UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER
(A) MAKES NO W ARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS
MANUALS OR OTHER DOCUMENTATION;
(B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT,
CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE
ENTIRELY AT THE USER’S RISK; AND
(C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE
ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE.
(D) INFORMS YOU THE INFORMATION IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE.
(E) RESERVES ALL RIGHTS.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 2018118
This manual is for qualified personnel only
6.1 Appendix 1 Problems and Solutions ........................................................................... 37
6.2 Appendix 2 USB communication port ......................................................................... 38
6.3 Appendix 3 RS232 communication port ...................................................................... 39
6.4 Appendix 4 RS485 communication port ...................................................................... 40
6.5 Appendix 5 BAT_T communication port ...................................................................... 41
6.6 Appendix 6 Optional port ............................................................................................ 41
6.7 Appendix 7 REPO port ............................................................................................... 42
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 1
1Safety
Important safety instructions
SAVE THESE INSTRUCTIONS - The instructions in this manual are deemed important and should
be closely followed at all times during installation and follow-up maintenance of the UPS and batteries.
Safety instructions in this manual act as a supplement to local safety codes and laws. Our company
does not assume any liability or responsibility caused by disobeying local safety codes and laws.
Before conducting any maintenance, repair, or shipment, first ensure that the UPS is turned off and
disconnected from all sources of internal and external energy
WARNING! This UPS contains lethal voltages and high temperature inside. All repairs and service
should be performed by AUTHORIZED AND QUALIFIED PERSONNEL ONLY. Keep unauthorized
personnel away from UPS.
WARNING! To reduce the risk of personal injury and equipment damage, abide by all local safety
codes and laws during operation, installation and maintenance.
WARNING! To reduce the risk of electric shock, disconnect the UPS from the main supply before
installing a computer inter-face signal cable. Reconnect the power cord only after signaling
interconnections have been made.
WARNING! (UPS having Internal Batteries): Risk of electrical shock – Hazardous live parts inside this
unit are energized from the battery supply even when the input AC power is disconnected.
WARNING! (No User serviceable Parts): Risk of electrical shock, do not remove cover. No user
serviceable parts inside. Refer servicing to qualified service personnel.
WARNING! (Non-isolated Battery supply): Risk of electric shock, battery circuit is not isolated from
AC input, hazardous voltage may exist between battery terminals and ground. Test before touching.
WARNING! (Fuses): To reduce the risk of fire, replace only with the same type and size of fuse.
WARNING! UPS units are extremely heavy. Caution should be taken in moving and positioning
equipment.
WARNING! To reduce the risk of fire or electric shock, install the UPS in a temperature and humidity
controlled, indoor environment, free of conductive contaminants (flammable gas, excessive dust, etc.).
Ambient temperature must not exceed 40°C (104°F). Do not operate near water or in excessive
humidity (95% maximum).
WARNING! To reduce the risk of overheating and fire, operate the UPS in a well-ventilated area.
WARNING! To reduce the risk of fire or electric shock, output overcurrent protection and disconnect
switch must be installed in accordance with local Electrical Codes.
WARNING! To reduce the risk of fire or electric shock, an external DC Circuit over current protective
device must be installed in accordance with the National Electric Code, ANSI/NFPA 70.
•10kVA UPS connect only to a circuit provided with DC 63 amperes maximum branch circuit
over current protection in accordance with the National Electric Code, ANSI/NFPA 70.
•15/20kVA UPS connect only to a circuit provided with DC 125 amperes maximum branch
circuit over current protection in accordance with the National Electric Code, ANSI/NFPA 70.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 2
Servicing of batteries should be performed or supervised by personnel with knowledge of batteries
and the required precautions. Keep unauthorized personnel away from batteries.
WARNING! A battery can present a risk of electric shock and high short circuit current. The following
precautions should be observed when working on batteries:
• Remove watches, rings, or other metal objects.
• Use tools with insulated handles.
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground.
WARNING! Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if groundings are removed during installation and maintenance.
WARNING! Risk of explosion if battery is replaced by an incorrect type. When replacing batteries,
replace with the same type and number of batteries or battery packs.
WARNING! Do not dispose of batteries in a fire. The batteries may explode. Dispose of used
batteries according to the instructions.
WARNING! Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes
and is toxic.
1.1Symbols used in this guide
WARNING!
Risk of Personal Injury - Observe the warning that a risk of personal injury such as electric shock, fire or chemical hazard is present
CAUTION!
Risk of Equipment Damage - Refer to the operator’s manual for additional information,
such as important operating and maintenance instructions
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 3
2 Main Features
2.1 Summary
This series UPS is a three-in-three-out high frequency online UPS. The UPS helps avoid power supply
problems, such as blackout, over-voltage, under-voltage, sudden voltage drop, high voltage pulse,
voltage fluctuation, surge, inrush current, harmonic distortion (THD), noise interference, frequency
fluctuation, etc.
This UPS can be applied to different applications including computer device, automatic equipment,
communication system and industry equipment.
2.2Functions and Features
3 Phase In / 3 Phase Out UPS
It is 3 Phase In / 3 Phase Out high-density UPS system.
Digital Control
This series UPS is controlled by Digital Signal Processor (DSP) which enhances and increases
reliability, performance, self-protection, self-diagnostics and so on.
Charging Current is configurable
Using the PC Software, the user may set the capacity of the batteries as well as the maximum charging
current. Constant voltage mode, constant current mode or floating mode can be switched
automatically and smoothly.
