KBB KS1000 Assembly And Operating Instructions Manual

Sliding door drive unit
KS1000
Assembly-and operating instructions
KBB Automated Entrances Inc.
ООО "АВТОМАТИКА"
http://avtomatika.ooo/
KS1000 Assembly-and operating instructions
1. Summary
1 Instruction of this manual--------------------------------------------------------------------3 11 Product Description---------------------------------------------------------------------------3 12 Application area----------------------------------------------------- ---------------------------5 13 Technical parameters--------------------------------------------------------------------------5 14 Security----------------------------------------------------------------------------------------- 5
2. Basic Assembly
2.1 Assembly types ----------------------------------------------------------------------------------- 6
2.2.Assembly instruction -----------------------------------------------------------------------------7
3. Components Installation
31 Installation of running carriage subassembly --------------------------------------------- 11 32 Installation of drive Unit--------------------------------------------------------------------- 14 33 Installation of reverse wheels------------------------------------------------------------ ---- 14 34 Installation of toothed belt----------------------------------------------------------- ------ 15 35 Installation of control unit-------------------------------------------------------------------- 16 36 Installation of control elements--------------------------------------------------------------16
4. Adjustment 41 Preparation before operation------------------------------------------------------------------17 42 Electrical settings-------------------------------------------------------------------------------17 43 System start-up----------------------------------------------------------------------------------18 44 Interruption of self-inspection-----------------------------------------------------------------18
Functions of operating device
51 General--------------------------------------------------------------------------------------------19 52 PSA controller(Option)---------------------------------------------------------------------19
521 Operating Functions1
st
level)---------------------------------------------------19
522 Setting functions2
nd
level------------------------------------------------------ 20
523 Programming function(3
rd
level)----------------------------------------------- -----21
524 problem indication4
th
level)-----------------------------------------------------26
53 Security Device------------------------------------------------ --------------------------------29 54 Main input & output terminal functions----------------------------------------------------29 55 Interlock functions-------------------------------------------------- ---------------------------30 56 Attention details--------------------------------------------------------------------------------31
3 3 5 5 5
6 7
11 14 14 15 16 16
17 17 18 18
19 19 19 20 21 26 29 29 30 31
6. Maintenance and troubleshooting
61 Security and guarantee----------------------------------------------------------------------------33 62 Maintenance--------------------------------------------------------------------------------------33 63 Trouble shooting---------------------------------------------------------------------- -----------33 64 KS1000 spare parts list--------------------------------------------------------------------------34 65 Environment protection treatment--------------------------------------------------------------35
Appendix
Appendix1Drive case installation--------------------------------------------------------------------36 Appendix2: T wo-wing Doors installation--------------------------------------------------------------37 Appendix3: Left-opening door Installation ------------------------------------------------------------38 Appendix4: Right-opening door Installation-----------------------------------------------------------39 Appendix5: Wire connection drawing of control unit------------------------------------------------ 40 Appendix6: Wire drawing of Battery electronic-mechanical lock-----------------------------------41 Appendix7: Wire drawing of start-up signal -----------------------------------------------------------42
Advice
<<Assembly and Operating instructions>> defines not only the responsibilities of quality guarantee between KBB and Users, but also the stipulation of generating and ceasing right & obligation in after-sales service respect. Please seriously read <<Assembly and Operating instructions>> before applying to KBB products
33 33 33 34 35
36 37 38 39 40 41 42
1. Summary 11 Instruction of this manual
z The manual offers instructions for the installation, adjustment, the maintenance, and
troubleshooting.
z The manual is just for professional persons from Metal construction and electronic
technology
z The manual includes the instruction to main components and all specifications of KS1000
sliding door
z The instructions for optional device are included in the deliveries of optional device of
KS1000 Sliding door drive Unit.
z Uses the following signs as important mark of certain dangers and significant explanation
Warning:
Be danger to the life and limb
Attention
Could cause components to be damaged or malfunction
Notes
Clues that facilitate the work
z KBB keep the right to modify its products. If some modification is done, we will not inform
users about it
z All dimensions unit without label are “ mm”
12 Product Description
Sliding door drive unit use modular design, including DC motor, microprocessor control unit, control panel, individual module, and optional components that required in the order. The drive unit is connected with an electronic cable. The structure of sliding door drive unit sees below:
1 Carrier profile 2Running gear 3Drive unit Figure 1.1 Section drawing of installing drive unit
A Overall length of guide way profile LW Valid passage width Figure 1.2 Installation drawing of door leaves
CE
3
4
6
5
8
7
1 Carriage profile 2 Running gear 3 Drive unit 4 Control unit 5 Electron-mechanic lock 6 Spare battery 7 Dentiform belt 8 Reverse wheel
9 Hinge-shape covering CE Closing point
Figure 1.3 Spare parts distributing drawing inside drive unit
13 Application area
Type Specification Net passage width
Max.weight /sliding door
Max.speed
according to
weight of door
Single wing left or right opening
107..115 700-1500mm 140kg 0.45-0.65m/s
Double wings 208..230 800-3000mm 90k g 0.45-0.65m/s
Two-wings double drive door
210..230 1000-3000mm 140k g 0.45-0.65m/s
Two-wings telescopic door (Left or right opening
211..230 1100-3000mm 90k g 0.45-0.65m/s
Four-wings telescopic
door
414..440 1400-4000mm 60k g 0.45-0.65m/s
Four- wings double
drive telescopic door
419..440 1900-4000mm 90k g 0.45-0.65m/s
14 T e chnical parameters
The socket and main cable supplied by user 220V+
10%50/60Hz10A Power consumption 200W Max driving power(static) 150N In case of power failure, the spare battery guarantees full operation for: 30min Temperature of working environment -30 ~ +50 The product only is used in dry rooms Max relative humidity90% Protection level IP23
1 5 Security
Once a sliding door is applied, the max. opening and closing speeds are automatically adjusted depending on the wing weight. Therefore, the do or users are not necessary to do any presetting
The entire security device has to be checked to ensure their faultless functions
Attention: The application limits of KS1000 sliding drive unit are defined in the sales documents.
