Notes on This Manual
At various points in this manual you will see notes and precautionary warnings regarding possible hazards. The meaning of the symbols used is explained below.
DANGER indicates an imminently hazardous situation which, if not avoided, will
result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided,
could result in death or serious injury.
!
DANGER
!
WARNING
!
CAUTION
CAUTION indicates a potentially hazardous situation which, if not avoided, may
result in minor or moderate injury.
CAUTION
CAUTION used without the safety alert symbol indicates a potentially hazardous
situation which, if not avoided, may result in property injury.
This symbol reminds you of the possible consequences of touching electrostatically sensitive components.
Note
Notes on use of equipment and useful practical tips are identified by the “Notice” symbol. Notices do not contain any information that draws attention to potentially dangerous or harmful functions.
© KEBA 2006 Specifications are subject to change due to further technical developments. Details presented may be subject to correction.
All rights reserved. Document: version 1.1 / article no.: 1000296
Filename: fm299pjen.doc, last saving on: 3. 10. 2006
A: KEBA AG, Gewerbepark Urfahr, A-4041 Linz, Tel.: +43 732 7090-0, Fax: +43 732 7309-10, E-Mail: keba@keba.com D: KEBA GmbH Automation, Leonhard-Weiss-Straße 40, D-73037 Göppingen, Tel.: +49 7161 9741-0,
Fax: +49 7161 9741-40, E-Mail: keba@keba.com
US: KEBA Corp., 100 West Big Beaver Road, Troy, MI 48084, US,Tel.: +1 248 526-0561, Fax: +1 248 526-0562,
E-Mail: usa@keba.com
CN: KEBA Ltd., Unit 2107 Air China Plaza, Xiaoyun Road 36 #, Chaoyang District, Beijing, 100027, China,
Tel.: +86 10 8447-5861, Fax: +86 10 8447-5871, E-Mail: china@keba.com
www.keba.com
Page 3
GA1060 Field bus master module Contents
History
Modification
from / to
V1.0 / 100106 meis
V1.0 / V1.1 030806 10, 11 Changes to chapter "Creation of cfg-file" meis
Date Modified
pages
Description Author
Project Engineering Manual, version: 1.1 / article no.: 1000296 3
© KEBA 2006
Page 4
Contents SANMOTION C FM 299/A
4 Project Engineering Manual, version: 1.1 / article no.: 1000296
© KEBA 2006
Page 5
GA1060 Field bus master module Contents
Contents
Brief description..............................................................................................................7
1
2 General safety instructions ............................................................................................8
3 Configuration...................................................................................................................9
Configuration with the KEMRO.Manager...........................................................................9
Creation of cfg-file............................................................................................................10
Setting the K-Bus address...............................................................................................11
4 Connections, wiring ......................................................................................................12
SDC Bus interface...........................................................................................................12
General information..............................................................................................12
Connector.............................................................................................................12
Cable....................................................................................................................12
Cable routing ...................................................................................................................13
Bus topology....................................................................................................................13
Schematic diagram of the bus topology bus terminating board.......................................14
5 Operation and displays.................................................................................................15
Status LED.......................................................................................................................15
GA1060 Bus Status LEDs ...............................................................................................15
6 Technical data................................................................................................................16
Project Engineering Manual, version: 1.1 / article no.: 1000296 5
© KEBA 2006
Page 6
Contents SANMOTION C FM 299/A
6 Project Engineering Manual, version: 1.1 / article no.: 1000296
© KEBA 2006
Page 7
GA1060 Field bus master module Brief description

1 Brief description

The FM 299/A module is a K2-200 field bus master module for the Sanyo
Denki drive bus.
FM 299/A
STATUS
CN1
CN2
RXTX
Front view FM 299/A module
Two FM 299/A modules can be operated on one control CPU.
Project Engineering Manual, version: 1.1 / article no.: 1000296 7
© KEBA 2006
Page 8
General safety instructions SANMOTION C FM 299/A