Advanced three-stage charging
1st stage: High constant current charging to 90%
nd
2
stage: Constant voltage to finish charging
3rd stage: Float replaces battery self-discharge
The 3-stage charging extends the life of the batteries and recharges batteries quickly.
Touch Display
With Touch screen and LED display it is quick and easy to determine UPS status and operational
parameters, such as input/output voltage, frequency, load%, battery% and ambient temperature, etc.
Intelligent Monitoring
An optional SNMP card can be used to remotely control and monitor the UPS.
Emergency Power Off Function
The UPS may be completely shut off when the EPO button is pressed. Remote EPO (REPO) function
is also available.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 4
3 Installation
3.1 Unpacking and Inspection
If any equipment received has been damaged during shipment, keep the shipping cartons
and packing materials and file a claim for shipping damage with the carrier. If you discover
damage after acceptance, file a claim for concealed damage with the carrier.
•Unpacking the UPS in a low-temperature environment may cause condensation to occur
inside the UPS enclosure. To reduce the hazard of electrical shock, do not install the UPS
until the inside and outside of the enclosure are absolutely dry.
Cut off the straps on the outside of the packaging and remove the outer packaging
Remove the cabinet inner package, unfasten the screws and remove the wooden bar fixed to
the cabinet.
Place the incline board to the ground, use the screws unfastened from the last step to fasten
the incline board with pallet.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 5
3.2Cabinet Overview
Front View Side View
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 6
(1) LCD panel / LEDs
(2) Intelligent Slot 1 (SNMP card/ Relay card)
(3) Intelligent Slot 2 (SNMP card/ Relay card)
(4) Dry contact port
(5) Power Switch
(6) USB port
(7) RS485 port
(8) RS232 port
(9) O/P Switch
(10) Maintenance switch with cover
(11) Bypass Switch
(12) Terminal block: Input, Output, GND
(13) Events port
(14) Cold Start
(15) EPO Switch
(16) REPO port
(17) Parallel port 2
(18) Parallel port 1
(19) I/P Switch
(20) Terminal block: Battery (DC)
10kVA Rear View (terminal block without cover)
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 7
(1) LCD panel / LEDs
(2) Intelligent Slot 1 (SNMP card/ Relay card)
(3) Intelligent Slot 2 (SNMP card/ Relay card)
(4) Dry contact port
(5) Power Switch
(6) USB port
(7) RS485 port
(8) RS232 port
(9) O/P Switch
(10) Maintenance switch with cover
(11) Bypass Switch
(12) Terminal block: Input, Output, GND
(13) Events port
(14) Cold Start
(15) EPO Switch
(16) REPO port
(17) Parallel port 2
(18) Parallel port 1
(19) I/P Switch
(20) Terminal block: Battery (DC)
15-20kVA Rear View (terminal block without cover)
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 8
3.3 Touch control panel
(1)LED(from top to bottom: “alarm”, “bypass”, “battery”, “inverter”) (2)LCD display
3.4 Installation notes
•When installing the cabinet, a minimum space 50cm in front, 50 cm on the sides and 50cm at
back of the cabinet should be maintained for access and good ventilation.
•Cooling of the UPS depends on the internal fan. Install the UPS in an area with good air
ventilation. Do not block the ventilation holes at the front and rear of the UPS.
•Place the UPS in a well ventilated, dry, clean and stable indoors environment. Avoid vibration,
dust, humidity, corrosive and flammable gases and liquids. To reduce high room temperature
extractor fans should be installed. Air filters should be used to prevent from dust entering the
UPS.
•The environment temperature around the UPS should in the range of 0 ~ 40°C. If the
environment temperature exceeds 40°C, the rated load capacity should be reduced by 12%
per 5°C. The max temperature should not exceed 50°C.
•Batteries should be mounted in an environment where the temperature is within the required
specs. Temperature is a major factor in determining battery life and capacity. In a normal
installation, the battery temperature is maintained between 15°C and 25°C. Keep batteries
away from heat sources or main air ventilation area, etc.
•
CAUTION!
Typical battery performance data are quoted for an operating temperature between
20°C and 25°C. Operating it above this range will reduce the battery life while
operation below this range will reduce the battery capacity.
CAUTION!
Should the equipment not be installed immediately it must be stored in a room
so as to protect it against excessive humidity and or heat sources.
CAUTION!
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 9
An unused battery must be recharged every 6 months. Temporarily connecting the
Altitude(m)
1500
2000
2500
3000
3500
4000
4500
5000
Load
coefficient
100%
95%
90%
85%
80%
75%
70%
65%
UPS
Cable Dimension
UPS to a suitable AC supply and activating it for the time required to recharge the
batteries.
CAUTION!
The highest altitude that UPS may work normally with a full load is 1500 meters.
The load capacity should be reduced when this UPS is installed at an altitude higher
than 1500 meters. Load coefficient equals max load at altitude divided by nominal
power of the UPS.
3.5External Protective Devices
For safety, it is necessary to install an external circuit breaker at the input AC supply and another at
the battery. This chapter provides guidelines for authorized personnel and qualified installers knowledge of local wiring codes and laws is essential.
External Battery
The UPS and its associated batteries are protected against the effect of over-current through a DC
compatible thermo-magnetic circuit-breaker (or a set of fuses) located close to the battery.
UPS Output
Any external distribution board used for load distribution shall be fitted with protective devices that
protect the UPS from becoming overloaded.
