Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Keatec RTM Series Modular Online UPS
208V/120Vac 2PH 2PH
(19U Mini Cabinet)
UNLESS SPECIFICALLY AGREED TO IN WRITING, SELLER
(A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR
OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION;
(B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER
SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH
INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK; AND
(C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE
BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED.
APPROVED CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE.
(D) INFORMS YOU THE INFORMATION IN THIS DOCUMENT IS SUBJECT TO CHANGE WITHOUT NOTICE.
(E) RESERVES ALL RIGHTS
(F) CONTENT USED WITH PERMISSION
Version: 1.0
Table of Contents
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
- Then check for Hazardous Voltage between all terminals
including the protective earth.
Risk of Voltage Backfeed
The isolation device must be able to carry the UPS input current.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
1.1 Important Safety Instructions
This UPS contains LETHAL VOLTAGES. All repairs and service must be performed by AUTHORIZED
SERVICE PERSONNEL ONLY. There are NO USER SERVICEABLE PARTS inside the UPS.
WARNING:
The UPS is designed for commercial and industrial purpose. It is forbidden to apply for any life
sustainment and support.
The UPS system contains its own energy source. The output terminals may carry live voltage
even when UPS is disconnected to an AC source.
To reduce the risk of fire or electrical shock, UPS installation has to be in a controlled room
where temperature and humidity are monitored. Ambient temperature must not exceed 40°C.
The system is only for indoor use.
Ensure all power is disconnected before installation or service.
Service and maintenance should be performed by qualified personnel only.
1.2 EMC
WARNING:
This is a product for commercial and industrial application in the second environment - installation
restrictions or additional measures may be needed to prevent disturbances.
1.3 Installation information
WARNING:
Installation must be performed by qualified personnel only.
The cabinets must be installed on a level floor suitable for computer or electronic equipment.
The UPS cabinet is heavy. If unloading instructions are not closely followed, cabinet may
cause serious injury.
Do not tilt the cabinets more than 10 degree.
Before applying electrical power to the UPS, make sure the Ground conductor is properly
installed.
Installation and Wiring must be performed in accordance with the local electrical laws and
regulations.
The disconnection device should be chosen based on the input current and should break line
and neutral conductors - four poles for three phases.
1
1.4 Maintenance
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
WARNING:
Only qualified service personnel should perform the battery installation.
The following PRECAUTIONS should be observed
(1.) Remove watches, rings, or other metal objects.
(2.) Use tools with insulated handles.
(3.) Wear rubber gloves and boots.
(4.) Do not lay tools or metal parts on top of batteries or battery cabinets.
(5.) Disconnect the charging source prior to connecting or disconnecting terminal.
(6.) Check if the battery is inadvertently grounded. If it is, remove the source of grounding.
Contacting with any part of the ground might result in electrical shock. The likelihood of
such shock can be prevented if such grounds are removed during installation and
maintenance.
UPS is designed to supply power even when disconnected from the utility power. After
disconnect the utility and DC power, authorized service personnel should attempt internal
access to the UPS.
Do not disconnect the batteries while the UPS is in Battery mode.
Disconnect the charging source prior to connecting or disconnecting terminals.
Batteries can result in a risk of electrical shock or burn from high short circuit current.
When replacing batteries, use the same number of sealed, lead-acid batteries.
Do not open or mutilate the battery. Release electrolyte is harmful to the skin and eyes, and
may be toxic.
1.5 Recycling the used battery
WARNING:
Do not dispose of the battery in a fire. Battery may explode. Proper disposal of battery is
required. Refer to your local codes for disposal requirements.
Do not open or mutilate the battery. Released electrolyte is harmful to the skin and eyes. It
may be toxic.
Do not discard the UPS or the UPS batteries in the trash. This product contains sealed,
lead-acid batteries and must be disposed properly. For more information, contact your local
recycling/reuse or hazardous waste center.
Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper
disposal, contact your local recycling/reuse or hazardous waste center.
2
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2. Installation
2.1 Initial Inspection
1. Visually examine if there is any damage inside and outside of packages in the process of the
transportation. If any damage, report it to the carrier immediately.
2. Verify the product label and confirm the consistency of the equipment.
3. If the equipment needs to be returned, carefully repack the equipment by using the original
packing material that came with.
2.2 Installation Environment
1. The UPS is designed for indoor use only and should be located in a clean environment with
adequate ventilation to keep the environmental parameters within the required specification.
2. Make sure that transportation routes (e.g. corridor, door gate, elevator, etc.) and installation
area can accommodate and bear the weight of the UPS, the external battery cabinet and
handling equipment.
3. The UPS uses forced convection cooling by internal fans. Cooling air enters the module
through ventilation grills located at the front of the cabinet and exhausted through grills
located in the rear part of the cabinet. Please do not block the ventilation holes.
4. Ensure that the installation area is spacious for maintenance and ventilation.
5. Keep the temperature of installation area around 30°C and humidity within 90%. The highest
operating altitude is 1000 meters above sea level.
6. If necessary, install a system of room extractor fans to avoid formation of room temperature.
Air filters are necessary if the UPS is operated in a dusty environment.
7. It is recommended that you parallel the external battery cabinets to the UPS. The following
instructions of clearances are suggested:
Keep a clearance of 100cm from the top of the UPS for maintenance, wiring and
ventilation.
Keep a clearance of 100cm from the back of the UPS and the external battery cabinets for
ventilation.
Keep a clearance of 150cm from the front of the UPS and the external battery cabinets
for maintenance and ventilation.
8. For safety concerns, we suggest that you shall:
Equip with CO2 or dry powder fire extinguishers near the installation area.
Install the UPS in an area where the walls, floors and ceilings were constructed by
fireproof materials.
9. Do not allow unauthorized personnel to enter the installation area. Assign specific personnel
to keep the UPS key.
3
Figure 2-1
1
2
3
Figure 2-2
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.3 Unpacking
1. Use a forklift to move the product to installed area. Refer to Figure 2-1. Please make sure the
bearing capacity of forklift is sufficient.
2. Please follow the order in Figure 2-2 to remove carton and foams.
4
3. Remove 2 fixing cabinet plates and loosen leveling feet by rotating them counterclockwise.
Then, move the cabinet from the pallet. Refer to Figure 2-3.
4. To fix the cabinet in position, simply rotate leveling feet clockwise. Refer to Figure 2-4.
Figure 2-3
Figure 2-4
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
5
The UPS is fixed on the pallet with 2 fixing cabinet plates. When removing it, pay attention to
the movement of the casters to avoid accidents.
The cabinet can be pushed forward or backward only. Pushing it sideward is not allowed.
When pushing the cabinet, pay attention not to overturn it as the gravity center is high.
Figure 2-5
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.4 Moving the Cabinet
1. If you need to move the UPS over a long distance, please use appropriate equipment like a
forklift. Do not use the UPS casters to move over a long distance.
2. After the UPS has been removed from the pallet to ground, we suggest that at least three
people move the UPS to the installation area. One person holds a lateral side of the UPS with
hands, another holds the other lateral side of the UPS with hands, and the other person pushes
the UPS either from the front side or from the back side to the installation area and avoid
tipping the UPS.
3. The casters are designed to move on level ground. Do not move the UPS on an uneven surface.
This might cause damage to the casters. Toppling the UPS could also damage the unit.
4. Ensure that the weight of UPS is within the designated bearing capacity of any handling
equipment.
5. At the bottom of the UPS, the two casters help you to move the UPS to a designated area.
Before you move the UPS, please turn the two leveling feet counterclockwise to raise them off
the ground. This protects the leveling feet from damage when moving the UPS. Refer to Figure
2-5.
6
With Battery
Without Battery
Photo
UPS Capacity
6KVA
12KVA
24KVA
UPS Module
no.
1 2 4
Cabinet
Height
19 U
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.5 UPS Cabinet
There are three options of UPS cabinet configuration.
7
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.6 Exterior
In the front of the cabinet, there are control panel and 4 module slots. These module slots can be
installed with UPS or battery modules. At the back of cabinet, communication slots,
communication ports and dry contact are included.
All wiring terminal blocks are allocated in the back of cabinet. The side panels are locked by screws.
The casters at the bottom of the UPS cabinet can be used to move this cabinet for short distances.
There are two leveling feet to fix and stabilize the UPS cabinet on the ground.
1. Control panel
2. UPS module
3. LCD display on UPS module
4. Battery pack
5. Leveling foot
6. Caster
7. Communication module
8. Dry contact
9. RS-232 port
Communication Module
10. USB port
11. Intelligent slot
12. Emergency power off port
13. AC input breaker
14. AC output breaker
15. AC terminal
16. Output receptacles (optional)
17. Battery terminal
18. DC breaker (optional)
8
Dimensions
UPS cabinet
Width
Depth
Height
19U Rack
443 mm
857mm
837 mm
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.6.1 Mechanical Data
9
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.6.2 Front / Rear Open View
Front open view: After removing panel covers, you will see the module slot and control panel.
Rear open view: You will see the Switch unit (Mains/Output) and AC breaker, communication ports
which is installed on the cabinet.
