Keating SERIES 2009 Operation Manual

Users Manual
CUSTOM PASTA SYSTEM®GAS SERIES 2009
READ AND SAVE THIS MANUAL FOR FUTURE REFERENCE.
RECORD THE MODEL AND SERIAL
NUMBERS OF THIS CUSTOM PASTA
SYSTE M® IN THE SPACES PROVIDED.
SERIAL NO. ______________________________
MODEL NO. _____________________________
KEEP THESE NUMBERS FOR FUTURE RE FERENCE.
IMPORTANT: Keep a copy of your bill of sale. The date on the bill establishes the warranty period
should service be required. If service is performed, it is in your interest to obtain and keep all receipts.
®
Keating Custom Pasta Systems
are not intended for household use.
This Owner’s Guide provides specific operating and service instructions for your model. Use the Custom Pasta Systems
®
only as instructed in this Service Manual.
CONTENTS:
SECTION I: INTRODUCTION
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
STAN DARD FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
MODEL VARIATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SAFETY PRECAUTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
SECTION II: INSTALLATION
DAMAGE DURING SHIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
DROP-IN CUTOUT/INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . .3
POSITIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
LEVELING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
RESTRAINING DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
ELECTRICAL CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
GAS LEAK TESTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
CHECK GAS SUPPLY PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . .6
SPECIAL NOTICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
WATE R AND DRAIN CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . .7
SECTION III: OPERATING THE PASTA SYSTEM
FILLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
LIGHTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
INDICATING LIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
COOKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
SHUTDOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
DRAINING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
CLEANING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
ELECTRONIC TIMERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-10
SECTION IV: MAINTENANCE
WARRANTY REPAIRS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
PREVENTIVE MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
SECTION V: SERVICE DIAGNOSIS
WATE R FILL AND SAFETY SH UT-OFF CIRCUIT BOARD
AND SENSOR CHECK . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11-12
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
TROUBLE SHOOTING CHART . . . . . . . . . . . . . . . . . . . . . . . . .13-16
REPLACEMENT OF A & B BOARDS . . . . . . . . . . . . . . . . . . . . . . .17
SECTION VI: PARTS LIST
ORDERING PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
CONTROL PANEL ASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . .18-19
GAS PASTA SYSTEM ASSEMBLY I . . . . . . . . . . . . . . . . . . . . . . . . .20
GAS PASTA SYSTEM ASSEMBLY II . . . . . . . . . . . . . . . . . . . . . . . .21
BASKET LIFT POWER SUPPLY BOX . . . . . . . . . . . . . . . . . . . . . . .22
SECTION VII: WIRING DIAGRAMS
PASTA SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
AUTO-LIFT GAS PASTA SYSTEM . . . . . . . . . . . . . . . . . . . . . . . .24-28
part# 018766
1-800-KEATING
www.keatingofchicago.com
gasPasta
03/11
This operating, installation, and service manual should be given to
WARNING
Improper installation
can cause damage,
injury or death.
ShockBurnsGas
the user. The operator of the Pasta System should be familiar with the functions and operation of the cooker. This manual must be kept in a prominent, easily reachable location near the Pasta System.
POST THIS LABEL IN A
PROM INENT LOCATION ON
YOUR UNIT
IMPORTANT
IN THE EVENT A GAS ODOR IS DETECTED, SHUT DOWN UNITS AT MAIN SHUT OFF VALVE AND CONTACT THE LOCAL GAS COMPANY OR GAS SUPPLIER FOR SERVICE.
WARNING
FOR YOUR SAFETY
DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR
Do not store flammable
liquids near this or any
other appliance.
Using any parts other than genuine, Keating of Chicago, Inc. factory manufactured part
ANY OTHER APPLIANCE.
IMPROPER INSTALLATION, ADJUSTMENT, ALTERATION, SERVICE OR MAINTENANCE CAN CAUSE PROPERTY DAMAGE, INJURY OR DEATH. READ THE INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS THOROUGHLY BEFORE INSTALLING OR SERVICING THIS EQUIPMENT.
relieves the manufacturer of all warranty and liability.
Keating of Chicago, Inc. (manufacturer reserves the right to change specifications at
any time.
i
I INTRODUCTION
Instructions in this manual should be read thoroughly before attempting to operate this Keating Gas Pasta Cooker. All installation and service on Keating equipment must be performed by qualified, certified, licensed and/or authorized installation or service personnel.