Over-Current
Protection devices shall be installed at the distribution panel of the incoming mains supply.
CAUTION!
Select a thermo-magnetic circuit-breaker with an IEC 60947-2 trip
curve C (normal) for 125% of the current as listed below.
10kVA: 50A Input Circuit Breaker required.
15kVA: 63A Input Circuit Breaker required.
20kVA: 80A Input Circuit Breaker required.
3.6Power Cables
The cable design shall comply with the voltages and currents provided in this section. Follow local
wiring codes and laws taking into consideration the environmental conditions (temperature and
physical).
WARNING!
Upon starting, ensure that you are aware of the location and operation of the
external isolators which are connected to the UPS input/bypass supply of the
mains distribution panel. Check to see if these supplies are electrically isolated.
Post any necessary warning signs to prevent any inadvertent operation.
For future expansion, it is recommended to install power cable according to the full rated capacity.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 10
cabinet
AC Input
(mm2)/(AWG)
AC Output
(mm2)/(AWG)
DC Input
(mm2)/(AWG)
Grounding
(mm2)/(AWG)
10KVA
8 / 8
8 / 8
20 / 6
8 / 8
15kVA
12 / 6
12 / 6
35 / (2x6)
8 / 6
20kVA
16 / 4
16 / 4
35 / (2x6)
10 / 4
Position
ACINPUT
ACOUTPUT
GROUNDING
Screw type
M6
M6
M6
Recommended torque(Nm)
6.5
6.5
6.5
Recommended installed screw torque
CAUTION!
Protective earth cable: Connect each cabinet to the main ground system. For
Grounding connection, follow the shortest route possible.
WARNING!
Failure to follow adequate earthing procedures may result in electromagnetic
interference or in hazards involving electric shock and fire.
3.7Power cable connections
Once the equipment has been finally positioned and secured, connect the power cables as described
in the following procedure.
•Verify the UPS is totally isolated from its external power source and also all power isolators of
the UPS are open.
•Check to see if they are electrically isolated and post any necessary warning signs to prevent
their inadvertent operation.
•Remove the cover of terminals.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 11
M / 1R Primary input line
IN/OUT Input / Output
Output-L1: Output Phase L1
Input-L1: Primary input Phase L1
Output-L2: Output Phase L2
Input-L2: Primary input Phase L2
Output-L3: Output Phase L3
Input-L3: Primary input Phase L3
Output-N: Output Neutral
Input-N: Input Neutral for primary and secondary
input
GND: Grounding
BAT+: Positive terminal of the battery string
BATN: Neutral terminal of the battery string
BAT-: Negative terminal of the battery string
3.7.1 Single input connection
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 12
3.7.2 Dual input connection
M / 1R Primary input line
IN/OUT Input / Output
B / 2R Secondary / Bypass input line (optional)
Output-L1: Output Phase L1
Mains-L1: Primary input Phase L1
Output-L2: Output Phase L2
Mains -L2: Primary input Phase L2
Output-L3: Output Phase L3
Mains -L3: Primary input Phase L3
Output-N: Output Neutral
Input-N: Input Neutral for primary and secondary
input
GND: Grounding
Bps-L1: Secondary input Phase L1
BAT+: Positive terminal of the battery string
Bps-L2: Secondary input Phase L2
BATN: Neutral terminal of the battery string
Bps-L3: Secondary input Phase L3
BAT-: Negative terminal of the battery string
Warning!
In the case of “split bypass” operation, make sure the copper between
each input lines have been removed. The AC input and the AC bypass
supplies must be referenced to the same neutral point.
Select the appropriate power cable (Refer to the table above).
Pay attention to the diameter of the connection terminal of the cable, it should be greater than or equal
to that of the connection poles.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 13
WARNING!
If the load equipment is not ready to accept power during commissioning,
ensure that the system output cables are safely isolated at their ends
Connect the safety earth and any necessary bonding earth cables to the copper
earth screw located on the floor of the equipment below the power connections.
All cabinets in the UPS must be grounded properly.
CAUTION!
The earthing and neutral bonding arrangement must be in accordance with local
and national codes of practice.
3.8Internal Battery Connection
The BAT+ of the UPS connect poles is connected to the anode of the positive battery, the BAT-N is
connected to the cathode of the positive battery and the anode of the negative battery, the BAT- is
connected to the cathode of the negative battery.
Factory setting of the standard unit is battery quantity - 20/40/60pcs, battery capacity - Maximum
12V9AH.
Wiring diagram for 20pcs of batteries installation
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 14
Wiring diagram for 40pcs of batteries installation
Wiring diagram for 60pcs of batteries installation
3.9 External Battery Connection
The UPS adopts positive and negative double battery framework, with 20pcs in series. A neutral cable
is retrieved from the joint between the cathode of the 10th and the anode of the 11th of the batteries.
Then the neutral cable, the battery Positive and the battery negative are connected with the UPS
respectively. The battery sets between the Battery anode and the neutral are called positive batteries
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 15
and that between neutral and cathode are called negative batteries. Users can choose the capacity
and the numbers of the batteries according to the set-up, however all must be the same type and Ah
rating.
Note
The BAT+ of the UPS connection poles is connected to the anode of the positive battery, the BAT- is
connected to the cathode of the positive battery and the anode of the negative battery, the BAT- is
connected to the cathode of the negative battery.
