Keating 2009 Installation Manual

Users Manual
INSTANT RECOVERY®GAS FRYER SERIES 2009
READ AND SAVE THIS MANUAL FOR FUTURE REFERENCE.
IMPORTANT:
RECORD THE MODE L AND SERIAL
NUM BERS OF THIS INSTANT RECOVERY
GAS FRYER IN THE SPACES PROVIDED.
Keep a copy of your bill of sale. The date on the bill establishes the warranty period should
SERIAL NO. ______________________________
®
MODEL NO. _____________________________
KEEP THESE NUMBERS FOR FUTURE REFERENCE.
service be required. If service is performed, it is in your interest to obtain and keep all receipts. Keating commercial fryers are not intended for household use.
The Owner’s Guide provides specific operating instructions for your model. Use the Instant
®
Recovery
Gas Fryer only as instructed in this Service Guide.
CONTENTS:
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . i
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION
DAMAGE DURING SHIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
DROP-IN FRYER COUNTER CUT-OUT/INSTALLATION . . . . . . . . 1
FIRST STEPS
POSITIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
VENTILATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
NATIONAL CODE REQUIREMENT . . . . . . . . . . . . . . . . . . . . . . . . . 2
GAS CONNECTORS & PIPE SIZE . . . . . . . . . . . . . . . . . . . . . . . . . 2
FLEXIBLE GAS CONNECTION
& QUICK DISCONNECT DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . 3
RESTRAIN ING DEVICES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
ELECTRICAL CONNECTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
LEVELING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
PLACING YOUR KEATING FRYER IN OPERATION
FILLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
LIGHTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
SHUTDOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
COOKI NG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
TIME R PROGRAMMING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
OIL BREAKDOWN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
DRAINING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
CLEANING AND BOIL-OUT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-10
OPERATOR SELF HELP CHECK LIST . . . . . . . . . . . . . . . 11
PREVENTATIVE MAINTENANCE
PREVENTIVE MAINTENANCE CHART . . . . . . . . . . . . . . . . . . . . . 11
HI-LIM IT CHECK BI-MONTHLY . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
THER MOSTAT CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
THER MOSTAT BULB POSITIONING . . . . . . . . . . . . . . . . . . . 11-12
WARRANTY REPAIRS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
TROUB LESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12-15
ORDE RING PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
PARTS LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16-30
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-47
WARRANTY INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
part# 038142
1-800-KEATING
www.keatingofchicago.com
gasFryer2009
01/14
i
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
FOR YOUR SAFETY
Do not store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
*As continuous product improvement occurs, specifications may be changed without notice.
Purchaser should post in a prominent location instructions to be followed in the event the user
smells gas. This information shall be obtained by consulting the local gas supplier.
THE EQUIPMENT IS TO BE INSTALLED TO COMPLY WITH THE BASIC PLUMBING CODE OF THE BUILDING OFFICIALS AND CODE ADMINISTRATORS INTERNATIONAL, INC. (BOCA) AND THE FOOD SERVICE SANITATION MANUAL OF THE FOOD AND DRUG ADMINISTRATION (FDA).
IF NOT INSTALLED, OPERATED AND MAINTAINED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS, THIS PRODUCT COULD EXPOSE YOU TO SUBSTANCES IN FUEL OR IN FUEL COMBUSTION WHICH CAN CAUSE DEATH OR SERIOUS ILLNESS AND WHICH ARE KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER, BIRTH DEFECTS OR OTHER REPRODUCTIVE HARM.
PROPANE GAS MAY EVENTUALLY LOSE ITS ODOR AND PRECAUTIONS SHOULD BE TAKEN TO ASSURE THAT PROPANE GAS IS NOT PRESENT EVEN THOUGH YOU DO NOT DETECT AN ODOR. IF THERE IS ANY DOUBT, YOU SHOULD CALL YOUR LOCAL PROPANE GAS SUPPLIER FOR ASSISTANCE.
WARNING
Improper installation
can cause damage,
injury or death.
ShockBurnsGas
POST THIS LABEL IN A
PROMINENT LOCATION
ON YOUR UNIT
WARNING
Do not store flammable
liquids near this or any
other appliance.
INTRODUCTION
Instructions in this manual should be read thoroughly before attempting to operate this Keating Gas Fryer. All installation and service on Keating equipment must be performed by qualified, certified, licensed and/or authorized installation or service personnel.
Operating information for Keating equipment has been prepared for use by qualified and/or authorized personnel.
Keating equipment is made in the U.S.A. and has American sizes of hardware. All metric conversions are approximate.
INSTALLATION INSTRUCTIONS
Proper installation will assure top performance. Alterations of any kind to your equipment will void the warranty. Before uncrating, check equipment carefully for damage.
IF EQUIPMENT ARRIVES DAMAGED
Keating does not assume responsibility for loss or damage incurred in transit.
IMPORTANT
This merchandise has been thoroughly inspected and carefully packed before leaving our plant. Responsibility for its safe delivery was assumed by the carrier at the time of shipment. Claims for loss or damage to the contents should, therefore, be made upon the carrier, as follows:
CONCEALED LOSS OR DAMAGE
Concealed loss or damage means loss or damage which does not become apparent until the merchandise has been unpacked. The contents may be damaged in transit due to rough handling even though the carton may not show external damage. When the damage is discovered upon unpacking, make a written request for inspection by the carrier’s agent within fifteen days of the delivery date. Then file a claim with the carrier since such damage is the carrier’s responsibility. By following these instructions carefully, we guarantee our full support of your claims to protect you against loss from concealed damage.
VISIBLE LOSS OR DAMAGE
Any external evidence of loss or damage must be noted on the freight bill or express receipt, and signed by the carrier’s agent. Failure to adequately describe such external evidence of loss or damage may result in the carrier refusing to honor a damage claim. The form required to file such a claim will be supplied by the carrier.
DO NOT RETURN DAMAGED MERCHANDISE
TO KEATING. FILE YOUR CLAIM AS ABOVE.