Operating information for Keating equipment has been prepared for use by qualified and/or authorized personnel.
Keating equipment is made in the U.S.A. and has American sizes of hardware. All metric conversions are approximate.
GENERAL
Keating Pasta Gas Systems are designed to give maximum production efficiency, delivering high quality food products. The following design features are incorporated in Keating Pasta Gas Systems.
STANDARD PASTA SYSTEMS
Sizes: 14 to 24
Water capacity 5-1/2 to 19 gallons
24 Pasta System can cook 6 lbs. of dry pasta per
load up to 110 lbs. per hour
ETL Certified
ETL Santitation Certified
NSF Certified
MODEL VARIATIONS
Basket-Lift Model: Basket-Lift Model Pasta Systems
come with all the same features as the standard models. The Basket-Lift mechanism lowers the baskets of food into the water when the timer button is pressed and raises the baskets when the cooking cycle is complete. Split baskets are required for these models.
SAFETY PRECAUTIONS
STANDARD FEATURES
Highly polished stainless steel vessel
Highly polished stainless steel front
Highly polished stainless steel heat transfer tubes
Highly polished stainless steel thermostat bulb
Highly polished stainless steel Hi-Limit sensor
Grid screen over heat transfer tubes
Automatic water fill with manual override
Water solenoid and indicating light
Starch overflow
Two electronic timers
Low water safety shutoff
1” full port front drain valve on 14;
1-1/4” for 18 and larger
High temperature limit control with manual reset
Patented accurate temperature control system ±2°F
Ideal 35” working height
100% safety pilot shut off
3/4” gas connection on single Pasta System
One pair of split baskets or one bulk basket
Patented dual thermostat system
Indicating lights for pilot and secondary thermostat
on
THIS SYMBOL WARNS YOU THAT SERIOUS BURNS OR OTHER INJURIES MAY RESULT IF SAFETY INSTRUCTIONS ARE NOT FOLLOWED.
KEATING PASTA SYSTEMS ARE NOT INTENDED FOR USE WITH COOKING OIL.
This service manual should be retained in a safe
place for future reference. The installation of your new Pasta System must conform to local codes or in the absence of local codes, with the current National Fuel Gas Code ANSI Z223.1/NFPA 54, (latest edition) Natural Gas Installation Code CAN/CGA-B149.1 or Propane Installation Code CAN/CGA-B149.2.
Your ventilation hood, when installed, must
conform to the current ANSI/NFPA 96 (latest edition).
No frame or restriction shall be constructed around
the Pasta System that will restrict air movement into the Pasta System’s combustion area or prevent proper ventilation.
Keating Pasta Systems are designed to operate on
the gas fuel specified on the serial plate and must not be operated with another gas fuel. They cannot be converted to another gas fuel by turning or engaging a switch.
STANDARD ACCESSORIES
Keating Klenzer Sample
Drain clean out rod
Sensor Cleaning Brush
1
WARNING
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any appliance.
You will post, in a prominent location, instructions to be followed
Do not store flammable
liquids near this or any
other appliance.
in the event the user smells gas. This information shall be obtained
from your local gas supplier. You may use the yellow stick-on label temporarily until you receive the data from your local gas supplier.
IMPORTANT: In the event a gas odor is detected, shut down unit at main shut-off valve and contact the local gas company or gas supplier for emergency service.
exposing any individual to a chemical known to the State of California to cause cancer or reproductive toxicity without first giving clear and reasonable warning to such individuals.” The Governor’s Scientific Advisory Panel added carbon monoxide
to the list of hazardous chemicals known to cause reproductive harm.
In order to establish full compliance with Proposition 65, we attached a yellow warning label to each gas fired Pasta System manufactured by Keating of Chicago, Inc.
Carbon monoxide would not be present in concentrations that would pose a “significant risk” to the consumer when the equipment is installed, operated and maintained as follows:
You must maintain this appliance free and clear
from combustibles.
You must maintain the following minimum
clearances from combustible and noncombustible construction:
CLEARANCES
Combustible Construction
Back 6" 0"
Right Side 6" 0"
Left Side 6" 0"
Adequate clearance for servicing and proper
operation must be maintained. Your Pasta System is designed to be serviced from the front.
Keating commercial Pasta Systems are intended
for other than household use.