Any application beyond the limits is not allowed.
2. Basic Assembly
21 Assembly Types
There are 6 assembly types available. A The assembly of lintel that made up of carrier profile and supporting profile.
B Lintel assembly with angle.
C Hanging assembly of steel board structure.
D Hanging assembly in corner
E Hanging on ceiling assembly in corner
F Hanging on Ceiling assembly with steel tube
22 Assembly
Assembly closing point CE determining the assembly position of the carrier profile Double winged sliding door
Single-winged sliding door The assembly way of opening from the right.mirror image for version when opening from the left
A Min. carrier profile length (2+LW+100) XY Possible over-length of carrier profile LW valid passage width CE Closing edge The following description is assembly example for double winged sliding door systems. It describes the assembly process of supporting frame and carrier profile. Other types of systems are assembled as the same on CE basis.
Assembly carrier profile
1Mark out the closing point CE on the carrier profile. Place the carrier frame on the floor and
use gradienter to adjust the level and mark out the water level line UK
CE Closing edge UK water level line that cause from the joint of carrier profile’ bottom edge and flatness
floor
LH Headroom
Gradiente
r
T
y
p
e
A
:
L
H
-
1
0
T
y
p
e
B
:
L
H
+
2
0
T
y
p
e
B
=
4
9
CE
Flat rule
r
X
T
y
p
e
A
=
1
3
5
I Magnified drawing
Meter elevation
2According to the following data, mark out the line L.
Assemble type A: LH-10 Assemble type B LH+20
3Draw the lower assembly edge of carrier profile 4Draw the vertical line of L line through the two centers of long-round holes at both ends of
carrier profile, and mark out the intersection point Q
Magnified drawing
Type A=135
Type B= 49
Type A:LH -10
TypeB: LH+10
Gradienter
Flat ruler
Attention: Horizontal deviation <1mm/m
10
CE
水平
平尺
5Drill the mounting holes for screws M8. 6Use screws and thinner washer to fix supporting profile (with type A) and carrier profile (with
style B). Notice to align the lower assembly edge M with closing point CE.
NoteAfter installation of carrier profile, install the running carriage set on carrier profile, and then put two blocks at two ends of carrier profile to prevent running carriage
set from sliding out.
承重梁
7Drill the other holes 8Assemble other fixing screws 9When assembling supporting profile(taking assembly type A as Example), hang the carrier
profile into supporting profile; adjust mounting holes and screw down using the screws (one screw every 400mm)M8X20 and washers
Gradiente
Flat ruler
(Carrier Profile)
Attention: Maximum difference between closing point and M point is not more than 2mm
11
3.Components Installation
31 Installation of running carriage set
The basic set of running carriage includes:
Running carriage set 2 sets Stop piece 1set Wiper brush 2sets Belt nip 1set
311 Assembling the running carriage
1Fix the wiper brush (4) on the outside of outer running carriage set by using the cheese head
screw M6x6 and washer
2According to the actual situation, select the required number running carriage sets(2) to insert
the carrier profile (1) from the side. If insufficient lateral space, loose the screw.(3), and rotate running carriage sets to the right position from the front
Figure 3.1
312 Assemble the stop piece on running carriage
Please fix the stop piece(5) on the running carriage sets(2) by using the cheese-head screw
M6X10 and washer. See Figure 3.2 & Figure 3.3.
Figure 3.2 Double-winged Sliding doors
12
Single-winged sliding door
CE
CE
Figure3.3
313 Installation of the sliding wings
1On the running carriage screwed the sliding wings.
2After completing the installation of the sliding wings, we should check the flexibility of the
counter-pressure roller (6) to make sure that the counter –pressure roller can be pushed manually, when running carriage (2) is shifted, the pressure ruler (6) must be able to stop.
3Adjust counter- pressure roller(6): slightly loose the Screw(7) about 1/2 circle, push the
screw along the slanting slots until the right position, and then screw it down. See Figure 3.4
Figure 3.4
314 The installation of stop piece on the carrier profile
3141 Double-winged sliding door
CE
Figure 3.5
Each stop piece (25) include 2 pieces inner hexagon screw
Attention: For both winged sliding door, when sliding sings closed, the stop pieces must touch
at the closing point CE (The closing pressure applied on the sliding wings must not exceed a maximum value of 80N) For both winged sliding door, when sliding sings closed, the stop pieces must touch at the closing point CE (The closing pressure applied on the sliding wings must not exceed a maximum value of 80N)
13
2 pieces washer 2 pieces M6 square nut Fix the stop pieces on the carrier profile directly. See Figure3.5
3142 Single-winged sliding door Open the door to right side(See Figure 3.6). Mirror –image for version opening to the left.
Figure 3.6 The stop piece (5-A) and the cross stop piece (8) include the following components: 2 pieces cheese-head screws 2 pieces washer 2 pieces M6 square nut. Fix the stop pieces on the carrier profile directly. See Figure3.6
315 The installation of belt driver
The sketch map of double-winged sliding door installation:
2 Running carriage sets 9 Belt driver 10 Fastening screw
Figure 3.7
The sketch map of single-winged sliding door installation: (next page)
Attention: When the door closing, the stop piece(5) and the stop piece(8) must touch. The
closing pressure on the sliding wings must not exceed a maximum value of 80N
14
Figure 3.8
According to different assembly types, , tentatively fix the belt driver onto the running carriage
set(2) by using the component (10) ( including 2 pieces cheese-head screws M6x10 and 2 piecesφ6 washers) . The final installation is made after adjusting the door center.
32 The installation of drive unit.
1
14
11
18
12
注意:
在使用两块驱动板时,请将4根跳线打开。
Caution!
For redundant drive units,remo ve all
4 jumps on the power board!
注意: 在维修和更换保险前,请拔掉电源线。 Caution! Remove power cord before sercice and
fuse replacement。
100 2AT
50/60
230
电压
零件号
保险
功率
频率
序列号
跳线帽
跳线
保险 2AT
注意: 仅限在干燥环境下使用, 请不要在工作时打开驱动器盖。 Caution! Only for dry rooms, Do not disconnect and plug in the internal connections and plug connection while they are carrying voltage。
13
16/17
15
PN01231055
Figure 3.9
Refer to the figure 3.9, and mark out measure “C” on the carrier profile.
