KEB 00.F4.010-3009 Instruction Manual

7/2003
PM.F4.01B-K102
KEB Memory Operator Memory Operator
BETRIEBSANLEITUNG
INSTRUCTION MANUAL
D 2
1. General................................................................................GB 4
1.1 Product Description ............................................................. GB 4
2. Memory Operator ............................................................... GB 5
2.1 Operation as Digital Operator .............................................. GB 5
2.2 Operation as Memory Operator............................................ GB 6
2.2.1 Upload ......................................................................................................GB 7
2.2.2 Download ..................................................................................................GB 7
2.2.3 Abort and Fault Acknowledgement ........................................................... GB 7
3. Special Functions ..............................................................GB 8
3.1 Interlock of the Mode FU_OP............................................... GB 8
3.2 Changing of the Baud Rate.................................................. GB 8
3.3 Drive Mode in the Memory-Operator .................................... GB 9
3.4 Software Date ...................................................................... GB 9
4. Error Messages................................................................GB 10
Table of Contents
00.F4.010-3009
1. General
This manual as well as the hardware and software are developments of the Karl E. Brinkmann GmbH. Errors and omissions excepted! The Karl E. Brinkmann GmbH prepared the documentation, software and hardware to the best of its knowledge, but no guarantee is given that the specifications will bring the user the efficiency aimed at. The Karl E. Brink­mann GmbH reserves the right to change the specifications without obligation. All rights reserved!
KEB Antriebstechnik develops, manufactures and distributes static frequency inverters worldwide in the industrial power range. Within the scope of automization, systems are needed which are more powerful and flexible . With this in mind KEB de v eloped a programming unit which makes it possible to program several inverters quickly and without internetworking. Parameter lists can be permanently stored in the programming unit, so they can be immediately retrieved when needed.
1.1 Product Description
The Memory Operator
- Can upload saved parameter lists from F4/S4 units
- Can download saved parameter lists
- Is downward compatible to the Digital-Operator (Exception: Drive-Mode)
- Can be directly connected to the F4/S4 units
Memory Operator
Operation as
Digital Operator
see section 2.1
Operation as
Memory Operator
see section 2.2
2. Memory Operator
The Digital Operator is the Standard Operator without interface in the KEB COMBIVERT F4/S4. The Memory Operator is do wnward compatible and can be used for normal operation except for one restriction.
During the operation of the Memory Operator the Drive Mode in COMBIVERT F4/S4 may not be activated, because the key assignment overlaps with the memory mode.
2.1 Operation as Digital Operator
wait until the display or LED is off
Insert Operator and switch on the unit
Switch off COMBIVERT
According to the baud rate of the Operator the display is shown for 5 Seconds.
with 9600 Baud with 19200 Baud
or
! also see 3.2 Changing of the Baudrate!
When the display switches the unit is ready for operation
Operation as Digital Operator
In this operating mode the parameter lists can
- be read from the inverter (Mode: FU_OP) (Upload)
- be written to the inverter (Mode: OP_FU) (Download)
Hold for approx. 5 sec. changes operating mode
Operation as Memory Operator
Switch off COMBIVERT
wait until the display or LED is off
Wait until display switches
with 9600 Baud with 19200 Baud
or
! also see 3.2 Changing of the Baud Rate!
Insert Operator and switch on the unit
Error Message Meaning
Display with locked Mode FU_OP. The Mode FU_OP (Upload) can be locked, to make sure that the data stored in the operator can not be overwritten.
see also section 3.1 Lock of the Mode FU_OP
Frequency inverter or servo controller was not recognized by the operator. P ossible Cause:
- Connection pin broken/missing
- Baud rate of the inverter / Servo-controller not in accordance with the baud rate of the operator
see 3.2 Change of the baud rate
To avoid problems for further operations, please pay attention to the following error messages!
! Further error messages see section 4 error messages!