ALWAYS instruct new employees on proper Pasta
System operation.
ALWAYS turn Pasta System off each night.
ALWAYS disconnect fuel source before servicing.
NEVER use a Pasta System with cooking oil.
NEVER leave a Pasta System unattended during
operation.
Keating Pasta Systems are NOT intended for use
with cooking oil.
NEVER move a Pasta System with any hot water
in it.
Non-Combustible
Construction
Installed in accordance with all local codes, or in
the absence of local codes, with the current National Fuel Gas Code A223.1/NFPA54, Natural Gas Installation CAN/CGA-B149.1 or Propane Installation Code CAN/CGA-B149.2.
Installed under a properly designed operating
exhaust hood.
Connected to the type of gas for which the
appliance is manufactured.
Pressure regulator is installed in the appliance and
adjusted for the manifold pressure marked on the serial plate.
If the inlet gas pressure exceeds 6" WC for natural
gas and 12" WC for Propane, an in-line pressure regulator is required. In-line pressure regulators are not supplied by Keating. They are to be provided and installed by others as directed by local codes.
Adequate air supply to the Pasta System.
The equipment is operated in the manner intended
using the proper utensils.
Keep the equipment clean and have it checked
periodically.
Burner air adjustments, mechanical maintenance
and repairs must be performed by qualified service personnel.
NEVER introduce objects or liquids into Pasta
System, while operational, which are not designed or made for cooking.
THIS COOKER MAY NOT BE ALTERED,
MODIFIED OR CHANGED IN ANY WAY.
The State of California enacted the California Safe drinking water and Toxic Enforcement Act of 1986, (Prop. 65), which “prohibits any person in the course of doing business from knowingly and intentionally
If the equipment is not installed, operated and maintained in accordance with the above, concentrations of carbon monoxide in excess of the established limits could be present in the kitchen environment.
ALL PERSONNEL IN THE WORK PLACE WHO MAY BE SUBJECT TO ANY EXPOSURE OF CARBON MONOXIDE MUST BE WARNED OF SUCH POSSIBLE EXPOSURE. THIS WARNING SHOULD
2
BE CONVEYED IN A MANNER SO THAT IT IS
WARNING
Improper installation
can cause damage,
injury or death.
ShockBurnsGas
CLEARLY UNDERSTOOD BY THE EMPLOYEE, AND THE EMPLOYEE SHOULD BE ASKED IF IN FACT HE OR SHE UNDERSTANDS THE CORRECT METHOD OF OPERATION OF THE EQUIPMENT AND THAT A RISK OF EXPOSURE EXISTS IF THE EQUIPMENT IS OPERATED IMPROPERLY.
IF NOT INSTALLED, OPERATED AND MAINTAINED IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS, THIS PRODUCT COULD EXPOSE YOU TO SUBSTANCES IN FUEL OR IN FUEL COMBUSTION WHICH CAN CAUSE DEATH OR SERIOUS ILLNESS AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.
II INSTALLATION
This Pasta System MUST be installed, inspected, calibrated and serviced by qualified and/or certified and/or licensed service personnel – you may void your Keating warranty if installation is not completed per current local, national and Keating specifications. Contact your dealer for assistance.
these instructions carefully, we guarantee our full support of your claims to protect you against loss from concealed damage.
VISIBLE LOSS OR DAMAGE
Any external evidence of loss or damage must be noted on the freight bill or express receipt, and signed by the carrier’s agent. Failure to adequately describe such external evidence of loss or damage may result in the carrier refusing to honor a damage claim. The form required to file such a claim will be supplied by the carrier.
DO NOT RETURN DAMAGED MERCHANDISE TO KEATING. FILE YOUR CLAIM AS ABOVE.
INSTALLATION
Installation must conform with local codes or, in absence of local codes, with the current National Fuel Gas Code Z223.1/NFPA 54, Natural Gas Installation CAN/CGA - B149.1 or Propane Installation Code CAN/CGA-B149.2.
DROP-IN PASTA COUNTER
CUTOUT/INSTALLATION
DAMAGE DURING SHIPMENT
The Pasta System has been assembled, tested and inspected at the factory. Upon arrival, the complete Pasta System should be checked for any damage that may have occurred during shipment.
IF EQUIPMENT ARRIVES DAMAGED
Keating does not assume responsibility for loss or damage incurred in transit.