The UPS uses (+/-120VDC input (20pcs batteries;10pcs for each “+” string and “-” string), please set
correct battery quantity and its capacity after UPS starts in AC mode (note the default values may be
different and must be updated). The charger’s current will be adjusted automatically per the battery
capacity selected. All related settings can be done through LCD panel or monitoring software.
CAUTION!
Ensure correct polarity battery string series connections. I.e. inter-tier and inter
block connections are from (+) to (-) terminals. Do not mix new and old batteries,
different capacities or brands.
WARNING!
Ensure correct polarity of string end connections to the Battery Circuit Breaker
and from the Battery Circuit Breaker to the UPS terminals. i.e. (+) to (+) / (-) to (-).
Disconnect one or more battery cell links in each tier. Do not reconnect these
links and do not close the battery circuit breaker unless authorized by the
commissioning engineer.
Multiple Battery Pack Connections
CAUTION!
Ensure correct polarity of the battery string series connection. DO NOT mix batteries
with different capacity or different brands, or new or old batteries.
WARNING!
Ensure correct polarity of string end connections to the battery circuit breaker, and
from the Battery circuit breaker to the UPS terminals (i.e. (+) to (+) / (-) to (-) / (n) to
(n)). Disconnect one or More battery cell links in each tier. Do not reconnect these
links and do not close the battery Circuit breaker unless all connections are
properly checked and approved.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 16
T SERIES UPS battery connection
3.10UPS Parallel Installation
The following sections introduce the installation procedures specific to a parallel system.
3.10.1 Cabinet installation
Connect all the UPS needed in the parallel system as below.
Make sure each UPS input breaker is in the “off” position and there is no output from any of the UPS.
Battery groups can be connected separately or in parallel, which means the system can be either a
separate battery or a common battery.
WARNING!
Make certain the N, A (L1), B (L2), C (L3) lines are correct and grounding is well
secured.
3.10.2Parallel cable installation
The shielded and double insulated control cables must be interconnected in a ring configuration
between UPS units as shown below. The ring configuration ensures high reliability of the control.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 17
3.10.3 Requirement for the parallel system
For a group of paralleled modules behave as one large UPS system and in order to assure that all
modules are equally utilized and comply with relevant wiring rules, follow the requirements below:
1) All UPS must be of the same rating and be connected to the same bypass source.
2) The Bypass and Mains input sources must be referenced to the same neutral potential.
3) The outputs of all the UPS modules must be connected to a common output bus.
4) The length and specification of power cables including the bypass input cables and the UPS output
cables must be the same. This facilitates load sharing when operating in bypass mode.
3.11 Computer access
To use the included software management program Muser4000 a USB connection is required. One
end of an USB cable connects to the computer and the other end connects to the USB port on the
UPS.
Open the Muser4000 software, then touch the “system” button.
The “Software Parameter Setting” window will open, as below. Select the COM port related to the UPS,
set the baud rate as 9600 and for the Protocol select “HIP”. Save these settings.
On the main page of Muser4000, click on the button of “Append. The “Append equipment” window will
open as below.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 18
Enter the name of the UPS into the “Equipment Name” box and select the ID address for the UPS in
the “Equipment address” box.
Click on the “Append” button to complete the connection between UPS and computer.
CAUTION!
Do not use the PC Software to set output voltage and frequency while the inverter
is running. Shut down the inverter, before using the PC Software to set theoutput
voltage and frequency.
4 Operation
4.1 Operation Modes
The UPS is a double-conversion on-line UPS that may operate in the following modes:
Normal mode
The rectifier/charger derives power from the AC Mains and supplies DC power to the inverter while
floating and boosting charge the battery simultaneously. The inverter converts the DC power to AC
and supplies to the load.
Battery mode (Stored Energy Mode)
If the AC mains input power fails, the inverter, which obtains power from the battery, supplies the
critical AC load. There is no power interruption to the critical load. The UPS will automatically return to
Normal Mode when AC recovers.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 19
Bypass mode
If the inverter is out of order, or if overload occurs, the static transfer switch will be activated to transfer
the load from the inverter supply to bypass supply without interruption to the critical load. If the
inverter output is not synchronized with the bypass AC source, the static switch will perform a transfer
of the load from the inverter to the bypass with power interruption to the critical AC load. This is to
avoid paralleling of unsynchronized AC sources. This interruption is programmable but typically set to
be less than an electrical cycle e.g. less than 15ms (50Hz) or less than 13.33ms (60Hz).
ECO Mode
When the UPS is at AC Mode and the requirement to the load is not critical, the UPS can be set at
ECO mode to increase the efficiency of the power supplied. In ECO mode, the UPS works in Lineinteractive mode, so the UPS will transfer to bypass supply. When the AC is out of the set window, the
UPS will transfer from bypass to Inverter and supplies power from the battery. The LCD shows all
related information on the screen.
Maintenance mode (Manual Bypass)
A manual bypass switch is available to ensure continuity of supply to the critical load when the
UPS is out of order or in repair and this manual bypass switch bears for equivalent rated load.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 20
4.2 Turn on/off UPS
4.2.1 Restart procedure
CAUTION!
Make certain grounding is correct and secure.
1) Set the Battery Breaker to the “ON”.
2) Switch ON the power switch for standard UPS.
CAUTION!
Check to see if the load is safely connected with the output of the UPS. If the load
is not ready to receive power from the UPS, make sure that it is safely isolated
from the UPS output terminals.
3) Switch ON UPS input switch
If the Rectifier input is within voltage range, the rectifier will start up in 30 seconds, the inverter will
start up after.