1. Control panel
2. Power/Battery module slots
3. Communication ports
4. AC terminals
5. DC terminals
6. AC breakers
7. DC breaker
Front and rear open view
10
Item
Function
Description
AC
Terminal
Output Block (O/P-L1,
O/P-L3, O/P-N)
Connects the
critical loads
Includes L1, L3 and Neutral
terminals.
AC Input Block (R, T,
N)
Connects main AC
source
Includes R, T and Neutral terminals.
For UPS Grounding
(PE)
For UPS grounding
Includes one grounding terminal- PE.
DC
Terminal
DC Terminal Block
(BAT+, BAT-N, BAT-)
Connects an
external battery
pack
Includes
Positive (+), Negative (-) and Neutral
(N) terminals.
AC terminals
AC input breaker
AC output breaker
DC terminals
DC breaker
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.7 Internal Mechanisms
2.7.1 Breakers
At the rear panel of the cabinet, you can see AC Input/Output breakers. Refer to below chart.
2.7.2 Wiring Terminal Blocks
Remove all panel covers and you will see the wiring terminal block. For UPS module wiring, please
check below chart and table.
AC Terminal DC Terminal
11
LED
Mode
BYPASS
LINE
BATTERY
ALARM
UPS Power On
● ● ●
●
Standby mode
○ ○ ○
○
Bypass mode
●
○○○
Line mode / Converter mode
○ ● ○
○
Battery mode
○
○ ● ○
Fault mode
○○○
●
Battery Test mode
○
●
●
○
ECO mode
●
●
○
○
Function Key
Description
Esc
When it is in Main screen, you can enter setting menu by pressing
ESC key.
Return to previous screen, when screen is not in Main screen.
Return to previous value in the same row, so you can change it.
For example, when changing 4-digit password, press “Esc” to
allow cursor back to previous digit.
Menu page navigation or digit modification.
Menu page navigation or digit modification.
Confirmation of commands, or cursor displacement.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.8 Control Panel
In front panel, there is a control panel to monitor and control the whole system, including LCD
display, 4 LED indicators and 6 function keys.
Control Panel
2.8.1 LED Indicators
Note:● means LED is lighting, and ○ means LED is faded.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.8.3 Audible Alarm
2.9 Introduction of Modules
The modular and hot-swappable design of UPS module makes it a highly cost-effective solution to
meet your power requirement. The number of UPS modules installed in the 19” cabinet can be
based on the initial needs. Once the power requirement increases, you can easily install more UPS
modules without interrupting the operation of the system.
13
No.
Item
Description
1
Fan
The UPS module uses forced convection cooling by these fans.
Cooling air enters the module through ventilation grills and exhalation
exhausts through grills located at the rear of the module. Please do
not block the ventilation area.
2
Battery Start
Button
When AC input is not existing, use this button to start battery power
for UPS.
3
LCD display
There is LCD display on the UPS module. It can show the UPS
information and the slave UPS information when operating in parallel.
4
Function Keys
There are four function keys in the UPS module. They can control and
monitor the single UPS module. Please refer to function key table for
the details.
5
LED indicators
There are four LED indicators to show UPS working status. Please
refer to LED indicator table for the details.
LED Indicators
BYPASS
LINE
BATTERY
ALARM
UP
DOWN
OFF/ESC
ON/ENTER
LCD Display
Function Keys
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.9.1 UPS module
Each UPS module is shipped with its own package. It has to be installed during the whole system
installation.
The capacity of each UPS module is 6kVA/6kW. It includes a power factor correction rectifier, a
battery charger, an inverter, an bypass circuit and control circuit.
14
Control Key
Description
ON/ENTER
Press this button to turn on the UPS.
Or press it to confirm the selection in the menu.
OFF/ESC
Press this button to turn off the UPS.
Or press it to return to the last menu.
UP
Press this button to select the previous item in the menu.
Or press this button to jump to previous page in the screen.
Or press this button to increase the number in the setting.
DOWN
Press this button to select the next item in the menu.
Or press this button to jump to next page in the screen.
Or press this button to decrease the number in the setting.
UP + DOWN
To allow LCD display to rotate 90 automatically, press these two
buttons at the same time. This operation is used to configure the
UPS in rack or tower display.
LED
Mode
BYPASS
LINE
BATTERY
ALARM
UPS Power On
● ● ●
●
Standby mode
○ ○ ○
○
Bypass mode
●
○○○
Line mode / Converter mode
○ ● ○
○
Battery mode
○
○ ● ○
Fault mode
○○○
●
Battery Test mode
○
●
●
○
ECO mode
●
●
○
○
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Table 2-1 The function keys for UPS module
Table 2-2 LED indicators for UPS module
Note:● means LED is lighting, and ○ means LED is faded.
15
Please follow the local wiring regulations. Follow environmental conditions and
refer to IEC60950-1.
Model
6KVA
12KVA
24KVA
Current (A)
34.1
68.2
136.4
Power cable (mm2)
10
16
35
Fixation torque force (lb-in)
20
20
20
Model
6KVA
12KVA
24KVA
Current (A)
37.5A
75
150
Power cable (mm2)
10
16
50
Fixation torque force (lb-in)
20
20
20
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.10 Power Cable
2.10.1 AC input and output maximum current and power cable configuration.
Note: Installer has to consider the max. current and wiring gauge when considering future
extension.
2.10.2 DC input maximum current and power cable configuration.
Warning:
1. The standard battery pack can contain 16 pcs of 12V 9Ah battery (8 pcs Pos+/8pcs Neg-). If
the load rating is over 6KVA, only one battery pack is not sufficient for the discharging current.
At least one more battery pack has to be installed in parallel.
16
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.11 Wiring
WARNING:
Before wiring, make sure the AC input and battery power are completely cut off.
Make sure the breakers, including AC input breaker, AC output breaker and DC breaker, are all
in the OFF position.
2.11.1 Installation Drawing
UPS Module Wiring
2.11.2 AC source connection
This UPS is for Single input application. Connect AC input to the AC power source. Please refer
to Installation Drawing for UPS wiring.
The sequence of two phase (R phase and T phase) can be connected freely. The wrong sequence
will not alarm for 2-phase UPS system when the UPS is powered.
The N wire must be connected firmly. A warning message will be indicated if the N wire is not
connected well. The UPS will show warning message as “ Warning! Bypass Input N Error”. Then,
the UPS will transfer to battery mode if battery pack is connected or transfer to standby mode and
no output if no battery pack is connected.
17
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.11.3 External Battery Pack Connection
After the battery pack is completely installed, be sure to set up nominal battery voltage, battery
capacity and maximum charging current in LCD setting. Otherwise, if battery setting is different
from actual installation, the UPS will keep warning. Please refer to section 4.1.6.3 and Table 4-6
battery setting list for details.
2.12 UPS module/Battery Pack Installation
2.12.1 Insert the UPS module
Warning: The UPS modules installed in the same cabinet must be at the same rating.
(1.) Insert the UPS module into an unoccupied slot by two persons.
(2.) Secure the UPS module to the cabinet by fixing the screws at the front panel of the UPS
module.
18
Before removing any UPS module, make sure the remaining UPS modules can
support the critical loads.
At least one UPS module MUST stay in the UPS cabinet in case the UPS system
is operating in Maintenance Bypass Mode.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2.12.2 Remove the UPS module
(1.) Use a screwdriver to remove the four screws from fixing holes.
(2.) Two people pull out together and remove the UPS module from its slot.
2.12.3 Battery Pack Installation/Removal
Please follow UPS module installation/removal steps to install and remove battery packs.
19
Standby Mode Diagram
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
3. Operation Mode and UPS Operation
3.1 Operation Mode
This modular UPS is a two-phase, three wire on-line, double-conversion and reverse-transfer UPS
that permits operation in the following modes:
Upon connecting to utility input power, the UPS is in Standby mode before UPS is turned on (if
BYPASS enable setting is Disabled), and charger function will be active when the battery is present.
The load is not powered under this mode.
3.2.2 Line Mode
In Line Mode, the rectifier derives power from the utility power, supplies DC power to the inverter
and the charger charges the battery. The inverter filters the DC power and converts it into pure
and stable AC power to the load.
20
Line Mode Diagram
Battery Mode Diagram
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
3.2.3 Battery Mode
The UPS automatically transfers to Battery mode if the utility power fails. There is no interruption
in power to the critical load upon failure.
In battery mode, the rectifier derives power from the battery and supplies DC power to the
inverter. The inverter filters the DC power and converts it into pure and stable AC power to the
load.
3.2.4 Bypass Mode
Upon connecting to utility input power, the UPS is in Bypass mode before UPS is turned on (if
BYPASS enable setting is Enabled), and charger function will be active when battery is present.
After UPS has been turned on, if the UPS encounters abnormal situations (over-temperature,
overload …, etc.), UPS will perform the load from the inverter to the bypass source with no
interruption. If the transference is caused by a recoverable reason, the UPS will turn back to line
mode when abnormal situation is solved.
21
Bypass Mode Diagram
ECO Mode Diagram
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
3.2.5 ECO Mode
The ECO Mode is enabled through the LCD setting menu. In ECO mode, the load is powered by
bypass when the bypass voltage and frequency are within the acceptable ranges. If the bypass is
out of range, the UPS will transfer the power source of load from bypass to inverter. In order to
shorten the transfer time, the rectifier and inverter are working when the UPS is in ECO mode.