IMPORTANT
This merchandise has been thoroughly inspected and carefully packed before leaving our plant. Responsibility for its safe delivery was assumed by the carrier at the time of shipment. Claims for loss or damage to the contents should, therefore, be made upon the carrier, as follows:
CONCEALED LOSS OR DAMAGE
Concealed loss or damage means loss or damage which does not become apparent until the merchandise has been unpacked. The contents may be damaged in transit due to rough handling even though the carton may not show external damage. When the damage is discovered upon unpacking, make a written request for inspection by the carrier’s agent within fifteen days of the delivery date. Then file a claim with the carrier since such damage is the carrier’s responsibility. By following
INSTALLATION NOTES
1. Minimum of 130 sq. in. unobstructed vent area near pasta cooker required for combustion.
2. All Drop-In Pasta must be 16” from any open flame.
3. Pasta must be located no more than 5” from counter top front.
3
4. Cabinet must be reinforced to support full weight of past in use (pasta, water, food, etc.).
5. Pasta cooker must be properly ventilated and located under an exhaust hood.
DROPPING THE PASTA COOKER INTO THE COUNTER TOP
it is only necessary to place the pasta cooker in such a position that the front edge overlaps the front raised edge of the opening.
Push the fryer forward as far as it will go holding the fryer on approximately a 15° angle, and then drop the rear of the pasta cooker into its proper position lowering it down gently so you do not deform the table or equipment stand.
turning the caster in or out. When the desired level is reached, tighten the jam nut. Adjustments of more than 3/4” are not recommended on any caster. The same procedure should be followed to level the Pasta System from front to back.
Figure 2-1
POSITIONING
CLEARANCES
Combustible Construction
Back 6" 0"
Right Side 6" 0"
Left Side 6" 0"
The pasta cooker must be no closer than 6" from any combustible material. When placed under an exhaust hood with a fire retardant system it must comply with ANSI/UL 507-(Latest Edition) and ANSI/NFPA 96­(Latest Edition). No frame or restriction can be constructed around the lower part of the pasta cooker that would restrict ventilation or air movement into the pasta cooker. You must insure adequate air supply to the pasta cooker. ALL connections and placement must comply with local and national codes. It is the responsibility of the owner and local installer to comply with these regulations when installing the Pasta System.
Adequate clearance for servicing and proper operation must be maintained. Your pasta cooker is designed to be serviced from the front. Do not place a pasta cooker next to a deep fat fryer. Hot oil and water can cause an unstable condition creating a hazardous situation. The pasta cooker will operate at highest efficiency when properly leveled.
Non-Combustible
Construction
Caster
Leg
RESTRAINING DEVICES
On Pasta System installations with casters, casters and jam nuts must be completely tightened. Adequate means must also be provided to limit the movement of the appliance without depending on the connector, the quick-disconnect device or its associated piping to limit the appliance movement.
Connectors must comply with ANSI Z21.69/CAN1 CAN/CGA 6.16 (latest edition) for connectors for movable gas appliances. Quick-disconnect devices must comply with ANSI Z21.41/CAN 1 6.9 (or latest edition) standard for quick-disconnect devices for use with gas fuel as applicable.
IF DISCONNECTION OF THE RESTRAINT IS NECESSARY, IT MUST BE RECONNECTED WHEN THE PASTA SYSTEM IS RETURNED TO ITS ORIGINALLY INSTALLED POSITION.
Counter model and floor model Pasta System cookers must be restrained to prevent tipping when installed in order to avoid splashing, spilling, etc. of hot liquid. The restraining method may be a manner of installation or by separate means.
LEVELING
The Pasta System will operate at its highest efficiency when properly leveled. Place a level on Pasta System vessel from side to side. For Pasta Systems on legs, the bottom foot of the leg is adjustable. Turn counter clockwise to increase height or clockwise to decrease height until level. For Pasta Systems on casters, the casters are adjustable by loosening the jam nut and
4
SPECIFICATIONS
Models
14 CUSTOM PASTA SYSTEM 3 5.5 gal. 109K 109K
18 CUSTOM PASTA SYSTEM 4 8.5 gal. 135K 90K 20 CUSTOM PASTA SYSTEM 4 13.5 gal. 135K 90K 24 CUSTOM PASTA SYSTEM 5 19.0 gal. 165K 145K 1" 1" 1" 1" 1"
Total No.
of Burners
Water
Capacity
Fuel Input (BTU/hr)**
Natural Gas
Propane (LP)
Gas
Single Pasta System Supply Pipe Sizes
(For various pipe lengths)
6' 12' 18' 24' 30'
3
/4"3/4"3/4" 1" 1"
3
/4"3/4"
3
/4"3/4"
1" 1" 1" 1" 1" 1"
NOTE: The pipe size table shown is predicated on the fact that this is the sole supply line for a single Pasta System. If multiple Pasta Systems are to be connected, consult your local gas utility for the proper gas pipe size.