4) Switch ON UPS output switch
If the rectifier fails at start-up, the bypass LED will light up. When the inverter starts up, the UPS will
transfer from bypass mode to inverter mode, and then the bypass LED extinguishes and the inverter
LED lights up. The status will be shown on the LCD display.
4.2.2Test procedure
CAUTION!
When the UPS is operating normally it may take 60 seconds to start up the system
and perform self-test completely.
1) Switch off the MAINS to simulate utility failure.
The rectifier will turn off and the battery should feed the inverter without interruption. Now the of battery
LEDs should be turned on.
2) Switch on the MAINS to simulate utility recovery.
The rectifier will restart automatically after 20 seconds and the inverter will supply to the load. It is
recommended to use Dummy loads for testing. The UPS can be loaded up to its maximum capacity
during load test.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 21
4.2.3 MAINTENANCE BYPASS
To supply the load from the Mains, activate the internal mechanical bypass switch.
CAUTION!
The load is not protected by the UPS when the internal mechanical bypass system
is active, and the power is not conditioned.
Switching to mechanical bypass
CAUTION!
If the UPS is running normally and can be controlled through the display, carry out
steps 1 to 5; otherwise, go to Step 4.
1. Open the cover of maintenance switch, the UPS turns to bypass mode automatically.
2. Turn on MAINTANCE breaker
3. Open BATTERY breaker
4. Switch OFF the MAINS breaker
5. Switch OFF OUTPUT breaker
Now the bypass source will supply to the load through the MAINTENANCE breaker.
Switching to normal operation (from mechanical bypass)
CAUTION!
Do not attempt to switch the UPS back to normal operation until it has been verified
that there are no internal UPS faults
1. Switch ON the output breaker.
2. Switch ON the input breaker.
The UPS powers from the static bypass instead of the maintenance bypass, the bypass LED will light
up.
3. Switch OFF the maintenance bypass breaker, the output is supplied by the static bypass of the
UPS.
4. Replace the maintenance switch cover.
The rectifier will operate normally after 30 seconds. If the inverter works normally, the system will be
transferred from bypass mode to normal mode.
4.2.4Cold start procedure
CAUTION!
Follow these procedures when the input AC Utility Failure, but battery is normal.
1. Set the Battery Breaker to the “ON” position
2. Switch the power switch to ON (power will feed to auxiliary power board).
3. Turn the output switch to ON
4. Trigger the cold start button.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 22
When battery conditions are normal the rectifier starts operation, the inverter starts 30s later and the
battery LED will be on.
CAUTION!
Press the start button for 30 seconds until the battery switch closes.
4.2.5Shut down procedure
CAUTION!
This procedure should be followed to completely shut down the UPS and the LOAD.
After all power switches, isolators and circuit breakers are opened, there should be
no output.
On-line mode:
1. Press OFF to shut down the UPS, wait about 30s.
2. Open the BATTERY breaker.
3. Open the battery power switch for standard UPS.
4. Switch to OFF the AC input breaker.
5. Open the OUTPUT breaker. The UPS shuts down.
6. To completely isolate the UPS from AC Mains, all switches for the utility input shall be turned
off.
7. At the primary input distribution panel, a label should be posted to advise personnel that the
UPS circuit is under maintenance.
Battery mode:
1. Press OFF to shut down the UPS, wait about 30s.
2. Open the BATTERY breaker.
3. Open the battery power switch for standard UPS.
4. Open the OUTPUT breaker. The UPS shuts down.
WARNING!
Wait for about 5 minutes for the internal DC bus and capacitors to completely
discharged.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 23
4.2.6 Parallel Settings
1. Connect the UPS to the computer.
2. Power on the UPS.
3. Open Muser4000 software, click “System”, then select -> “User Set”
4. From “User Set” window click “Set”.
5. From the “Data Set” window select “Parallel” for the “Work Mode” value, then click “Set” to
save the values, as shown below. The UPS will sound a “beep” to indicate that the setting
has been correctly saved.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 24
6. From the “Data Set” window select “Ups ID” and put the ID value for the parallel UPS in the
box on the right side. Click “Set” to save the values, as shown below. The UPS will sound a
“beep” to indicate that the setting has been correctly saved.
CAUTION!
After changing the parallel system ID, the connection between Muser4000 and UPS
equipment may be interrupted. If this occurs, re-connect per the instructions
described previously.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 25
4.2.7 Parallel Commissioning
Parallel system should be commissioning when the stand-alone units are ready
Take 4 units in parallel for example.
1) Confirm the input/output wires connection and input phase sequence are correct; switch off the battery
breaker, and measure the +/- bat voltage of all battery group are normal.
2) Connect the parallel cable, it should be formed loop connection。
3) Switch on the input breaker of unit 1,and access LCD setting interface to setting the working mode、ID、
parallel number、redundant number. Require setting the in series number、capacity of battery. The output
voltage level and Bypass protection range are default setting.
4) Turn off the input breaker of Unit 1, and make sure the UPS is off. Turn on the input breaker of Unit 2,access
the LCD setting interface, setting the parallel working mode, ID(NO.2) , parallel 4 units, redundant
number .The other setting are the same as UPS 1 operation.
5) For Unit 3 and Unit 4 UPS, the operation setting are all the same as Unit 1 and 2.
6) Turn on Bypass/input/output breaker of all the paralleled UPS, then confirm all the setting are correct. Each UPS has their owed different ID.