INSTALLATION NOTES
1. All Drop-In Fryers must be 16" from any open flame.
2. Fryer must be located no more than 5" from counter top front.
3. Cabinet must be reinforced to support full weight of fryer in use (Fryer, oil, food, etc.).
4. Fryers must be properly ventilated and located under an exhaust hood.
DROPPING THE FRYER INTO THE COUNTER TOP
It is only necessary to place the fryer in such a positon that the front edge overlaps the front raised edge of the opening.
Push the fryer forward as far as it will go holding the fryer on approximately a 15° angle, and then drop the rear of the fryer into its proper position lowering it down gently so you do not deform the table or equipment stand.
FIRST STEPS
POSITIONING
Keep appliance area free and clear of any combustibles. Position the Keating Gas Fryer 6 inches (152mm) from any combustible material. A minimum of 24 inches (610mm) should be provided at the front of the Keating Gas Fryer for servicing and proper
DROP-IN FRYER COUNTER
CUTOUT/INSTALLATION
1
FRYER
“A” “B”
10×11 DI
13" 211/2"
10×11 DI E2000
13" 22"
14DI
16" 231/2"
18DI
20" 29"
5/8"
TYP. 45°
“A”
5/8"
DETERMINED BY
CUTTING TOOL
USED
5/8"
“B”
BEND UP 90° ON ALL SIDES TO FINAL OPENING SIZE (“A” X “B”), THEN CLOSE CORNERS BY WELDING AN INSERT PIECE (OR OTHER SUITABLE METHODS) FOR A LEAK FREE FIT.
1/8"
CUT LINE
5/8"
operation. Air for combustion enters the fryer from the bottom of the cabinet and the bottom of the control panel.
DO NOT BLOCK BOTTOM OF KEATING INSTANT
RECOVERY
®
GAS FRYER CABINET. DO NOT OBSTRUCT FLUE.
Your Keating Instant Recovery
®
Gas Fryer is designed
to be serviced from the front.
MINIMUM CLEARANCE
MINIMUM CLEARANCE
SUITABLE FOR NON COMBUSTIBLE FLOORS
VENTILATION
The Keating Gas Fryer must be installed in an area providing adequate air supply and ventilation. Do not obstruct the flow of combustion and ventilation air. Proper ventilation is one of the important considerations for efficient operation of the Keating Gas Fryer. It should be installed so that the products of combustion are removed efficiently without producing drafts that will interfere with proper burner operation. The intake for the exhaust fan should not be placed close to the flue of the Keating Gas Fryer to insure proper air flow necessary for combustion. The area around the front and bottom of the Keating Gas Fryer must be kept clear and unobstructed. In the U.S.A. the ventilation systems must conform to the ANSI/NFPA96 latest edition. A minimum of 18" (457mm) should be maintained between the flue outlet and the lower edge of the grease filters. Must be installed at least 16" away from any open flame. It is the responsibility of the owner and the local installer to comply with national and local codes.
NATIONAL CODE REQUIREMENT
The installation must conform with local codes, or in the absence of local codes, with the National Fuel Gas code, ANSI Z223.1 or the Natural gas Installation Code, CAN/CGA-B149.1 or the Propane Installation Code, CAN/CGA-B149.2. Flexible connectors must comply to ANSI Z221.69/CAN/CGA1.16. Keating equipment is designed and manufactured to operate only on the type of gas specified by the user and indicated on the serial plate located inside the door. The gas may be natural, propane or manufactured. The type of gas cannot be converted to another gas fuel by turning or engaging a switch.
GAS CONNECTIONS AND PIPE SIZE
A single Keating Gas Fryer requires a standard gas pipe size of 3/4 inch (19mm) I.D. connection. Multiple fryers with a common manifold will require a minimum of 1 1/4 inch I.D. gas supply line. The size of the gas supply pipe is very important. If the pipe is too small you will have low gas pressure at the Keating Gas Fryer manifold. Low gas pressure will cause slow recovery and/or delayed ignition, amongst other problems. If you have a question about gas pipe size, call your local gas company.
Before connecting new pipe to the Keating Gas Fryer the pipe must be blown out to remove all foreign particles. These particles in the controls or burners may cause improper or dangerous operating conditions.
Pipe joint compounds that are used on threaded joints of appliance piping shall be resistant to the action of liquefied petroleum gases (Loctite PST 56765). When using pipe joint compound do not apply to the first two threads. Use only a very small amount and only on male threads. This will prevent clogging of burner orifices and the gas valve. Never use compound on female threads as it might be pushed into the gas valve.
Have your installer check for gas leaks using a soap and water solution before operating.
DO NOT USE AN OPEN FLAME TO CHECK FOR GAS LEAKS.
1) The Keating Gas Fryer and its individual shut off valves must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.45kPa) (13.84 in WC). High pressure can damage the gas valve causing a hazardous condition. Excessive pressure introduced to the fryer may void the warranty.
2.) The appliance must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.45 kPa).
NOTE: Keating fryers use a constant pilot that will emit a very small amount of gas at all times.
NOTE: Line pressure must be kept below 10 (Nat), 13 (LP) during leak test to avoid damage to the gas
valve.
If more than one gas unit is on the same supply line, you may require a larger line. Consult your local gas company to assure adequate volume and pressure. Refer to serial plate for proper gas requirement for your particular model.
Clearances
Combustible Non-Combustible
Construction Construction
Back 6" 0"
Right Side 6" 0"
Left Side 6" 0"
2
WAR NIN G
Do not use open flame
to check for leaks.
3
FLEXIBLE GAS CONNECTORS AND QUICK
DISCONNECT DEVICES
For an appliance equipped with casters:
The installation shall be made with a connector that complies with the Standard for Connectors for Movable Gas Appliances, ANSI Z21.69 or the Standard for Connectors for Moveable Gas Appliances, CAN/CGA-6.16, and a quick disconnect device that complies with the Standard for Quick­Disconnect Devices for Use With Gas Fuel, ANSI Z21.41 or the Standard for Quick Disconnect Devices for Use with Gas Fuel, CAN1-6.9.
RESTRAINING DEVICES
1.) Adequate means must be provided to limit the movement of the appliance without depending on the connector and the quick-disconnect device or its associated piping to limit the appliance movement.
Fryer must also be restrained to prevent tipping when installed so that hot liquid splashing is avoided.