1.Insert square nuts into T groove.
2.Fasten the drive unit (12) on measure point “C” of the carrier profile with inner hexagon screws and washer
3.Connect the cable (13) towards the groove (14), insert the line cable(15) into the groove from
the side, and then fasten the cable.
4. After assembly of the control unit, connect the cables (16) and (17).
Note: The groove(14) is applied to mount outer cables and control components, such as PSA. Prior to fix the cable, install the components. The groove(18) is applied to
in-house connect battery control panel of control unit.
33 The installation of the reverse wheel
Assembly position of the reverse wheel in the carrier profile is shown in appendix.
1.Insert nut into “T” groove
Attention: Prior to fixing the driver unit on the carriage profile, check if the four cables are
plugged into the control panel.
15
2. Te ntatively fix the reverse wheel(19) on the carrier profile(1) with inner hexagon screw and
washer.
The final assembly is carried out after the toothed belt has been in position. See Figure3.10
Figure 3.10
34 Installation of the toothed belt
1According to the attached drawing, determine the length "D” of toothed belt.
Figure 3.11 2Slightly loosen the fasten screws 3Insert toothed bel t(21) ends each with 3 teeth into belt clip (22) 4Tighten the screw(20) Fig. 3.11 5Place the toothed belt onto the drive pulley and the reverse wheel
Figure 3.12
6Push the reverse wheel(19) outwards until toothed belt(21) lies flat. Tighten the screws
slightly(23)
7Use a hammer to knock reverse wheel(19) until the dentiform belt has the following tension
See Fig. 3.13
16
Figure 3.13
8Tighten fastening screw(23)
Setting the door Center( Take the double-winged door as example) When adjusting, belt-clip (9) must not be tightened. 1Push the sliding wings(24) until distances A and B are the same. If adjusting is insufficient ,
check the belt lengths or dimension C. See the drawing Figure 3.14 in appendix.
Figure 3.14
2Tighten the belt clip.
35 The installation of the control unit
Assembly position in the carrier profile. See the drawing in appendix
Attention: Take care when tightening the toothed belt (21). If insufficient and excessive
tension of the toothed belt increases the wear and causes noise during the operation.
Attention: Checking the door “open” stop pieces. In the open position , the sliding wing(24)
must touch the two stop pieces at the same time.
Attention: If the installation is equipped with locking combination parts and spare battery, this
unit must be installed before the control is mounted
17
Figure 3.15
1Insert nuts(11) in “T” groove.
2. Fasten the control unit (25) onto the carrier profile with inner hexagon screws and washer.
Tight en the screws
3. Connect the cable of drive unit (26)
36 The installation of control panel PSA
The location of control panel is determined by the actual installation project. The position of inlet
box and connecting cable is determined by the requirement of customers.
1According to the wire diagram of the control unit, connect cable plugs to the control panel
(terminals 25/26) The shielding must be fastened to the control unit.
2Connect the cable(30) to the PSA panel (terminals 1/2). The shielding must be fastened to
PSA metal parts.
So
1632
Rst
SET
PN01231063
W
4
2
Ht
Sc
8
Nt
1
ERR
PSA lock
1To lock PSA , dismantle strap of PSA panel. 2Concrete operation process: See chapter 5.
4. Adjustment
Attention: Max length of the connecting cable is 50m. A shielded plug must be used
18
41 Preparation before operation
All KS1000 basic components and optional parts have been fixed and arranged .
All cables are ready for using.
Any additional control and security units have been fixed and connected
42 Electrical Settings
No preliminary settings can be made before the first application.( Stop pieces must be fixed as requirement). The running distance , the maximum permission speed , and maximum force are set automatically during the set-up(reset) process of drive unit.
Setting-up procedure
The setting-up procedure is implemented when the drive unit is taken in the operation for the first
time or after a reset.
z During the first operation, all the values on the second level are reset to standard. After the
door has already been in operation, reset is made with “Reset” switch(Figure 5.1) or PSA( Figure 5.2.2)
z If the door weight exceeds approx .10kg, all the values on the second level remain
memorized after a power failure accident. It means that no setting-up procedure is needed.
z A RESET will not influence the value of any third level
Function of setting up procedure:
z Test all the hardware components of the control unit. z Check all the connected components(PSA panel, electro-mechanical lock, battery board) The
door closes as far as the “closed” position with a set-up speed of 0.07m/s
z When the program selector is set in the locking position, sliding door is locked and remains
such status. In all the other programmed positions, the opening signal is effected automatically.
z The sliding door opens with a set-up speed of 0.075m/s as far as the “open” position。During
opening process, the lock is checked and average friction is determined.
z A short-time acceleration of wing checks the quality of the door. The quality determined the
maximum permission speed.
Total wing weight (KG) Maximum opening
speed m/s
25-125 0.65
125-160 0.55
>160 0.4
The closing speed is 66% of the maximum opening speed
Attention: If there are no light barriers fitted, two wire links must be connected at the
corresponding terminals according to the connection diagram of control unit.
Attention: For the single- winged door opening to right: soft switch 12 must to be set to ON
19
4.3 System Start-up
1. Being the sliding wings into the center position
2. Plug in the power plug
3. On KS1000 control board, LEDS 5V/24V and POWER are lit
4. With PSA, LED 32 flashes approx.5 seconds after plug-in. The installation set its up and
remains open. LED 32 operating function manual is lit. If another LED is lit along with the flashing LED 32, then the corresponding operating function is set.
4.4Interruption of self -inspection
The setting up procedure can be interrupted by the following things:
Program switch or PSA is on a locked operating position (lock/one way)
The door closes and remains. The setting up procedure can be completed on ly after a valid opening command(key), or after selecting another operating function. E.g.” automatic” with PSA: LED32 flashes and LED 1” lock” or LED2 “one way” is lit. SEE chapter 5.2.1 for setting the operation functions.