NOTE: Fuel ratings for propane gas Pasta System cookers in the U.S. may differ from natural gas models. In Canada, propane ratings are the same as U.S. natural gas ratings.
NOTE: Roughly half of all service calls result from inadequate gas supply. Do not use pipe sizes smaller than recommended in the table above.
GAS CONNECTION
HAVE YOUR PLUMBER OR GAS COMPANY CHECK FOR LEAKS.
PIPE JOINT COMPOUNDS RESISTANT TO PROPANE GASES MUST BE USED.
BEFORE OPERATING THIS PASTA SYSTEM, CHECK PIPE JOINTS FOR LEAKS BY USING A SOAP AND WATER SOLUTION OR SNIFFER ONLY. DO NOT USE AN OPEN FLAME!
WARNING
FOR YOUR SAFETY: Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
You will post, in a prominent location, instructions to be followed in the event
Do not store flammable
liquids near this or any
other appliance.
the user smells gas. This information shall be obtained from your local gas supplier.
Connect the Pasta System to the main gas supply line at the rear of the Pasta System. See figure 2-3 above.
The piping should be a minimum of 3/4" NPT supply pipe for a single Pasta System at the burner manifold. Batteries require larger supply lines. Installation must conform with local codes, or in the absence of local codes, with the current National Fuel Gas Code ANSI Z223.1/NFPA 54, Natural Gas Installation Code CAN/CGA-B149.1 or Propane Installation Code CAN/CGA-B149.2.
A3/4" IPS manual gas valve is shipped with each single Pasta System for field installation. Batteries have a factory installed manual gas valve for each Pasta System. The required gas pressure for proper operation of each Pasta System is 4" water column (WC) for natural gas and 10” water column (WC) for Propane gas at the burner manifold. Remove the allen head test plug on the gas valve and using a manometer to check pressure.
Figure 2-3
Main Gas and Water Supply Connection
Gas Supply
Water Supply
If the inlet gas pressure exceeds 7" WC for natural gas and 11" WC for Propane, an in-line pressure regulator is required. In-line pressure regulators are not supplied by Keating. They are to be provided and installed by others as directed by local codes.
NOTE: If more than one gas Pasta System is on the same supply line, you may require a larger line. Consult your local gas company to assure adequate volume and pressure. Refer to serial plate for proper gas requirements for your particular model.
5
ELECTRICAL CONNECTION
WARNING
The Keating Custom Pasta Gas System is equipped with a 9' neoprene covered, 3 wire electrical cord with a three-pronged grounded plug for protection against electrical shock. This plug must be placed into a
Plug into a
properly grounded
three-prong receptacle.
120V properly grounded three-pronged outlet (NEMA 5-15 or 5-
20). For proper grounding procedures
see local codes or, in the absence of local codes, the current National Electrical Code ANSI/NFPA 70 or Canadian Electrical Code CAN 22.2 as applicable.
NOTE: The electrical wiring diagram for the Pasta System is attached to the inside of the Pasta System door. Some of the more common versions are included in the back of this manual.
CHECK GAS SUPPLY PRESSURE
Special attention should be given to the supply pressure and gas flow pressure at the supply connection to the Pasta System. The nominal gas should be 4" WC for natural gas and 10" WC for propane gas.
If the supply pressure is lower or higher than the rated (nominal) pressure, then the reason should be investigated and the gas supplier contacted.
If the supply is lower than 2 1/2" WC or higher than 7" WC for natural gas or lower then 9” WC or higher than 12" WC for propane gas, then the Pasta System should be shut down and a service company or supplier notified. No adjustments should be made and the Pasta System should not be operated.