2.) The restraint means must be attached to the rear of the Keating Gas Fryer within 2" of the center line width and approximately 1-5/8" from the bottom of the cabinet back to allow the restraining bolt to be anchored to the cabinet back between the cabinet bottom and inner liner.
IF DISCONNECTION OF THE RESTRAINT IS NECESSARY, IT MUST BE RECONNECTED WHEN THE KEATING GAS FRYER IS RETURNED TO ITS ORIGINALLY INSTALLED POSITION.
INSTALLATION
The installer is responsible for attaching the tipping restraint. See page 3 for drop-in installation.
ELECTRICAL CONNECTION
The Keating Gas Fryer, when installed, must be electrically grounded in accordance with local codes, or in the absence of local codes, the National Electrical Code, ANSI/NFPA No. 70. or the Canadian Electrical Code, CSAC-22.2 as applicable. A wiring diagram is located on the last page or on the inside of the door. In the U.S.A. and Canada, the electrical supply must be 120 VAC, 60 Hz.
This appliance is equipped with a three-
prong 120 Volt NEMA 5-15 (grounding)
plug for your protection against shock
hazard and should be plugged directly
into a properly grounded and polarized
three-prong receptacle. Do not cut or
remove the grounding prong from this
plug. (Model AA has no electric
connection).
LEVELING
The Keating Gas Fryer will operate at its highest efficiency when properly leveled. Place a level on the fryer from side to side. For fryer on legs, the bottom foot of the leg is adjustable. Turn counterclockwise to increase height, or clockwise to decrease height until level. For fryers with casters, the casters are adjustable by loosening the jam nut and turning the caster in or out. When the desired level is reached, tighten the jam nut. Adjustments of more than 3/4" cannot occur with any caster. The same procedure should be followed to level the fryer from front to back.
PLACING KEATING GAS
FRYER IN OPERATION
NEVER LEAVE YOUR FRYER OPERATING UNATTENDED.
(When all previous instructions have been completed). Check the serial plate on the panel inside the door to
determine if the burner is set up for the proper type gas before connecting the quick-disconnect or piping from the building gas supply pipe.
a. Maximum INCOMING gas pressure
NATURAL GAS – 7 inches W.C. with burners on LP GAS – 11 inches W.C. with burners on
b. Fryer MANIFOLD gas pressure
NATURAL GAS – 4 inches W.C. with burners on LP – 10 inches W.C. with burners on
ALWAYS disconnect fuel source and power supply before servicing.
NEVER move a fryer when full of oil.
NEVER introduce objects or liquids into fryer, while operational, which are not designed or made for cooking.
THIS FRYER MAY NOT BE ALTERED, MODIFIED OR CHANGED IN ANY WAY.
NOTICE
Restraining devices
required.
WARNING
Plug into a
properly grounded
three-prong receptacle.
4
FILLING
NOTE: Before filling the fryer make certain the fryer
vessel is sanitized, dry and the drain valve is completely closed.
NOTE: Solid shortening can not be used in a Keating Model AA Gas Fryer. If solid shortening is used, it should be melted prior to filling the fryer vessel. Damage done by melting solid shortening in the fryer vessel will void the warranty.
Oil expands when heated. The Max line has been provided to ensure optimum cooking while ensuring the safety of the operator. Do not overfill the fryer vessel.
Max Line
Fill the fryer vessel with oil or MELTED solid shortening up to the Max line.
BE SURE THE HEAT TRANSFER TUBES ARE COMPLETELY COVERED WITH OIL BEFORE SWITCHING THE FRYER ON. IF OIL LEVEL DROPS BELOW TOP OF HEAT TRANSFER TUBES, SEVERE DAMAGE TO FRYER AND INJURY TO OPERATOR MAY RESULT.
LIGHTING INSTRUCTIONS
(See lighting instructions plate attached to the inner door of Keating Gas Fryer.) Model AA does not require an electrical connection.
Make sure that the Keating Gas Fryer is plugged in. If not your fryer will not operate. Make sure that the main gas valve on the gas supply line to the Keating Gas Fryer is in the ON position.
AIR IN THE GAS SUPPLY LINE MAY REQUIRE A LONGER THAN NORMAL PERIOD OF TIME TO LIGHT YOUR FRYER DURING INITIAL INSTALLATION OR AFTER OVERNIGHT SHUTDOWN
NOTE: Unless you have an AA model, your fryer cannot be operated during a power failure.
AA MODELS OPERATING INSTRUCTIONS
AA CONTROL PANEL – SERIES 2000
AA CONTROL PANEL – SERIES 2006
AA CONTROL PANEL – SERIES 2010
START-UP PROCEDURE
WARNING: DO NOT START FRYER WITHOUT FIRST FILLING FRY POT.
STEP 1. Set thermostat to the "OFF" position. STEP 2. Turn "MAIN POWER" switch to the "OFF"
position. STEP 3. Turn gas valve knob to "PILOT" position. STEP 4. Light constant pilot located on left side of
pilot runner tube. STEP 5. Push and hold the gas valve knob for 30
seconds and release. STEP 6. With the pilot still on, turn gas valve knob to
the "ON" position. STEP 7. Set thermostat to desired temperature, turn
"MAIN POWER" switch to the "ON"
position. The burners will come on.
SHUTDOWN PROCEDURE
STEP 1. Set thermostat to the "OFF" position. STEP 2. Turn "MAIN POWER" switch to the "OFF"
position. STEP 3. Turn gas valve knob to the "OFF" position. STEP 4. Turn gas supply valve to the "OFF" position. STEP 5. Check to make sure all burners and pilot are
extinguished.
POWER
OFF ON
5
SERIES 2000 BB MODELS
OPERATING INSTRUCTIONS
BB CONTROL PANEL – SERIES 2000
START-UP PROCEDURE
WARNING: DO NOT START FRYER WITHOUT FIRST FILLING FRY POT.
STEP 1. Set "MELT-IDLE-FRY" switch to "IDLE"
position and thermostat to the "OFF" position.
STEP 2. Turn "MAIN POWER" switch to the "ON"
position.
STEP 3. Light constant pilot located on left side of
pilot runner tube.