3.2.6 Shutdown Mode
When the UPS is in the off state and the utility power source is absent, the UPS will enter into
shutdown mode.
Or when the UPS has discharged the battery to the cut-off level, the UPS will enter into shutdown
mode as well.
When the UPS enters this mode, it is going to shut off the control power of UPS. The rectifier,
charger and inverter are all in off state.
22
Shutdown Mode Diagram
Do not start the UPS until the installation is completed.
Make sure the wiring is correct and the power cables are fixed firmly.
Make sure input and output breakers are switch OFF.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
3.3 UPS Operation
3.3.1 AC Startup
Ensure to follow this procedure when turning on the UPS from a fully powered-down condition.
The operating procedures are as follows:
Step 1: Refer to “Chapter 2 Installation” to connect the power cables and install the UPS modules
and the battery packs required for the UPS system.
Step 2: Switch ON the DC breaker.
Step 3: Switch ON the AC input breaker to power the UPS.
Step 4: The UPS will enter into Standby Mode if the setting of Bypass mode is disabled.
23
After turning on, UPS will do self-test and start up inveter. UPS will be transferred to Line mode
when all UPS modules are ready.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Or the UPS will enter into Bypass Mode, if the setting of Bypass mode is enabled.
Step 5: Make sure there is no warning or fault event happening. If any warning or fault occurs,
please refer to Chapter 6 Troubleshooting to solve it.
Step 6: Press Power ON/OFF button for two seconds to enter into Line Mode as shown below.
24
Battery Start button
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Step 7: Switch ON the output breaker. AC startup procedure is complete.
3.3.2 Cold Start Startup
Step 1: Insert battery pack to 19U mini rack system.
Step 2: Press the “Battery Start” button on each UPS module to start up the control power of all
UPS modules as shown below.
Step 3: Press the “Battery Start” button on communication module to start up the power as
shown below.
Battery start button
Step 4: After pressing the “Battery Start” button, UPS will enter into Standby mode. Refer to the
diagram below for LCD display.
25
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Step 5: Before UPS enters into shutdown mode, please press “Power On/Off” button for 2
seconds immediately as shown in the diagram below.
Step6: Then, UPS will enter Battery Mode as shown in the diagram below.
26
Bypass Mode Setting is Disabled
Bypass Mode Setting is Enabled
Bypass Mode Setting is Disabled
Bypass Mode Setting is Enabled
UPS enters Shutdown Mode.
UPS enters Standby Mode.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Step 6: Switch ON the output breaker. Cold start startup procedure is complete.
3.3.3 Turn off Operation
3.3.3.1 Bypass Mode/ Standby Mode Turn Off Operation
The UPS operates in the Standby Mode or Bypass Mode depending on the “Bypass Mode” Setting.
The LCD diagrams are shown below.
Step 1: Switch OFF the AC input breaker. The LCD diagrams are shown below.
27
It is normal to show “Un-Connection” screen
when UPS modules have shut off their control
power.
UPS enters Shutdown Mode.
It is normal to show “Un-Connection” screen
when UPS modules have shut off their control
power.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Step 2: Switch OFF the AC input breaker to disconnect the AC power to the UPS. Wait until the
LCD is OFF.
Step 3: Switch OFF the DC breaker if the UPS will disconnect the AC power for a long time.
28
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
3.3.4.2 Line Mode Turn Off Operation
The LCD diagrams are shown below when the UPS operates in the Line Mode.
Press “Power On/Off” button for 2 seconds to turn off the UPS. Or use the Menu-Control-System
Turn Off to turn off the UPS.
After turning off, the UPS will tranfer to Standby Mode or Bypass Mode depending on the “Bypass Mode” Setting.
Next, follow the Bypass Mode/ Standby Mode Turn Off Operation procedure.
29
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
3.3.4.3 Battery Mode Turn Off Operation
The LCD diagram is shown below when the UPS operates in the Battery Mode.
Press “Power On/Off” button for 2 seconds to turn off the UPS. Or use the Menu-Control-System
Turn Off to turn off the UPS.
After turning off, the UPS will tranfer to Standby Mode.
Next, follow the Bypass Mode/ Standby Mode Turn Off Operation procedure.
30
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4. Control Panel and Display Description
4.1 System 5.7” LCD Screen Description
4.1.1 Initial Screen
Upon starting, the UPS executes self-test. The initial screen displays and remains still
approximately for 5 seconds as shown in Figure 4-1.
Figure 4-1 Initial screen
4.1.2 Main Screen
After initialization, the main screen will display as Figure 4-2. Main screen is divided into five parts.
(1) UPS Mode: Current operation mode.
(2) UPS Flow Chart: Current flow chart and measurement data.
(3) Menu: Press “Esc” button to enter Menu screen.
(4) UPS model name with power rating. If the power rating followed with (R), it means the UPS
system is in redundant configuration.
(5) Date and Time.
Figure 4-2 Main screen
31
Figure 4-4 Menu screen
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.1.3 MENU Screen
In the Main Screen, press “Esc” button to enter the MENU screen
Use “” or “” buttons to choose different menus, and Press “” button to enter the sub
screen, as shown in Figure 4-3 and 4-4.
Figure 4-3 Menu tree
4.1.4 Control Screen
Use “” or “” buttons to choose CONTROL option, and press “” button to enter the
submenu, as shown in Figure 4-5, 4-6 and 4-7.
Figure 4-5 Control submenu tree
32
Figure 4-6 Control screen page 1
Figure 4-7 Control screen page 2
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
When the control option is selected by pressing “” button, the confirmation screen will pop up.
Use “” or “” button to choose “V” (YES) or “X” (NO). Choose “V” and press “” button to
confirm command or choose “X” to cancel command, as shown in Figure 4-8.
33
Figure 4-8 Confirmation screen
Figure 4-10 Measurement Menu Screen
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.1.5 Measurement Screen
Use “” or “” button to choose MEASUREMENT option, and press “” button to go into the
submenu, as shown in Figure 4-9 and 4-10.
Figure 4-9 Measurement menu
Use “” or “” button to choose System and UPS module option (MASTER#00 or SLAVE#01).
Then, press “” button to go into the submenu, as shown in Figure 4-11.
34
Figure 4-11 Measurement source selection Screen
Menu
Item
Explanation
Input
L-N Voltage (V)
Input phase voltage (L1, L2). Units 0.1V.
Frequency (Hz)
Input Frequency (L1, L2). Units 0.1Hz.
Output
L-N Voltage (V)
Output phase voltage (L1, L2). Units 0.1V.
L-N Current (A)
Output phase current (L1, L2). Units 0.1A.
Frequency (Hz)
Output Frequency (L1, L2). Units 0.1Hz.
Power Factor
Output Power Factor (L1, L2).
Bypass
L-N Voltage (V)
Bypass phase voltage (L1, L2). Units 0.1V.
Frequency (Hz)
Bypass Frequency (L1, L2). Units 0.1Hz.
Power Factor
Bypass Power Factor (L1, L2).
Load
Sout (KVA)
Apparent power (L1, L2). Units 0.01KVA.
Pout (KW)
Active power (L1, L2). Units 0.01KW.
Load Level (%)
The percentage of the UPS rating load (L1, L2). Units
1%.
Battery
Positive Voltage (V)
Battery Positive Voltage. Units 0.1V.
Negative Voltage (V)
Battery Negative Voltage. Units 0.1V.
Positive Current (A)
Battery Positive Current. Units 0.1A.
Negative Current (A)
Battery Negative Current. Units 0.1A.
Remain Time (Sec)
Battery run time remaining. Units 1Min.
Capacity (%)
The percentage of the capacity of the battery. Units 1%.
Test Result
Battery test result
Charging Status
Battery charging status
Temperature1(°C)
Internal temperature of UPS module. Units 0.1°C.
Temperature2(°C)
Battery cabinet temperature of extra communication
card T1. Units 0.1°C.
Temperature3(°C)
Battery cabinet temperature of extra communication
card T2. Units 0.1°C.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Use “” or “” button to choose Input, Output, Bypass, Load, and Battery option, and press
“” button to go into submenu. The measurement can be read as listed in Table 4-1.
Table 4-1: Measurement data
35
Figure 4-13 Enter password Screen
Figure 4-14 SETUP Submenu Screen
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.1.6 Setup Screen
Use “” or “” button to choose SETUP options. It’s required to enter password to access
GENERAL, SYSTEM, BATTERY and PRE-ALARM sub-menus, as shown in Figure 4-12.
Figure 4-12 Setup menu
When the SETUP option is selected by pressing “” button, it will pop up a screen requesting to
enter password will pop up, as shown in Figure 4-13.
It’s required to enter 4-digit password to enter SETUP submenu. If incorrect password is entered,
the LCD screen will ask for re-entery.
If correct password is entered, the LCD will enter the SETUP submenu, as shown in Figure 4-14.
There are two levels of password protection, user password and maintainer password.