ONLY BY CERTIFIED PROFESSIONAL
1. Turn off main gas supply valve.
2. Remove pressure measuring stud screw located at the “out-flow” (closest to gas burner) of the gas valve and attach a manometer.
DO NOT CUT OR REMOVE THE GROUNDING PRONG FROM THIS PLUG.
GAS LEAK TESTING
Prior to lighting your Pasta System:
1. Make sure all thermostats, switches and safety valves are in the “OFF” position.
2. Turn main supply gas cock (Item 18, page 20) to the “ON” position.
3. Have your plumber or gas company check for leaks with a soap solution or sniffer. (NEVER check with an open flame)
4. Have your plumber or gas company representative light the constant pilot. (Not necessary if your Pasta System has an optional spark ignitor.)
NOTE: It is estimated that half of all service calls made on Keating Pasta Gas Systems result from an inadequate gas supply. During installation, have a gas company representative make certain that the Pasta System is receiving adequate gas pressure and volume.
PROPANE GAS MAY EVENTUALLY LOSE ITS ODOR AND PRECAUTIONS SHOULD BE TAKEN TO ASSURE THAT IT IS NOT PRESENT EVEN THOUGH YOU DO NOT DETECT AN ODOR. IF THERE IS ANY DOUBT, YOU SHOULD CALL YOUR LOCAL PROPANE GAS SUPPLIER FOR ASSISTANCE.
3. Remove cover screw from the gas valve pressure adjustment valve.
4. Open main gas supply valve and start Pasta System according to instructions with the thermostat set at 190°F(87.8°C).
5. Once the Pasta System is in operation, adjust pressure valve to 4" WC for natural gas and 10” WC for propane gas.
6. Turn Pasta System off, close main gas supply valve, remove manometer and tighten cover screw into pressure measuring stud.
SPECIAL NOTICES
The Pasta System should be operated only in an area that has good air circulation.
The Pasta System must be installed under an electrically powered ventilating hood.
The operator should be properly trained to the functioning of the Pasta System.
This instruction manual should be supplied to the operator.
Constructional changes to the area where the Pasta System is installed shall not affect the air supply to the Pasta System. The installation, start-up and changes required when changing from one gas type to another can be performed only by a certified professional.
The Pasta System is intended only for commercial use and is to be operated only by professionals.
It is required that the Pasta System is regularly inspected for proper function. The frequency of inspections are dependent of the Pasta System usage, however it should be performed at least once a day.
After adjustment or service work the Pasta System has to be checked for gas leaks.
6
NOTE: After conversions, readjustments or service work, the Pasta System has to be tested for proper functioning. Basically the following applies:
CALIBRATION
For Calibration refer to page 12 – Calibration. Note: Calibration is not covered under warranty.
WATER AND DRAIN CONNECTIONS
The water supply connection, located at the bottom rear of the Pasta System and marked water inlet, is a standard 3/8" female pipe connection. The water pressure should be between 20 - 60 psi. If the pressure exceeds 60 psi, a pressure regulator must be used. The water temperature must not exceed 150°F(65.6°C). Hot or warm water is not needed due to the instant recovery of the Pasta System; however, it’s use is not detrimental.
Figure 3-1
Manual Water Fill Level
When the water fill toggle switch (located between the green and blue indicating lights) is turned on, the Pasta System vessel automatically will be filled to the proper level. If the vessel is being manually filled with water from a faucet or through the manual fill button, fill to just below the overflow deck. The black manual fill button is located to the right of the blue water fill indicating light.
Connections suitable for hot water must be used. All connections must be tested for leaks before using the Pasta System.
NOTE: For Pasta Systems with casters, flexible hose must be used to avoid leaking when the Pasta System is moved for cleaning.
If during operation the boil is killed when water automatically enters the Pasta System, turn the water pressure down until water is added without killing the boil.
The drain terminates within inches of the floor and is designed for the standard dump to drain opening. In most cases, the health department will not allow a direct connection between the Pasta System drain and the floor receptacle. Contact your local health department for specific information in your area.
IT MAY BE NECESSARY TO INSTALL A BACK FLOW PROTECTOR OR CHECK VALVE ON THE WATER SUPPLY LINE TO THE PASTA SYSTEM. CHECK WITH EITHER YOUR LOCAL WATER OR HEALTH DEPARTMENT TO DETERMINE IF THIS IS NECESSARY IN YOUR SPECIFIC AREA.