When setting up, the door opens first: Check the assembly position of the belt joint
as per the attached drawing
The sliding door does not move: No light barrier or no strap fitted. For PSA, red error LED flashes along with red LED. See chapter 5.2.4 KS1000 motor driver unit: safety problem.
5
Control unit and PSA control panel (Optional)
5.1 General
KS1000 drive unit can be operated as follows:
5.1.1Adopt PSA control panel or Program/ Selection switch (Standard)
When selecting the Program/Selection switch, input 21, 22 have four positions for your selection: lock-up, one-way, full-open (Automatic), partial open (Automatic), (refer to chapter 5.4 Inputs).
Reset via inputs 25,26 (Press for 2 seconds at least).
PSA can be used as a temporary programming unit for function selection or fault code analysis stated in chapter 5.2.2, 5.2.3. Upon moving the PSA, restart the power switch to preserve the programming values.
5.1.2 PSA control board (Optional) The inputs 25,26 connecting PSA will realize the functions of the sliding door, PSA functions could be locked by the following mode:
1. Connect one switch (i.e.: switch lock) to the inputs 3/4 of the PSA (Refer to chapter 3.7).
2. Apply soft switch No.9 (Refer to 5.2.3) to make PSA control lock effective. An operation is
only possible after entering the code , after one minute without operation, the PSA resumes the locked states.
5.2 PSA control unit (Optional)
All the functions can be identified and set by the PSA control panel. The Number of the LED’s on
20
the front board corresponds to their binary value. The soft switch and the related error number are obtained by adding the numbers next to the lit LED’s. Examples: The lit LED’s 16/4/1 16+4+1=21 soft switch/error code 21 Communication between control unit and PSA control panel are fail-safe and tamper-proof via a modern bus system (Two wire line).
There are four levels in PSA 1
st
level Operation functions
2
nd
level Setting functions
3
rd
level Program functions. At this level, settings can only be made by professional exp ert
4
th
level Malfunction indication functions
5.2.1 Operation (1
st
level)
1.The operation function sign appears above the LED of the PSA control panel.
2. The operation functions selected are indicated by the related LED
3. button, and button can be used for selecting the program. The LED will be effective upon 2 seconds. The following is the meaning of signs
Manual operation LED32 The door is at a standstill, the leaf is released and can be moved manually.
Keep open LED 16 The door opens and remains.
Full open (Automatic) LED8 The door is not locked. When it is actuated, the door will be opened automatically.
Partial open (Automatic) LED4 When the door is actuated, the open width reduced; the others remain as the “Full open” please refers to the settings.
21
One-way in/out One-way traffic. The door is locked (Standard), only the inside sensor will effectively actuate the door to open.
Night LED1 The door is locked. Only the switch lock can effectively actuate the signal to open the door. The inside sensor is effective when only the door doesn’t close.
Setting the half open:
1. Select the partial open LED4. Upon 2 seconds, the required function can be set in the following position:
Keep open LED16 The door is half open. One-way in/out LED2 The door is half open under the inner sensor influence Lock-up LED1 The door is half- open by the switch lock
2. Select the full open LED8 to restore the full open. Other program switch refers to 5.4
5.2.2 Setting functions (Second Level) The abbreviation of the setting functions is displayed under the LED of the PSA panel. Press button or button to select the related function. Press the SET button to actuate the related function. The flashing frequency is an indication of the regulated value (High frequency=high speed/short keep –open time) The button or button is also used to modify the set value ( means quicker or longer, means slower or shorter) Press the button SET or more than 1minute on the PSA without any operation, the system resumes the 1
st
level.
*Rst(reset) LED 32 The door is started and set up (Chapter 4.2), when pressing RESET button under the battery-powered mode, the drive unit stops and the control unit is shut off. *So LED 16 Set the opening speed. The standard velocity is 100%( it is set when diagnosing), the velocity adjustable range is: 40-100% of standard velocity *Sc LED 8 Set the closing speed. The max speed is 66% of the standard velocity. The velocity adjustable range is: 25-66% of the standard velocity *W LED4 Set the width of half open. The standard width is 65% of full opening width. It is adjustable within 25-90% of full opening width. *Ht LED2 Set the hold- open time. The standard hold time is 2 seconds. The adjustable range is 0-10 seconds. It is selected via the inside/outside opening contacts, the infrared light detectors LS1/LS2 and is independent of the program switch position.
22
*Nt LED1 Set the night keep-open time. The standard hold time is 7 seconds. The adjustable range is 0-30 seconds. It is selected via switch lock and is independent of the program switch.
Notice:
1.The standard settings are validated upon the first commission of the door.
2.If the reset is made after adjustments have been changed on the 2
nd
level, the speed of open and
close and the keep open time will be reset to the standard val ue.
3. If after a RESET, the speed of open and close and opening width will be reset. The soft switch
should be set to ON position (Refer to 5.2.3, the 3
rd
level)
5.2.3 Programming function The control unit through PSA can set the special functions under different occasions. The
setting value remains unchanged under the reset or power failure.
Programming process : (How to select?)
1. When the Program/Selection button turns to the lock-up ( LED1), press the SET button
more than 2 seconds until the LED light is red.
2. Input , access the 3
rd
level
(If the time of the fault code or time beyond 10 seconds, PSA will returns to the 1
st
level.
If want to set, please repeat it.
