on UDP/IP designed by KEBA is used. The protocol also implements a transfer of param­eters. Parts of the data exchange are handled cyclically like a live check to detect connection errors between KeTop T10 is active.
The communication protocol is integrated into the firmware of the KeTop T10. The firmware also contains all (inertial) sensor evaluation to derive the orientation of the device.. Furthermore a small web server on the device allows basic diagnosis and network settings.
Inertial sensor processing
The KeTop T10 contains a 6D IMU (inertial measurement unit), consisting of 3 accelerometers and 3 gyroscopes, which measure the motion of the device in space. The sensor software contains all necessary sensor processing and state control to provide the robot control with the current orientation of the de­vice and filter undesired vibrations like e.g. from tremor of the hand of the operator.
To get reliable orientation results from the sensors, the sensors have to be calibrated at the beginning of operation. This is done automatically after power­up as soon as the device is in rest position. Due to the inertial sensors the KeTop T10 only can calculate the orientation relative to the starting orientation. Therefore before operation the KeTop T10 has to be put in a defined orientation relative to the robot. The automatically calculated orientation is stored as ref­erence direction via the reference button.
Sensor errors lead to a growing deviation of the orientation in horizontal direc­tion. To keep the quality of the orientation at a high level the KeTop T10 has to be referenced about every 10 minutes. The user can check the accuracy of the current orientation at any time by activating device's own orientation button.
The used gyro sensors (measuring angular speed), have a measurement range of 2000°/s. If this range is exceeded it is necessary to restore the original orientation by re-referencing.

3.2 Integration of the KeTop T10 into robot control

The KeTop T10 is equipped with an Ethernet interface for exchanging I/O data between device and control. The hardware interface is compatible with the
Project engineering manual V1.0218
Page 19
KeTop T10
System overview
standard devices of the KeTop product line. So KeTop T10 may be used al­ternating with another KeTop device on one control without hardware change.
Software structure
KVC is used as a communication protocol for exchanging data between device and control and provides means of:
I/O data exchange (keyboard, joystick, orientation and display information)
Connection live check
Parameterization of KeTop T10
Fig.3-1: KeTop T10 integration; Software structure
For connecting KeTop T10 to a robot control additionally to the required I/O device driver implementing KVC protocol the integration to the jog manage­ment has to be using (the jog management evaluates the user interactions with the controls of the KeTop T10 and derives mode, direction and speed for robot jogging).
KVC Server Development Kit
The KVC SDK (Server Development Kit) supports a quick implementation of the driver software for the control. The KVC SDK contains a reference server implementation for Windows delivered as source code in the programming language C and a KeTop T10 emulation that can be used for testing a KVC driver implementation.
The reference implementation is containing all operating system dependent functions in a module to make porting to different operating systems an easy task. Furthermore the reference server is integrated in a test program. This dialog based application provides all functions of the KVC communication for interactive test.

3.3 Using KeTop T10 for jogging a robot

Robot jogging usually is performed using predefined coordinate systems as world coordinates or tool coordinates. Usually the robot is moved in a desired direction by pressing a button or deflecting a joystick.
Using KeTop T10 for jogging a robot is quite similar. But instead of selecting a desired axis with a special button, the axis is shown in space with the device itself (e.g. for selecting the vertical axis the KeTop T10 is held in vertical di­rection, for jogging horizontal the KeTop T10 is held horizontal, and so on). For
Project engineering manual V1.02 19
Page 20
System overview
adjusting jog speed and positive or negative direction the joystick is used. So the direction and movement of the thumb always directly corresponds to the robot movement, which is the most intuitive way. The joystick can also be moved toward the operator to make intuitively a movement of the robot towards the operator.
The buttons on the KeTop T10 can be used for selecting different jog modes and coordinate systems. The display can be used for showing selected modes and additional information, such as error status. The following chapter gives a suggestion, how to use a KeTop T10 for jogging a robot.

3.3.1 Suggestion for jog functions

As the robot control is in charge of the jog functions, any modifications are possible. The suggested function set is a typical implementation which has proved useful in field tests by KEBA.
The KeTop T10 provides a joystick with a button function which is used for jogging or moving the robot. The jog operation can be switched between Car­tesian coordinates and robot joints. Furthermore the KeTop T10 provides a new motion mode for the alignment of the Tool Center Point (TCP) without changing the position, called "virtual handle mode".
KeTop T10
Jogging in Cartesian space
One of the following Cartesian modes can be chosen:
Free mode (free movement)
Coordinate mode - movement of the robot is aligned to coordinates (“snap-
to-grid”)
In free mode the direction of the KeTop T10 directly gives the direction of movement without aligning to a coordinate system.
In coordinate mode the directions are defined by a selected coordinate system (world / object / tool). Also several tool coordinate systems can be defined and selected. The axis of movement is selected by the direction of the KeTop T10 itself and corresponds to the axis of the coordinate system which is closes to the axis defined by the length dimension of the KeTop T10. Coordinate mode can be seen as a kind of “snap-to-grid” variant of the free motion mode.
Advantage of the free mode is that any arbitrary direction of robot motion can be achieved. Coordinate mode is useful for jogging very precisely when fine adjusting robot position.
The joystick is used to control the jog speed and in either translation or rotation. Deflecting the joystick forward and backward activates translation along the selected (= pointed with the device) axis. Deflecting left and right activates rotation around the selected axis. This way position and rotation of the robot can be changed in alternation very easy without any operation mode switching. Thus the movement of the thumb directly corresponds to the produced move­ment of the robot. A simultaneous translation and rotation is locked by the firmware. Therefore an oblique diagonal deflection of the joystick results in the
Project engineering manual V1.0220
Page 21
KeTop T10 System overview
activation of the movement (translation/rotation) which is interpreted by the device.
The direction of the KeTop T10 can be changed during active jogging at any time. This results in a continuously changing motion direction in free mode and a direction jumping from one axis of the coordinate system to the next in aligned mode (= integrated tracking functionality).
Jogging robot joints
The keypad is used for toggling jog mode between Cartesian mode and joint mode. In joint mode the joystick is used for jogging the active joint. The active joint can be selected by the keypad (keys "Plus" and "Minus").
Virtual handle mode ("grabbing")
When the joystick is pressed, the Tool Center Point (TCP) follows directly any orientation change of the KeTop T10. This gives the impression of grabbing the TCP directly and changing the orientation manually. So the KeTop T10 serves as a virtual handle of the TCP. The position of the Tool Center Point itself is unchanged. Due to safety standards the rotation speed of the robot is limited in virtual handle mode. When the KeTop T10 is rotated nearly in the allowed speed limit in grab operation, a warning is displayed, and if the speed is too high, the robot movement will be stopped.
All motion functions (translation, rotation, grab) are locked against each an­other to prevent unexpected behavior of the robot.
Project engineering manual V1.02 21
Page 22
Description of the product KeTop T10

4 Description of the product

The handheld terminal KeTop is a portable operating and display device with rugged design without an operating system. Using Ethernet, the KeTop is ideal for a great variety of applications.

4.1 Front view

Fig.4-1: Front side of the device
1
... Emergency stop switch (twin circuit) or stop
switch (option)
3 ... Joystick 4 ... Membrane keypad 5 ... Strain relief and bend protection for connection
cable
2 ... TFT display
Project engineering manual V1.0222
Page 23
KeTop T10

4.2 Rear view

Description of the product
Fig.4-2: Back side of the device
1
... Type plate
2 ... Enabling control device

4.3 Side view

Fig.4-3: Side view of the device

4.4 Ergonomic Features

Operation by right-handed and left-handed people
Easily readable display
Project engineering manual V1.02 23
Page 24
Description of the product KeTop T10
Operation with one hand possible (low weight, optimal handle situation)

4.5 Housing

Vibration- and shock resistance
Housing made of non-flammable material (UL 94-V0), impact-resistant,
withstands water, cleaning agents (alcohol and tensides), oil, drilling oils, grease and lubricants
Extremly sturdy housing. Drop-tested on industrial flooring from a height of 1.5 m (59 in).

4.6 Type Plate

1
... Manufacturer 2 ... Material name
3 ... Material number / revision 4 ... Country of origin 5 ... Serial number 6 ... Technical data (Voltage / power supply) 7 ... Date of production (month/year) 8 ... Ambient temperature 9 ... UL marking 10 ... UR marking 11 ... Manufacturer's address 12 ... CE marking of conformity
Project engineering manual V1.0224
Page 25
KeTop T10 Display and operating elements

5 Display and operating elements

Membrane keys with mechanical pressure point
Backlighted LC color display, 1,45", 65,000 colors, 128 x 128 pixels

5.1 Membrane keypad

The KeTop T10 is equipped with a membrane keypad with 10 keys, the two bottom keys have predefined functions. For the keypad assignment see "Ke­Top KVC programming manual". The keypad operation is carried out exclu­sively with the fingers.
Fig.5-1: Membrane keypad for KeTop T10
By pressing the key ( 1) the direction of the KeTop T10 gets controlled and displayed (orientation button).
To re-reference the KeTop T10 it has to be held in the desired direction, then the key (2) has to be pressed (reference button).

5.1.1 Key assignment

The keys are numbered from left to right and from top to bottom.
0
1 2
Project engineering manual V1.02 25
Page 26
Display and operating elements
3 4 5 6 7 8
9
10
The order corresponds to the position in the bit string and the KVC code, i.e. 0 for the leftmost bit, etc. The joystick button therefore is in the KVC bit pattern on the leftmost and has the KVC code 0.