2 General safety instructions

z The device is defined as an "open type equipment" so that it must be
installed in a control cabinet.
z The safety instructions in the project engineering handbook "K2-200
automation system” are to be complied with.
CAUTION
Turn off the power supply before inserting or removing the module. Otherwise,
the module can be destroyed or undefined signal states can lead to damage of the control system.
8 Project Engineering Manual, version: 1.1 / article no.: 1000296
© KEBA 2006
Page 9
GA1060 Field bus master module Configuration

3 Configuration

Only a name has to be assigned for the configuration of the FM 299/A. In
addition, the GA1060 bus must be configured, also with its name and the
cycle time.
The FM 299/A can be configured at the CPU module in two different ways:
Via Kemro.manager
through the creation of cfg-files with a text editor
Two FM 299/A modules can be operated on one CPU.

Configuration with the KEMRO.Manager

The Kemro.managers can be used to configure all modules of a systems as
well as the Sanyo Denki converters of the QSE series.
At selection of the FM 299/A one column is automatically created for the
bus connection, which is then used to connect the drives.
Once all modules have been specified in the system and after all
parameters have been adjusted the Kemro.manager creates the necessary
cfg-files.
Project Engineering Manual, version: 1.1 / article no.: 1000296 9
© KEBA 2006
Page 10
Configuration SANMOTION C FM 299/A

Creation of cfg-file

The FM 299/A and the GA1060 bus do not have any special parameters except for their name and cycle time.
The configuration file is used to configure also the drives operated at the GA1060 – see the following example.
Example:
[IO.ONBOARD.KBUS:0] name = "Kbus" cycleTime = 0.001 traceWord = 0
[IO.ONBOARD.KBUS:0.FM299:0]
name = "FM299_Interface" traceWord = 0
[IO.ONBOARD.KBUS:0.FM299:0.GA1060B:0]
name = "GA1060B_Bus" cycleTime = 0.002 traceWord = 0
The following information describes the configuration of one of SDC’s QSE­drive controller. Please refer to the relevant drive documentation for a description of the parameters and additional information.
[IO.ONBOARD.KBUS:0.FM299:0.GA1060B:0.QSE:0]
name = "Axis_0" address = 0 MOCODE = 16#1017 ENCODE = 16#800B ENTYPE = 16#8300
driverMode = 3 positionMode = 1
maxPositionExponent = 32
positionOffset = 0.0 posUnitsToIncrements = 16.00 velUnitsToRpm = 11.777 torqueUnitsToPercent = 13.66
comBank = 16 // default = 17 resBank = 65 // default = 66
periodNum = 10 periodDenom = 200
traceWord = -1
[IO.ONBOARD.KBUS:0.FM299:0.GA1060B:0.QSE:0.BANK1]
DAT2 = 16#0001 DAT3 = 16#0001 DAT4 = 16#0005 DAT5 = 16#0000 DAT6 = 16#0032 DAT7 = 16#0090
10 Project Engineering Manual, version: 1.1 / article no.: 1000296
© KEBA 2006
Page 11
GA1060 Field bus master module Configuration
DAT8 = 16#0000
DAT9 = 16#0000
[IO.ONBOARD.KBUS:0.FM299:0.GA1060B:0.QSE:0.BANK8]
DAT2 = 16#0030
DAT3 = 16#1000
DAT4 = 16#0000
DAT5 = 16#0050
DAT6 = 16#0020
DAT7 = 16#0100
DAT8 = 16#0000
DAT9 = 16#0000
For user with a higher userlevel the following configuration entry is
available:
[IO.ONBOARD.KBUS:0.FM299A:0]
optional=0 / optional configuration:
/ 0 ... when the module is not available
/ an "Error" occurs
/ 1 ... when the module is not avialable
/ a "Warning" occurs

Setting the K-Bus address

The modules are addressed via the address switch. A maximum of two FM
299/A modules can be operated on one K2-200 control CPU.
The address switch is located on the right side underneath the lower cover.
The K-Bus plug is located underneath the upper cover.
ADR0
ADR1
Position of the address switch
On leaving the factory the FM 299/A module is set to address 0 and both
covers are closed.
Project Engineering Manual, version: 1.1 / article no.: 1000296 11
© KEBA 2006
Page 12
Connections, wiring SANMOTION C FM 299/A

4 Connections, wiring

SDC Bus interface

General information

To ensure adequate stability the GA1060 drive bus must be built as fully shielded interface. Consequently the entire bus periphery must be provided with an uninterrupted shield connection.