7) Turn on all the battery breaker and confirm the parameter (V/I) are normal.
8) Connected the Load, and check whether the output current are balance.
Switch on and off the utility breaker to test all the UPS converters system from Utility to battery and
restored function are working find
4.3 The Touch Display
(1) LED indicator (2) LCD touch display
Introduction
The display provides more functions than those described in this manual.
CAUTION!
The setting of most parameter cannot be set when the UPS is in
inverter mode.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 26
4.3.1 Home page
The home page (Sys.status icon) displays the operation of the UPS by flow chart.
Touch the bypass icon to enter the bypass data window, touch the back icon return to last
window and touch the homepage icon jump to main page.
Touch the mains icon to enter the mains data window, touch the back icon return to last
window and touch the homepage icon jump to main page.
Touch the Output icon to enter the output data window, touch the back icon return to last
window and touch the homepage icon jump to main page.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 27
Touch the battery icon to enter the battery data window, touch the back icon return to last
window and touch the homepage icon jump to main page.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 28
4.3.2 Run Info
From the Home page, touch the Run.info icon to enter the information page.
Touch the Status Information icon to enter the status data window, click the back icon return to last
window and click Sys.status icon to jump to homepage page.
4.3.3 Alarms
From the Home page, touch the Alarm icon to enter the alarms page.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 29
Touch the Current Alarm icon to enter the alarm data window, touch on the back icon return to last
window and touch on the homepage icon jump to main page.
Touch the history icon to enter the history window, can see the history data, touch the back
icon return to last window and touch the homepage icon jump to main page.
4.3.4 Settings
Touch the Settings icon to enter settings pages, touch the back icon return to last window and
touch the homepage icon jump to main page.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 30
4.3.5 Maintenance
Touch Maintenance icon to enter setting page, touch the back icon return to last
window and touch the homepage icon jump to main page.
4.3.6 Functions
Touch Functions icon to enter setting page, touch the back icon return to last window
and touch the homepage icon jump to main page.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 31
3.5 Display Messages/Troubleshooting
Code
(ST)
Information
stand for
LED
Fault
Bypass
Battery
Inverter
1
Initialized
EXTINGUISH
EXTINGUISH
EXTINGUISH
EXTINGUISH
2
Standby Mode
EXTINGUISH
EXTINGUISH
X
EXTINGUISH
3
No Output
EXTINGUISH
EXTINGUISH
X
EXTINGUISH
4
Bypass Mode
EXTINGUISH
LIGHT
X
EXTINGUISH
5
Utility Mode
EXTINGUISH
EXTINGUISH
X
LIGHT
6
Battery Mode
EXTINGUISH
EXTINGUISH
LIGHT
EXTINGUISH
7
Battery Self-
diagnostics
EXTINGUISH
EXTINGUISH
LIGHT
EXTINGUISH
8
Inverter is
starting up
EXTINGUISH
X
X
EXTINGUISH
9
ECO Mode
EXTINGUISH
X X X
10
EPO Mode
LIGHT
EXTINGUISH
X
EXTINGUISH
11
Maintenance
Bypass Mode
EXTINGUISH
EXTINGUISH
EXTINGUISH
EXTINGUISH
12
Fault Mode
LIGHT
X X X
Fault code (Err)
UPS Alarm Warning
Buzzer
LED
1
Rectifier Fault
Beep continuously
Fault LED lit
2
Inverter fault(Including Inverter bridge
is shorted)
Beep continuously
Fault LED lit
3
Inverter Thyristor short
Beep continuously
Fault LED lit
4
Inverter Thyristor broken
Beep continuously
Fault LED lit
5
Bypass Thyristor short
Beep continuously
Fault LED lit
6
Bypass Thyristor broken
Beep continuously
Fault LED lit
7
Fuse broken
Beep continuously
Fault LED lit
8
Parallel relay fault
Beep continuously
Fault LED lit
9
Fan fault
Beep continuously
Fault LED lit
10
Reserve
Beep continuously
Fault LED lit
11
Auxiliary power fault
Beep continuously
Fault LED lit
12
Initializtion fault
Beep continuously
Fault LED lit
13
P-Battery Charger fault
Beep continuously
Fault LED lit
14
N-Battery Charger fault
Beep continuously
Fault LED lit
15
DC Bus over voltage
Beep continuously
Fault LED lit
16
DC Bus below voltage
Beep continuously
Fault LED lit
17
DC bus unbalance
Beep continuously
Fault LED lit
18
Soft start failed
Beep continuously
Fault LED lit
19
Rectifier Over Temperature
Twice per second
Fault LED lit
20
Inverter Over temperature
Twice per second
Fault LED lit
This section lists the event and alarm messages that the UPS might display. The messages are listed in
alphabetical order. This section is listed with each alarm message to help you troubleshoot problems.
Display messages
Operational Status and Mode(s)
CAUTION:"X" means it is determined by other conditions
Alarm Information
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 32
21
Input neutral loss
Twice per second
Fault LED lit
22
Battery reverse
Twice per second
Fault LED lit
23
Cable connection error
Twice per second
Fault LED lit
24
CAN comm. Fault
Twice per second
Fault LED lit
25
Parallel load sharing fault
Twice per second
Fault LED lit
26
Battery over voltage
Once per second
Fault LED blinking
27
Mains Site Wiring Fault
Once per second
Fault LED blinking
28
Bypass Site Wiring Fault
Once per second
Fault LED blinking
29
Output Short-circuit
Once per second
Fault LED blinking
30
Rectifier over current
Once per second
Fault LED blinking
31
Bypass over current
Once per second
BPS LED blinking
32
Overload
Once per second
INV or BPS LED blinking
33
No battery
Once per second
Battery LED blinking
34
Battery under voltage
Once per second
Battery LED blinking
35
Battery low pre-warning
Once per second
Battery LED blinking
36
Internal Communication Error
Once per 2 seconds
Fault LED blinking
37
DC component over limit.