3. After LED ERROR switch off, display the soft switch 1.
4. Press button or button to select the required soft switch number. The soft
switch numbers are displayed on the PSA control panel by 1/2/4/8/16. The status of this switch is displayed
Example: LED16/4/1 are lit 16+4+1 soft switch number 21
5. Switch over the status of the soft switch by pressing the key simultaneously or the button
SET. LED ON soft switch on LED OFF soft switch off
6. With & button, reset the soft switch to 0 ( No LED is lit)
7. Return to the 1
st
level by pressing the SET button (Return to level 1 automatically if the PSA is not operated) Switch No. Function LED32 Remark 0 Exit from level 3 to level 1 1 One-way mode, the door is lock;
One-way mode, the door is unlock
ON
2 Light output on terminal 24;
Alarm output on terminal 24
ON
3 Gong on terminal 23;
Inter-lock on terminal 23
ON *
4 The control unit is passive locked;
The control unit is active locked
ON *
5 Emergency close terminal 12;
Emergency open terminal12
ON
6 Full function battery-powered mode ON
23
Only one open or close
7 Power failure open only,
Power failure close only
ON
8 Standard reduced distance
About 180mm reduced distance on opening position
ON
9 PSA code lock off
PSA code lock on
ON
10 Keep open time (standard)
Keep open time direct closure
ON
11 Winter/ Summer actuation off
Winter/Summer actuation on
ON
12 Drive unit 1 (Rotation direction
normal) Drive unit 1 ( Anti-rotation direction normal)
ON R
13 Drive unit2 (Rotation direction
normal) Drive unit2 (Anti-direction normal)
NO R
14 Adaptor connected to batteries
Adaptor connected to the emergency power
ON
15 All switch restores to default
Retain changed values
ON R
16 Interlock, impulse the memorized
Interlock, impulse the non­memorized
ON
17 Test program off
T est program on
ON
18 After reset retain set value (level 2) ON 21 The batteries mode off at lock position
The batteries mode on at lock position
ON
22 Last battery-action mode on “OFF” at
lock position. Last battery-action mode on" ON" at lock position
ON
27 Standard brake distance
When the door opens, the brake distance is 150mm
ON
28 Floor lock not applied
Floor lock applied
ON
30 Emergency-input terminal 12 standard
mode Emergency-input terminal 12 emergency- stop
ON
24
31 Closing hindrance standard
Closing hindrance special
ON
Default, corresponds to the standard setting, LED32 not lit.
This setting is reset after a RESET (standard) * The selection applies to the standard lock. R Only active after RESET
No.1 One-way operation
In the lock-up position, the door is locked.
In the lock-up position, the door is unlocked.
No.2 Light output on terminal 24
In the position lock-up of the program switch, all the control elements trigger an impulse
during 60 seconds on this output.
Alarm output on terminal 24
This output is actuated if an error is detected (Refer to chapter 5.2.4), The output is activated
until the error has been eliminated.
No.3 Gong on terminal 23
If the infrared light detector LS1 is cut, this output is actuated for an impulse lasting for 1
second at the interval of 0.5 second.
Interlock input/output on the terminal 23
For standard interlock refer to chapter 5.5
No.4 Standard interlock
Master lock: When require interlocking, one sliding door( normally the inside one) has to be defined as master control system. Under this circumstance, the two soft switch No. 3 has to be set to ON.
No.5 Emergency- open instead of emergency-close
The setting is ON, the signal input of terminal 12 makes the sliding door emergency opened. The order makes the door leaf open the door at the set speed at any position & program/selection position. Emergency-open has the highest priority. i.e., higher than switch lock, manual emergency unlocking and interlock.
No.6 Full battery-powered emergency mode (OFF)
As soon as mains power failure occurs, the sliding door is automatically and without interruption switched to battery-powered emergency operation or to the back-up power network. The sliding functions have any restriction until the exhaustive discharge limit of the emergency battery has been reached. For the last action, please refer to the soft switch no.7.
Only open or close action (ON)
When the sliding door has been switched over to the emergency battery mode, one last opening or closing movement is carried out, depending on the soft switch No.7.
NO.7 Open or close in the event of a power failure (See soft switch No. ON) OFF
The sliding door is closed and locked at the lock-up position. The door is open at any other position. If the one-way in/out lock has been selected, and the door is open, the lock remains released.
25
ON
Door closes in all program switch positions, the control panel power is shut. Opening via wake-up. After each wake-up the door is closed. If the door is not yet closed, the above function applies after the exhaustive discharge limit the emergency battery has been reached.
No.8 Sliding distance OFF
Standard sliding distance
ON
When the open width is up to 180mm, the velocity will slow.
No.9 Active the PSA code lock, refer to chapter 5.1 ON PSA code lock is effective, instead of the switch lock. No.10 Keep open time OFF Keep- open time starts at the moment that the door reaches the open position and all start signal
don’t come into use.
ON Keep- open time starts at the moment that the start signal deactivates. Example, in an interlock
application, the door may reverse or close when fail to reach the opening poison, after the person has left the door area and provided that a short keep time. Under this circumstance, it is necessary to use direction-sensitive radars.
No.11 W inter/Summer
Winter/Summer actuation ON only makes sense for the sliding door, which is equipped with direction-sensitive radars. The reduced opening width is canceled when bi-directional traffic. ( i.e. radars inside and outside activated at the same time)
NO.12 Changing the direction of rotation of the drive unit 1 NO.13 Changing the direction of rotation of the drive unit 2. No.14 Battery –powered mode
Refer to option ( Battery instruction)
Battery-powered emergency mode
By means of soft switch No. 14, a fixed direct current (21-30V) powers the input (X13). The soft switch switches the charging electronics off, in order to prevent the current from flowing back into the power network. Differing from the battery mode, the operation is not interrupted in the Night of the program switch (No wake-up). However, the operation is interrupted if the voltage drops below 19.5V during the standstill respectively below 16.5V when the door is moving.
No.15 Reset function
Strictly speaking, the soft switch 15 is not a real soft switch, but to set the reset function to the soft switch lacking the default. If LED 32 is lit, which means that at least one soft switch No. (1….31) is set. Press the button at the same time, all the soft switch value is neglected, so the function has a general effect, it should be followed by a RESET.
No.16 Interlock impulse is memorized (Shut)
If the soft switch is ON, the start signal is memorized ( That is to say, only the opposite door has been closed, the above command will be memorized)
No.17 Test program
Start the test program (The control unit generates automatically open command), all the start signal is superior to the inner command. The reset operation will cause this function to be deleted.
26
No.18 After reset: value of 2nd level
If the soft switch is OFF, the velocity and the partial width will restore to the standard value (Refer to 5.2.2) If the soft switch is ON, the set value will be retained.