Connector

9-pole D-SUB socket connector with completely conductive shell. The cable shielding must be connected plane with the shield cover of the plug. An additional connection of the shield and the ground is not necessary.

Cable

Pin assignment:
Pin Meaning
Pin1 GA1060 Bus + Pin2 GA1060 Bus ­Pin3 – 8 GND Pin9 n.c.
Cable type
Shielded, twisted pair data cables with a characteristic impedance of 100 – 120 Ω.
Structure
Twisted pair, shielded with signal ground.
Twisted pai r data c ables (GA 1060 Bus+, GA1060 Bus-)
Signal ground (SGND)
Shield with signal ground
A multi-core twisted cable can also be used. Attention must be paid that the GA1060 Bus+ and the GA1060 bus-lines are guided in a common twisted pair of wires.
12 Project Engineering Manual, version: 1.1 / article no.: 1000296
© KEBA 2006
Page 13
GA1060 Field bus master module Connections, wiring

Cable routing

Signal and data lines that are foreign to the system and not connected to
the Kemro-control must not be routed in the same cable as the system’s
own signal and data lines. All shielded signal, data and low voltage supply
lines with contacted shields on either side can be routed parallel to one
another and parallel to the energy supply lines.

Bus topology

The GA1060 drive bus is a bus system that must be closed on either end with a bus terminating board.
The FM 299/A can be operated at the end of the bus line or at any section of the bus line. CN1 and CN2 can be located anywhere
The total bus length must not exceed 10 meters, whereby the gaps between the individual participants can be freely selected.
Drive contr ols
FM 299/A
STATUS
CN1
BA
CN2
RXTX
FM 299/A
STATUS
Drive contr ols
CN1
BT
BT
Drive contr ols
BT
CN2
RXTX
BT … bus terminating board
Project Engineering Manual, version: 1.1 / article no.: 1000296 13
© KEBA 2006
Page 14
Connections, wiring SANMOTION C FM 299/A

Schematic diagram of the bus topology bus terminating board

If the FM 299/A is connected at one bus terminating board of a GA1060 drive bus, a terminating board must be connected to the free plug. This is done by soldering a resistance with 120 Ω in between the Pins 1 and 2 (GA1060 Bus).
120
1
6
GND GND GND
n.c.
9
5
GA1060-Bus interface with activated bus terminating board
Ω
GA1060 Bus+ GA1060 Bus­GND GND GND
14 Project Engineering Manual, version: 1.1 / article no.: 1000296
© KEBA 2006
Page 15
GA1060 Field bus master module Operation and displays

5 Operation and displays

Status LED

LED color Function
orange System start-up
green Communication alive, no error
red After switch-on -> module faulty
In cyclical mode -> Communication error, no communication possible

GA1060 Bus Status LEDs

LED color Labeling Function
yellow TX Indicates transmission activity
green RX Indicates receiving activity
Project Engineering Manual, version: 1.1 / article no.: 1000296 15
© KEBA 2006
Page 16
Technical data SANMOTION C FM 299/A

6 Technical data

General information
Logic supply 5V via K-Bus Power consumption: Max. 1.0 W Safety class: III according to EN 61131-2 Displays on the front panel: LEDs for transmission and receipt and for the status display Max. number of modules at one CPU module 2
GA1060 Interface
Data transmission rates 10 Mbit/s Max. cable length 10 m (between first and last participant)
Dimensions:
Footprint: Module height: 120 mm Mounting depth: 100 mm Front panel width: 22.5 mm Module width (incl. K-Bus plug): 32.5 mm Weight: 130 g
Standards:
The module conforms to the following standards: General information
UL 508 UL – listed
Product standard for programmable controllers: IEC 61131-1:2003 General information IEC 61131-2:2003 Hardware
16 Project Engineering Manual, version: 1.1 / article no.: 1000296
© KEBA 2006