STEP 4. Hold the "PUSH TO LIGHT" switch in until
the amber "PILOT ON" light comes on. STEP 5. Set thermostat to desired temperature. STEP 6. Set "MELT-IDLE-FRY" switch to "FRY." The
burners will come on. Select "MELT" with
solid shortening until liquid shortening is 1"
from full, then switch to the "FRY" position
after packing shortening around burner
tubes.
SHUTDOWN PROCEDURE
STEP 1. Set "MELT-IDLE-FRY" switch to "IDLE"
position and thermostat to the "OFF"
position. STEP 2. Turn "MAIN POWER" switch to the "OFF"
position. Its green light will go off. STEP 3. Check to make sure all burners and pilot are
extinguished.
SERIES 2006 BB MODELS
OPERATING INSTRUCTIONS
BB CONTROL PANEL – SERIES 2006
START-UP PROCEDURE
WARNING: DO NOT START FRYER WITHOUT FIRST FILLING FRY POT.
STEP 1. Set thermostat to the "OFF" position. STEP 2. Turn "MAIN POWER" switch to the "ON"
position. The power ON light will illuminate.
STEP 3. Hold the "PUSH TO LIGHT" switch over
until the amber "PILOT ON" light comes on.
Release switch. STEP 4. Set thermostat to desired temperature. STEP 5. Set "MELT-FRY" switch to "FRY." The
burners will come on. Select "MELT" with
solid shortening until liquid shortening is 1"
from full, then switch to the "FRY" position
after packing shortening around burner
tubes.
SHUTDOWN PROCEDURE
STEP 1. Set thermostat to the "OFF" position. STEP 2. Turn "MAIN POWER" switch to the "OFF"
position. STEP 3. Check to make sure all burners and pilot are
extinguished.
SERIES 2006 BB SPARK IGNITION
OPERATING INSTRUCTIONS
BB SPARK IGNITION CONTROL PANEL – SERIES 2006
START
-UP PROCEDURE
WARNING: DO NOT START FRYER WITHOUT FIRST FILLING FRY POT
STEP 1. Set thermostat to the "OFF" position.
STEP 2. Turn "MAIN POWER" switch to the "ON"
position. STEP 3. Set thermostat to desired temperature. STEP 4. Set "MELT-FRY" switch to "FRY." The
burners will come on. Select "MELT" with
solid shortening until liquid shortening is 1"
from full, then switch to the "FRY" position
after packing shortening around burner
tubes.
SHUTDOWN PROCEDURE
STEP 1. Set thermostat to the "OFF" position. STEP 2. Turn "MAIN POWER" switch to the "OFF"
position. STEP 3. Check to make sure all burners and pilot are
extinguished.
6
SERIES 2000 TS MODELS
OPERATING INSTRUCTIONS
TS CONTROL PANEL – SERIES 2000
START-UP PROCEDURE
WARNING: DO NOT START FRYER WITHOUT FIRST FILLING FRY POT.
STEP 1. Set "MELT-IDLE-FRY" switch to "IDLE"
position and thermostat to the "OFF" position.
STEP 2. Turn "MAIN POWER" switch to "ON"
position. Its green light and the timers will come on.
STEP 3. Light constant pilot located on left side of
pilot runner tube.
STEP 4. Hold the "PUSH TO LIGHT" switch for 30
seconds. The pilot runner tube will light. STEP 5. Set thermostat to desired temperature. STEP 6. Set "MELT-IDLE-FRY" switch to "FRY" with
oil in the fry pot. The burners will come on.
Select "MELT" with solid shortening until
liquid shortening is 1" from full mark then
switch to the "FRY" position after packing
shortening around burner tubes.
SHUTDOWN PROCEDURE
STEP 1. Set thermostat to the "OFF" position. STEP 2. Turn "MAIN POWER" switch to the "OFF"
position. Its green light will go off. STEP 3. Check to make sure all burners and pilot are
extinguished.
SERIES 2006 TS MODELS
OPERATING INSTRUCTIONS
TS CONTROL PANEL - SERIES 2006
TS CONTROL PANEL - SERIES 2009
START
-UP PROCEDURE
WARNING: DO NOT START FRYER WITHOUT
FIRST FILLING FRY POT.
STEP 1. Set thermostat to the "OFF" position. STEP 2. Turn "MAIN POWER" switch to "ON"
position. Its green light and the timers will come on.
STEP 3. Light constant pilot located on left side of
pilot runner tube.
STEP 4. Hold the "PUSH TO LIGHT" switch for 30
seconds. The pilot runner tube will light. STEP 5. Set thermostat to desired temperature. STEP 6. Set "MELT-IDLE-FRY" switch to "FRY" with
oil in the fry pot. The burners will come on.
Select "MELT" with solid shortening until
liquid shortening is 1" from full mark then
switch to the "FRY" position after packing
shortening around burner tubes.
SHUTDOWN PROCEDURE
STEP 1. Set thermostat to the "OFF" position. STEP 2. Turn "MAIN POWER" switch to the "OFF"
position. Its green light will go off. STEP 3. Check to make sure all burners and pilot are
extinguished.
SERIES 2009 TS SPARK IGNITION
MODELS OPERATING INSTRUCTIONS
TS SPARK IGNITION CONTROL PANEL SERIES 2006
TS SPARK IGNITION CONTROL PANEL SERIES 2009
START-UP PROCEDURE
WARNING: DO NOT START FRYER WITHOUT
FIRST FILLING FRY POT.
STEP 1. Set thermostat to the "OFF" position. STEP 2. Turn "MAIN POWER" switch to "ON"
position. Its green light and the timers will
come on. STEP 3. Set thermostat to desired temperature. STEP 4. Set "MELT-IDLE-FRY" switch to "FRY" with
oil in the fry pot. The burners will come on.
1-800-KEATING
275
250
T3T2
T1
SET
1-800-KEATING
350
375
T3T2
T1
SET
L
A
T
O
I
C
D
A
T
L
F
I
I
B
H
R
S
E
A
T
MELT - FRYPOWER POWER ON PILOT ONPILOT
325
300
7
Select "MELT" with solid shortening until liquid shortening is 1" from full mark then switch to the "FRY" position after packing shortening around burner tubes.