No.21 Battery mode in the lock-up position OFF
No emergency operation in the Lock-up position (the main power is switch off), except opening via key-operated switch Wake-up. ON (soft switch no.6 OFF) Battery powered emergency operate in the lock-up position to realize the emergency operation.
No.22 Lock function setting in the battery mode OFF
Standard lock function
ON
During the battery mode and in the lock-up position, if the soft switch is set to ON, the door will open when the battery power is exhausted ( Last action) In the battery mode and in the one-way lock position, the door will open and keep open( Uses as the last action)
No.27 Setting OFF
Standard reduced sliding distance
ON
Increase the sliding distance to around 150mm, applied to the heavy leaf and/or the small distance of the two walls.
No.28 Floor lock function ON
When the Program/Selection switch from the lock-up position to full open( Automatic), if the start signal exist at the same time, the door will open at a low speed within the range of 100mm, upon which the door continues to open normally. When in the Program/Selection switch position Lock-up, a switch lock signal is given, the door will open at the slow speed and with reduced force within the first 100mm.
No30. Emergency functions on terminal 12 OFF
The emergency open or emergency close depends on the soft switch 5.
ON
When the terminal 12 stops, the soft switch 5 lose its function. As soon as the emergency signal is actuated, the door will stop.
No.31 Closing hindrance standard
As soon as the leaf(s) meets any obstacle during the closing the motion, it(they) will be reversed. The movement is repeated until the obstacle has been removed and the leaf(s) are completely closed.
Closing hindrance special
The first four closing attempt is the same as the standard. When in the fifth attempt, the door switches to the open position. The fault code 31 will be displayed on the PSA. This situation will be corrected by the switch lock, emergency terminal 12 or PSA manually.
27
5.2.4. Malfunction indication (4th level)
In the event of a fault, the normal program position display is interrupted every 2 seconds for a duration of 1 second to display a red error code (LED ERR lights up together with error number the fault code. LED1/2/4/8/16) The error number will be obtained by adding the number of the red lit by LED light. Example: 2 seconds: LED 8 is lit= Full open automatic 1 second: red LED ERROR lights up together with LED8/4 8+4 = 12 fault code 12 If the last fault have been deleted, press the button SET, it can be displayed in the program/selection (Automatic) position (LED8). The next actuation of the button and button or without operation within 1 minute on the PSA, the PSA will resume to the 1
st
level. Fault code Fault Warning 1 Drive unit 1 defective F YES 2 Incorrectly connected plug to
adaptor X4
F YES
3 Drive unit 1 is obstructed
during the learning path smaller than 230mm
FE YES
4 The learning path on the drive
unit 1 greater than 9800mm
FE YES
5 Excessive friction on the drive
unit1 to cause the large travel resistance force.
FE YES
6 Drive unit 2 defective F YES 7 Drive unit 2 is obstructed
during the learning path smaller than 230mm
FE YES
8 The learning path on the
drive unit 2 greater than 9800mm
FE YES
9 Excessive friction on the drive
unit 2 to cause the large travel resistance force.
FE YES
10 Control unit is defective F YES 11 Short circuit 24V(External
connection or control unit)
K* NO
12 Lock monitor problem, the
path smaller than 38mm/lock monitor
F YES
13 Lock fault K YES 14 Error infrared light
detector( connection or
K YES
28
barrier)
15 Power interrupt, (emergency
battery mode)
K NO
16 Emergency battery is not
operative
K YES
17 Close position error K NO 18 Floor lock YES 20 Jumper on power-print not
plugged
E YES
31 Closing hindrance special F YES * The 24v power supply is switched off. E The error is only identified during the setting-up procedure F Fatal fault( The system is switched to manual) K Error message remain as long as the mode error is pending.
NO.1-10 Basic kinds (Fatal fault) will cause the system interrupt. No.11 It will cause the fatal fault during the adjusting. If occur the fault, th e power is switc hed off
for 10 seconds and switched on for 0.6 second to check if voltage is normal, if not, repeat the former action. No.12 Without the inside position and lock position monitor: three attempts with reset, then display the error.
With lock position monitor: The error will display as soon as it is checked.
No.13 Error can be checked only equipped with the inside po sition monitor and lock program position
No.14
Error can be checked in the open position. If in the lock program position, the door will close at slow speed upon 8 seconds, even if the fault remains. No.15 Under the emergency battery-powered, the display will keep until the battery is exhausted. ( Example: lock-up program position)
No.16 Fault exists in adaptor, cable, safe and battery. No.17 Display the door to be pushed off the closing position. For example, the installation center
seam is sealed, and checks the vehicle or the adjustment of the net width.
No.18 The floor lock fails to open. No.31 Closing hindrance special
Eliminate the hindrance by pressing the emergency button, the switch lock or manual mode. If there are several errors, the error first detected is the one displayed. The warning refers to the warning output and is activated according to the error table(YES)
The LEDs on the electronic PCB ‘s indicate additional status and error displays which complement the information supplied via PSA.
Supply voltages
Internal electronics 5V(ON) External voltage 24V(ON) Motor power supply POWER(ON)
29
Infrared light detectors LS1/LS2 (ON) Emergency stop STOP (OFF) Emergency battery charge CHARGED( ON) “ blinking”
The status displayed between brackets indicates if the control unit is operative.
5.3 Safety elements and functions
Infrared light detectors LS1 and LS2 z If the infrared light detectors are cut off, the drive unit is reversed. In the open position the
hold-open time is reset.
z If the door is not closed, the infrared light detector LS1 activates the gong (impulse duration 1
second).
z Prior to a closing motion the infrared light detectors are tested. z If only one infrared light detector is connected, a bridge must be inserted on the second input.
Reversing and stopping mechanism:
z Limits the static force to max. 150N; z Reversing for the closing movement and stopping for the opening movement. After the next
impulse, the movement is continued at slow speed in the same sense of travel (V = 0.18m/s).