36
UPS operation
Mode
Setting item
Standby
Mode
Bypass
Mode
Line
Mode
Battery
Mode
Battery
Test
Mode
Fault
Mode
Converter
Mode
ECO
Mode
Authorization
User
Maintainer
General
Model Name
Y Y Y Y Y Y Y Y Y Language
Y Y Y Y Y Y Y Y Y
Y
TIME
Y Y Y Y Y Y Y Y
Y
Change
Password
Y Y Y Y Y Y Y Y Y
Y
Audible Alarm
Y Y Y Y Y Y Y Y Y
Y
Factory Reset
Y Y
Y
EPO Function
Y
Y
System
Output Voltage
Y Y
Y
ECO Voltage
Range
Y Y Y Y
Y
ECO Frequency
Range
Y Y Y Y
Y
Bypass Voltage
Range
Y Y
Y
Bypass
Frequency
Range
Y Y
Y
ECO Mode
Y Y Y Y Y Bypass Mode
Y Y
Y
Converter Mode
Y Y
Y
Battery Mode
Delay Time
Y Y Y Y Y Y
Y
Cold Start
Y Y Y Y Y Y Y Y
Y
System
Shutdown Time
Y Y Y Y Y Y Y Y
Y
System Restore
Time
Y Y Y Y Y Y Y Y
Y
Redundancy
Y Y Y Y Y Y Y Y
Y
Charger Test
Y Y Y Y Y
Y
Battery
Nominal Battery
Voltage
Y Y
Y
Battery Capacity
in Ah
Y Y Y Y Y Y Y Y
Y
Battery Groups
Y Y Y Y Y Y Y Y
Y
Maximum
Charging
Current
Y Y
Y
Battery
Low/Shutdown
Setting
Y Y Y Y Y Y
Y
Periodic Battery
Test
Y Y Y Y Y Y Y Y
Y
Battery Test
Interval
Y Y Y Y Y Y Y Y
Y
Battery Test
Type
Y Y Y Y Y Y Y
Y
Battery Age Alert
Y Y Y Y Y Y Y Y
Y
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
The default password for user is “0000”. It could be changed by user.
The manitainer password is owned by service personnel.
Entering different level of password can access to differnet settings. The setting can be changed in
different operation mode. Table 4-2 lists the relevant information.
Table 4-2: All setting items in Setup Menu
37
Pre-Alarm
Y Y Y Y Y Y Y Y
Y
Figure 4-15 Setup-General Screen page 1
Figure 4-16 Setup-General Screen page 2
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
“Y” meansthat this setting item can be set in this operation mode.
4.1.6.1 Setup-General Screen
Use “” or “” buttons to choose between different sub-menus, and press “” button to go
into the GENERAL setting screen, as shown in Figure 4-15 and 4-16. General setting can be set in
any operating mode and Setup-General setting list is shown in Table 4-3.
38
Figure 4-17 SETUP Confirmation screen
Setting Item
Sub Item
Explanation
Model Name
Enter UPS Name (xxxxxxxxxx).
The max. Length is 10 characters.
Language
--
Provides 3 optional LCD languages:
English (Default)
Traditional Chinese
Simplified Chinese
TIME
Adjust Time
Set current date and time.
(yyyy / mm / dd hour : min : sec)
MUST be set after UPS installation
System Installed Date
Set system installed date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
System Last Maintain
Date
Set system latest maintenance date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
Battery Installed Date
Set battery installed date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
Battery Last Maintain
Date
Set battery latest maintenance date
(yyyy / mm / dd)
2017/1/1 (Default)
MUST be set after UPS installation
Change
Password
--
Set New Password.
0000 (Default)
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Use “” or “” buttons to choose the setting options for setting requirement, then press
“” button. The confirmation screen will pop up. Use “” or “” button to choose “V” (YES)
or “X” (NO). Choose “V” and press “” button to confirm setting or choose “X” to cancel the
setting, as shown in Figure 4-17.
Table 4-3: Setup-General setting list
39
Audible
Alarm
Audible Mute
It is to mute the buzzer when UPS in any mode.
Disable (Default)
Enable
Battery Mute
It is to mute the buzzer when UPS in Battery mode.
Disable (Default)
Enable
Fault Mute
It is to mute the buzzer when UPS in Fault mode.
Disable (Default)
Enable
Bypass Mute
It is to mute the buzzer when UPS in Bypass mode.
Disable (Default)
Enable
Factory
Reset
--
Restore to factory default setting
EPO
Function
--
Set EPO active status
Normal Close Active (Default)
Normal Open Active
Figure 4-18 Setup-System Screen page 1
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.1.6.2 Setup-System Screen
Use “” or “” button to choose between different sub-menus, and press “” button to go
into the SYSTEM setting screen, as shown in Figure 4-18, 4-19 and 4-20.
40
Figure 4-19 Setup-System Screen page 2
Figure 4-20 Setup-System Screen page 3
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
System setting can be set only when UPS is operating in certain mode. Please check Table 4-2 for
the available operation modes. If it’s not able to set up in specific mode, the warning screen will
appear, as shown in Figure 4-21.
Set ECO voltage range:
Upper Range
(Output Setting Voltage +6V) ~ (Output Setting
Voltage +12V)
(Output Setting Voltage +6V) (Default)
Lower Range
(Output Setting Voltage -6V) ~ (Output Setting
Voltage -12V)
(Output Setting Voltage -6V) (Default)
ECO Frequency Range
Set bypass Frequency range:
Upper/ Lower limit
+/- 2Hz (Default)
+/- 3Hz
+/- 4Hz
BYPASS
SETTING
Bypass Voltage Range
Set bypass voltage range:
Upper Range
(Output Setting Voltage +6V) ~ 155V
140V (Default)
Lower Range
(Output Setting Voltage -6V) ~ 88V
88V (Default)
Bypass Frequency
Range
Set bypass Frequency range:
Upper/ Lower limit
+/- 1Hz
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Setup-System setting list is shown in Table 4-5.
Table 4-5: Setup-System setting list
42
+/- 2Hz
+/- 3Hz
+/- 4Hz (Default)
ECO Mode
--
Set ECO mode
Disable (Default)
Enable
Bypass
Mode
--
Set bypass mode
Disable
Enable (Default)
MUST be reviewed after UPS installation.
If you need the Bypass power when UPS is OFF, please
enable it.
Converter
Mode
--
Set converter mode
Disable (Default)
Enable
Set Output Frequency
50Hz (Default)
60Hz
Battery
Mode Delay
Time
--
Set system shutdown delay time in battery mode
(Disable or 10~990Min).
Disable (Default)
Not 0: Enable
When this feature is enabled, UPS will shut off output
after UPS operates in Battery mode for certain seconds.
Cold Start
--
Set cold start
Disable (Default)
Enable
After “Enable” is set, the UPS can be turned on without
connecting to utility by pressing Battery Start Button.
Refer to cold start operation for the details.
System
Shutdown
Time
--
Set system shutdown time (0.2~99min)
0.2 min (Default)
This delay time will start counting when the
CONTROL-Shutdown Restore command is executed.
System
Restore
Time
--
Set system restore time (0~9999min)
1 min (Default)
This delay time will start counting after shutdown time is
elapsed when the CONTROL-Shutdown Restore
command is executed.
Redundancy
--
Set redundancy
Redundancy: the QTY of redundant UPS module(0~9)
0(Default)
MUST be set after UPS installation
Charger Test
--
Set charger test
Disable (Default)
Enable
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
43
Figure 4-22 Setup-Battery Screen page 1
Figure 4-23 Setup-Battery Screen page 2
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.1.6.3 Setup-Battery Screen
Use “” or “” button to switch different sub-menus. Press “” button to go into the
BATTERY setting screen, as shown in Figure 4-22 and 4-23.
Battery setting can be set only when UPS is operating in standby mode. If it’s not in standby mode,
the warning screen will appear as shown in Figure 4-24. See Setup-Battery setting list in Table 4-6.
MUST be set after UPS installation or Battery
capacity is changed.
Battery Groups
Set battery groups (1~10).
1 (Default)
Maximum
Charging
Current
--
Set battery maximum charging current (1~40A)
4A (Default)
MUST be set after UPS installation or Battery
capacity is changed.
Battery Low/
Shutdown
SETTING
Battery Low
Voltage
Set battery low voltage (10.5~11.5V)x(battery Number)
11.2V x Battery Number (Default)
Battery Low
Capacity
Set battery low capacity (20~50%)
20% (Default)
Battery Shutdown
Voltage
Set battery voltage point for system shutdown in battery
mode (9.6~10.7V) x (battery Number)
9.6V x Battery Number (Default)
BATTERY TEST
Periodic Battery
Test
Set periodic battery test disable or enable
Disable (Default)
Enable
Battery Test
Interval
Set battery test interval (7~99 Days)
30 Days (Default)
Battery Test Type
Set testing time for battery test
Short Time(10S) (Default)
Long Time(0.1M~0.9M)
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Table 4-6: Setup-Battery setting list
45
Long Time(1M~99M)
Till Battery Low
Battery Age
Alert
Battery Age Alert
(Months)
Set battery age for replacement.
(Disable,12~60Months)
Disable (Default)
If this feature is enabled and the battery has been
installed over this period, there is a warning “Battery
Age Alert” to indicate it.
