22
*Nt LED1
Set the night keep-open time. The standard hold time is 7 seconds. The adjustable range is 0-30
seconds. It is selected via switch lock and is independent of the program switch.
Notice:
1.The standard settings are validated upon the first commission of the door.
2.If the reset is made after adjustments have been changed on the 2
nd
level, the speed of open and
close and the keep open time will be reset to the standard val ue.
3. If after a RESET, the speed of open and close and opening width will be reset. The soft switch
should be set to ON position (Refer to 5.2.3, the 3
rd
level)
5.2.3 Programming function
The control unit through PSA can set the special functions under different occasions. The
setting value remains unchanged under the reset or power failure.
Programming process : (How to select?)
1. When the Program/Selection button turns to the lock-up ( LED1), press the SET button
more than 2 seconds until the LED light is red.
2. Input , access the 3
rd
level
(If the time of the fault code or time beyond 10 seconds, PSA will returns to the 1
st
level.
If want to set, please repeat it.
3. After LED ERROR switch off, display the soft switch 1.
4. Press button or button to select the required soft switch number. The soft
switch numbers are displayed on the PSA control panel by 1/2/4/8/16. The status of this
switch is displayed
Example: LED16/4/1 are lit 16+4+1 soft switch number 21
5. Switch over the status of the soft switch by pressing the key simultaneously or the button
SET.
LED ON soft switch on
LED OFF soft switch off
6. With & button, reset the soft switch to 0 ( No LED is lit)
7. Return to the 1
st
level by pressing the SET button (Return to level 1 automatically if the
PSA is not operated)
Switch No. Function LED32 Remark
0 Exit from level 3 to level 1
1 One-way mode, the door is lock;
One-way mode, the door is unlock
ON
2 Light output on terminal 24;
Alarm output on terminal 24
ON
3 Gong on terminal 23;
Inter-lock on terminal 23
ON *
4 The control unit is passive locked;
The control unit is active locked
ON *
5 Emergency close terminal 12;
Emergency open terminal12
ON
6 Full function battery-powered mode ON