5.4 The main outputs and inputs of control unit outputs
All the outputs (with the exception of battery check, power supply) are electronic outputs (not potential free) with a maximum load of 24 V, 300MA. These outputs are to be used for an external application via a relay. z Power supply 24V, 0 V terminal = 2/5/6/8/16/20
24V terminal = 1/7/13/15/19 This power supply is short-circuit-proof (chapter 5.2.4) and designed for a maximum load
of 2 A. z Terminals 29, 30 and 31 output BATT CHECK.
This output is used for indicating the emergency battery status. See option (0633-999/16). It is the only relay output and has a maximum load capacity of 24VDC/1A.
z Connector X 15 output locking
The electro-mechanical lock is bi-stable, i.e. prior to an opening the locking mechanism is shortly actuated in order to shift the locking hook to the unlocked position. After the wings have reached the CLOSED position. They are again locked.
Inputs
z Program switch without PSA Program position T erminal 21 Terminal 22 Locking the door EXIT Switched to 0 V Automatic full open Switched to 0 V Automatic half open Switched to 0 V via 2 diodes * Program switch with PSA (position AUTOMATIC) Program position T erminal 21 Terminal 22
30
Locking the door Switched to 0 V EXIT Switched to 0 V Automatic full open Automatic half open Switched to 0 V via 2 diodes z Terminals 25 and 26
By short-circuiting the PSA connection during 2 seconds (terminals 25 and 26), a RESET can be carried out with or without PSA.
z Terminal 27
Stop (emergency stop 1) If this input is interrupted:
* The motor speed is immediately reduced. * The 5 V and 24 V supply is switched off ------ The sliding door is stopped. If this input is closed: * The sliding door closes slowly, and then will operates normally according to the program
switch position.
* The door reached the CLOSED position with PSA, LED32 flashing, and then it continues
to function normally according to the program switch position. z Emergency stop (X4 on drive unit)
If this input is cut off, the motor is immediately stopped and stands still. The door wings can be moved by hand.
5.5 Interlock operation
Principles
z Both installations must be plugged into respectively the same power supply; z Interlock function in program switch position Night and Exit (locked); z In order to guarantee the interlock function, both program switches must be in the same
position;
z However, the communication via the interlock connection functions in any position of the
program switch. This means that doors, which are not in a locked program switch position, are capable of blocking other doors, which are in a locked program switch position. Conversely, the pending signal is not taken into account.
z Opening commands are memorized. z Memorization of the opening impulses can be suppressed by softswitch no. 16. z The EMERGENCY OPEN or EMERGENCY CLOSE function has priority. z If a door remains hooked in the locking mechanism, the other door is released after a short
delay time has expired.
z Double openings are prevented by a special timing order arrangement, even if two opening
commands exist at the same time.
Procedure Both doors are closed. The MASTER supplies a signal, which must be answered by the SLAVE; otherwise the signal is repeated by the MASTER. If in the reverse case the MASTER fails to respond, the SLAVE will repeat the request. If one of the doors is not CLOSED, it transmits a 0 V signal to its interlock output. After a RESET or a mains failure the synchronization is always made by the MASTER. This ensures that the setting-up procedure is carried out in accordance
31
with the requirements of the interlock. z The interlock can also be combined with KS1000 sliding door, folding door.
Safety interlock
z Four opening elem. (e.g. push-buttons) are required. z After an opening element (A1) or (B1) has been actuated. The respective door is opened and
closed again after the hold-open time has expired. In order to open the second door, another opening element (A2) or (B2) must be operated within the interlock.
A1 A2 B2 B1
23 20
12 11 10
9 8 7
23 20
12 11 10
9 8 7
INTERLOCK
0V
EM KEY RD2
RD1 0V 24V
RD2
24V
RD1 0V
KEY
EM
INTERLOCK
0V
Hospital interlock
z Only two opening elements are required. z Softswitch no. 16 must be positioned on OFF. z After an opening element (A) or (B) has been activated, the respective door is opened and
closed again after the hold-open time has expired; then the second door is opened without any actuation of an opening element.
z For safety reasons at least one opening element (C) must nevertheless be installed within the
interlock area.
.
RD2
0V
RD1 24V
EM KEY
A
C
10
7
8
9
11
12
INTERLOCK
0V
20
23
B
10
7
8
9
11
12
RD2
0V
RD1
24V
EM KEY
20
23
INTERLOCK
0V
100R
200μF 200μF
5.6 Particular instructions for the users
5.7Infrared light detectors fault
If the installation is open when the premises close, because the infrared light detectors are interrupted, the door will close nonetheless at slow speed when the system is switched to the program position NIGHT, in spite of the fault.
32
Emergency battery “wake-up”.
The emergency battery set allows unrestricted operation for approx. 30 minutes.
6. MAINTENANCE AND TROUBLESHOOTING
6.1 Security and warranty
Regular maintenance and checking at least once a year is absolutely required in order to guarantee a long life span and safe operation of the KS1000 sliding door .
Maintenance must be carried out by specifically trained personnel, see chapter 6.2 If the maintenance is neglected or carried out by unauthorized personnel, the manufacturer respectively the distributor cannot be held responsible for any damages that might occur and their consequences.
Any subsequent intervention or modification of the KS1000 sliding door shall only be carried out by specially trained personnel.
Warning:
Before working on live elements, always pull out the power plugs and the emergency battery plug!
6.2 Maintenance
Check the function of different elements (as far as KS1000 sliding door are included in the installation) according to the operating instructions.
To avoid jeopardizing the safety of the door users, any defective safety elements may not be disconnected in order to continue the operation of the door.
In order to guarantee the availability of the installation, a preventive replacement of any elements showing signs of wear is strongly recommended.
Attention:
Don’t use floating water to wash machine box. Do not use any corrosive detergent.