Figure 4-25 Setup-Pre-Alarm screen
Setting Item
Sub Item
Explanation
Line Voltage
Range
--
Set line voltage range:
Upper limit
+5%
+10%
+15% (Default)
+20%
Lower limit
-5%
-10%
-15%
-20% (Default)
Line
Frequency
Range
--
Set line frequency range:
Upper / Lower limit
+/- 1Hz
+/- 2Hz
+/- 3Hz
+/- 4Hz (Default)
Load
--
Set UPS Overload percentage (40~100%)
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.1.7 Pre-Alarm Screen
Use “” or “” button to switch different sub-menus. Press “” button to go into the
Pre-Alarm setting screen, as shown in Figure 4-25.
Pre-Alarm setting can be set in any operation mode. See Setup-Pre-Alarm setting list in Table 4-7.
Table 4-7: Setup-Pre-Alarm setting list
46
100% (Default)
Set UPS load unbalance percentage (20~100%)
100% (Default)
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.1.8 Information Screen
In INFORMATION menu, you can check the serial number, firmware versions, system
configuration and settings of the UPS. There are sub-menus under the INFORMATION, including
Identification, System and Battery, as shown in Figure 4-26 and 4-27.
Figure 4-26 Information menu
Figure 4-27 INFORMATION screen
4.1.8.1 INFORMATION - Identification Screen
When Identification submenu is selected, the Model Name, Serial No. and Firmware Version will be
displayed, as shown in Figure 4-28 and 4-29. Use “” or “” button to switch between different
pages.
47
Figure 4-28 Identification screen page 1
Figure 4-29 Identification screen page 2
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.1.8.2 INFORMATION - System Screen
When System submenu is selected, the information such as system power, nominal voltage,
nominal frequency … etc. will be displayed, as shown in Figure 4-30 and 4-31. Use “” or “”
button to switch between different pages.
48
Figure 4-30 INFORMATION System screen page 1
Figure 4-31 INFORMATION System screen page 2
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.1.8.3 INFORMATION - Battery Screen
When Battery submenu is selected, the battery information such as nominal battery voltage,
capacity, charging current … etc. will be displayed, as shown in Figure 4-32 and 4-33. Use “” or
“” button to switch between different pages.
49
Figure 4-32 INFORMATION Battery screen page 1
Figure 4-33 INFORMATION Battery screen page 2
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.1.9 Events Screen
In EVENT menu, you can check the current events, history events and reset all events, as shown in
Figure 4-34 and 4-35.
Figure 4-34 Events menu
50
Figure 4-35 Events screen
Figure 4-36 Alarm warning screen
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
When event occurs, you will see flashing warning text in the Main Screen as shown in Figure 4-36.
4.1.9.1 Current Events
When event occurs, it will display Module ID and alarm code in Current Events screen. It can save
up to 50 events in current list. Only 4 events can be listed in one page. Therefore, if it exceeds
more than four, you have to press “” or “” button to read other events as shown in Figure
4-37.
51
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Figure 4-37 Current Events screen
4.1.9.2 History Events
The detailed event information is saved in history events. It can save up to 500 events in history
events. When warning occurs, it will display alarm code, alarm time and Module ID. When fault
event occurs, it will display alarm code, alarm time and Module ID. (Refer to Chapter6
Troubleshooting) In order to record more historical information about the UPS system, the
important setting changed (refer to Table 4-8 Important setting changed), UPS operation mode
changes (refer to Table 4-9 UPS mode change) and control action executes (refer to Table 4-10
Control execution) will be saved in History Events. Refer to Figure 4-38 for display screen.
Figure 4-37 History Events screen
4.1.9.3 Reset All Events
The Maintainer password is required to enter Reset All Events screen as shown in Figure 4-38.
Then, use“” or “” buttons to choose “V” (YES) or “X” (NO). Choose “V” and press “”
button to reset all events or choose “X” to cancel this action as shown in Figure 4-39.
52
Item
No.
Description
Item
No.
Description
1
Setup! Model Name
2
Setup! Language
3
Setup! Adjust Time
4
Setup! System Installed Date
5
Setup! System Last Maintain Date
6
Setup! Battery Installed Date
7
Setup! Battery Last Maintain Date
8
Setup! Change Password
9
Setup! Audible Alarm
10
Setup! Factory Reset
11
Setup! EPO Function
12
Setup! Output Voltage
13
Setup! ECO Voltage Range
14
Setup! ECO Frequency Range
15
Setup! Bypass Voltage Range
16
Setup! Bypass Frequency Range
19
Setup! ECO Mode
20
Setup! Bypass Mode
21
Setup! Converter Mode
22
Setup! Battery Mode Delay Time
23
Setup! Cold Start
24
Setup! System Shutdown Time
25
Setup! System Restore Time
26
Setup! Redundancy
27
Setup! Charger Test
28
Setup! Nominal Battery Voltage
29
Setup! Battery Capacity in Ah
30
Setup! Battery Group
31
Setup! Maximum Charging Current
32
Setup! Battery Low Voltage
33
Setup! Battery Low Capacity
34
Setup! Battery Shutdown Voltage
35
Setup! Periodic Battery Test
36
Setup! Battery Test Interval
37
Setup! Battery Test Type
38
Setup! BATTERY Age Alert
39
Setup! Line Voltage Range
40
Setup! Line Frequency Range
41
Setup! Load
42
Item
No.
Description
Item
No.
Description
1
UPS Mode! Power On Mode
2
UPS Mode! Standby Mode
3
UPS Mode! Bypass Mode
4
UPS Mode! Line Mode
5
UPS Mode! Battery Mode
6
UPS Mode! Battery Test Mode
7
UPS Mode! Fault Mode
8
UPS Mode! Converter Mode
9
UPS Mode! ECO Mode
10
UPS Mode! Shutdown Mode
11
UPS Mode! Un-Connection
12
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Figure 4-38 Reset All Events screen Figure 4-39 Reset All Events Confirmation screen
4.1.9.4 History Record
Table 4-8: Important setting changed
Table 4-9: UPS mode change
53
Item
No.
Description
Item
No.
Description
1
Control! System Turn On
2
Control! System Turn Off
3
Control! Manual Battery Test
4
Control! Cancel Battery Test
5
Control! Turn To Bypass
6
Control! Shutdown Restore
7
Control! Cancel Shutdown
8
Control! Charger Turn On
9
Control! Charger Turn Off
10
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Table 4-10: Control execution
54
Main Interface
Batt Test
SR Off
Input
Output
Bypass
Load
Bat
Bypass
ECO
Output
System Time
Others
Bat
Identification
System
Bat
History Events
Reset Events
Press button “Enter”
Press button “Esc”
Press button “Enter”
Press button “Esc”
Press button “Enter”
Press button “Esc”
Press button “Enter”
Press button “Esc”
Press button “Enter”
Press button “Esc”
Control
Press either button “UP”or “DOWN”
Press button “Esc”
Measurement
Setting
Information
Events
Turn To Bypass
Charger Off
Turn On
Current Events
Local
Master
Slave1
Slave9
Press button “Enter”
Press button “Esc”
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.2 LCD Screen in UPS Module
4.2.1 LCD Structure
The entire LCD structure is demonstrated as below diagram.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.2.2 Main interface (Home Page)
After initialization, the main screen will display as below.
Main screen (Home Page)
1) UPS Mode: Current operation mode.
2) It will display the UPS running status mode and parallel information as below table.
3) Input and output information.
4) Battery capacity, load level and backup time/warning or fault codes. When alarms happen, the
warning or fault information will display. When UPS is operated in Battery mode or Battery Test
mode, the backup time will display.
When the front panel is not operated for 2 minutes, the display page will return back to home page.
Press the “UP” or “DOWN” button to enter the operation menu (Refer to 4.2.3).
When it displays home page in LCD, if UPS is in bypass or standby, you could press the
“ON/ENTER” button to turn on the UPS to line / converter / ECO / battery mode according to the
setting and input status.
→→
56
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
When UPS is turned on, you could press the “OFF/ESC” button to allow UPS to bypass mode or
standby.
→→
4.2.3 Operation menu
4.2.3.1 Main menu
→
Main screen(Home page) Main menu
1) After pressing the “UP” or “DOWN” button on the main screen (Home page), it will display five
items in operation menu: Control / Measurement / Setting / Information / Events.
2) Press “UP” or “DOWN” button to select item.
3) Press “ON/ENTER” button to confirm the selection.
4) Press “OFF/ESC” button to return back to main scree (Home page).
4.2.3.2 Control
In “Control” screen, it’s real-time command for UPS.
“Turn On” will be displayed if UPS is not turned on. “Turn Off” will be displayed if UPS is turned
on.
“Bat Test” will be displayed if UPS is not in Battery Test Mode. “Cancel Test” will be displayed
if UPS is in Battery Test Mode.
“Turn to Bps” will be displayed all the time no matter what status UPS is. But this action is only
57
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
effective when the input power is available.
“SR Off” will be displayed if UPS is not turned on. “SR On” will be displayed if UPS is turned on.
“Charger Off” will be displayed if charger is working. “Charger On” will be displayed if charger
is turn off.
Generally speaking, only one selection will be displayed in the screen and it depends on UPS
status.