5.2 Joystick

The KeTop is equipped with a 2-axis joystick inclusive joystick button. This is evaluated by the software and can be read via the KVC server.
To avoid that the joystick is damaged when the device falls to ground, a short joystick is used.
Value range: -128 to +127 per axis (256 increments)
KeTop T10

5.3 Display

All information is represented by symbols, there is no text. The display contents are generated by the control and only shown on the display. The only excep­tions are the error messages that are displayed directly on the KeTop.
The display has a size of 128 x 128 pixels and provides 13 spaces for the symbols:
Fig.5-2: Display spaces
Space Size of the symbols
0 64 x 64 1-12 32 x 32
The firmware of the KeTop T10 contains three sets of symbols with fixed def­initions. In the KVC protocol you can programme which symbols are used and how the individual symbols are arranged on the display. The selection of sym­bols used in the KVC server cannot be changed during operation of the KeTop T10. The symbols defined for the operation and eror indications (see chapter
Project engineering manual V1.0226
Page 27
KeTop T10 Display and operating elements
19 "Appendix: Icon sets" on page 78)are preset and cannot be changed or
deleted.
Project engineering manual V1.02 27
Page 28
Connection and wiring KeTop T10

6 Connection and wiring

6.1 Power supply

WARNING!
Please observe the safety-relevant information in the chapter 2.3 "Personnel
safety instructions" on page 16.
Specification of power supply lines in the TTxxx connection cable:
Cross section: AWG24 (0.24mm²)
Material: zinc-coated copper strand
Line resistance: 90 Ohm/km ( 145 Ohm/mile)

6.2 Emergency Stop Button and grey Stop Button

The emergency stop button respectively the grey stop button used on the KeTop features two circuits. The contacts are normally closed.
The red-yellow emergency stop button of the handheld terminal meets the re­quirements of the EN ISO 13850. It must be designed as an emergency stop of category 0 or category 1 (see EN 60204-1 chapter 9.2.5.4.2) on the basis of the risk assessment for the machine. The connection of the positive-break contacts to an appropriate monitoring system must meet the safety category (in accordance with EN ISO 13849-1) which is defined by means of the risk assessment (in accordance with EN ISO 14121-1) of the machine.
Optionally the KeTop is also available with a grey stop button instead of the red-yellow emergency stop button. In principal the grey stop button has the same functionality as the red-yellow emergency stop button. If the handheld terminal is not plugged in, the grey color of the stop button should avoid the usage of the non-effective (emergency) stop button in dangerous situations. For a more information about this topic see chapter "CE Conformity, Directives and Standards".
The grey stop button fulfils also all mechanical aspects of the EN ISO 13850 and differs from the emergency stop button only by its color.
Project engineering manual V1.0228
Page 29
KeTop T10 Connection and wiring
WARNING!
Not fully functional emergency stop devices may have fatal consequences! Emergency stop switches which are red-yellow marked must be effective under all circumstances in all operating modes of a machine or plant.
Store handheld terminals with not operational red-yellow emergency stop switches on a place where the operator cannot see it, so that he can not mistake the device.
Handheld terminals which are plugged in and out frequently for temporarely use, must not have a red-yellow emergency stop switch. Such devices must be equipped with a grey stop switch.
Resetting an activated emergency stop facility must not result in uncon­trolled start-up of machines or installations.
The emergency stop button does not replace other safety facilities.
The emergency stop button on the handheld terminal does not replace the
emergency stop buttones to be mounted directly on the machine.
Some mechanical errors in emergency stop switches can be recognized at operation only.
Test the function of the emergency stop switch when the device had been exposed to mechanical shock (e.g. it had been fallen on the ground).
Additionally the emergency stop switch must be tested cyclic (6 monthly). Watch the machine stopping after the emergency stop switch had been pushed.
For further informations to emergency stop switch observe chapter "Direc­tives and Standards".

6.3 Enabling Control Device

The KeTop is equipped with one enabling control device. The enabling control device consists of a 3-position operating element. An essential feature are the two-channel circuits and the forced opening according to EN 60947-1 and EN 60947-2 to the third switch position.

6.3.1 Functioning

The enabling control device can be in the following three positions:
Position Function
1 home position is not pressed
2 enabling is pressed
3 panic is pressed strong
Enabling control
device
Contacts
enabling outputs are open
enabling outputs are closed
enabling outputs are open
Project engineering manual V1.02 29
Page 30
Connection and wiring
WARNING!
The enabling control device must be tested cyclic (6 monthly) by pressing the panic position. Watch the machine performing the panic function after pressing the enabling switch.
Enabling
KeTop T10
Fig.6-1: Contact travel diagram for enabling
Panic
The pushing of the actuating elements into the panic position is evaluated in a way that the enabling position is skipped when the actuating elements are re­leased.
Fig.6-2: Contact travel diagram for panic
Project engineering manual V1.0230
Page 31
KeTop T10 Connection and wiring
Information
At the KeTop, the enabling control devices always feature two circuits.
To meet the safety category 4 PL e in accordance with EN ISO 13849-1, the enabling control device must be realized with 2 circuits and these circuits have to be dynamically monitored on short circuits and shunt currents. These two circuits have to be concurrent considering the operating cycle with respect to the B
value of the safety device. The safety category 4 PL e means that one
10d
single failure most not lead to the loss of the safety function and one single failure is detected during or before the next request (e.g switching-on or at the end of a machine cycle).
The monitoring of the simultaneity by the control relay is necessary, because otherwise maybe a failure culmination would not be recognised and this would cause the loss of safeness.
According to the EN60204-1 the enabling control devices shall be implemented in such a way, that at position 1 (Off function - the control element is activeted) and position 3 (Off function - the control element is pressed down to panic position) at least one of the stop categories 0, 1 or 2 is initialized.
For calculation of the PL for the safety function "enabling" the safety-related characteristic values (B
-values) of all involved components have to be in-
10d
cluded. For details for calculating the PL for the whole safety function see EN ISO 13849-1, chapter 6.3, appendix H and appendix I.

6.3.2 Example of Connection with control relay (PILZ PNOZ)

CAUTION
Technical data of the control relay have to be observed in the final application! Otherwise it is possible that the rated voltage tolerance of the KeTop is limited.
The following example is a support for realizing the end application.
Project engineering manual V1.02 31
Page 32
Connection and wiring
KeTop T10
Fig.6-3: Suggested wiring
... Hand-held terminal 2 ... Enabling control device
1 3 ... Hand-held terminal connection cable 4 ... 17 pin male connector 5 ... Intermediate cable 6 ... Connection box 7 ... Enabling of dangerous movement!
The grafic shows a suggested wiring of enabling switches to fulfill safety cat­egory 4 PL e for the enabling switch with PILZ control relay. Also follow the instructions described in the PILZ operating manual about the device
Project engineering manual V1.0232
Page 33
KeTop T10
Connection and wiring
PNOZ s3. For calculation of the whole safety function "enabling" the control relay and all subsequent components have to be considered.

6.4 Foreseeable Misuse of Enabling control device

Foreseeable misuse means the not allowed fixing of the enabling control de­vice in the enabling position. The foreseeable misuse of the enabling control device must be restricted.
The following measures causing the stop of the machine in the manual mode are recommended:
Inquiry of the enabling control device when turning on the machine/plant and inquiry of the enabling control device when changing the operating mode from automatic to manual (The enabling control device must not be in the enabling position.).
The enabling control device must be released within a defined period and pushed into the enabling position again. The length of the period must be defined according to the activity.
WARNING!
The enabling control device is only suitable as safety function if the oper-
The enabling control device is only used to enable commands for perform-
Only the person who operates the enabling control device is allowed to work
For further informations regarding the enabling control device please pay

6.5 Ethernet

The standard version of the KeTop is equipped with an Ethernet interface, the signals are transferred by shielded lines in the connection cable.
The following interface parameters are defined and cannot be changed:
ator activating the enabling control device recognizes the dangerous sit­uation in time so that he can immediately take the necessary measures to avoid such situations. As additional measure reduced speed of the move­ment can be necessary. The allowed speed must be determined by means of a risk assessment.
ing dangerous movements. The commands themselves must be activated by a separate operating element (key on handheld terminal).
in the dangerous area.
attention to chapter "Machinery Safety".
10 MBit/s
UDP and TCP/IP protocol
Project engineering manual V1.02 33
Page 34
Connection and wiring KeTop T10

6.6 Connector plug

The supply voltage and the signals (emergency stop, Ethernet, KVC sig­nals, ...) of the KeTop T10 are merged in one cable and are plugged via one connector to the control cabinet.

6.6.1 Pin assignment

Fig.6-4: Pin assignment connector plug
Pin No. Signal designation Description
1 24 V DC Supply voltage (24 V) 2 GND Ground 3 E-Stop Circuit 2 Emergency stop (circuit 2) 4 E-Stop Circuit 2 GND Emergency stop (ground circuit 2) 5 E-Stop Circuit 1 Emergency stop (circuit 1) 6 E-Stop Circuit 1 GND Emergency stop (ground circuit 1) 7 Enabling Device Circuit 1 Enabling control device (circuit 1) 8 Enabling Device Circuit 1 GND Enabling control device (ground circuit 1) 9 n.c. Not connected 10 n.c. Not connected 11 n.c. Not connected 12 Enabling Device Circuit 2 Enabling control device (circuit 2) 13 TD+ Ethernet (Transmit +) 14 TD- Ethernet (Transmit -) 15 RD+ Ethernet (Receive +) 16 RD- Ethernet (Receive -) 17 Enabling Device Circuit 2 GND Enabling control device (ground circuit 2)
Project engineering manual V1.0234
Page 35
KeTop T10

7 Operating behaviour

After being switched on and a short self-test, the KeTop T10 is ready for op­eration. The device tries to establish a connection to a control system which will be used to exchange data for the keyboard, the joystick, the display and the orientation. Based on the user entries the control system determines the content of the display and the actions of the robot. The device also includes a web server for diagnostics and for the configuration of the network.

7.1 Start-up

The start-up of the KeTop begins automatically after connecting the power supply and proceeds in the following order:
1) Starting of the boot loader and loading of the firmware The software of the device consists of a boot loader and of the firmware.
Firmware updates are provided only by the manufacturer.
2) Self-test During this phase the device carries out several self-tests (e.g. validity of
EEPROM contents such as symbol data, proper functioning of the sen­sors, ...) On the display, the splash screen, containing the firmware version number, the company logo and the IP address, is shown.
3) Connecting to server and calibration After the self-test the device tries to establish a KVC connection to the
control system. As long as no connection has been established, an ap­propriate symbol is shown on the display.
In parallel, the inertial sensors are calibrated. For this purpose the Ke­Top must be in an steady position (e.g. on the wall brackets). As long as the device is connected with the control system and the calibration has not been finished, the symbol "waiting for calibration" is shown on the display. If the device is not in a steady position during start-up, the calibration will be carried out later.
4) Referencing After the calibration is finished and the connection with the control system
has been established, the device has to be referenced which means the orientation of the KeTop will be defined related to the roboter. For this purpose, the KeTop has to be positioned in the desired start orientation and the reference button has to be pressed (see fig. 5-1 "Membrane key-
pad for KeTop T10" on page 25. As long as the referencing has not been
finished, the symbol "waiting for referencing" is shown on the display.
5) Start-up successful If the start-up and the initialization of the device was successful, i.e. the
KeTop has been calibrated and referenced correctly and is connected to the control system, the device can be used by the application. The symbols specified by the control system are shown on the display. If no symbol has been set by the application the display stay black.
Operating behaviour
Project engineering manual V1.02 35
Page 36
Operating behaviour KeTop T10

7.2 Referencing during operation

Sensor errors lead to a growing horizontal deviation of the orientation. There­fore the referencing of the KeTop must be repeated from time to time. The user can check the accuracy of the current orientation at any time by activating the orientation button of the KeTop (see fig. 5-1 "Membrane keypad for KeTop
T10" on page 25). The display will show a symbol with a compass indicating
the supposed referencing direction. As soon as the orientation of the device matches the supposed referencing direction, the compass needle will change its color from red to green. A necessary reset of orientation is performed by holding the KeTop T10 into the defined direction and pressing the reference button (see fig. 5-1 "Membrane keypad for KeTop T10" on page 25).
Information
Every 10 minutes the referencing of the KeTop T10 become invalid au­tomatically and the icon for "Reference lost" is shown. The operator is forced to re-reference the device.
By a fast position change (e.g. by a fall) which exceeds the measuring range, the reference can become invalid. The exceeding of the measuring range ist detected automatically.
During the heating phase of the device a higher drift of orientation can occur. This phase can last up to 30 minutes.
Long working phases or fast temperature changes can lead to a higher deviation of orientation. This can be improved by placing the KeTop T10 from time to time for approx. 20 seconds into an steady position (e.g. in the wall bracket). Thereby the inertial sensors of the device will be automatically recalibrated.
Project engineering manual V1.0236
Page 37
KeTop T10 Configuration

8 Configuration

The KeTop T10 is configured externally on a PC via web server which is a integrated on the KeTop T10. For this the KeTop T10 has to be connected with a PC.