Once per 2 seconds
INV LED blinking
38
Parallel Overload
Once per 2 seconds
INV LED blinking
39
Mains volt. Abnormal
Once per 2 seconds
Battery LED lit
40
Mains freq. abnormal
Once per 2 seconds
Battery LED lit
41
Bypass Not Available
BPS LED blinking
42
Bypass unable to trace
BPS LED blinking
43
Inverter on invalid
44
Reserve
45
inverter not on
46
Output switch not ON
Once per 3 seconds
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 33
5Optional cards – SNMP / Relay
SNMP card: internal SNMP / external SNMP optional
1) Loosen the 2 torque screws (on each side of the card).
2) Carefully pull out the card.
Reverse the procedure for re-installation
The slot called SNMP supports the MEGAtec protocol.
Note: NetAgent II-3 port is also a tool to remotely monitor and manage any UPS system
NetAgent II-3Ports supports the Modem Dial-in (PPP) function to enable the remote control via the
internet when the network is unavailable.
In addition to the features of a standard NetAgent Mini, NetAgent II has the option to add NetFeeler
Lite to detect temperature, humidity, smoke and security sensors. NetAgent II also supports multiple
languages and is setup for web-based auto language detection.
Typical topology of the UPS Network Management
Relay card
A 10-pin terminal is supported to offer the signals of Bypass, Utility Failure, Inverter On,
Battery Low, UPS fault, UPS Alarm, and UPS Shutdown.
The relay communication card contains six dry contact outputs and one dry input. The inputs
and outputs are factory programmed according to functions listed in the table
Table: Relay Contacts (communication card)
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 34
6 Specifications
Model
T 3310UL
T 3315UL
T 3320UL
Capacity (VA/Watts)
10k / 10k
15k / 15k
20k / 20k
INPUT
Rectifier input
Rated AC Input Voltage
208/120Vac or 220/127Vac, 50/60Hz, 3-Phase, 4-Wire Plus Ground
Input Voltage Range
(Startup/Operating)
-20%, +25% (96-150Vac or 102-159Vac), Full load
Input Voltage Range
(Operating)
-40%, +25% (72-150Vac or 76-159Vac), <50% Load
Frequency
50 or 60Hz (40-70Hz Range)
Power Factor
0.99 (40% linear load)
Harmonic distortion (THDi)
≤2% (100% nonlinear load)
Bypass input
Rated AC Voltage
208/120Vac or 220/127Vac, 50/60Hz, 3-Phase, 4-Wire Plus Ground
Bypass voltage Range
Upper limit: +10, +15, +20 or 25% (default: +20)
Lower limit: -10, -20, -30 or -40 (default: -30)
Bypass frequency Range
±10%
Synchronization - Window
±1%/±2%/±4%/±5%/±10% optional (default: ±10%)
Max current (A)
Breaker50A
Breaker63A
Breaker 80A
Upstream protection,
bypass line
Thermomagnetic circuit-breaker rated up to 125% of nominal output
current. IEC 60947-2 curve C.
Current rating of neutral
cable (A)
1.7×In
Generator Input
Support
OUTPUT
Inverter
Output
Power factor
1.0
Rated AC Voltage 1
208/120Vac or 220/127Vac, 50/60Hz, 3-Phase, 4-Wire Plus Ground
Voltage Regulation
±1%
Transient Voltage Response
±5% (linear load)
Phase Balance
120° ±1° (100% unbalanced load)
Frequency
1.Line Mode: synchronize with input; when input frequency >±10%
(±1%/±2%/±4%/±5% optional), output (50/60±0.1%)Hz.
2.Battery Mode:(50/60±0.1%)Hz
Crest factor
3:1
Harmonic distortion (THD)
< 1% (linear load), <3% (non-linear load)
Overload
Capacity
AC Mode
Load ≤110%: last 60min ≤125%: last 10min ≤150%: last 1min >150%
turn to bypass immediately
Bat. Mode
Load ≤110%: last 10min ≤125%: last 1min ≤150%: last 5S >150% shut
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 36
6.1 Appendix 1 Problems and Solutions
No.
Problem
Possible reason
Solution
1
Utility is connected but
the UPS cannot be
powered ON.
Input power supply is not connected;
Input voltage low; Input switch of UPS
is not switched ON.
Measure UPS input voltage /
frequency is within the window.
Check UPS input is switched ON.
2
Utility normal, but Utility
LED light not on, the
UPS is operating in
battery mode
The input breakers of UPS are not ON;
input cable not well connected
Switch ON the input breaker;
Make sure the input cable is well
connected.
3
The UPS does not
indicate any fault, but no
output voltage
Output cable not well connected;
Output breaker not switched ON
Make sure the output cable is well
connected; Switch ON output
breaker.
4
Utility LED is flashing
Utility voltage exceeds UPS input
range.
If the UPS operates in battery mode,
pay attention to the remaining
backup time needed.