SHUTDOWN PROCEDURE
STEP 1. Set thermostat to the "OFF" position. STEP 2. Turn "MAIN POWER" switch to the "OFF"
position. Its green light will go off. STEP 3. Turn gas supply valve to the "OFF" position. STEP 4. Check to make sure all burners and pilot are
extinguished.
SERIES 2000 - 2010 CPU MODELS
OPERATING INSTRUCTIONS
CPU CONTROL PANEL SERIES 2000
CPU CONTROL PANEL SERIES 2009
CPU CONTROL PANEL SERIES 2010
START-UP PROCEDURE
WARNING: DO NOT START FRYER WITHOUT
FIRST FILLING FRY POT.
STEP 1. Light mini pilot located next to the left
burner when facing fryer. STEP 2. Turn gas supply to the ‘ON’ position. STEP 3. Depress the main power switch to the ‘ON’
position. STEP 4. Make sure CPU is turned off. STEP 5. Engage the (Push to Light) switch and hold
until indicator light remains on or the pilot
runner tube remains lit. STEP 6. Turn the CPU on by pressing on/off button. STEP 7. Select melt cycle or heat cycle. STEP 8. Select the desired temperature. See the
computer manual for more information.
SHUTDOWN PROCEDURE
STEP 1. Turn CPU off by pressing the on/off button. STEP 2. Depress the main power switch to the off
position. STEP 3. Turn gas supply to the "OFF" position. STEP 4. Wait five minutes before restarting or
relighting fryer.
SERIES 2000 CPU SPARK IGNITION MODELS
OPERATING INSTRUCTIONS
CPU SPARK IGNITION SERIES 2000
START-UP PROCEDURE
WARNING: DO NOT START FRYER WITHOUT
FIRST FILLING FRY POT.
STEP 1. Turn gas supply to the ‘ON’ position. STEP 2. Depress the main power switch to the ‘ON’
position. STEP 3. Turn CPU to the ‘ON’ position. STEP 4. Select melt cycle or heat setting. STEP 5. Select the desired temperature. See the
computer manual for more information.
SHUTDOWN PROCEDURE
STEP 1. Turn CPU off by pressing the on/off button. STEP 2. Depress the main power switch to the ‘OFF’
position. STEP 3. Turn gas supply to the "OFF" position. STEP 4. Wait five minutes before restarting or
relighting fryer.
COOKING
Keating's Instant Recovery®Gas Fryer is designed to provide maximum production efficiency and deliver high quality food products. Low- temperature cooking, highly polished stainless steel and a true COLD ZONE mean extended oil life. Follow cooking procedures on next page for your model.
Cold Zone
OPERATION OF THIS FRYER SHOULD BE LIMITED TO PERSONNEL WHO HAVE BEEN THOROUGHLY TRAINED IN OPERATING PROCEDURES.
CARE SHOULD BE TAKEN WHEN LOWERING BASKETS INTO FRYER TO PREVENT SPLASHING HOT OIL FROM FRYER VESSEL.
If your fryer has timers, push the T1,” “T2 or T3 button on the digital timer(s). For fryers with automatic basket lift, basket(s) will lower into fryer vessel.
When timer(s) sounds, carefully lift basket(s) out of hot oil. For fryers with automatic basket lift, a buzzer will sound and the basket(s) will rise automatically. Allow oil to drain before removing.
DO NOT LIFT BASKETS DIRECTLY OUT OF THE FRYER VESSEL WITHOUT DRAINING AS SEVERE INJURY MAY RESULT.
USE ONLY KEATING APPROVED BASKETS IN YOUR FRYER. NEVER OVERFILL FRY BASKETS. DO NOT BANG BASKETS ON BASKET HANGERS OR ON FRYER VESSEL.
Place basket(s) on basket hanger on splashback of fryer and allow to drain.
SHUTDOWN INSTRUCTIONS
Always turn the fryer off each night. See Shutdown procedure.
TS MODEL TIMER
OPERATING INSTRUCTIONS
PART # 056921
DIGITAL TIMERS
The electronic timers, standard on TS models, provide a clearly visible and accurate display and are very easy to use. Three different, independent cook times can be set using this timer - T1, T2, and T3.
PROGRAMMING
To program the timers, the unit must be in the idle mode. Press and hold the set button for approximately two seconds. The display will show SEt. Press T1, T2, or T3 for the cook time to be programmed. The display will show the current setting for that cook time. Use the up or down button to increment or decrement the setting. When the setting is correct, press and hold the set button again for approximately two seconds. The display will show "StO" for approximately two seconds and the timer will return to normal operation. Repeat the process as necessary for the other timers.
OPERATING LOGIC
When the timer is powered up, the display will show the time setting for the cook time that was operated last and the relay output contacts will be open. To start a cycle, press the desired cook time button (T1, T2 or T3). The
display will begin to countdown from the preset time setting and the relay output contacts will close. During the countdown the colon will flash at a one-second rate. When the countdown has reached "00:00" the relay output contacts will open, the display will flash, and the audible alarm will sound. To cancel the audible alarm, press any button.
PAUSE FEATURE
To pause a cycle in progress, press any button. The relay output contacts will open, the display will flash, and the countdown will pause. To resume the countdown, press any button. The display will resume the normal countdown and the relay output contacts will close.
CANCELING A CYCLE
To cancel a cycle in progress press and hold any button for approximately two seconds. The relay output contacts will open and the display will show the time setting for the channel last used.
OIL BREAKDOWN
As part of a Preventive Maintenance Program, the oil in your fryer needs to be filtered regularly. The initial investment in the frying system is far less than the total overall costs of oil during the life of the fryer, and with regular filtering, you can realize substantial savings in oil costs, as well as maintenance charges. We have listed some of the conditions which are catalysts in the breakdown of oil:
1. Contact with Oxygen
2. Carbonization of Crumbs and Food Particles
3. Non-Stainless Steel Surfaces
4. Keep Salt and Seasonings Away From Oil
5. Prolonged High Temperatures
DRAINING
Operator in safety gear
ALWAYS SHUT THE FRYER OFF COMPLETELY BEFORE DRAINING. THE FRYER SHOULD BE DRAINED ONLY UNDER THE SUPERVISION OF PROPERLY TRAINED PERSONNEL. A DRAIN PIPE AND COVERED CONTAINER SUITABLE FOR USE WITH HOT OIL SHOULD BE USED TO ENSURE THE SAFETY OF THE OPERATOR.