8.1 Connection KeTop T10 - PC

The KeTop is connected by way of the junction box JB 001 (siehe chapter
14.2 "Junction Box JB 001" on page 46) via Ethernet to the PC. There are
two connection options:
Connection via switch
Direct connection
Connection via switch
In this connection option a switch is provided between the junction box and the PC. For the connection a 1:1 standard Ethernet cable is used.
Fig.8-1: Connection KeTop T10 - PC via Switch
1
... KeTop T10 2 ... Junction box JB 001
3 ... Switch/Hub 4 ... PC
Direct connection
In this connection option the KeTop T10 is connected directly via the junction box to the PC. For the connection a 1:1 standard Ethernet cable is used.
Fig.8-2: Direct connection KeTop T10 - PC
... KeTop T10 2 ... Junction box JB 001
1 3 ... PC
Project engineering manual V1.02 37
Page 38
Configuration KeTop T10
Information
If there is no connection, this is indicated by a symbol (see chapter 19
"Appendix: Icon sets" on page 78).

8.2 Configuration of the KeTop T10

After the KeTop has been connected to the PC, you can access the configu­ration mask on the PC, by opening a web browser with the address <IP address of the KeTop>/settings.shtml. At delivery, the default IP address is set to
192.68.25.11. The following configurations can be set:
Device IP-Address: Configuration of the desired IP address of the KeTop
Server IP-Address: Configuration of the IP address of the desired control
Netmask: Configuration of the subnet mask
Fig.8-3: Configuration of the addresses
The settings will be active after a restart.
Information
For questions related to the network operation please contact your network administrator.
Project engineering manual V1.0238
Page 39
KeTop T10 Diagnostics

9 Diagnostics

Current errors or warnings are shown on the display of the KeTop by a symbol (see chapter 19 "Appendix: Icon sets" on page 78).
The KeTop offers diagnostics information about the firmware version, the cur­rent network configuration and the current errors and warnings. There are three ways to show this information:
on the display of the KeTop T10 (diagnostics screen)
via the integrated web server
via KVC
A description of the status codes and errors codes can be found in the appen­dix.
Diagnostics screen
Diagnostics information can be shown on the display of the KeTop. This diag-
nosctics screen is opened by pressing and (see fig. 5-1 "Membrane
keypad for KeTop T10" on page 25).
Integrated web server
The information can also be queried via the integrated web server. The web server can be opened on a PC via an internet browser. This requires to connect the KeTop with the PC and to enter the IP address of the device in the browser.
Fig.9-1: Current settings
Configuration Description
Version Firmware version Server-IP IP adrdess of the server (control) Device-IP | MAC IP and MAC address of the KeTop Netmask Subnet mask
Project engineering manual V1.02 39
Page 40
Diagnostics KeTop T10
Configuration Description
Uptime Elapsed time since start up of the KeTop
Information about:
KVC connection
Calibrating
Referencing
Status
Selftest result
Warnings
Errors
If warnings or errors occur the corresponding error codes wil be written in the respective line. Meanings of the codes see chapter 20 "Ap-
pendix: Status and error codes" on page 85.
Status code is displayed. Meaning of the status code see chapter 20
"Appendix: Status and error codes" on page
85.
KVC
In addition, the status code of the KeTop is transferred via KVC to the control where it can be read out. For further information see "KeTop KVC programming manual".
Project engineering manual V1.0240
Page 41
KeTop T10 Maintenance

10 Maintenance

The device itself is maintenance-free.
Project engineering manual V1.02 41
Page 42
Disposal KeTop T10

11 Disposal

11.1 Disposal of the module

CAUTION
Please observe the regulations regarding disposal of electric appliances and electronic devices!
The symbol with the crossed-out waste container means that electrical and electronic devices including their accessories must not be disposed of in the household garbage.
The materials are recyclable in accordance with their labeling. You can make an important contribution to protecting our environment by reusing, renewing and recycling materials and old appliances.
Project engineering manual V1.0242
Page 43
KeTop T10 Technical Data

12 Technical Data

12.1 In general

Rated supply voltage: Maximum interruption time of supply voltage:
Inrush current: <1A Power consumption: 1.2 W (50 mA to 24 V DC)
Display:
Touchscreen: No Keypad: Equipment class: III according to EN 61131-2 and EN 50178
Protection class: IP54

12.2 Environmental conditions

Operating temperature: Storage temperature: -20 °C to +70 °C (-4 °F to 158 °F) Transport temperature: -25 °C to +70 °C (-13 °F to 158 °F) Relative humidity (non-condensing): 5 % to 95 %
Vibration resistance (operation):
Shock resistance (operation): 15 g / 11 ms (EN 61131-2)
24 V DC (rated voltage tolerance 19,2 V DC to 30 V DC according to EN 61131-2)
10 ms (acc. to EN 61131-2)
1,45'' TFT-LCD, LED-backlight, 65.000 color, 128 x 128 Pixel
65,000 color
Membrane keypad with tactile feedback
maximum 10 keys
0 °C to 45°C (32 °F to 113 °F)
(EN 61131-2)
5 Hz f < 9 Hz with 3,5 mm (0.138 in)
9 Hz f < 150 Hz with 1 g (0,035 pounds)

12.3 Interface

Ethernet:
Data transmission rate: 10 MBit/s
1

12.4 Mechanical properties

Construction:
Flammability class: UL94-V0 Dimensions:
Width: 210 mm
Height: 62 mm
Project engineering manual V1.02 43
ABS housing withstands grease, oil, lubricants, alcohol, etc.
Page 44
Technical Data KeTop T10
Depth: 75 mm Weight: ca. 250 g (without cablel) Drop-tested: 1.5 m on industrial floor

12.5 E-Stop ratings (respective grey halt-button)

Rated voltage: 24 V DC Minimum current: 10 mA (each contact) Maximum current: 1000 mA (each contact) Utilization category: DC-13 (in accordance with IEC 60947-5-1)
B
Schlegel: Design: 2 circuits, external wiring Galvanic isolation: 500 V AC to the rest
: 250 000
10d

12.6 Enabling control device

Output type: Voltage: 24 V DC Current: 500 mA (max.)
B
:
10d
Actuating force:
Galvanic isolation: 500 V AC to the rest
Solid-state output
2nd position: 1 000 000 3rd position: 1 000 000
from 1st position to 2nd position: 3 N typical from 2nd position to 3rd position: 17 N typical
Project engineering manual V1.0244
Page 45
KeTop T10 Options

13 Options

This chapter describes the options the KeTop is available with.

13.1 Grey stop switch

In place of the emergency stop switch a gray stop switch can be used. See
chapter 6.2 "Emergency Stop Button and grey Stop Button" on page 28.
Project engineering manual V1.02 45
Page 46
Accessories

14 Accessories

14.1 Wall bracket KeTop T10

The powder-coated black wall bracket is used for stationary operation, storage or calibration of the KeTop
KeTop T10
Fig.14-1: Carrier

14.1.1 Dimensions

Fig.14-2: Front and side view of the wall bracket (all dimensions in mm)

14.2 Junction Box JB 001

This chapter describes the junction box JB 001 which is used to connect a KeTop to a PLC via Ethernet.
Project engineering manual V1.0246
Page 47
KeTop T10 Accessories

14.2.1 Views and basic dimensions

Fig.14-3: View of the JB 001
1
... Mounting nut
Project engineering manual V1.02 47
Page 48
Accessories

14.2.2 Connectors

KeTop T10
Fig.14-4: Connectors of the JB 001
K1
... 17-pin Coninverse female connector
for the KeTop connection cable
S3 ... RJ-45 female connector for connec-
tion to a PLC
1)
The requiered mating plug for terminal block S2 can be orderd from Co.
"Phoenix" with material number FMC 1.5/11-ST-3.5.
2)
via Ethernet

14.2.3 Connection diagram

The connection diagramm shows the connection of power supply, control lines (emergency stop switch and enabling control device) and data lines via the junction box.
S2 ... 11-pin terminal block for power supply
and control line (emergency stop switch, enabling control device). For this terminal block a plug will be nee-
1)
ded.
2)
S4 ... 9-pin DSUB male connector for CAN
connection
Project engineering manual V1.0248
Page 49
KeTop T10
Accessories
WARNING!
Danger to persons by electric shock!
Only supply the device with power from voltage sources having protective extra-low voltage (e.g. SELV or PELV acc. to IEC 61131-2)
Only connect voltages and circuits which are safely separated from dan­gerous voltages (e.g. by means of sufficient insulation) to connections, terminals or interfaces up to a rated voltage of 50 V.
Ethernet
Fig.14-5: Connection diagram for Ethernet: KeTop T10 via junction box JB 001
Information
Point-to-point connections between KeTop and PLC require a crossed cable.

14.2.4 Shielding inside the Control Cabinet

In many cases, several interference sources exist in the control cabinet, such as servo drive modules, transformers, contactors and relays. Therefore it is necessary to continue the cable shield from the connector shell (control cabi­net) up to the PLC (continuous connection from handheld terminal up to PLC).
Project engineering manual V1.02 49
Page 50
Accessories KeTop T10
Fig.14-6: Shield connection in the control cabinet
1
... Control cabinat (max. 5 mm wall thickness) 2 ... Junction Box JB 001
3 ... Connection cable to KeTop 4 ... CAN cable to host control

14.2.5 Mounting Instructions

Fig.14-7: Dimension dfrawing for the mounting opening of the JB 001
... Zoom view of the mounting opening
1 2 ... Control cabinet wall (max. 5 mm wall thickness)
Project engineering manual V1.0250
Page 51
KeTop T10

14.2.6 Technical data of Junction Box JB 001

General data
Accessories
Rated supply voltage (KeTop):
Power consumption:
Inrush current (KeTop): see chapter "Technical Data - In general" Safety class: Protection degree: IP20
24 V DC (rated voltage tolerance 19.2 V DC to 30 V DC according to EN 61131-2)
Without KeTop: none With KeTop: see chapter "Technical Data - In
general"l
III in accordance with EN 61131-2 and EN 50178
Environmental conditions
Operating temperature: Storage temperature: -25 °C to +70 °C (-13 °F to 158 °F) Relative humidity (non-condensing): 5 % to 95 %
Vibration resistance (operation):
Shock resistance (operation): 15 g / 11 ms (IEC 60068-2-27)
5 °C to 55 °C (41 °F to 131 °F)
IEC 60068-2-6:
5 Hz f < 9 Hz at 7 mm
9 Hz f < 150 Hz at 2 g
Mechanical properties
Construction: Flammability class: UL94-V0
Dimensions:
Width: 67.2 mm (2.6457 in)
Height: 76.1 mm (2.9961 in)
Depth: 26 mm (1.0236 in)
Weight: 220 g (0.485 lb)
Steel panel housing, blue zinc coated, with­stands grease, oil, lubricants, alcohol, etc.