1) Turn On/Turn Off
This item is for turning on/off the UPS.
a) On Bypass mode, it will display “Turn On” in control menu. If it is selected and confirmed,
the UPS will transfer to line mode, converter mode, ECO mode, or battery mode according
to the setting and input status.
→→
NOTE: You may simply turn on UPS by pressing “ON/ENTER” button in main scree (Home
page). It’s not necessary to enter control menu to turn on the UPS.
b) On line mode, converter mode, ECO mode or battery mode, it will display “Turn Off” in
control menu. If it is selected and confirmed, the UPS will transfer to bypass mode or
shutdown mode.
→→
NOTE: You may simply turn off UPS by pressing “OFF/ESC” button in main scree (Home
page). It’s not necessary to enter control menu to turn off the UPS.
2) Battery Test / Cancel Test
a) It is to check if the UPS could work well in battery mode and test the battery performance.
Except UPS is in Battery Test mode, “Battery Test” selection will be displayed under all
operation modes.
58
Setting Item
Sub Item
Explanation
Bat Test Type
Short Time
10-second test time.
Long Time
When testing time is longer than 1 minute, please select
“Long Time” and the duration is able to set up.
(1~99min)
10 min (Default)
Till to Bat Low
Test until the battery is low voltage.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
→→→
However, it could execute this test in Line/Converter mode and reminder will pop up in the screen.
When “Yes” is selected, the screen will return back to home page with “Battery Test Mode”
displayed on top. If the test is completed, the displayed status will change back to UPS current
mode. There are four battery test types to select. Refer to Table 4-11.
Table 4-11: Battery Test Type
b) On Battery Test mode, it will display “Cancel Test” in control menu. When “Cancel Test” is
selected, the screen will change back to UPS current mode.
→→
3) Turn to Bypass
If it is selected and confirmed, the UPS will transfer from Line mode to Bypass mode.
→→
4) SR On / SR Off
a) On Line/Battery/Battery Test/Converter/ECO mode, it will display “SR On” in control menu.
If it is selected and confirmed, the screen will return back to home page. Shutdown and
59
Setting Item
Sub Item
Explanation
SR On
Shutdown Time
Set system shutdown time (0.2~99min)
0.2 min (Default)
Restore Time
Set system restore time (0~9999min)
1 min (Default)
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
restore time can be selected as in Table 4-12.
When “Shutdown Time” countdown ends, the UPS will turn off. Then, the “Restore Time”
will start to count. When countdown ends, the UPS will be turned on and back to current
mode.
→→→
→
Table 4-12: Shutdown Restore Time
b) On Standby/Bypass/Fault mode, it will display “SR Off” in control menu. If it is selected
and confirmed, the screen will return back to home page and system will back to current
mode.
If “SR On” is selected and confirmed, When UPS in Line/Battery/Battery
Test/Converter/ECO mode, it will display “SR Off” in control menu. If it is selected and
confirmed, the screen will return back to home page and system will cancel this function.
→→
5) Charger Off / Charger On
a) “Charger Off” will be displayed under all operation modes when charger is working. If it is
selected and confirmed, the screen will return back to home page. And charger will stop
60
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
charging the battery.
→
b) “Charge On” will be displayed under all operation modes when charger is turned off. If it is
selected and confirmed, the screen will return back to home page. And charger will charge
the battery.
→
4.2.3.3 Measurement
Measurement displays the measurement value of the parameters such as voltage / current /
frequency / power / capacity / time etc. Every UPS could display the measured value of the whole
system. Press “” or “” button to explore the pages.
→
“Local” means the current UPS module. “Master” and “Slave<n>” means the other UPS module in
this parallel system.
61
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
→→→→
→→
4.2.3.4 Setting
This page is used to configure the parameter settings. It’s necessary to enter password to enter
submenus. The default password is 0729. There are submenus under the Setting, including Bypass,
ECO, Output, SystemTime, Others and Battery, as shown below.
→→
NOTE: Some settings will be only available in some operation modes. If the setting is not available
in current mode, the LCD will show prompt message with “Item can’t be set in this mode”. Press
any button or just wait for several seconds until this message fades.
62
Interface
Description
1. Status
1.1 Open/Forbid:
Open: Bypass allowed. When selected, UPS will run at
Bypass mode depending on bypass enabled/disabled
setting.
Forbid:Bypass not allowed. When selected, it’s not
allowed for running in Bypass mode under any situations.
The default setting is Open.
1.2 Enable/Disable
This option appears only when Bypass status is set to
“Open”.
Enable: Bypass enabled. When selected, Bypass mode is
activated.
Disable: Bypass disabled. When selected, automatic
bypass is acceptable, but “manual bypass” is not
available. “Manual bypass” means users manually operate
UPS to Bypass mode (for example, in AC mode turning off
the UPS to Bypass mode). Then, the UPS will go to bypass
mode but without output if it is turned off in AC mode.
The default setting is Enable.
NOTE: The following items are only available in bypass
mode:
2. HighLoss V: Set the acceptable high voltage for bypass.
Setting range is from (Rated Output Volt +6V) to 155V
and the default value is 140V.
3. LowLoss V: Set the acceptable low voltage for bypass.
Setting range is from 88V to (Rated Output Volt - 6V) and
the default value is 88V.
4. HighLoss F: Set the acceptable high frequency for
bypass.
50 Hz: Setting range is from 51Hz to 54 Hz.
60 Hz: Setting range is from 61Hz to 64Hz.
The default value is 54.0Hz/64.0Hz.
5. LowLoss F: Set the acceptable high frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46Hz/56Hz.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
1) Bypass setting (only available or effective on bypass mode and standby mode)
63
Interface
Description
1. Status
Enable: Enable ECO Function
Disable: Disable ECO Function
If ECO function is disabled, voltage range and frequency
range for ECO mode still can be set, but it is meaningless
unless the ECO function is enabled. The default setting is
Disable.
2. HighLoss V: High voltage point in ECO mode. The
setting range is from (Rated Output Volt +6V) to (Rated
Output Volt +12V) and the default setting is (Rated
Output Volt +6V).
3. LowLoss V: Low voltage point in ECO mode. The
setting range is from (Rated Output Volt -12V) to (Rated
Output Volt -6V) and the default setting is (Rated
Output Volt -6V).
4. HighLoss F: Set High frequency point for ECO mode.
50 Hz system: Setting range is from 52Hz to 54Hz.
60 Hz system: Setting range is from 62Hz to 64Hz.
The default value is 52Hz/62Hz.
5. LowLoss F: Set Low frequency point for ECO mode.
50 Hz system: Setting range is from 46Hz to 48Hz.
60 Hz system: Setting range is from 56Hz to 58Hz.
The default value is 48Hz/58Hz.
Interface
Description
1. Volt:
100: Presenting the rated output voltage with 100Vac
110: Presenting the rated output voltage with 110Vac
115: Presenting the rated output voltage with 115Vac
120: Presenting the rated output voltage with 120Vac
127: Presenting the rated output voltage with 127Vac
The default value is 120Vac.
2. Freq:
50Hz: The output frequency is setting for 50Hz.
60Hz: The output frequency is setting for 60Hz.
NOTE: CVCF should be enabled to modify this item.
If CVCF is disabled, output frequency will be decided according
to the latest normal utility frequency. If it is within 46Hz and
54Hz, the output frequency will be 50.0Hz. If it is within 56Hz
and 64Hz, the output frequency will be 60.0Hz.
3. CVCF:
Enable or disable converter mode.
Enable: The output frequency will be fixed at 50Hz or 60Hz
according to setting of “Freq”. The input frequency could be
from 46Hz to 64Hz.
Disable: The output frequency will synchronize with the input
frequency within 46~54 Hz for 50Hz system or within 56~64 Hz
for 60Hz system.
NOTE: CVCF means Constant Voltage and Constant Frequency.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
2) ECO setting(only available or effective on bypass mode, standby mode, Line mode and ECO
mode)
3) Output setting (only available or effective on bypass mode and standby mode)
64
It represents converter mode.
The default setting is Disable.
Interface
Description
SystemTime:
Date, Time and Week can be modified via this interface. Input the
actual Time, the unit will automatically adjust timer after “”
button is pressed.
Interface
Description
1. Hot standby(only available or effective on bypass mode and
standby mode):
Enable: Hot standby function is enabled. It means that the current
UPS is set to be host of hot standby system, and it will automatically
restart after AC recovery even without battery connected.
Disable: Hot standby function is disabled. The UPS is running at
normal mode and can’t restart without battery.
The default setting is Disable.
2. Audible Mute(available or effective for all modes):
Enable: It is to mute the buzzer.
Disable: It is to enable the buzzer when UPS have alarms or UPS
is working in bypass mode or Battery mode.
The default setting is Disable.
3. Redundancy (available or effective on all modes):The setting is
quantity of redundant UPS module. The setting range is 0~9. The
setting quantity must be less than the number of UPS modules in
the system. The default value is 0.
4. Factory Reset (only available or effective on bypass mode and
standby mode): Restore to factory default setting.
5. Bat Mute(available or effective on all modes):
Enable: It is to mute the buzzer when UPS in Battery mode.
Disable: It is to enable the buzzer in Battery mode. The default setting is Disable.