ENTER
F/R
FUNC. SPEED
+
2.2 Operation as Memory Operator
According to the baud rate of the inverter the display is shown 5 seconds
FUNC. SPEED
START
ENTER
F/R
ENTER
F/R
FUNC. SPEED
START
ENTER
F/R
ENTER
F/R
FUNC. SPEED
➡➡➡➡
+
➡➡➡
+
Operating mode: download
Operating mode: upload
Changes to the operating mode: upload
Starts the upload process
Upload operating
Upload completed
Confirms the upload
Hold for approx. 5 sec. switches to normal operation
when Display „no_Lo“ see section 3.1 Lock Mode FU_OP
Operating mode: download
Starts the download process
Download operating
Download completed
Confirms the Download
Hold for approx. 5 sec. switches to normal operation
2.2.3Abort and Fault knowledgement
With the „Stop“-key a read- or write process can be interrupted. The error message Err.1 is displayed. With the „Enter“-key the error message is accepted and the operator changes into the selected operating mode. Data, transfered before interruption are written in the selected target unit. A parameter list, which is interrupted during the transfer to the operator or COMBICARD displays at transmission (e.g.: mode OP-FU) the error message Err .6, because the list does not include all parameters .
2.2.1 Upload
2.2.2 Download
START
STOP
START
STOP
The mode FU_OP (Upload) can be locked, to make sure that the data stored in the operator can not be overwritten.The status is displayed by pressing the POWER-ON button and the „FUNC.-key“ simultaneously.
Lock Mode FU_OP:
Enable Mode FU_OP:
enable mode
FU_OP (Upload)
locked the mode FU_OP
goes back into normal operation
Locked mode
FU_OP (Upload)
goes back into normal operation
release of mode FU_OP
FUNC. SPEED
FUNC. SPEED
➥➥
Press
Switch on
Inverter
Press
Switch on
Inverter
START
START
STOP
➥➥
START
START
STOP
➥➥
T o adjust the baud rate of the operator to the baud rate at FU , the operator can operate with 9600 baud or with 19200 baud. The actual adjusted baud rate is displayed by pressing the POWER-ON button and the „START-key“ simultaneously.
Increase Baud Rate:
Decrease Baud rate:
Press
Switch on
Inverter
9600 Baud
increase baud rate to 19200 baud
goes back into normal operation
Press
Switch on
Inverter
19200 Baud
goes back into normal operation
decrease baud ra­te to 9600 baud
After changing of the baud rate the display of the operator goes into nor­mal operation.
3.2 Changing of the Baud Rate
3. Special functions
3.1 Lock Mode FU_OP
T o s witch an inverter/servo with Memory-Operator into the memory mode do the following:
ENTER
F/R
+
FUNC. SPEED
press
Memory Mode
Inverter/Servo in Drive-Mode
To return to the Drive-Mode, do the following:
ENTER
F/R
+
FUNC. SPEED
press
Inverter/Servo is in the CP-Mode
Inverter/Servo in Drive-Mode
Enter the Drive-Mode password in CP.0
Drive-Mode
The Drive-Mode can not be exited when inverter type 45 (agree with F4-S V1.0) is used
If the STOP-key is pressed when the programmer is switched on, the software date of the memory operator is shown.
Day Month Year
3.3 Drive-Mode in the Memory-Operator
3.4 Software Date
GB 10
Memory capacity is not sufficient to read in parameters. (In mode FU-OP)
Unit is not suited for data transmission with the memory operator.
Parameters have not been saved completely in the operator memory (RAM).
During download into memory and
errors message occurred (Err.1....5).
Thus, not all parameters could be saved.
The connected inverter’s address does not correspond to the inverter address saved in the memory.
- Clear error message by pressing the ‘ENTER’-key → inverter’s address will not be changed
- By pressing the ‘START’-key → the error is cleared and the addresses in the memory operator are down­loaded.
Download to the inverter was stopped (With Mode OP_FU)
The inverter was not in state „noP“ during writing parameter Fr.01 open control release and start „download“ again.
Saved (e.g. type 45) and connected (e.g. type 46) inverter do not correspond. All type numbers can be displayed (In mode OP_FU)
- Clear message by pressing the ‘ENTER’ -key → download is stopped.
- Clear message by pressing the ‘START’-key → download continues. This function is used e.g. to change inverter-software­versions, to transfer old download lists onto the new software.