14.3 KeTop CB211 Connection Box

The KeTop CB211 connection box is used for integration of the KeTop in the machine/system. It is suitable for wall mounting and can also be mounted on a mounting rail through the use of the mounting rail assembly kit (KeTop DR200).
Project engineering manual V1.02 51
Page 52
Accessories KeTop T10

14.3.1 Views and basic dimensions

Fig.14-8: View and device description of the Gateway box
1
... Status and error LEDs 2 ... PG gland (M20) for voltage supply, enabling
control device and emergency stop
3 ... PG gland (M16) for separate
functional ground (status as supplied with dummy plugs)
5 ... PG glands (M16) for data lines 6 ... PG glands (M16) for data lines (status as sup-
4 ... Coninvers female connector for KeTop con-
nection cable
plied with dummy plugs)
WARNING!
Danger to persons by electric shock!
Only supply the device with power from voltage sources having protective extra-low voltage (e.g. SELV or PELV acc. to IEC 61131-2)
Only connect voltages and circuits which are safely separated from dan­gerous voltages (e.g. by means of sufficient insulation) to connections, terminals or interfaces up to a rated voltage of 50 V.
Project engineering manual V1.0252
Page 53
KeTop T10 Accessories

14.3.2 Interior view

Fig.14-9: Interior view of connection box
K1
... 17-pin female connector (Coninvers)
for KeTop connection cable
X3 ... Terminal block for data lines SHIELD ... Cable shield clamp with con-
X1 ... Terminal block for power and
Details about connecting the connection box KeTop CB 211 to the KeTop see chapter "Connection and wiring".

14.3.3 Technical data of the connection terminals

The following technical data apply to the X1 and X3 connector terminal blocks already available in the connection box:
Connection capacity:
rigid / flexible / wire gages:
flexible with wire end ferrules without / with
plastic sleeve: Grid dimension: 3,81 Insulation length: Tightening torque: 0,22-0,25 Nm
Order data of Co PHOENIX:
0,14-1,5 mm2 / 0,14-1,5 mm2 / 28-16 AWG 0,25-1,5 mm2 / 0,25-0,5 mm
7 mm
control lines (enabling control device and emergency stop)
nection surface for cable shield of data lines (not used for strain-relief of the cable!)
2
2
Gateway-terminal block
PHOENIX
Type Part no.
X1 MCVR 1.5/6-ST-3.81 1827169 X3 MCVR 1.5/7-ST-3.81 1827172 X4, X4B MCVR 1.5/10-ST-3.81 1827208
Project engineering manual V1.02 53
Page 54
Accessories
Information
Consider the connection capacity of the terminal blocks when selecting the connection cable.
Use the following screwdriver to connect the wires to the terminal blocks: Blade: 0.4 x 2.5 x 80 mm, Length: 160 mm
Multi-line connections (2 wires in one terminal) are not allowed. Use the X4B terminal block for continuing the field bus.

14.3.4 Drilling template for wall mounting

KeTop T10
Fig.14-10: Drilling template for the Gateway box (specifications in mm)
Information
A scaled drilling template (scale 1:1) can be downloaded from
www.ke-
ba.com via LoginIndustrial automation (Doc.No.: 1007622).
For wall mounting, we recommend the following screws and materials:
Chipboard screw: Ø 4 x 40mm
Project engineering manual V1.0254
Page 55
KeTop T10 Accessories
Head form: flat head Max. head diameter: Ø 9 mm
Recommended rawlplug: Ø 6 x 30mm

14.3.5 DIN Rail Holder Mounting Set KeTop DR200

The DIN rail holder KeTop DR200 is available as accessory and will be moun­ted on the rearside of a KeTop CB2xx connection box. So the connection box can be easily snapped onto a DIN rail.
DIN Rail Holder Mounting Set
Tab.14-11: DIN Rail Holder Mounting Set for connection box
DIN Rail Holder fixed on the rear side of the
gateway-box
Project engineering manual V1.02 55
Page 56
Accessories

14.3.6 Use of Connection Box

KeTop T10
Fig.14-12: Connection box KeTop CB211 in control cabinet
1
... Control cabinat (max. 5 mm wall thickness) 2 ... Connection Box
3 ... Connection cable to KeTop 4 ... Power supply, emergency stop,
5 ... KeTop IC220 or KeTop IC224 6 ... Dust protection cap 7 ... Data line

14.3.7 Minimum Bending Radius of Cable

Fig.14-13: Required minimum distance outside and inside the control cabinet
enabling control device
Project engineering manual V1.0256
Page 57
KeTop T10 Accessories

14.3.8 Accessories

Accessories Usable for Description
Intermediate cable
KeTop IC220 (2 m) KeTop IC240 (4 m)
DIN Rail Holder Mounting Set KeTop DR100
Strapping plug KeTop BC001
Connection box to connection ca­ble
For mounting on the rearside of a KeTop CB2xx connection box.
Serves for bridging the emergency stop circuits if the KeTop is unplug­ged.

14.3.9 Technical Data of Connection Box KeTop CB211

General data
Rated supply voltage: Maximum interruption time of supply voltage: Power consumption: Inrush current: max. 5.6 A (with limitation of current) Safety class: Protection degree: IP65
24 V DC (rated voltage tolerance 19.2 V DC to 30 V DC according to EN 61131-2)
10 ms (following EN 61131)
10.8 W (600 mA at 18 V DC, 450 mA at 24 V DC)
III in accordance with EN 61131-2 and EN 50178
Environmental conditions
Operating temperature: Storage temperature: -20 °C to +70 °C (-4 °F to 158 °F) Relative humidity (non-condensing): 5 % to 95 % Vibration resistance (operation): (IEC 60068-2-6)
Shock resistance (operation): 15 g (0.033 pound) / 11 ms (IEC 60068-2-27)
0 °C to 50 °C (32 °F to 122 °F)
5 Hz f < 9 Hz with 7 mm (0.276 in) 9 Hz f < 150 Hz with 2 g (0.0044 pound)
Mechanical properties
Construction: Flammability class: UL94-V0
Dimensions:
Width: 160 mm
Height: 140 mm
Depth: 70 mm
Weight: 500 g
ABS housing, withstands grease, oil, lubri­cants, alcohol, etc.
Project engineering manual V1.02 57
Page 58
EC directives and standards KeTop T10

15 EC directives and standards

15.1 EC directives

2006/42/EC 2004/108/EC EMC directive
2011/65/EC RoHS directive

15.2 Standards

For examination of the conformity of the KeTop regarding the directives the following legally not bounded european standards has been used:
Examination of the conformity regarding the directive of machinery
EN ISO 13850:2008
EN 60204-1:2006 chap. 9 and 10
Examination of the conformity regarding the directive of EMC
EN 61131-2:2007 chap. 8, 9 and 10
Directive for the safety of machinery with the application MD 2006/42/EC
Safety of machinery - emergency stop equipment, func­tional aspects, principles for design
Safety of machinery - Electrical equipment of machines, general requirements
Programmable Controllers, Part 2: Equipment require­ments and test
Other standards
For the design of the safety concept some parts of the following legally not bounded european standards has been used.
General procedure and safety principles
EN ISO 12100:2010
Safety of machinery - Basic concepts - risk evaluation and risk abatement
Enabling control device
EN 60204-1:2006
EN ISO 10218-1:2011
EN 60947-5-8:2006
EN 60947-1:2007
EN 60947-5-1:2004
Safety of machinery - Electrical equipment of machines
- Part 1: General requirements Manipulating Industrial Robots - Safety requirements -
Part 1: Robots Low-voltage switchgear and controlgear - Part 5-8: Con-
trol circuit devices and switching elements - Three-posi­tion enabling switches
Low-voltage switchgear and controlgear - Part 1: Gen­eral rules
Low-voltage switchgear and controlgear - Part 5-1: Con­trol circuit devices and switching elements - Electrome­chanical control circuit devices
Project engineering manual V1.0258
Page 59
KeTop T10 EC directives and standards
Stop switch and emergency stop switch
EN ISO 13850:2008
EN 60204-1:2006 chap. 9 and 10
Safety of machinery; emergency stop equipment, func­tional aspects; principles for design
Safety of machinery - Electrical equipment of machines
- Part 1: General requirements
Ergonomics
EN 614-1:2006 EN 614-2:2000 Interaction of the design of machines and the work task
EN 894-3:2008
Safety of machinery - Ergonomic design principles - Part 1: Terminology and general principles
Safety of machinery – Ergonomics requirements for the design of displays and control actuators – Part 3: Control actuators
Stability and impermeability of casing
EN 60529:1991 EN 61131-2:2007 chap. 12
Protection degree of casing Programmable controllers - Part 2: Equipment require-
ments and tests
Electrical safeness and fire protection
EN 61131-2:2007 chap. 11 EN 50178:1997 Electronic equipment for use in power installations
Programmable controllers - Part 2: Equipment require­ments and tests
Environmental Conditions
EN 61131-2:2007 chap. 4 EN 50178:1997 Electronic equipment for use in power installations
Programmable controllers - Part 2: Equipment require­ments and tests
For the US market these standards had been used furthermore:
UL examination for industrial control equipment
UL 508
Industrial Control Equipment (NRAQ, NRAQ7)
UL examination for robotic applications
UL 1740
Industrial Robots and Robotic Equipment E216950 (TETZ2, TETZ8)
Project engineering manual V1.02 59
Page 60
Declaration of conformity KeTop T10