6. Fault Mute(available or effective on all mode):
Enable: It is to mute the buzzer when UPS in Fault mode.
Disable: It is to enable the buzzer in Fault mode. The default setting is Disable.
7. Bypass Mute(available or effective on all mode):
Enable: It is to mute the buzzer when UPS in Bypass mode.
Disable: It is to enable the buzzer in Bypass mode.
The default setting is Disable.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4) SystemTime setting (available or effective on all mode)
4) Others setting
65
Interface
Description
1. Dischg Protect: Enable or disable battery discharge protection.
Enable: Battery discharge protection function is enabled. When UPS
have been continuously working in “battery/battery test
mode”, the UPS will automaticallyshut down when the
backup time set next is achieved.
Disable: Battery discharge protection function is disabled.
Backup Time: When discharge protection is enabled, this setting time can be counted.
1~990: The maximum discharge time can be set from 1 to 990
minutes. UPS will shut down to protect battery after backup
time arrives when the “Dischg Protect” is enabled. If “Dischg
protect” is disabled, then this setting does not make sense
whatever the value is. The default value for this setting is 990
minutes.
2. Cold Start:
Enable: UPS could be turned on without mains.
Disable: UPS could not be turned on without mains.
3. Charger Test:
Test the battery charger even without battery. After entering this item,
it will pop up a screen showing “Yes” and “No”. If selecting “Yes”, the
UPS will execute charger test. After test, the LCD screen will return to
main scree (home page) and show battery voltages on BAT+ and
BAT-.
4. Low Volt:
Set battery low warning voltage. The setting range is from 10.5~11.5V
per piece. The default value is 11.2V.
5. Under Volt:
Set battery low cut off voltage. The setting range is from 9.6~10.7V
per piece. The default value is 9.6V.
6. Periodic Test:
Enable: UPS will test the battery periodically.
Disable: UPS will not test the battery periodically.
7. Periodic Test:
When periodic test is enabled, please set up battery test interval. The
setting range is from 7 days to 99 days. The default value is 30-day.
8. BatNum:
Set battery number in the system. The setting range is from 8 to 10
pieces. The default value is 8.
9. Chg Curr:
Set maximum charge current. The setting range is from 0~40A. The
default value is 4A.
10. Bat Groups: Set the number of battery group ranging from 1 to
10. The default value is 1 group;
11. Bat Cap: Set the battery capacity such as 7AH, 9AH, 10AH, 12AH,
17AH, 26AH, 40AH, 65AH, 100AH and so on. The default value is 9AH.
12. Factor: Calibrate the displayed backup time by adjusting this
multiplier factor. The formulation is listed below:
Displayed backup time=Original calculated backup time×Multiplier
factor
The value of default factor is 1.0. The setting range is from 0.5 to 2.
Item 10~12 are used for the battery backup time calculation.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
5) Battery
66
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
4.2.3.5 Information
In Information page, you can check the serial number, firmware version, system configuration and
settings of the UPS. There are submenus under the Information, including Identification, System
and Battery, as shown below. Information displays all parameter setting value and status.
1) Identification shows the UPS Module name, serial no, UPS display version, communication
module version, CPU version and system LCD version.
→→
2) System shows the UPS configuration.
→→→→
→→
67
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
3)Battery shows the battery configuration.
→→→
4.2.3.6 Events
In Event page, you can check the current events, history events and reset events.
1) Current Events
When an event occurs, it will display alarm code in Current Events page. If events exceed more
than one page, press “” or “” button to read other events.
→
2) History Events
The detailed event information is saved in history events. It can save up to 160 pages in history
events. When a warning occurs, it will display alarm code, alarm time and UPS mode. When a
fault event occurs, it will display fault code, alarm time/date and UPS operation mode. (Refer to
Chapter 6 Troubleshooting)
→
68
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
3) Reset Events
It’s necessary to enter password to enter Reset Events page as shown below. Then, press “” or
“” button to choose “Yes” to clear all history events or “No” to cancel the reset action.The
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
5. Communication Module
Front View:
Back View:
EMBS port (external maintenance bypass signal port)
5.1 Battery Start Button
The communication module can be turned on without connecting to utility by pressing Battery
Start Button.
5.2 Status LED
The green LED represents operation status of communication module.
5.3 Output Dry Contact Port
These 6 output dry contacts are normally open. It’s also able to set the feature for each dry contact
port through the Dry Contact Config tool. Please refer to next section for the detailed installation
and configuration.
Figure 5-2 Dry Contact Output Port
70
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
5.3.1 Configuration
Step 1: Please access the www.power-software-download.com and select Communication Setting
Tool icon. Please download and install this tool in your computer. After this tool is installed
successfully, it will leave a short icon on the desktop.
Step 2: Start this tool in your computer. Then, it will pop up a screen as below.
Step 3: Click “Read Setting” button to check the current setting of the output dry contact port.
Step 4: Check all settings. There are 18 options to select for contact and listed in Table 5-1. Once
output dry contact settings are selected, click “Setting Confirm” button.
71
Contact
Message
Description
1
Load on inverter
The UPS is working normally.
2
Load on bypass
The UPS is in Bypass mode.
3
Load on Battery
The UPS is in Battery mode.
4
Low battery
The battery voltage is low.
5
Bypass input abnormal
The bypass voltage or frequency is
abnormal.
6
Battery test failure
Performs the battery test. The
battery test fails.
7
Internal communication
failure
DSP and MCU stop communication in
UPS module.
8
External parallel
communication failure
Communication error between UPS
modules.
9
Output overload
warning/shutdown
Connected load is over rated output
of the UPS.
10
UPS module fault
shutdown
The module fails and the UPS shuts
down.
11
UPS module warning
The module has errors, but the UPS
can still function normally.
12
EPO Active
Urgently power off the UPS.
13
Maintain Bypass
The UPS transfers to Maintain bypass
mode.
14
Module over
temperature
warning/shutdown
The temperature is too high.
15
Battery replacement
Overdue for battery replacement
(Compared with system setup.)
16
Bypass static switch fault
The bypass “static transfer switch” is
abnormal.
17
Line AC fail
Power failure
18
Redundancy failure
Redundancy setting error.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Table 5-1: Output Dry Contact List
72
Pin13Pin14Pin15Pin16
12V
12V
Dry Contact Input 1
Dry Contact Input 2
Pin1Pin2Pin3Pin4Pin5Pin6Pin7Pin8
SCL
SDA
3.3V
GND
SCL
SDA
3.3V
GND
External Battery cabinet
temperature 1
External Battery cabinet
temperature 2
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
Step 5: “Default setting” button: It’s to reset all configurations back to default value.
5.4 Input Dry Contact Port
There are two sets of input dry contact to receive external signals for UPS to take response.
5.5 Battery Dry Contacts (Option)
This port is to detect the temperature of external battery packs. It’s necessary to install “sensor
kit” (optional accessory) when using these battery dry contacts.
73
Pin1Pin2
12V
EPO Input
EPO logic setting
Position
Description
N.C (Default)
Pin1 & Pin2
EPO activated when Pin1 & Pin2 is open status.
N.O
Pin1 & Pin2
EPO activated when Pin1 & Pin2 is short circuited.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
5.6 EPO Port
This UPS is equipped with an Emergency Power off (EPO) port that can be operated by a remote
contact assigned by the user. Users can set the logic (N.C or N.O) of this EPO function through LCD
panel.
Table 5-2 Description of EPO port
If EPO logic setting is Normal Closed (N.C), EPO is triggered when pin1 and pin2 is open.
Otherwise, EPO logic setting is Normal Opened (N.O). EPO is triggered when pin1 and pin2 is
connected.
5.7 External Maintenance Bypass Signal Port (EMBS)
On the back panel of communication module, there is an external maintenance bypass signal port.
This port can be connected to external maintenance bypass switch. If not in use, please connect
the terminal port as below for UPS normal operation.
5.8 Other Communication Interface
5.8.1 Local Communication Ports – RS232 & USB
Note: The RS232 and USB ports can’t work simultaneously.
5.7.2 Communication Slot
The SNMP card, Modbus card or AS400 card can be inserted into this slot to work with the UPS.
74
LCD Message
Explanation
Solution
Fault 01:Bus Start Fail
The rectifiers could not start within
specified time due to low DC-bus
voltage.
Turn off UPS and then restart the UPS.
If it fails again, contact service personnel.
Fault 02:Bus Over Volt
DC-bus voltage exceeds the maximum
voltage.
Contact service personnel.
Fault 03:Bus Under Volt
DC-bus voltage is lower than the
minimum value.
Contact service personnel.
Fault 04:Bus Unbalance
DC-bus voltage is not balanced
Contact service personnel.
Fault 05:Bus Volt Vary
DC-bus voltage changes too fast.
Contact service personnel.
Fault 06:PFC Over Curr
PFC current is higher than the maximum
current.
Contact service personnel.
Fault 07:Over Temperature
The temperature in UPS is higher than
85°C. At this time, the UPS is off.
Check if the ambient temperature is over
specification.
Or contact service personnel.
Fault 08:Batt SCR Short
Battery SCR is short circuited.
Contact service personnel.