8
9
1. Operator should be outfitted with proper attire including:
•Oil and heat resistant gloves
•Oil and heat resistant apron
•Safety goggles
•Oil and heat resistant footwear
2. Turn off the fryer and open the door.
3. Put suitable container under drain valve.
4. Drain oil from fryer by slowly turning handle. The drain will be completely open after 1/4 turn.
5. After fryer drains close the drain valve.
6. Filtering may be done at this step.
NOTE: Fryers with a central filter and under fryer filter
will drain differently. (See page 9.)
CLEANING AND BOIL-OUT
FOR A SINGLE FRYER
When cleaning and boiling out your fryer use Keating Sea Powder and Keating Klenzer to keep your fryer in top condition.
1. Operator should be outfitted with proper attire including:
•Oil and heat resistant gloves
•Oil and heat resistant apron
•Safety goggles
•Oil and heat resistant footwear
Turn the fryer off. Remove baskets and screen.
2. Drain oil from fryer, see draining.
A KEATING FRYER OR FILTER SHOULD BE DRAINED ONLY UNDER THE SUPERVISION OF PROPERLY TRAINED PERSONNEL. WHEN DISCARDING OIL, A COVERED RECEPTACLE APPROVED FOR USE WITH HOT OIL SHOULD BE USED. USE OF A NON-APPROVED RECEPTACLE OR METHOD OF DRAINING THE OIL COULD JEOPARDIZE THE SAFETY OF THE OPERATOR.
3. Remove oil container to a secure area to prevent accidental spillage.
4. Close the drain valve.
5. Fill fryer vessel to Max line with water.
6. Set thermostat and turn fryer on to bring water to a gentle boil. Once boil has been reached, turn fryer off.
UNDER NO CIRCUMSTANCES SHOULD THE FRYER AND FILTER BE LEFT UNATTENDED DURING BOIL-OUT. TRAINED PERSONNEL MUST BE PRESENT DURING THE PROCEDURE TO PREVENT BOIL OVER OR TO TURN OFF THE POWER IF WATER DROPS BELOW HEATING TRANSFER TUBES.
7. Dissolve
2
/3 cup of Keating Sea Powder for every
five gallons of water and let soak for 1/2
hour. If there is a large build-up of carbonized grease, allow for fryer to soak overnight.
8. While soaking, a natural fiber brush may be used to scrub the tubes and inside walls of fryer. Drain the water and Sea Powder into a dry suitable receptacle and remove from cooking area. Sprinkle Keating Klenzer liberally on tubes and sides of fryer vessel. A non-abrasive scouring pad may be used to remove the now softened carbonized grease. Thoroughly rinse fryer vessel with potable water to remove all Klenzer. Prior to refilling with oil, wipe the inside of the fryer vessel making sure all water and Klenzer have been removed.
NOTE: Do not pump water through the filter system.
DO NOT DAMAGE OR REPOSITION THERMOSTAT PROBE AS THIS MAY AFFECT THE ACCURACY OF THE FRYER.
DO NOT MIX WATER AND HOT OIL
9. Close the drain valve.
10. Check thermostat bulb positioning.
11. Refill the fryer with new or filtered oil.
TO AVOID DAMAGING THE FRYER, DO NOT POWER WASH, SPRAY OR HOSE IT DOWN WHILE CLEANING IT.
CLEANING AND BOIL-OUT FOR A FRYER
WITH BUILT IN FILTER SYSTEM
When cleaning and boiling out your fryer use Keating Sea Powder and Keating Klenzer to keep your fryer in top condition.
DO NOT PUMP WATER THOUGH YOUR FILTER SYSTEM.
REFER TO YOUR FILTER MANUAL FOR INSTRUCTIONS ON PROPER USE
SAFE & EASY FILTER
(SIDE VIEW)
A KEATING FRYER OR FILTER SHOULD BE DRAINED ONLY UNDER THE SUPERVISION OF PROPERLY TRAINED PERSONNEL. WHEN DISCARDING OIL, A COVERED RECEPTACLE APPROVED FOR USE WITH HOT OIL SHOULD BE USED. USE OF A NON-APPROVED RECEPTACLE OR METHOD OF DRAINING THE OIL COULD JEOPARDIZE THE SAFETY OF THE OPERATOR.
1.Operator should be outfitted with proper attire including:
–Oil and heat resistant gloves –Oil and heat resistant apron –Safety goggles –Oil and heat resistant footwear
2. Turn the fryer off.
A cleaning hose and wand have been provided for discarding oil.
3. Attach cleaning hose to quick disconnect located on the bottom right side of your filter.
4. Remove baskets and screen. Drain fryer into the central filter drawer.
5. Open the discard valve located near the quick disconnect in the filter cabinet.
6. The hose may now be used to pump the oil into the shortening handling system and discarded properly.
7. Remove oil container to a secure area to prevent accidental spillage.
8. Close the drain valve.
9. Fill fryer vessel to “Fill Level” line with water.
10. Set thermostat and turn fryer on to bring water to a gentle boil. Once boil has been reached, turn fryer off.
UNDER NO CIRCUMSTANCES SHOULD THE FRYER AND FILTER BE LEFT UNATTENDED DURING BOIL-OUT. TRAINED PERSONNEL MUST BE PRESENT DURING THE PROCEDURE TO PREVENT BOIL OVER OR TO TURN OFF THE POWER IF WATER DROPS BELOW HEATING TRANSFER TUBES.
11. Dissolve 2/3 cup of Keating Sea Powder for every five gallons of water and let soak for 1/2 hour. If there is a large build-up of carbonized grease, allow fryer to soak overnight.
12. While soaking, a natural fiber brush may be used to scrub the tubes and inside walls of fryer. Pump the water and Sea Powder into a dry suitable receptacle and remove from cooking area. Sprinkle Keating Klenzer liberally on tubes and sides of fryer vessel. A non-abrasive scouring pad may be used to remove the now softened carbonized grease. Thoroughly rinse fryer vessel with potable water to remove all Klenzer. Prior to refilling with oil, wipe the inside of the fryer vessel making sure all water and Klenzer have been removed.