16 Declaration of conformity

16.1 EC Declaration of Conformity

Project engineering manual V1.0260
Page 61
KeTop T10

17 Appendix: Machinery Safety

Guidelines of the European Union
An essential goal of the European Union is the realization of a single European market and thus free trade. This means that quantitative import limitations of goods between the member states are prohibited.
Goods that endanger the safety of persons or the environment are an exemp­tion. Member states can prohibit such products on their country's territory. To ensure free trade for these products, the national safety regulations of the member states are standardized via guidelines set forth by the European Un­ion.
These guidelines apply for a number of product classes, such as for example machines, medical products, as well as toys. However, corresponding guide­lines were also developed for additional common safety aspects of products, such as protection against electricity, explosion protection or electro-magnetic compatibility. The guidelines are directed towards member states, who must implement them into the respective national laws. The guidelines therefore have legally binding effects.
Appendix: Machinery Safety
With the CE label the manufacturer certifies to have met all obligations of the EC guidelines applicable for the product. The CE symbol, which is affixed to the products by the manufacturer himself, is the "passport" within the EU and intended for the overseeing authorities.
In addition, independent, accredited certification organizations can verify the conformity with the EU guidelines and confirm this with a EU design sample certification.
Both the Electromagnetic Compatibility Directive (EMC 2004/108/EC) and the Machinery Directive (MD 2006/42/EC) are applicable to the handheld termi­nals.
Machinery Safety
Additional measures must be taken wherever faults arising in the machinery may cause personal injury or significant material damage. These measures must also guarantee a safe operating condition for the whole system in the event of a fault. According to the Machinery Directive (MD) a machine is con­sidered to be "a totality of components or appliances linked together, of which at least one can move". The directive also implies, that " Machinery must be designed and constructed so that it can be operated, adjusted and maintained without putting persons at risk when these operations are carried out under the conditions foreseen".
Although the handheld terminal is not, strictly speaking, a machine, it does, however, perform important tasks to guarantee the safety functions of a ma­chinery to which it is attached.
The handheld unit has, for example, the “Emergency Stop" safety function and an enabling control device for use in special operating modes. It is, as a result, a “Safety Component" in the sense of the Machinery Directive.
Project engineering manual V1.02 61
Page 62
Appendix: Machinery Safety
Safety components, or parts whose failure or faulty operation put the safety of people within the hazard area of the machine in danger, fall expressly within the range of application of the Machinery Directive.
The fundamental requirements that the Machinery Directive places on the manufacturer are as follows:
To carry out a hazard and risk analysis
To comply with the integration of safety principles
To compile and keep a technical construction file
To provide solutions in accordance with the latest state of the art
To recognise conformity by means of harmonised Standards
To apply CE marking
The same basic requirements apply to safety components. In their particular case, it must be proven that failure or malfunction are not possible, or that malfunction does not lead to a hazardous situation.

17.1 "Hazard and Risk Analysis"

KeTop T10
The manufacturer of a machine is required to analyse its machine throughout its operating life and in all modes of operation, and to document all hazards that may possibly arise. This has to be done without taking into account pos­sible protection devices.
The next step is to formulate a goal for protection against each identified hazard and subsequently to define one or more protective measures to achieve the protection goal.
Further details about the procedure for carrying out the hazard and risk anal­ysis and lists of commonly occurring hazards can be found in the following Standards:
EN 12100-1 and EN 12100-2 "Safety for machinery - Basic concepts, gen­eral principles for design"
EN 14121-1 "Safety of machinery - Risk assessment"

17.2 "Principles for the Integration of Safety"

In Appendix I, Chapter 1.1.2 of the Machinery Directive 2006/42/EC there is a clear procedure and sequence for the selection of protective measures:
Eliminating or minimising the hazards
This takes place at the design stage of the machine. These measures include, for example:
A reduction in the use of energy (power, revolutions, voltages etc.) as far as this is possible
The avoidance of unnecessary sharp points or edges
Project engineering manual V1.0262
Page 63
KeTop T10
Appendix: Machinery Safety
The avoidance of human errors by means of the ergonomic and logical design of operating devices
The avoidance of hazardous materials and commodities
Taking protective measures against hazards that cannot be eliminated
These measures include, for example:
Guards, railings, housings
Protective devices (light barrier for hazard elimination)
Protective control equipment (enabling control devices, two-hand controls,
speed monitoring etc.)
User information about residual hazards
This last of the three options is used if residual hazards remain after the first two options have been applied. These measures include, for example:
Warning notices
Training and organisational measures
The use of personal protective equipment

17.3 "Technical Construction File"

The technical construction file contains all the documents that are required to prove the safety of the machinery / safety component. These are, for example:
A complete drawing of the machinery or safety component including con­trol circuit diagrams
Hazard and risk analysis
Calculations
Research and test results
A list of the basic safety requirements of the Machinery Directive applicable
to the machine and a description of the solutions
Applied Standards
Operating instructions
A list of the quality assurance measures in the procedure
The technical construction file must be retained for a minimum of 10 years after the supply of the last product, and must be presented within a period of a few days in the event of a claim for damages.

17.4 "State of the Art"

This means technical possibilities at a certain point of time that are based on certain scientific and technical knowledge. The state of the art also means something that is commercially viable, that is it can be realised by the majority in the industrial sector concerned.
Project engineering manual V1.02 63
Page 64
Appendix: Machinery Safety
The state of the art is defined as the state of development of advanced pro­cedures, equipment or operating methods, that makes the practical applica­bility of the measure appear assured overall in respect of the targeted goals (e.g. the goals of protection of work, protection of the environment, safety of third parties and operating efficiency: namely to achieve a generally high level overall in relation to the aspects under consideration).
The state of the art can develop further irrespective of the Standards.
KeTop T10
17.5 "Recognition of Conformity by means of Harmonised Stand­ards"
The European Directives mainly contain general requirements for the safety of products; however they do not contain details of how to carry them out.
The European Standards Institutes are responsible for this. They provide im­plementation proposals for real safety problems or specific product classes. Standards that are assumed to meet and correctly interpret the requirements of the Directives are known as “Harmonised Standards”. Most of the available Standards, however, are not harmonised.
By applying and implementing harmonised Standards, a manufacturer can claim conformity for the respective product. However, the Standards, in con­trast to the Directives, are not legally binding. This means that the manufacturer may also take into consideration other solutions that are not described in the Standards; but these solutions must attain at least the same safety level as the relevant Standards and satisfy the requirements of the appropriate Directives.
17.6 Selection of Performance Level and Safety Categories in ac­cordance with EN ISO 13849-1
The Machinery Directive demands that a fault in control circuit logic, or inter­ference or damage thereto, shall not lead to a hazardous situation.
This general approach is substantiated in EN ISO 13849-1 "Safety of machi­nery - Safety related parts of control systems", which defines Performance Levels (PL a to e) for control parts that are relevant to safety. The PL depends on the safety category, the MTTFd-value and the degree of coverage of diag-
nosis (DC As in the preceding standard EN 954-1, the safety category describes the
structure of the safety function. The Performance Level (PL), which describes the conditional probability of failure and the defect discernability of the safety function, has been added.
) of the corresponding safety circuit.
avg
The selection of the PL has to be done by the manufacturer of a machine depending on the real risk potential. The risk potential will be be determined from a hazard and risk analysis. In case of hazards that can cause irrevisible injury or death usually a Performance Level not less than PL d is required.
Project engineering manual V1.0264
Page 65
KeTop T10
Appendix: Machinery Safety
The category of the Performance Level determines if
the system has been built in single circuit technology, which means that a failure will lead to a loss of safety, although the availability of components and parts is high (category 1)
the system has been built in single circuit technology, which means that a failure will lead to a loss of safety, but the failure will be detected by the system and will be displayed somehow or other (category 2)
the system has been built in multiple (2) circuit technology and that a fault will not lead to loss of safety (category 3) or
the system has been built in multiple (2) circuit technology and a build up of multiple faults will not lead to loss of safety (category 4).
Starting from category 3 it is also important in this context that individual faults are detected in time to avoid a build up of faults, which may finally lead to loss of safety.
Faults that have to be detected in electric and electronic systems are for ex­ample short circuits between multiple circuits, interrupts, short circuits or contacts that are stuck together. Special certified safety control devices are often used to detect faults in the individual safety circuits, which have a certain PL. The PL quoted for these devices is only attained, however, if also the whole machine circuit under review lies within the scope of the respective PL and the PL of all components supporting the safety functions has to be considered. The PL must always be considered in relation to a complete safety function and not as applied to individual components or parts.
A guide for easily calculating the PL for a safety function consisting of several individual components can be found in standard EN ISO 13849-1 chapter 6.3 and appendix H and I.
If safety components are being connected in series, the individual component with the least PL determines the PL of the whole safety function. For example a safety function consisting of 3 components, one with category 4 PL e, another one with category 3 PL d and a third component with category 2 PL c will have a PL c for the whole safety function. This means that a fault will lead to loss of safety, although components with category 4 PL e are integrated into the safety function, as one of the components being used has category 2.
When chaining several PLs the overall PL can decrease. For more information read EN 13849-1 chapter 6.3.
The proof of attainment of a safety category can take place with the aid of an FMEA (Failure Mode and Effects Analysis), in which all the faults that could possibly arise are simulated, either theoretically or in practice, and it is dem­onstrated that the requirements of the category are fulfilled.

17.7 Application of Handheld Terminals in Special Operating Modes

For the manual control of machines in special operating modes, where safety depends on the timely reaction of the operating staff, it is absolutely essential
Project engineering manual V1.02 65
Page 66
Appendix: Machinery Safety
that the operator can overlook the operating area. The handheld terminal has the advantage that the operator can get very close to the control panel. At the same time, the danger of misuse increases with mobility since, in remote lo­cations where it is not possible to observe the operating area, machine move­ments can also be set in motion with the handheld terminal, knowingly or unknowingly. The machine operator, therefore, has to find the right compro­mise between necessary flexibility and a reasonable limitation of the working range when selecting the corresponding cable length for the handheld termi­nal’s. It is not possible for the working range of radio-operated handheld terminal’s to be limited by means of the cable; therefore additional technical solutions are required for these handheld terminal’s.
If the machine or equipment is operated with the handheld terminal, care must be taken at this time to ensure that operation can only be controlled by the handheld terminal and cannot be operated from any other point on the equip­ment. The hazard zone may only be entered by the person who is operating the handheld terminal. If it should be necessary for more than one person to work in the hazard zone at the same time, each person present requires an enabling control device and machinery movement may only be allowed after all the enabling control devices have been activated.
KeTop T10

17.8 Information about the Emergency Stop Button

In theory, a perfectly designed machine should not require an emergency stop button, since the Machinery Directive demands that a machine must be safe throughout its lifetime and in all operating modes.
In practice, however, one is aware that unforeseen situations arise, in spite of all precautions. In order to enable fast shutdown of the machine in these cases, or to avert danger, an emergency stop button is provided on most machines.
As can be seen from the following illustration, a machine is permanently in the hazard state from the viewpoint of the emergency stop button, for as long as this is not activated.
Fig.17-1: Neutral position (not activated) Fig.17-2: Emergency stop button pressed
Tab.17-3: Emergency stop button functions
Project engineering manual V1.0266
Page 67
KeTop T10
Appendix: Machinery Safety
The emergency stop button may not, therefore, serve as the primary safety device but is provided exclusively to cover any residual risks.
Instead of this and depending on the mode of operation, other methods should be employed as the primary safety device, for example guards, light barriers and two-hand control devices or enabling control devices.
When the emergency stop button is activated, the entire machine or all of the machines that are switched together in a plant must be lead to a safe state e.g. by stopping and switching off the power to the endangering drive mechanisms (stop categories 0 or 1 in accordance with EN 60204-1).
The release of the emergency stop button must not cause any uncontrolled restart of the machine.
Irrespective of whether a handheld terminal has an emergency stop button or not, permanently installed, universally identifiable and easily accessible emer­gency stop buttons must be provided at selected points around the machine in every case.

