At various points in this manual you will see notes and precautionary
warnings regarding possible hazards. The meaning of the symbols used is
explained below.
• DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
• WARNING indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
!
DANGER
!
WARNING
!
CAUTION
• CAUTION indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury.
CAUTION
• CAUTION used without the safety alert symbol indicates a potentially hazardous
situation which, if not avoided, may result in property injury.
This symbol reminds you of the possible consequences of touching
electrostatically sensitive components.
Note
Notes on use of equipment and useful practical tips are identified by the
“Notice” symbol. Notices do not contain any information that draws
attention to potentially dangerous or harmful functions.
The FM 299/A and the GA1060 bus do not have any special parameters
except for their name and cycle time.
The configuration file is used to configure also the drives operated at the
GA1060 – see the following example.
Example:
[IO.ONBOARD.KBUS:0]
name = "Kbus"
cycleTime = 0.001
traceWord = 0
[IO.ONBOARD.KBUS:0.FM299:0]
name = "FM299_Interface"
traceWord = 0
[IO.ONBOARD.KBUS:0.FM299:0.GA1060B:0]
name = "GA1060B_Bus"
cycleTime = 0.002
traceWord = 0
The following information describes the configuration of one of SDC’s QSEdrive controller. Please refer to the relevant drive documentation for a
description of the parameters and additional information.
To ensure adequate stability the GA1060 drive bus must be built as fully
shielded interface. Consequently the entire bus periphery must be provided
with an uninterrupted shield connection.
Connector
9-pole D-SUB socket connector with completely conductive shell.
The cable shielding must be connected plane with the shield cover of the
plug. An additional connection of the shield and the ground is not
necessary.
Cable
Pin assignment:
Pin Meaning
Pin1 GA1060 Bus +
Pin2 GA1060 Bus Pin3 – 8 GND
Pin9 n.c.
Cable type
Shielded, twisted pair data cables with a characteristic impedance of 100 –
120 Ω.
Structure
Twisted pair, shielded with signal ground.
Twisted pai r data c ables (GA 1060 Bus+,
GA1060 Bus-)
Signal ground (SGND)
Shield with signal ground
A multi-core twisted cable can also be used. Attention must be paid that the
GA1060 Bus+ and the GA1060 bus-lines are guided in a common twisted
pair of wires.
Schematic diagram of the bus topology bus terminating board
If the FM 299/A is connected at one bus terminating board of a GA1060
drive bus, a terminating board must be connected to the free plug. This is
done by soldering a resistance with 120 Ω in between the Pins 1 and 2
(GA1060 Bus).
120
1
6
GND
GND
GND
n.c.
9
5
GA1060-Bus interface with activated bus terminating board
Logic supply 5V via K-Bus
Power consumption: Max. 1.0 W
Safety class: III according to EN 61131-2
Displays on the front panel: LEDs for transmission and receipt and for the status display
Max. number of modules at one CPU module 2
GA1060 Interface
Data transmission rates 10 Mbit/s
Max. cable length 10 m (between first and last participant)
Dimensions:
Footprint: Module height: 120 mm
Mounting depth: 100 mm
Front panel width: 22.5 mm
Module width (incl. K-Bus plug): 32.5 mm
Weight: 130 g
Standards:
The module conforms to the following standards:
General information
UL 508 UL – listed
Product standard for
programmable controllers:
IEC 61131-1:2003 General information
IEC 61131-2:2003 Hardware