DO NOT DAMAGE OR REPOSITION THERMOSTAT PROBE AS THIS MAY AFFECT THE ACCURACY OF THE FRYER.
DO NOT MIX WATER AND HOT OIL
13. Close the drain valve and disconnect the cleaning hose from filter machine.
Quick disconnect will remain hot for approximately 15 minutes.
14. Check thermostat bulb positioning (should be 1 paper thickness away from heat tube).
15. Refill the fryer with new or filtered oil.
Wait until filter drawer is cool before cleaning, approximately 15 minutes.
16. Remove filter drawer, drain, clean and dry.
17. Prepare filter drawer and return to filter cabinet.
TO AVOID DAMAGING THE FRYER, DO NOT POWER WASH, SPRAY OR HOSE IT DOWN WHILE CLEANING IT.
18. Pump must be primed with oil after boil-out with water.
Failure to lubricate pump may cause severe damage to Filter System.
Connect hose here to discard oil
10
11
OPERATOR SELF HELP
Before calling for service, review this list. It may save you both time and expense. This list includes common occurrences that are not the result of defective workmanship or materials in this appliance.
NOTE: For a fryer with a Central Filter or Safe & Easy
®
Filter always check the rear drain operating handle before attempting to use the fryer. A safety switch prevents the fryer from operating if the handle is not pushed in completely and latched. (See figure 3-2)
Figure 3-2
Rear Drain Operating Handle
PREVENTIVE MAINTENANCE
Preventive maintenance should be done in daily, weekly, monthly and yearly intervals as necessary. Following preventive maintenance procedures will help keep your fryer working efficiently. Proper care and servicing will lead to years of quality performance.
PREVENTIVE MAINTENANCE CHART
HI-LIMIT CHECK BI-MONTHLY
Place an accurate thermometer in the oil. If the Hi-Limit Control doesn’t shut off the fryer between 425°F and 450°F, have it replaced.
THERMOSTAT CALIBRATION
You will need:
One screwdriver with 1/8" wide flat blade
One accurate fryer thermometer
1. Set thermostat to desired frying temperature.
2. Allow fryer to cycle three times.
3. Place an accurate thermometer in the oil.
Thermostat calibration
NOTE: Locate thermometer in same position for every
calibration. Left front corner of fryer vessel at the High Limit Bulb is recommended.
4. If temperature of fryer is found to be more or less than 15°F off, remove the thermostat knob. There are (4) screws holding the dial plate in place. Loosen the screws and reset the dial plate to match the thermometer reading.
BEFORE REPLACING, TEST THERMOSTATS These operational problems can easily be corrected
by thermostat bulb positioning.
Keating’s patented thermostat application is accurate within 2°F of the dial setting between 250°F – 350°F. This accuracy is attained only if the thermostat bulb is placed properly against the heat transfer tube. To quickly and accurately test for proper bulb placement, a single thickness of writing paper should be pulled through between the tube and the bulb with medium resistance.*
1. *For gas fryers 14":
The end of thermostat bulb should touch the
burner tube.
2. For gas fryers 10×11, 18" & larger:
If the bulb is too loose, the paper will slip through
with little or no resistance. A fryer with a thermostat bulb that is too loose will overshoot.
Overshoot: The thermostat takes a long time to cycle and then misses its preset temperature by 20°F - 40°F yielding a poor quality product.
If the bulb is too tight, the paper will either not pull
through or it will tear. A fryer with a thermostat bulb that is too tight will short cycle.
Short Cycle: The thermostat will cycle rapidly while the fryer is in the idle mode; the temperature will be erratic.
TIME
FRAME
OPERATOR/OWNER
Daily
Check lights and controls.
Check that the oil is up to Max Line.
Clean all baskets.
Drain, strain or filter oil.*
Weekly
Drain and clean fryer.*
Boil-out fryer.
Bi-Monthy
Monthly
Hi-Limit & Test procedures.
Check calibration of the thermostat.
Yearly
QUALIFIED SERVICE PERSONNEL ONLY
Check burner flame color and adjust
air shutters.
Remove and clean all orifices.
• Clean Pilot Runner Tube.
• Check and replace wing turbulators.
*High production facilities should be checked more often. Contact your local service company to perform maintenance and repairs.
OCCURRENCE SOLUTION
Fryer does not operate:
Check power cord, unit plugged in?
Thermostat is in the off position.
Check gas supply.
Reset High Limit.
Thermostat Bulb Positioning 10×11, 18 & larger
Fryer Gas
DO NOT ADJUST THERMOSTAT SET SCREW - IT VOIDS ANY WARRANTY ON PART
WARRANTY REPAIRS
Keating's warranty begins with the date of
installation. In the event that your Fryer, under
warranty, needs repairs other than routine cleaning,
you are required to contact
KEATING OF CHICAGO, INC. (1-800-KEATING)
before calling a local service company.
SERVICE
Servicing should only be performed by qualified and licensed service companies.
THERMOSTAT REQUIRED TEST EQUIPMENT:
Multimeter (for testing continuity)
CHECKING CONTINUITY WITH THE MULTIMETER
1. Rotate the thermostat shaft until an audible click is heard.
2. Rotate the thermostat shaft left and right ten times causing the switch to click on and off ten times, while using the Multimeter to verify continuity.
3. If the switch does not show continuity during all ten trials, replace the thermostat.
DISASSEMBLING THE THERMOSTAT WILL VOID THE THERMOSTAT WARRANTY.
1. Set compression ring onto capillary end of bulb finger tight,
1
/2" from end of capillary.
2. Insert new thermostat bulb through control panel back.
3. Apply oil resistant flexible sealant onto compression fitting thread before installing fitting into fryer vessel.
4. Position bent portion of bulb against far right heat transfer tube and install compression fitting
snugly into fryer vessel.
5. Adjust bulb so at least 2" of bent portion of it is next to heat transfer tube and tighten compression nut onto compression fitting for fryer 10x11, 18 & up. The end of thermostat bulb should touch the burner tube for 14" fryers.