17.9 Application of Emergency Stop Button and Stop Button on the Handheld Terminal

The Machinery Directive does not specify any detailed requirements in respect to the colouring of the operating elements for emergency stop. The require­ment states: “The device must have clearly identifiable, clearly visible and quickly accessible controls“.
Emergency stop buttons are usually identified by red/yellow. The specific de­sign should have a signalling function whose effect is that any person, and especially untrained people, can quickly recognise the control as the device to eliminate a hazard in the case of an emergency.
One imperative requirement for equipment identified in this way is, therefore, that it must be possible to trigger a safe state at any time and in any operating mode, without further knowledge of the machine (see also EN ISO 13850).
It is not acceptable for an emergency stop button to be enabled temporarily, since this can lead to faulty operation and life threatening loss of time in panic situations.
If one considers handheld terminals in relation to these requirements it is evi­dent that a differentiation must be made as to whether an emergency stop button on the handheld terminal may be used or not, depending on specific criteria and applications.
Permanently installed handheld terminals: Emergency stop button
Permanently installed handheld terminals are provided with a cable by means of which the handheld terminal is connected to the designated machine. The handheld terminal is usually connected to or disconnected from the machine with the machine switched off. This takes place during the installation or de-
Project engineering manual V1.02 67
Page 68
Appendix: Machinery Safety
installation process. The handheld terminal’s are not designed to be connected or disconnected whilst the machine is operating.
On many simple machines the handheld terminal is also the only operating option, so that, without the handheld terminal, the machine cannot be put into operation at all. Nonetheless, if the connector is unplugged from the machine during operation the emergency stop circuit is broken and the emergency stop function of the machine is activated, causing the machine to stop.
If a handheld terminal is uninstalled from a machine and is not reinstalled im­mediately, the equipment must be locked out in order to avoid confusion with a functioning handheld terminal. The machine can only be put back into oper­ation again after a new handheld terminal has been installed.
This procedure must be described in the operating instructions for the machine and is the responsibility of the operator.
Due to the fact that plugging and unplugging takes place only rarely and that the machine is out of operation when unplugged, the risk of an accident as the result of a non-operational emergency stop button is considered to be very low and the use of red/yellow identification is therefore permissible.
KeTop T10
The red/yellow emergency stop button must be connected into the emergency stop circuit of the machine in any case and must cause the power supply to the machine or set of machines in a plant to be switched off (stop category 0 or 1 in accordance with EN 60204-1).
Radio controlled handheld terminals: Stop button
Wireless handheld terminal’s present a different case. These devices are not normally assigned to a specific machine but can be frequently logged on and off whilst the machine is in operation and can also be switched between dif­ferent machines. For this reason the stop button is not always operational and the operating status is not clear to everyone.
Therefore, for stop functions in wireless controllers, EN 60204-1:2006 "Safety of Machinery. Electrical Equipment of Machines" (Chapter 9.2.7.3), demands:
"The operating means to initiate this stop function shall not be marked or labelled as an emergency stop device, even though the stop function initiated on the machine can be an emergency stop function."
For this reason, for radio controlled handheld terminal’s KEBA uses a stop button that features all the mechanical characteristics of a normal emergency stop button but is of a neutral grey colour.
In contrast to the red/yellow emergency stop button there is no need to switch the stop output signals of the radio receiver into the machine’s normal emer­gency stop circuit. It can also be used to stop individual safety zones of a machine or plant, where functions such as “Safe operational stop” can be trig­gered. This means that the drive components are safely maintained in con­trolled shutdown by means of active, powered drives (stop category 2 in accordance with EN 60204-1). This can prevent the loss of reference data and facilitates fast restart of the machines.
Project engineering manual V1.0268
Page 69
KeTop T10
Appendix: Machinery Safety
The trained handheld terminal or machine operator is aware of the function assigned to the button and knows the current operating mode in each case as well as the current assignment of the machine. For this reason the colouring is not disadvantageous to the machine operator.
The safety gain is that, in the case of inactive or unassigned equipment, no danger of confusion is presented to third parties in respect of functional emer­gency stop buttons.
Temporary plug-in handheld terminals: Stop button
Some cabled equipment is provided with a quick-release connector (e.g. bay­onet) that makes it possible to plug in and unplug the handheld terminal quickly and ergonomically whilst the machine is in operation. Such handheld terminal’s are provided for frequent alternation of operation between one or more ma­chines and are needed there on a temporary basis, for commissioning or setting up purposes.
By means of several measures, such as bridging connectors or relay circuits, the emergency stop circuits of the machine are bridged when the handheld terminal is unplugged so that the machine can also continue to run in normal operation without the handheld terminal. Start-up and operation of the machine can then take place using an independent operating device.
These handheld terminals share the same problems as the radio terminals, since due to frequent plugging and unplugging it cannot be ruled out that dis­connected handheld terminal’s with ineffective stop buttons may be left lying or hanging temporarily in a machine shop or factory in the neighbourhood of working machines and may be mistaken for functional units in an emergency situation.
This special case is not clearly treated in the corresponding Standards. How­ever, in the Product Standards for presses (EN 692:2004, EN 693:2001, EN 12622:2001, EN 13736:2003) one finds the following clear statement:
"Any disconnectable control station shall not incorporate an emergency stop button if the press can be operated while this controls station is disconnected."
Further Product Standards are currently under review. In several discussions with external notified bodies and technical committees
it was also determined that temporary, plug-in handheld terminals should be treated as radio handheld terminal’s.
The approach to constructively eliminate hazards by using clear colour coding, in preference to any organisational measures, also corresponds to the “Prin­ciples for the Integration of Safety” of the Machinery Directive and is therefore legally binding.
For this reason, temporary plug-in handheld terminals may likewise only be equipped with a grey stop button.
Project engineering manual V1.02 69
Page 70
Appendix: Machinery Safety
Since handheld terminals made by several other manufacturers are on the market with a grey stop button and have been certified by nominated test cen­tres, the state of the art requirement is also met.

17.10 Information about enabling control devices

Many machines have both a normal and special operating modes. The machine fulfils its primary mission in normal (automatic) operation. In this
mode of operation, safety is guaranteed by closed, guards and/or with protec­tive devices.
A machine’s special operating modes serve to maintain normal operation. In doing so, safety must be guaranteed in a way that is different to normal oper­ation, since hazardous areas of the machine can now be entered and targeted machine movements have to be possible. The enabling control device plays a primary role here.
KeTop T10
This application requires the enabling control device to eliminate the hazards that are to be controlled in a timely manner, before any personal injury occurs. Additional safety measures may be necessary for this purpose, such as safely reducing the speed of drive mechanisms.
In contrast to the emergency stop button respectively the stop button, a ma­chine in special operating mode with an enabling button is in a safe state as long as this enabling button is not activated (see illustration).
Fig.17-4: Enabling functions
... "Neutral position" not activated 2 ... "Enabling" pressed
1 3 ... "Panic" pressed heavily
The enabling function is also described in EN 60204-1:2006 and corresponds to the state of the art.
The panic position on 3 stage enabling control devices was introduced be­cause limbs often become cramped when a person is in a state of shock and
Project engineering manual V1.0270
Page 71
KeTop T10 Appendix: Machinery Safety
as a result is not able to release the enabling control device. For this reason, firmly pushing down on the enabling control device also leads to switch off.
The controller must be designed in such a way that machine movement is not initiated directly when the enabling control device is activated but only as a result of the additional activation of a control button. This may be via the hand­held terminal’s membrane keyboard or graphical software buttons on the touch screen.
An optionally available joystick can also be used to trigger the machine move­ment signal.
According to EN 60204, only stop categories 0 or 1 are allowed for the enabling function, i.e. stopping the machine with the enabling control device must al­ways be combined with switching off the power supply to the drive mecha­nisms.
In order to prevent incorrect, permanent activation of the enabling control de­vice by mechanical fixing devices, it is recommended to limit the maximum duration of an accepted enablement. This must be achieved by means of a controller located downstream to the handheld terminal.
An enabling control device is not a replacement for a two-hand control device, which is specified for some machines (e.g. presses) and must therefore not be confused.
In contrast to the enabling control device, the two-hand control device forces the endangered limbs of the operator into a safe position whilst the machine is in motion.
Project engineering manual V1.02 71
Page 72
Appendix: Electromagnetic Compatibility