Fault 11:Inv Start Fail
Inverter voltage cannot reach desired
voltage within specified time.
Turn off UPS and then restart it. If it fails
again, contact service personnel.
Fault 12:Inv Volt High
Inverter voltage is too high.
Contact service personnel.
Fault 13:Inv Volt Low
Inverter voltage is too low.
Contact service personnel.
Fault 14:Inv Short R
R phase inverter output is short circuited
Contact service personnel.
Fault 15:Inv Short S
S phase inverter output is short circuited
Contact service personnel.
Fault 16:Inv Short T
T phase inverter output is short circuited
Contact service personnel.
Fault 17:Inv Short RS
R-S inverter output is short circuited
Contact service personnel.
Fault 18:Inv Short ST
S-T inverter output is short circuited
Contact service personnel.
Fault 19:Inv Short TR
T-R inverter output is short circuited
Contact service personnel.
Fault 1A:Nega Power R
R phase inverter output negative power
is beyond the range.
Contact service personnel.
Fault 1B:Nega Power S
S phase inverter Output Negative Power
is beyond the range.
Contact service personnel.
Fault 1C:Nega Power T
T phase inverter Output Negative Power
is beyond the range.
Contact service personnel.
Fault 21:Inv STS Open
Inverter relay or STS is open.
Contact service personnel.
Fault 22:Inv STS Short
Inverter relay or STS is short circuited.
Contact service personnel.
Fault 23:Op STS Open
Output relay or STS is open.
Contact service personnel.
Fault 24:Op STS Short
Output relay or STS is short circuited.
Contact service personnel.
Fault 25:Wiring Fail
The wiring is wrong.
Contact service personnel.
Fault 26:Bat Fuse Open
Battery fuse is broken.
Contact service personnel.
Fault 27:Charge Short
The battery is short circuited.
Contact service personnel.
Fault 31:Para Comm Fail
The communication between UPS
modules is interrupted.
Contact service personnel.
Fault 32:Host Line Fail
The host line between UPS modules
fails.
Contact service personnel.
Fault 33:OP Curr Unbal
The load share line between UPS
Contact service personnel.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
6. Troubleshooting
Most of the fault and warnings need to be released by authorized service personnel. Few of them
can be solved by users themselves.
75
modules fails.
Fault 34:Ver Incompat
The firmware version between UPS
modules is incompatible.
Contact service personnel.
Fault 41:DSP Comm Fail
The internal communication in UPS
module is interrupted.
Contact service personnel.
Fault 42:Over load
Heavy overload causes UPS fault.
Reduce some load.
Fault 43:Charger Fail
Battery polarity is connected reversely or
charger voltage is abnormal.
Contact service personnel.
Fault 44:Model Fault
UPS model is not able to identify.
Contact service personnel.
Fault 45:Mcu Comm Fail
As stated.
Contact service personnel.
Fault 46:CT Satiation
Load current sensor is abnormal.
Contact service personnel.
Fault 47:Fan Fault
The two fans are stuck or broken.
Make sure fans work well when UPS is
working.
Warning 01:BatLow
Battery voltage is low.
Charge the battery when the mains is
normal.
Warning 02:BatOpen
Battery is not connected.
1. Check battery breaker status.
2. Check if the battery connection is
well connected.
3. Check the setting of Nominal Battery
voltage.
4. Contact service personnel if
necessary
Warning 03:BatPhaseLoss
The voltage between positive and
negative battery is different.
Check the battery connection.
Warning 04:LineIpNLoss
Neutral loss
Check if the Neutral connection is well
and contact service personnel.
Warning 05:LinePhaseError
As stated.
Check if the Mains phase sequence is
correct and contact service personnel.
Warning 06:LineVoltError
As stated.
Check if the input wiring is correct or
contact service personnel
Warning 07:LinePhaseFail
As stated.
Contact service personnel
Warning 08:OverCharge
Battery voltage is too high.
Check the setting of Nominal Battery
voltage and contact service personnel.
Warning 09:ChgFail
Battery voltage is detected as low level.
However, the charge is able to work.
Contact service personnel.
Warning 0A:OverTemp
The temperature in UPS is higher than
75°C. At this time, the UPS is still
running.
Check if the ambient temperature is over
specification.
Or contact service personnel.
Warning 0B:PFCCurUnbal
PFC current is unbalance.
Contact service personnel
Warning 0C:FanError
Fan error.
Check if the fan is blocked or contact
service personnel.
Warning 0D:LineFuseOpen
Fuse is broken.
Turn off UPS and replace a good one with
the broken one. If UPS fails again after
you do this, contact the service
personnel.
Warning 0E:IICEepromFail
EEPROM operation error
Contact service personnel.
Warning 11:BypassIpNLoss
Neutral loss.
Check if the Neutral connection is well
and contact service personnel.
Warning 12:BpsPhaseError
Bypass phase error.
Check if the Bypass phase sequence is
correct and contact service personnel.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
76
Warning 13:BpsVoltError
Bypass voltage error.
Check the wiring or contact service
personnel
Warning 14:BpsPhaseFail
As stated.
Contact service personnel
Warning 15:OverLoad
In line mode, the connected devices are
demanding more power than the UPS
can supply.
Reduce some load and check output
Load-Capacity in specification.
Warning 16:OverLoadLock
The connected devices are demanding
more power than the UPS can supply.
UPS will transfer to bypass mode from
line mode.
Reduce some load and check output
Load-Capacity in specification.
Warning 17:EpoActive
Check the EPO connector.
Check if the connector is loose when EPO
acts abnormally.
Warning 18:MaintainOpen
The UPS is in maintenance mode.
Check if the 2-pin plate is not connected
to EMBS connector on the back panel of
communication module when it acts
abnormally.
Warning 19:LineDiff
Each module gets different line voltage
when they are in parallel.
Contact service personnel.
Warning 1A:BypassDiff
Each module gets different bypass
voltage when they are in parallel.
Contact service personnel.
Warning 1B:InvCurUnbal
As stated.
Contact service personnel.
Warning1C:BpsUnstable
UPS switches between bypass mode and
standby mode five times in 30 minutes
due to abnormal utility.
Contact service personnel.
Warning 1D:RedundancyFail
As stated.
Check if redundancy setting is correct or
not. Then, contact service personnel.
Warning! Battery Age Alert
Battery life is expired.
Check if the battery has been used over
its service age. Or contact service
personnel.
Warning! Dry Contact Input
Alarm 1
As stated.
Remove the node
Warning! Dry Contact Input
Alarm 2
As stated.
Remove the node
Warning! Control Module
SPS 1 Fault
As stated.
Contact service personnel.
Warning! Control Module
SPS 2 Fault
As stated.
Contact service personnel.
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
77
7. Service
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
This chapter introduces how to replace the UPS module.
Warning:
1. Only the customer service engineers can do this service.
2. Remove the UPS modules from top to bottom, so as to prevent cabinet from toppling due to
high center of gravity.
7.1
UPS module replacement
Warning:
Confirm UPS is in Line mode or Bypass mode.
Confirm at least one UPS module remains in the UPS cabinet after one UPS module is
removed.
If all UPS modules have to be removed, the replacement MUST be under Maintenance Bypass
Operation Mode.
1. The ALARM LED (RED) is lit on the UPS module to indicate the UPS module output is off and
disconnected from UPS system.
2. Use a screwdriver to remove the four screws from fixing holes.
3. Two people pull out together and remove the UPS module from its slot together.
4. After servicing the module, push the module into the cabinet and tighten the screws on both
sides. If there are more than one UPS module to re-install, please wait 30-second before
installing another module.
5. The re-installed UPS module will be turned on automatically when UPS is in line mode.
78
8. Specifications
Item
Normative reference
Uninterruptible power systems (UPS) –Part 1:
General and safety requirements for UPS
IEC/EN62040-1
Electromagnetic compatibility (EMC) requirements
for UPS
FCC 47 CFR15, Subpart B
Method of specifying the performance and test
requirements of UPS
IEC/EN62040-3
Notes:
ESD
IEC/EN 61000-4-2 Level 3
RS
IEC/EN 61000-4-3 Level 3
EFT
IEC/EN 61000-4-4 Level 3
Surge
IEC/EN 61000-4-5 Level 3
CS
IEC/EN 61000-4-6 Level 3
Power-Frequency Magnetic field
IEC/EN 61000-4-8 Level 3
Low Frequency Signals
IEC/EN 61000-2-2 Level 10V
Conduction
IEC/EN62040-2 Category C3
Radiation
IEC/EN62040-2 Category C3
Item
Unit
Specifications
Noise within 1 m
dB
Max. 60
Altitude
m
≤1000, derate power by 1% per 100m between 1000m and
2000m
Relative humidity
% RH
0 ~ 95, non-condensing
Operating temperature
°C
0 ~ 40°C
(Output capacity will be derated when temperature is over
30°C. It will be derated to 90% at 35°C and 80% at 40°C.
Storage and
transportation
temperature for UPS
°C
-15 ~ 60
Keatec RTM Series Modular Onlne UPS 208-120Vac 2PH-2PH User Guide English 20180109
The chapter states the specifications of UPS.
8.1 Conformity and Standards
The UPS has been designed to conform to the European and international standards listed in