6. Replace burners.
7. Replace control panel back.
8. Slide back fabric shield over capillary and carefully coil capillary. Avoid crimping.
9. Reconnect wires to thermostat body.
10. Replace two screws which hold thermostat body to control panel.
11. Replace control panel.
12. Replace three retaining screws and washers which hold dial plate in place.
13. Replace thermostat knob.
14. Connect electric power source. Turn on gas and pilots.
15. Boil out fryer.
16. Refill fryer with oil to “Max” line.
17. Start fryer, preheat and calibrate with thermometer.
TROUBLESHOOTING
Millivolt Gas Valves
Part # 023625 (natural) & 023624 (LP)
MILLIVOLT CONTROL VALVE
To check Resistance of the gas valve, connect one wire to the valve as shown.
1. Resistance between the THTP & TH terminals
must be 11.5⍀±0.2⍀
2. Resistance between the THTP & TP terminals
must be 10.0⍀±0.2⍀
If resistance is outside of specifications listed, the gas valve must be replaced.
Before replacing thermopile check millivolt readings.
THERMOPILE READINGS:
With all wires connected, with the pilot on and burners off, the thermopile reading at the TP&THTP terminals should be ~325mv. With the burners on, the millvolt reading should be ~200mv. A replacement thermopile part # is 022770.
12
13
PROBLEM PROBABLE CAUSE SOLUTION
Constant pilot won’t light. a. Gas isn’t turned on.
b. Clogged constant pilot tubing.
c. Constant pilot valve isn’t turned on.
a. Turn manual gas valve on. If using
flexible connector with quick disconnect, make sure quick disconnect is completely engaged.
b. Turn fryer and manual gas valve off.
Clean tubing.
c. Turn constant pilot valve on and adjust
pilot flame height to 3/8 to 1/2 flame.
Runner pilot tube won’t light. a. Gas isn’t turned on.
b. No electricity to fryer (BB & TS models).
c. Gas valve knob in incorrect position
(AA & CMG models).
d. Hi-Limit has been activated.
e. Clogged runner pilot orifice(s).
f. Drain valve isn’t pushed in completely
(fryers with built-in filter system).
a. Turn manual gas valve on. If using
flexible connector with quick disconnect, make sure quick disconnect is completely engaged.
b. Plug fryer into approved outlet.
c. Rotate gas valve knob to pilot position.
Depress and hold for 30 seconds.
d. Push Hi-Limit reset button located under
control panel.
e. Turn fryer and manual gas valve off.
Clean orifice(s) and other parts as necessary.
f. Push in and latch drain valve handle to
activate rear drain safety switch. Turn off fryer & turn back on.
Runner pilot won’t stay lit.
a. Verify if size of incoming gas line to fryer
and manifold gas pressure are adequate.
b. Turn fryer and manual gas valve off.
Clean orifice(s) and pilot tube.
c. Adjust pilot flame height.
d. If it takes more than 60 seconds for pilot
to stay lit, replace flame switch control.
e. Push Hi-Limit reset button located under
control panel.
f. Install or adjust flue restrictors. If problem
persists, contact your HVAC representative.
g. Perform millivolt tests. Replace faulty
thermopile or gas valve.
h. See diagnosis on page 14.
SERVICE DIAGNOSIS
The following diagnosis is only to be used as a guide to qualified service personnel. Keating recommends that you use a qualified service company. Call 1-800-KEATING if you need assistance in locating a qualified service company.
TROUBLESHOOTING CHART
a. Low gas supply or pressure.
b. Dirty runner pilot tube or pilot orifice(s).
c. Low pilot flame height.
d. Flame switch control is faulty
(BB & TS models).
e. Hi-Limit has been activated.
f. Exhaust problems or drafts in kitchen.
g. Thermopile or gas valve is faulty
(AA & CMG models).
h. Delayed ignition.
Burners will not light. a. Gas valve knob in incorrect position
(AA & CMG models).
b. Switch not set to fry (BB & TS models).
c. Thermostat is faulty.
d. Fry/Off/Melt switch (BB & TS models) or
On/Off switch (AA & CMG models) is faulty.
e. Faulty gas valve.
a. Rotate gas valve knob to ON. Turn
power switch ON. Set thermostat to desired temperature.
b. Set MELT/IDLE/FRY switch (or
MELT/FRY switch) to FRY. Set thermostat to desired temperature.
c. Push and hold in Hi-Limit test button. If
burners come on, replace thermostat.
d. Replace switch.
e. Replace gas valve.
Fryer overshoots temperature setting. a. Thermostat bulb improperly placed.
b. Thermostat out of calibration.
a. Adjust bulb position. See pages 11-12 –
Thermostat Bulb Positioning.
b. Calibrate thermostat. See page 11 –
Calibration.
Delayed ignition. a. Dirty runner pilot tube or pilot orifice(s).
b. Low pilot flame height.
c. Exhaust problems or drafts in kitchen.
d. Low gas supply or pressure.
a. Turn fryer and manual gas valve off.
Clean orifice(s) and pilot tube.
b. Adjust pilot flame height.
c. Install or adjust flue restrictors. If
problem persists, contact your HVAC representative.
d. Verify if size of incoming gas line to fryer
and manifold gas pressure are adequate.
Oil in fryer vessel smokes. a. Oil has begin to breakdown.
b. High carbon content in oil.
c. Dirty fryer vessel.
d. Inferior grade of oil.
e. Fryer is overheating.
f. Hi-Limit Control has failed.
a. Replace oil.
b. Filter oil completely, replace if necessary.
c. Boil-out fryer.
d. Check with supplier for the grade of oil
needed for your cooking applications.
e. Check calibration of thermostat (See
page 10) and replace if necessary.
f. Check if Hi-Limit trips at 425º F. If not,
replace Hi-Limit.
Fryer vessel boiling over. a. Over-filling fryer with oil.
b. Product overloaded in fryer vessel.
c. Oil breakdown causing foaming.
d. Water in the cold zone.
a. Fill fryer up to Max Level line as oil will
expand when heated.
b. Follow recommended cooking
production figures in determining proper size of loads
c. Replace oil.
d. Stir oil repeatedly with a paddle until
water boils off. Filter oil. If necessary, allow oil to cool. Drain about one quart of it to remove remaining water.
TROUBLESHOOTING CHART (continued)
14
Loading...
+ 36 hidden pages