18 Appendix: Electromagnetic Compatibility

The European Union obligates its member states to harmonise their statutory provisions in respect of electromagnetic compatibility by means of Directive 2004/108/EC. In the following text this Directive is abbreviated to the EMC Directive.
All electrical and electronic device that is put into circulation in Europe must, therefore, conform to the fundamental safety requirements of the EMC Direc­tive. According to this Directive, electromagnetic compatibility is the ability of a device, plant or system to work satisfactorily in the electromagnetic environ­ment, without itself causing electromagnetic interference that would be unac­ceptable to all devices, plant and systems present in this environment.
In addition to the legal requirements described above, the reliable functioning of an electrical device is also a fundamental quality characteristic of such a device.
As well as basic information concerning electromagnetic compatibility, the fol­lowing pages describe the implementation of the EMC requirements in respect of the KeTop product range of handheld terminal devices.
KeTop T10
18.1 The electromagnetic environment – interference sources, inter­ference sinks and coupling paths
There are a number of artificial and also natural sources of interference in the electromagnetic environment that can affect electrical and electronic device.
The most well-known natural interference phenomenon is atmospheric dis­charge (lightning discharge).
Artificial sources of interference are, on the one hand, intentional, such as mo­bile radio, amateur radio, TV and radio transmitters, and, on the other hand, unintentional, such as microwave ovens, arc welding, ignition systems, high voltage device, electric motors, electronic device and also electrostatic dis­charge.
Atmospheric discharge (lightning)
Atmospheric discharge can take place directly or indirectly on power and com­munication lines. The consequence of such an impact if there is insufficient protection is the destruction of the electrical device.
Atmospheric discharge is simulated in accordance with the international test standard IEC 61000-4-5 (EN 61000-4-5 for Europe) – "Electromagnetic com­patibility (EMC). Testing and measurement techniques. Surge immunity test".
The relevant international product standard for control systems, IEC61131-2 (EN61131-2 for Europe), divides the areas of application into zones. Higher or lower levels of interference can be expected depending on the zone in ques­tion. All Kemro control systems and also the products of the KeTop range are suitable for application in Zone B.
Project engineering manual V1.0272
Page 73
KeTop T10
Appendix: Electromagnetic Compatibility
The product standard requires the testing of surge immunity in accordance with IEC 61000-4-5.
Electrostatic discharge (ESD)
Materials can be charged by contact followed by subsequent separation. This effect only arises when at least one of the two materials is a non-conductor. As a result, discharge may take place if a charged conductor, or one that is changed by the influence of an electronic field, comes near a metallic object.
After charging, the possible voltages between the charged bodies can reach over 10 kV.
The most frequent occurrence of electrostatic discharge takes place between people and metallic objects. Since one is practically unnoticed of discharges below 3500 V and yet electronic components are destroyed by low voltages, ESD damage to electronic components often goes unnoticed.
The international Standard IEC 61000-4-2 (EN 61000-4-2 for Europe) is used to simulate the measurement of electrostatic discharge. The international product standard IEC 61131-2 (EN 61131-2 in Europe) for programmable con­trols demands testing to IEC 61000-4-2 and also defines the severity level.
Technical systems as interference sources
Technical systems can act as sources of interference. In doing so, the inter­ference may be intentional or unintentional. Electromechanical energy is often also used for material processing.
Periodically occurring interference:
Ignition impulses of combustion engines
Sparking of commutator motors
Electromagnetic fields of induction furnaces, arc welding device, micro-
wave device etc.
Pulse currents from frequency converters and switching power supplies
Electromagnetic fields of radio and telecommunications device
Randomly occurring interference:
Ignition impulses of fluorescent lamps
Switching procedures on inductive electrical circuits
Contact bounces when closing or opening make-and-break contacts
Voltage fluctuations on heavy load switching procedures
There is a series of test standards for the above listed sources of interference, intentionally or unintentionally caused by technical systems, which simulate this interference:
IEC 61000-4-3 High Frequency Electromagnetic Field Immunity Test
IEC 61000-4-4 Electrical Fast Transient / Burst Immunity Test
Project engineering manual V1.02 73
Page 74
Appendix: Electromagnetic Compatibility
IEC 61000-4-6 Test of Immunity to Conducted Disturbances, Induced by High Frequency Fields
IEC 61000-4-8 Power Frequency Magnetic Field Immunity Test
IEC 61000-4-11 Voltage Dips, Short Interruptions and Voltage Variations
Immunity Test
All the international Standards listed here are also available as European Standards. The Product Standard IEC 61131-2 demands testing to these Standards and also defines the severity level.
Technical systems as interference sinks
In the case of functional interference, EMC problems first arise at interference sinks. The following interference sinks can be identified dependent on the de­gree of immunity to electromagnetic influences:
KeTop T10
Immunity Interference sinks
Transformers
max
min
Tab.18-1: Examples for technical systems as interference sinks
Circuit breakers, contactors
Relays
Power transistors
Transistor circuits
Integrated switching circuits
Control systems without integrated switching circuits are unthinkable and would therefore not be sufficiently immune without suitable EMC measures.
Coupling paths
The transfer of interference signals from an interference source to an interfer­ence sink can take place via various coupling paths.
Coupling paths very often consist of two or more parallel lines running closely together. The coupling is a field coupling that takes place at low frequencies either via the electrical field (capacitive coupling) or via the magnetic field (in­ductive coupling).
At high frequencies and with corresponding expansion of the parallel running lines one speaks about an electromagnetic coupling due to close linking of both field types.
Project engineering manual V1.0274
Page 75
KeTop T10
Direct coupling can occur when electrical circuits from the interference source and electrical circuits from the interference sink have common line compo­nents.
If there is a large distance between an interference source and an interference sink then one speaks of a radiation coupling.

18.2 EMC measures on KeTop

The KeTop is designed for industrial applications. Considerable electromag­netic and electrostatic interference can occur in this environment. For this reason special emphasis was placed on interference immunity and data se­curity in the design of the device. The EMC design implemented and described below considers all the above named sources of interference and the possible coupling paths.
All shielding and filter measures (filtered power supply) in the KeTop are carried out directly on the printed circuit board.
The special design of the KeTop cable guarantees interference immunity even for greater connection lengths, i.e. the data lines (communication signals) are shielded and so they are separated from the control lines (power supply, enabling control device, emergency off, key-operated switch etc.) inside the KeTop cable.
Power supply lines in the control cabinet are usually unshielded. They are therefore laid outside the KeTop cable shield in order to prevent a coupling with the sensitive data lines.
The unshielded control and power supply lines are either filtered on entry into the shielded housing of the KeTop or separated from the electronics in such a way that any interference signals carried by these lines cannot affect the internal electronics of the KeTop.
It is not necessary to lay the KeTop cable separately.
Appendix: Electromagnetic Compatibility
Shield connections
The cable shield of the KeTop cable can be considered to be an extension of the KeTop shielded housing (=printed circuit board) to the shielded housing of the communication partner (e.g.: PLC). From this it can be deduced that the shielded connections from the cable shield to the device shields make a fun­damental contribution to the interference immunity of the KeTop. It is not necessary to wire shielded connections to earth. The shielding connection in the KeTop is made via the RJ-45 connector in the connection slot.
Connecting the KeTop via the connection box (e.g. CB211) guarantees safe shielding protection right through to the communication partner. All connection cables available from KEBA guarantee correct shielding connection.
For self-made cables the following conditions must be met for shielding data lines:
On every connector design (DSUB or RJ-45) the cable shield must be connected to as large a surface area of the connector housing as possible.
Project engineering manual V1.02 75
Page 76
Appendix: Electromagnetic Compatibility
Fig.18-2: Correct shield connection for DSUB and RJ-45 connectors
1
... Metallised or metallic housing
2 ... Connect the shield to a large surface area
The use of pig tails for contacting the cable shield via plug pins is unsuit­able. The inductivity of such pig tails represents high impedance resistance for higher frequency interference; this means an apparent break in the cable shield. Interference is then no longer diverted and works directly on the inner lines.
KeTop T10
Fig.18-3: Insufficient contacting of a cable shield
1
... No pig tails
Shielding inside the control cabinet
In many cases a range of interference sources, such as servo drive modules, transformers, contactors and relays, is present in the control cabinet. It is therefore necessary to run the cable shield from the connector housing (control cabinet) to the control (continuous connection from the handheld terminal to the control). When using the appropriate connection box and a shielded cable for the data line from the connection box to the control, the continuous, high frequency compatible connection of the shield from the KeTop to the control is guaranteed.
If for some reason a connection box cannot be used, the continuous connection of the shielding on less critical interface types takes place by contacting the connector housing with the control cabinet and inside the control cabinet by contacting the shielding with the control cabinet (using shielding clips). The smaller the distance between the contacting of the connector housing on the
Project engineering manual V1.0276
Page 77
KeTop T10 Appendix: Electromagnetic Compatibility
control cabinet to the cable clip in the control cabinet, the better the shield damping.
The interference immunity of the device with the connection type presented above is also decisively influenced by the satisfactory separation of the control signals and the data line signals. The better the separation of the two signal types and the shorter the shielding connection, the higher will be the interfer­ence immunity of the complete system.
If the Ethernet is used as the communications interface one of the two con­nection cables provided for the purpose of connecting to a control system must be used (IC020 or IC040). Both cables carry the Ethernet signals to a suitable connector (RJ-45) and thereby produce a continuous shielding connection and also the required characteristic impedance of the cable.
Project engineering manual V1.02 77
Page 78
Appendix: Icon sets KeTop T10

19 Appendix: Icon sets

This appendix contains a listing of from KEBA provided icons which can be displayed on the display of the KeTop. The following icons are available:
Predefined internal icons
Icons with 64 x 64 pixels for the applicaton (Icon set 2)
Icons with 32 x 32 pixels for the applicaton (Icon set 3)
Information
Icon set 1 is not available for the user.
Additionally the buildup of the following customized icon sets can be requested from KEBA:
Predefined internal icons
Customized icons with 64 x 64 pixels (Icon set 4)
Customized icons with 32 x 32 pixels (Icon set 5)
The following description of the icons for the application are suggestions for use. The final use of the icons depends on the control application.

19.1 Predefined internal icons

These icons are included in the firmware and displayed by this. The set con­tains of three icons with 32 x 32 pixels which are displayed in the top left corner of the display and of eight icons with 64 x 64 pixels which are displayed in the center.
Symbols with 32 x 32 pixels
Icon Description
Information
Warning
Error
Project engineering manual V1.0278
Page 79
KeTop T10 Appendix: Icon sets
Symbols with 64 x 64 pixels
Icon Description
Waiting for host connection or control error
Calibration successful
Calibration not successful or not calibrated
Calibration in progress
Referencing not successful or reference lost
Referencing not successful or reference lost
Referencing successful
Connected with host

19.2 Icons with 64 x 64 pixels for the application (Icon set 2)

These icons contains of 64 x 64 icons for individual use in the application.
ID Icon Description
KeTop T10 ready
1 Black Display
2
3 Calibration successful
or empty space
Waiting for host connection or control error
Calibration not successful
4
Project engineering manual V1.02 79
or not calibrated
Page 80
Appendix: Icon sets KeTop T10
ID Icon Description
5 Calibration in progress
Referencing not successful
6
7 Referencing successful
8 Device not active
9 Joint mode active
10 Cartesian tool mode active
or reference lost
11 Cartesian object mode active
12 Cartesian free mode active
13 Internal error
14 Connected with host
15 Grab mode active
16 Emergency stop pressed
17 Information
18 Joint mode not available
19 Drive(s) has/have no power
20 Cartesian tool mode not available
Project engineering manual V1.0280
Page 81
KeTop T10 Appendix: Icon sets
ID Icon Description
21 Cartesian object mode not available
22 Device has been moved too fast during grab mode
23 Warning
24 Moved during jog start
25 Figure null

19.3 Symbols with 32 x 32 pixels for the application (Icon set 3)

This iconset consists of icons with 32 x 32 pixels for individual use in the ap­plication.
ID Icon Description
1 Black Display Empty space
2 Figure null
3 Figure one
4 Figure two
5 Figure three
6 Figure four
7 Figure five
8 Fidure six
9 Figure seven
Project engineering manual V1.02 81
Page 82
Appendix: Icon sets KeTop T10
ID Icon Description
10 Figure eight
11 Figure nine
12 Symbol A
13 Symbol B
14 Symbol C
15 Symbol D
16 Symbol E
17 Symbol F
18 Connected with host
19 Joint mode active
20 Cartesian tool mode active
21 Cartesian object mode active
22 Empty bar bottom
23 Full bar below
24 first endposition (lower)
25 second endposition (upper)
Project engineering manual V1.0282
Page 83
KeTop T10 Appendix: Icon sets
ID Icon Description
26 Information
27 Error
28 Warning
29 Device not active
30 Device not active
31 Emergency stop pressed
32 Cartesian free mode active
33 Grab mode active
Waiting for host connection
34
35 Joint mode not available
36 Drive(s) has/have no power
37 Cartesian tool mode not available
38
39
or control error
Referencing not successful or reference lost
Referencing not successful or reference lost
40 Cartesian object mode not available
Project engineering manual V1.02 83
Page 84
Appendix: Icon sets KeTop T10
ID Icon Description
41 Empty bar left
42 Empty bar right
43 Full bar left
44 Full bar right
45 Calibration successful
Calibration not successful
46
or not calibrated
47 Calibration in progress
48 Referencing successful
49 Device has been moved too fast during grab mode
50 Moved during jog start
Project engineering manual V1.0284
Page 85
KeTop T10

20 Appendix: Status and error codes

In this appendix the status and error codes of the KeTop T10 and their mean­ings are explained.