Installation
check clean grease Adjust General installation condition V Manually make the door move freely
V V
Door guides/guide way rail V V V Sealing joints V V V Side panels/protection wings V V Coverings/Hinge type cover V V Check tight fitting of the screws V
33
and the nuts
Clean the installation V V
Drive unit
Drive unit V V V Holding power in closed position V Transmission elements: such as: toothed belt, flat belt, cables, rods, and chains
V V V
Carrying- and counter pressure rollers/ traveling carriages
V V V
Carrier rails V V V Open/ close positions V V
Control unit
Electrical connections V Control functions V V Program switch (Check all the positions)
V
Emergency battery V
Control Elements
All the control elements: such as:
sensor, radar, key operated switch , contact carpet
V V V
Safety elements
Reversing /stopping mechanism V V V Door locking/ manual unlocking
mechanism
V V V V
Mechanical emergency opening V V Monitoring switch V V V Light barrier V V V Additional safety elements V V V Miscellaneous Stickers/rating plates V V
6.3 T roubleshooting:
Warning
Before doing any check and other work on the control unit , always pull out the power plug Malfunctions Visual checking Reason Corrective/ solution Door is blocked in any position
Emergency stop (X4 control unit), Emergency stop terminals 27.28)No LED light on control unit.
No wire link or defective connection PSA on manual NO power or fuse fine-wire defect
Make a bridge connection Check PSA on automatic
34
Door is blocked in open position
Program switch Emergency opening Light barrier LS1/LS2 connected. Opening element
PSA on open or manual Light barrier cut, defective or wrong connections
PSA on automatic Check connection and the
light barriersLS1/LS2
Door remains
closed
Program switch(PSA) Emergency closing
PSA on lock, one way, manual position. Emergency close activated
PSA on automatic Check the connections or
element.“ Door keeps on short opening and closing movement
Door movement
Stopping mechanism active Defective control unit
Check the mechanical
part(traveling carriage,
guide ways , wings, etc) Replace the control unit.
During the closing motion , the door suddenly reopens automatically .
Dorr movement Reversing Mechanism active
Defective control unit
Check the mechanical
part(traveling carriage,
guide ways , wings, etc) Replace the control unit.
The locking
is not energize d in the program switch position NIGHT
Door attempts to open but remains locked
Defective locking magnet Defective locking PCB Defective control unit
Check the connection Measure the magnet Replace the locking PCB Replace the control unit
Warning
Should it not be possible to eliminate any potential dangerous malfunction immediately. If necessary, the door should stop operating, and shall be repaired as soon as possible. Every maintenance and troubleshooting which has been carried out should be fully noted in the check book
64 KS1000 spare parts
Name Part number
Essential
Carrier Profile Control unit(KSM) PN01231054 Drive Unit(KSD) PN01231055
35
Mobile-wing running
carriage set
PN01231058
PSA PN01231063 Mechanism elements Electronic elements
Optional
Operator cover
Fixed elements of operator
cover Bottom baffle Side cover Batteries set(KSB) PN01231056 Electro-mechanical lock PN01231059
65 Environment protection treatment
An ecological acceptable disposal of the sliding door is possible, by separating and recycling the
individual materials. No particular inspection is required for the environment protection
36
辅梁
支撑梁
胶合页
盖板
旋转定位片
下盖板
盖板
旋转定位片
胶合页
支撑
1:盖板安装
Supporting Profile
Carrier profile
Rubber Hinge
Cover
Rotation Positioning piece
Bottom cover
Rubber Hinge
cover
Rotation positioning piece
Bottom Cover
Appendix 1: Drawing of Cover installation
Carrier
profile
37
38
39
40
ope
n /auto /nigh
t
Operating element open inside
2
Appendix 5: Wiring diagram of control unit
2
seleck
4
3
PSA
2
1
Drive unit
1
X6
7 8
5 6
X5
MCU
RS232 /RS48
5
4
3
2
1
emergency jumpe
r
plu
g
4
p h o t o c e l l s
A c t i v a t i n g
d e v i c e
X7
14
13
12
11
10
9
ws/
White
br/Brow
n
sw/Blac
k
gn/Gree
n
gr/Grey
special function for revolving door onl
y
X8
24
23
21 22
20
19
18
17
16
15
X9
25 26
Drive unit
plu
g
emergency jumpe
r
With PSA function night
jumper if element missing
Operating element open outsid
e
Emergency opening/closing programmable by PSA
Operating element open on key-operated switch
jumper if element missin
g
Operating element open inside Operating element open outside Operating element open on key-operated switch Emergency opening/closing programmable by PSA
Activatin
device
Drive unit 1
Driver unit 2
Jumper if element missing
41
VERAK
TUZUK
电子机械锁控制
(双向)
6:电池、电子机械锁接线
锁门到位连接端
开锁到位连接端
人工开锁
g
n
M
检测电池是否接 好的跳线
电压监控30V/15VA
停止跳线
G
1
24V
1.3Ah
1.3Ah的电池组
VER
1
A11
MCU
2
2x0.5mm
X15
2
1
r
t
S
W
插座
电池板
TUW
1
A25
BATPR
1
(Opt.
)
X14
X10
2
4x0.5mm
g
e
g
n
b
r
w
s
X16
GND
KEY
VERAK
TUZUK
4
3
2
NOT O
K
O
K
0
V
STO
P
N
O
N
C
C
ACC
U
控制
电池
8AT
X13
X12
r
t
s
w
s
w
+24
V
2
2X1.5mm
s
w
GND
GND
GND
KEY
Electro-mechanical lock (two-way)
Manual unlocking
Door monitor contact
Locking display contact
Plug
Stop jumper
Battery voltage monitor 30V/15VA
Check battery plugged in Supplied with bridge connection
Battery 1.3Ah
Plug
Battery board
Batteries
Appendix 6: Wiring diagram of battery & Electro-mechanical lock
42
Activating Device
s
8
7
6
ge
b
r
gn
b
r
ws
g
r
Radar
/
OPT Senso
r
OKI
MCU
ge
g
r
ws
gn
NOT
OKA
5
1
0
11
1
2
Radar
/
OPT Senso
r
operating element open on key-operated switch
Emergency opening/closing programmable by PSA
Activating Devices
Key
Radar/ OPT Sensor
Radar/ OPT Sensor
Operating element open inside
Operating element open outside
Operating element open on Key-operated switch
Emergency opening/closing programming by PSA