5
Battery LED is flashing,
but no charge voltage
and current
Battery breaker not switched ON,
batteries are damaged, reversely
connected. Battery number and
capacity are not set correctly.
Switch ON battery breaker. If
batteries are damaged, replace all
batteries and correct cable polarity;
Set the correct battery number and
capacity.
6
Buzzer every 0.5
seconds, displays “output
overload”
Overload
Remove some or all of the load
7
Buzzer long beeps, LCD
display “29” fault code
The UPS output is in short circuit
Make sure the load is not in short
circuit, and then restart the UPS.
8
The UPS only works on
bypass mode
UPS is set to ECO mode, or the
transfer times to bypass mode are
limited.
Set UPS to working mode (nonparallel), reset the transfer times for
bypass, re-start the UPS
9
Cannot Black start
Battery switch is not properly closed.
Battery fuse is blown open. Battery
reserve is low. Wrong battery quantity
set; Power breaker in the rear panel not
ON.
Close the battery switch. Change
fuse. Recharge battery. Power ON
the UPS with AC and set battery
quantity. Switch ON power breaker.
10
Buzzer beeps
continuously and LCD
indicates 1,3,5,9,15, etc.
fault codes
UPS is out of order
Consult with local agent for repair
If the UPS does not work normally, please check the installation, wiring and operation. If all these
conditions are confirmed without solving the problem, please consult the local agent right away and
provide them with the information below.
(1) Product model name and serial number.
(2) Describe the fault in detail, such as display info, LED lights status, etc.
Read the user manual carefully.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 37
6.2 Appendix 2 USB communication port
PC USB port
UPS USB port
Description
Pin 1
Pin 1
PC: +5V
Pin 2
Pin 2
PC: DPLUS signal
Pin 3
Pin 3
PC: DMINUS signal
Pin 4
Pin 4
Signal ground
Definition of port:
Connection between PC USB port and UPS USB port.
Available function of USB
• Monitor UPS power status.
• Monitor UPS alarm info.
• Monitor UPS running parameters.
• Timing off/on setting.
Communication data format
Baud rate ---------- 9600bps
Byte length ---------- 8bit
End bit ---------- 1bit
Parity check ---------none
CAUTION!
USB, RS232 and RS485 interface cannot be used at the same time, only one
can be used at any time.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 38
6.3 Appendix 3 RS232 communication port
PC RS232 port
UPS RS232 port
Pin 2
Pin 2
UPS send, PC receive
Pin 3
Pin 3
PC send, UPS receive
Pin 5
Pin 5
ground
Definition of Male port:
Connection between PC RS232 port and UPS RS232 port
Available function of RS232
• Monitor UPS power status.
• Monitor UPS alarm info.
• Monitor UPS running parameters.
• Timing off/on setting.
RS-232 communication data format
Baud rate ---------- 9600bps
Byte length ---------- 8bit
End bit ---------- 1bit
Parity check ---------none
CAUTION!
USB, RS232 and RS485 interface cannot be used at the same time, only one can
be used at any time.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 39
6.4 Appendix 4 RS485 communication port
Device (RJ45)
UPS (RJ45)
Description
Pin 1/5
Pin 1/5
485+ “A”
Pin 2/4
Pin 2/4
485 - “B”
Pin7
Pin7
+12Vdc
Pin8
Pin8
GND
Definition of port:
Connection between the Device’s RS485 port and UPS RS485 port.
Available function of RS485
• Monitor UPS power status.
• Monitor UPS alarm info.
• Monitor UPS running parameters.
• Timing off/on setting.
• Battery environment temperature monitoring.
• Charging voltage modulation depending on batteries temperature
RS-485 communication data format
Baud rate ---------- 9600bps
Byte length ---------- 8bit
End bit ---------- 1bit
Parity check ---------none
CAUTION!
USB, RS232 and RS485 interface cannot be used at the same time, only one can
be used at any time.
NOTE: RS485 port pin7 is 12Vdc.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 40
6.5 Appendix 5 BAT_T communication port
Device (RJ45)
UPS (RJ45)
Description
Pin 1/5
Pin 1/5
485+ “A”
Pin 2/4
Pin 2/4
485 - “B”
Pin7
Pin7
+12Vdc
Pin8
Pin8
GND
UPS
Instruction
Pin1
UPS Battery Low
Pin2
AC Power Failure
Pin3
Turn off UPS
Pin4
Common GND
Definition of port:
Connection between the Temperature senator RJ45 port and UPS RJ45 port.
Available function of BAT_T
• Battery environment temperature monitoring.
• Charging voltage modulation depending on batteries’ temperature.
6.6 Appendix 6 Optional port
Definition of Male port:
Instruction:
Function 1 description (Optional):
•Drive the bypass breaker when feedback alarm.
Function 2 description (Optional):
•Drive the battery breaker when battery voltage low.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 41
6.7 Appendix 7 REPO port
Button
UPS REPO
Description
Pin 1
Pin 1
EPO
Pin 2
Pin 2
GND
Definition of port:
Connection diagram:
Connection between the button and UPS REPO port.
•A remote emergency stop switch (Dry contact signal and “normally open” - not provided) can
be installed in a remote location and connection through simple wires to the REPO connector.
•The remote switch can be connected to several UPS in a parallel architecture allowing the
user to stop all units at once.
KE 4256-5492 Keatec T Series 10-20kVA PF1.0 208Vac with Internal Battery 7.0 Touch Screen Users Guide English 20181118
This manual is for qualified personnel only Page 42
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.