(Beispiel)
4. Error Messages
Display Description Cause / Remedy
Frequency inv erter or servo controller was not recognized by the operator
Connection pin broken/missing; Baud rate not correct adjusted; Operator or controller defective
Upload unpossible - Data of the inverter cannot be load in the operator
Mode FU_OP (UPLOAD) is locked. (see 3.1)
Selected operation canceled by user . “STOP” -key was pressed while
display was flashing
During an active operation (e.g. download) the connected inverter or servo is no longer recognized by the operator.
Connection pin broken or missing, transmission interrupted, frequency inverter/servo controller is switched off.
© KEB xx.F4.xxx-xxxx 7/2003
Karl E. Brinkmann GmbH
Försterweg 36 - 38 • D - 32683 Barntrup
Telefon 00 49 / 52 63 / 4 01 - 0 • Fax 00 49 / 52 63 / 4 01 - 1 16
Internet: www .keb .de • E-mail: inf o@keb .de
KEB Antriebstechnik GmbH & Co. KG
Wildbacher Str. 5 • D - 08289 Schneeberg
Telefon 0049 / 37 72 / 67 - 0 • Telefax 0049 / 37 72 /67 - 2 81
E-mail: info@keb-combidrive.de
KEB Antriebstechnik Austria GmbH
Ritzstraße 8 • A - 4614 Marchtrenk
Tel.: 0043 / 7243 / 53586 - 0 • FAX: 0043 / 7243 / 53586 - 21
Kostelni 32/1226 • CZ - 370 04 Ceské Budejovice
Tel.: 00420 / 38 / 731 92 23 • FAX: 00420 / 38 / 733 06 97
E-mail: info@keb.at
KEB Antriebstechnik
Herenveld 2 • B - 9500 Geraadsbergen
Tel.: 0032 / 5443 / 7860 • FAX: 0032 / 5443 / 7898
E-mail: koen.detaeye@keb.de
KEB China
Xianxia Road 299 • CHN - 200051 Shanghai
Tel.: 0086 / 21 / 62350922 • FAX: 0086 / 21 / 62350015
Internet: www.keb-cn.com • E-mail: info@keb-cn.com
Société Française KEB
Z.I. de la Croix St. Nicolas • 14, rue Gustave Eiffel
F - 94510 LA QUEUE EN BRIE
Tél.: 0033 / 1 / 49620101 • FAX: 0033 / 1 / 45767495
E-mail: sfkeb.4@wanadoo.fr
KEB (UK) Ltd.
6 Chieftain Buisiness Park, Morris Close
Park Farm, Wellingborough, GB - Northants, NN8 6 XF
Tel.: 0044 / 1933 / 402220 • FAX: 0044 / 1933 / 400724
Internet: www.keb-uk.co.uk • E-mail: info@keb-uk.co.uk
KEB Italia S.r.l.
Via Newton, 2 • I - 20019 Settimo Milanese (Milano)
Tel.: 0039 / 02 / 33500782 • FAX: 0039 / 02 / 33500790
Internet: www.keb.it • E-mail: kebitalia@keb.it
KEB - YAMAKYU Ltd.
15 – 16, 2 – Chome, Takanawa Minato-ku
J – Tokyo 108 -0074
Tel.: 0081 / 33 / 445-8515 • FAX: 0081 / 33 / 445-8215
E-mail: kebjt001@d4.dion.ne.jp
KEB Portugal
Lugar de Salgueiros – Pavilhao A, Mouquim
P - 4760 V. N. de Famalicao
Tel.: 00351 / 252 / 371 318 • FAX: 00351 / 252 / 371 320
E-mail: keb.portugal@netc.pt
KEB Taiwan Ltd.
1F, No.19-5, Shi Chou Rd., Tounan Town
R.O.C. - Yin-Lin Hsian / Taiwan
Tel.: 00886 / 5 / 5964242 • FAX: 00886 / 5 / 5964240
E-mail: keb_taiwan@mail.apol.com.tw
KEB Sverige
Box 265, Bergavägen 19
S-430 93 Hälsö
Tel.: 0046 31 961520 • Fax: 0046 31 961935
E-mail: thomas.crona@keb.de
KEBCO Inc.
1335 Mendota Heights Road
USA - Mendota Heights, MN 55120 Tel.: 001 / 651 / 4546162 • FAX: 001 / 651 / 4546198 Internet: www.kebco.com • E-mail: info@kebco.com
Loading...