20.1 Status codes

The status code consists of five digits. Each digit delivers information about a certain part of the device:
0 0 0 0 0
Sensors KVC Application Display EEPROM
In the following tables the meanings of the digits are explained:
Sensors
Code Diagnosis code Description
0 1 2 3
INU_OK INU_SENSOR_READ INU_SENSOR_RATE INU_SENSOR_VALUE
No error Measuring value cannot be read Unexpectedly large number of measuring values Implausible measuring value
Appendix: Status and error codes
KVC
Code Diagnosis code Description
0 1 2 3
KVC_OK KVC_NOT_INIT KVC_PROTOCOL_ERR KVC_CONN_UNSTABLE
No error KVC cannot be initialized Protocoll error Connection unstable (Warning)
Application
Code Diagnosis code Description
0 1 2
3 4 5
APPL_OK APPL_NOT_INIT APPL_EEPROM
APPL_DISPMAN
APPL_DEVMON
APPL_DEACTIVATED
No error Application cannot be initialized Application cannot read or write to EEPROM Display manager cannot write (e. g. icon size mismatch,
invalid icon number, etc.) Error monitoring the devices Device deactivated (e.g. joystick not available, no key-
board available, etc.)
Display
This error code is binary coded and shows incorrect iconsets.
Project engineering manual V1.02 85
Page 86
Appendix: Status and error codes KeTop T10
Code Description
0 No error 1 Error in first two sets (internal icons and 64 x 64) 2 Error in third set (32 x 32) 3 Error in first two sets and in third set 4 Error in fourth set (64 x 64 customized) 5 Error in first two sets and in fourth set 6 Error in third and fourth set 7 Error in first two sets, in third set and in fourth set 8 Error in fifth set (32 x 32 customized) 9 Error in first two sets and in fifth set A Error in third and fifth set B Error in first two sets, in third set and in fifth set C Error in fourth set and in fifth set D Error in first two sets, in fourth set and in fifth set E Error in third, fourth and fifth set F Error in all sets
EEPROM
No. Description
0 No error 1 EEPROM cannot be read (bus or storage error)

20.2 Codes for errors or warnings

The error code respective the warning code is a more detailed description of the status code and explains occured errors and warnings. The code consists of a double figure.
Error
No
.
00
01
02
03
04
05
Enum ID Description
eKvcErrorNotIni­tialized
eKvcErrorWrong­TelNr
eKvcErrorMsgTo­Long
eDevmonErrorMax­Listeners
eDevmonErrorNo­tInitialized
eDispManErrorNo­tInitialized
KVC cannot be initialized, start up failed
Wrong telegram number
Received KVC message too long Maximum number of devices reached, re-
ceiving device cannot be added Device monitoring cannot be initialized
Display manager cannot be initialized
Appendant diag-
nosis code
KVC_NOT_INIT
KVC_PROTOCOL_ERR
KVC_PROTOCOL_ERR
APPL_DEVMON
APPL_NOT_INIT
APPL_NOT_INIT
Project engineering manual V1.0286
Page 87
KeTop T10 Appendix: Status and error codes
Warning
No
.
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Enum ID Description Error behavior
eKvcWarningMs­gIgnoredCyclic
eKvcWarningMs­gIgnoredAnticy­clic
eKvcWarning­WrongTelLenReq­State
eKvcWarning­WrongTelLenParam­Read
eKvcWarning­WrongTelLenParam­Write
eKvcWarningRecv­SafetyTel
eKvcWarningCon­nAbort
eKvcWarningMa­nyIgnoredMsg
eKvcWarningRe­peatingConnAbort
eKvcWarningEe­promReadingFail
eKvcWarningEe­promDataInvalid
eKvcWarningNot­SupportedParam
eKvcWarningInva­lidParNr
eKvcWarning­WrongParLen
eDevmonWarning­DefaultValueJoy
eDevmonWarning­DefaultValueKeys
Incoming cyclic KVC message ignored (message queue full)
Incoming anticyclic KVC message ignored (message queue full)
Wrong telegram length of received request state telegram
Wrong telegram length of received parameter read telegram
Wrong telegram length of received parameter write telegram
Received safety tele­gram, although not supported on KeTop T10
KVC connection lost (detected by timeout)
Warning when more than 4 messages will be ignored within 20 seconds
Warning when more than 4 messages will be ignored within 10 seconds
Reading device info from EEPROM failed
(Parts of) EEPROM data not initialized or invalid
KVC parameter not supported on KeTop T10
KVC parameter num­ber does not exist
Wrong length of KVC parameter value (quo­ted length and real length differ)
Failed to read number of joystick axes from EEPROM
Failed to read number of keys from EEPROM
Reset of warning after 20 seconds
Reset of warning after 20 seconds
Reset of warning after 20 seconds
Reset of warning after 20 seconds
Reset of warning after 20 seconds
Reset of warning after 20 seconds
Reset of warning on reconnecting.
Reset of warning if less than 5 mes­sages are ignored within the next 20 seconds
Reset of warning if less than 5 mes­sages are ignored within the next 10 seconds.
-
-
-
-
-
Taking default value
Taking default value
Appendant diag-
nosis code
-
-
KVC_PROTOCOL_ERR
KVC_PROTOCOL_ERR
KVC_PROTOCOL_ERR
KVC_PROTOCOL_ERR
-
KVC_CONN_UNSTA­BLE
KVC_CONN_UNSTA­BLE
APPL_EEPROM
APPL_EEPROM
KVC_PROTOCOL_ERR
KVC_PROTOCOL_ERR
KVC_PROTOCOL_ERR
APPL_DEVMON
APPL_DEVMON
Project engineering manual V1.02 87
Page 88
Appendix: Status and error codes KeTop T10
No
.
16
17
18
19
20
21
22
23
24
25
26
27
28
29
Enum ID Description Error behavior
eDevmonWarning­DefaultValueOri
eDevmonWarning­DefaultValueDev­Pin
eDevmonWarnin­gOriDeactivated
eDevmonWarning­KeysDeactivated
eDevmonWarning­JoystickDeactiva­ted
eDevmonWarnin­gEepromRWFail
eDevmonWarnin­gInvalidBaseUCT
eDevmonWarnin­gInvalidJoyUCT
eDevmonWarnin­gInvalidKeysUCT
eDevmonWarnin­gInvalidOriUCT
eDispManWarning­DrawIconFailed
eDispManWarnin­gInvalidTileId
eDispManWarnin­gInvalidIconSet­Full
eDispManWarnin­gInvalidIconSet­Big
Failed to read informa­tion from EEPROM if orientation data is available at all or whether it shall be in­terpreted or not
Failed to read device pin from EEPROM
Stopped to interpret orientation because INU is defect
Deactivated keys be­cause of a hardware problem
Deactivated joystick because of a hardware problem
Failed to read from EE­PROM – hardware or ressources problem
Too large base update cycle time (UCT) – base UCT must be less than the UCT of the other devices and more than zero
Too small UCT for joy­stick – joystick UCT must be at least the base UCT
Too small UCT for the key image – key UCT must be at least the base UCT
Too small UCT for ori­entation interpretation – orientation UCT must be at least the base UCT
Failed to draw system icon in the upper left corner
Given tile-id is higher than the number of tiles
Given set-id contains full screen icons, which cannot be set by the user
Given set-id contains big icons, but tile-id is for small icons
Taking default: supposing orien­tation data is available and it shall be used
Taking default value
-
-
-
-
Setting base UCT to its default (i.e. 5ms)
Setting joystick to its default (i.e. 25ms)
Setting key UCT to its default (i.e. 5ms)
Setting orienta­tion UCT to its de­fault (i.e. 100ms)
-
-
-
-
Appendant diag-
nosis code
APPL_DEVMON
APPL_DEVMON
APPL_DEACTIVATED
APPL_DEACTIVATED
APPL_DEACTIVATED
APPL_EEPROM
APPL_DEVMON
APPL_DEVMON
APPL_DEVMON
APPL_DEVMON
APPL_DISPMAN
APPL_DISPMAN
APPL_DISPMAN
APPL_DISPMAN
Project engineering manual V1.0288
Page 89
KeTop T10 Appendix: Status and error codes
No
.
30
31
32
33
Enum ID Description Error behavior
eDispManWarnin­gInvalidIconSetS­mall
eDispManWarning­ScreensaverDe­faultVal
eKeySeqWarning­FactoryReset­Failed
eKeySeqWarning­FailedSaveJoyCa­libVal
Given set-id contains small icons, but tile-id is for big icons
Failed to read screen­saver timeout from EE­PROM
Factory reset failed – failed to read default values from EEPROM
Failed to read joystick calibration flags from EEPROM
-
Screensaver timeout will be set to zero, that means the screensaver is turned off.
-
-
Appendant diag-
nosis code
APPL_DISPMAN
APPL_EEPROM
APPL_EEPROM
APPL_EEPROM
Project engineering manual V1.02 89
Page 90
Appendix: KVC telegrams on KeTop T10 KeTop T10

21 Appendix: KVC telegrams on KeTop T10

This appendix explains how the KeTop T10 executes the KVC telegrams. Fur­thermore the parameter provided on the KeTop T10 are listed and example values for them are shown.
Concurrency of KVC telegrams
According to the protocol definition state requests will be transmitted cyclically which means the executing is always one after another.
Parameter requests are carried out as necessary and have to be serialized on the server: The server can only send another request after the acknowledge of the previous request has been received. This ensures that each parameter request is executed correctly.
A synchronization between status requests and inquiries parameter is not nec­essary, since they are handled in several buffers. So state requests and parameter requests can be handled in parallel.
KVC parameter on the KeTop T10
Parameters for changing and returning the configuration on the KeTop T10
Parameter Example content
ScreenSaverTime 20000 [ms] ScreenSaverState activated
DevHWInfoData
CpuInfoData frequ 50000000, ram 98304 DevTypeInfo KeTop T10, FreeRTOS
FirmwareVersion
BootSystemVersion 1.6, KEBA Bootloader v1.06
NetConfig
DiagnosisDataLength 5 ClientDiagnosis 20000 DisplayTileCount 13
DisplayData
MonitorCycleTime 5 (ms)
1, 4, 0, 2549, 15308652, 86839, 15308652, 0, 23388
1.4, KeTop T10 v 1.004 (Wed Nov 6 15:42:55 GMT
2013)
192.168.137.151, 255.255.255.0, 192.168.137.1,
192.168.137.234, 0
Representation of syntax <Tile#: [Set-Id/Icon­Id]>
0:[2/12] 1:[3/1] 2:[3/1] 3:[3/1] 4:[3/1] 5: [3/1] 6:[3/1] 7:[3/1] 8:[3/1] 9:[3/3] 10:[3/4] 11:[3/5] 12:[3/1]
Parameter as commands for KeTop T10
Parameter Process
Reset Reset Calibrate Kalibration of the sensor OrientationReset Referencing = Reset of the orientation
Project engineering manual V1.0290
Page 91
KeTop T10 Appendix: KVC telegrams on KeTop T10
For more information see "KeTop KVC Programmierhandbuch".
Project engineering manual V1.02 91
Loading...