III OPERATING
FILLING
NOTE: Before filling the Pasta System make certain the vessel is sanitized, dry and the drain valve is completely
closed.
LIGHTING
In the event of a power failure, check to see if constant pilot is still burning before resuming operation. If not, wait five minutes to allow any accumulated gas to escape and then re-light the constant pilot.
Figure 3-2
Lighting Controls
1. Open the main supply gas cock.
2. Turn “On” main power On/Off switch (located between the amber and green indicating lights).
3. Light the constant pilot (located next to left burner as you face it). If your Pasta System has an optional spark ignitor, omit this step.
4. Activate pilot light momentary switch (left top corner) and hold about 30 seconds, releasing it after pilot indicting light is illuminated. If the runner pilot tube fails to stay lit, wait five minutes before attempting to relight to allow any accumulated gas to escape.
5. Set the primary (left) thermostat to 212°F(100°C) and the secondary (right) thermostat to 190°F(87.8°C) or
Constant pilot location
7
less. Setting the secondary thermostat above 190°F(87.8°C) could allow the Pasta System to boil over or short cycle.
INDICATING LIGHTS
Amber–shows the runner pilot is lit.
Green–shows the secondary (right) thermostat is
calling for heat from the center burner(s).
Blue–shows water is filling into the Pasta System
vessel through the Pasta System water solenoid valve.
NOTE: The black manual water fill button is located to the right of the blue indicating light. This may be used to add water manually by depressing.
A. Standard Pasta System
1. Fill Pasta System as described on page 7 – Filling.
2. Set primary (left) thermostat to 212°F(100°C) and secondary (right) thermostat to 190°F(87.8°C).
3. When the water starts boiling, lower baskets slowly into the hot water.
4. Set timer for left or right side basket, whichever is being lowered into water.
5. When timer sounds, lift basket out of water. Place on basket hanger rods on splashback of Pasta System to allow draining of excess water.
B. Basket-Lift Model
COOKING
Keating Pasta Gas Systems are designed to provide maximum production efficiency and deliver high quality food products. Low-temperature cooking and highly polished stainless steel mean greater energy savings. Two thermostats are used to provide instant recovery and to save energy while water is boiling. The secondary (right) thermostat calls for additional heat at start up or occasionally when water is added. Follow cooking procedures below for your model.
NOTE: Use of sodium chloride (salt) during the cooking process will have a detrimental effect on the cooker tank and will void the warranty.
OPERATION OF THIS PASTA SYSTEM SHOULD BE LIMITED TO PERSONNEL WHO HAVE BEEN THOROUGHLY TRAINED IN OPERATING PROCEDURES.
USE ONLY KEATING APPROVED BASKETS IN YOUR PASTA SYSTEM. NEVER OVERFILL BASKETS. DO NOT BANG BASKETS ON BASKET HANGERS OR PASTA SYSTEM VESSEL.
1. Fill Pasta System as described on page 7 – Filling.
2. Set primary (left) thermostat to 212°F(100°C) and secondary (right) thermostat to 190°F(87.8°C).
3. Fill basket(s) to proper level and place on upper basket hanger rods on splashback of Pasta System.
4. Set timers to desired cooking time using T1, T2 or T3. (For Programming Timers see page 9-10 for 14” BL models & 10 for all others).
5. Push Start/Stop or T1, T2, or T3 button on timer(s). Basket(s) will automatically lower into the Pasta System vessel.
6. When cooking cycle is complete, an audible alarm will sound and the basket(s) will raise automatically. Allow water to drain before removing.
SHUTDOWN
1. Turn main power On/Off switch to “OFF” position.
2. Turn gas supply valve to “OFF” position.
3. Check to make sure all burners and pilots are extinguished.
CARE SHOULD BE TAKEN WHEN LOWERING BASKETS INTO PASTA SYSTEM TO PREVENT SPLASHING HOT WATER FROM PASTA SYSTEM VESSEL.
NEVER LIFT BASKETS DIRECTLY OUT OF THE PASTA SYSTEM VESSEL WITHOUT DRAINING AS SEVERE INJURY MAY RESULT.
NOTE: For counter model Pasta Systems, always check the rear drain operating handle before attempting to use the Pasta System. A safety switch prevents the Pasta System from operating if the handle is not pushed in completely and latched.
8
Loading...
+ 23 hidden pages